Refrigeration
BTUH Capacity Requirements
Model BTUH
N0922L & F1222L 5,000
N1322L, F1522L, N1322NCL & F1522NCL 7,200
Condensing Units Used and Holding Charge
Unit Condensing Unit Holding Charge
N0922L
F1222L
NME954-RHS-A/C
or rack
R404A
N1322L
F1522L
None - rack only R404A
N1322NCL
F1522NCL
None - rack only Nitrogen
Remote low side models require connection to a
dedicated condensing unit or a rack system.
Recommended Tubing from Head to Condensing Unit
Suction Line: 5/8" OD
Liquid Line: 3/8" OD
Distance limits:
Maximum distance between dedicated condensing
unit and head: 75 feet.
Condensing Unit Elevation over Ice Making
Section: 35 feet.
Note: Elevations greater than 20 feet require
installation of a suction line trap at the 10 foot mark.
Ice Making Section
Elevation over Condensing Unit: 15 feet.
Line Routing:
Allowed: One rise after a drop.
Allowed: One drop after a rise.
Not Allowed: More than one rise after a drop
Not Allowed: More than one drop after a rise
Roof Attachment
Install and attach the remote condensing unit to the
roof of the building, using the methods and practices
of construction that conform to the local building
codes, including having a roong contractor secure
the condenser to the roof.
Refrigeration Installation:
Connections
The liquid and suction ttings on the back of the
cabinet are stubs. The liquid line size is 3/8" OD. The
suction line size is 5/8" OD.
1. On R-404A models recover the R404A holding
charge or on the “NCL” units vent Nitrogen
2. Cut the stubs off.
3. Braze line set tubing to each tting. Sweep with
dry nitrogen while brazing.
4. Dedicated condensing unit: Evacuate complete
system to 50 microns.
5. Open the ball valves.
Rack: The skills of a refrigeration technician are
required to connect the ice machine to the building’s
refrigeration system.
Notes:
R-404A models: 10 ounces of R-404A refrigerant
is in the system as a holding charge.
Be sure the liquid connection is NOT in series with
another liquid line valve.
Local Codes must be observed.
Dedicated condensing unit: Add refrigerant charge.
Recommended starting eld charge:
N0922L or F1222L: 8 lb R-404A
N1322L or F1522L: n/a - rack only
N1322NCL or F1522NCL: n/a - rack only