LG Electronics ARWB096BAS4

User Manual - Page 7

For ARWB096BAS4.

PDF File Manual, 45 pages, Download pdf file

Loading ...
Loading ...
Loading ...
7
ENGLISH
CAUTION
• Do not install Multi V water outdoors. Always install indoor like
machine room.
• Inverter product may generate electric noise. Keep the body
from computer, stereo etc. at enough distance. Specially leave
space from indoor remote controller to shoes electric devices at
the above 3m in weak electric wave area. Insert the power
cable and other wire into separate conduit.
!
Select installation location of the HR unit suitable for following condi-
tions
- Avoid a place where rain may enter since the HR unit is for indoor.
- Sufficient service space must be obtained.
- Refrigerant pipe must not exceed limited length.
- Avoid a place subject to a strong radiation heat from other heat
source.
- Avoid a place where oil spattering, vapor spray or high frequency
electric noise is expected.
- Install the unit at a place in which it is not affected by operation noise.
(Installation within cell such as meeting room etc. may disturb busi-
ness due to noise.)
- Place where refrigerant piping, drain piping and electrical wiring
works are easy.
Inspection door
(servicing space)
481(18-15/16)
345(13-19/32)
300(11-13/16)
more
300(11-13/16)
more
(Servicing space) (Servicing space)
1
2
3
7
453(17-27/32)
174(6-27/32)
174(6-27/32)
218(8-19/32)
182(7-5/32)
450(17-23/32)
450(17-23/32)
100(3-15/16) more
(Serviceing space)
300(11-13/16)
more
450(17-23/32)
more
(Servicing space)
(Servicing space)
54
6
419(16-1/2)
61(2-13/32)
137(5-13/32)
124(4-7/8)
128(5-1/32)
30(1-3/16)
100(3-15/16) more
(Serviceing space)
60(2-3/8)
NOTE
!
• Be sure to install the inspection door at the control box side.
• If reducers are used, servicing space must be increased equal to
reducer's dimension.
(unit: mm(inch))
No. Part Name
Description
PRHR031A/PRHR041A PRHR021A
1
Low pressure
Gas pipe con-
nection port
Ø28.58(1-1/8) Brazing con-
nection
Ø22.2(7/8) Brazing connec-
tion
2
High pressure
Gas pipe con-
nection port
Ø22.2(7/8) Brazing connec-
tion
Ø19.05(3/4) Brazing con-
nection
3
Liquid pipe con-
nection port
Ø15.88(5/8) Brazing con-
nection (PRHR041A)
Ø12.7(1/2) Brazing connec-
tion (PRHR031A)
Ø9.52(3/8) Brazing connec-
tion
4
Indoor unit Gas
pipe connection
port
Ø15.88(5/8) Brazing con-
nection
Ø15.88(5/8) Brazing con-
nection
5
Indoor unit Liq-
uid pipe connec-
tion port
Ø9.52(3/8) Brazing connec-
tion
Ø9.52(3/8) Brazing connec-
tion
6
Control box - -
7
Hanger metal M10 or M8 M10 or M8
Loading ...
Loading ...
Loading ...