INSTALLATION
ENGLISH
The location of the Anchor bolts
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom shall have width of at least 100mm(3-15/16 inch) under
the Unit’s legs before being fixed.
• The outdoor unit supports should nave minimum height of 200mm(7-7/8 inch).
• Anchor bolt must be inserted at least 75mm(2-15/16 inch).
At least 100mm(3-15/16 inch)
At least 100mm(3-15/16 inch)
At least 100mm(3-15/16 inch)
At least 100mm(3-15/16 inch)
At least 100mm(3-15/16 inch)
At least 100mm(3-15/16 inch)
Center of the Unit
For outdoor units should not
be supported only by the
corner supports.
Center of the Unit
730(28-3/4)
760(29-29/32)
65(2-9/16)
65(2-9/16)
Unit : mm(inch)
At least
65(2-9/16)
At least
65(2-9/16)
Chassis
Outdoor Unit Capacity
A [mm(inch)] B [mm(inch)]
Ton HP
UX2 6Ton 8 HP 920(36-7/32) 792(31-3/16)
UX3 8~14Ton 10~14,18HP 1240(48-13/16) 1102(42-3/8)