WIRING CONNECTION
21
ENGLISH
Precautions when laying power
wiring
Use round pressure terminals for connections
to the power terminal block.
When none are available, follow the
instructions below.
- Do not connect wiring of different
thicknesses to the power terminal block.
(Slack in the power wiring may cause
abnormal heat.)
- When connecting wiring which is the same
thickness, do as shown in the figure below.
Power wirer
Round pressure terminal
It is forbidden to
connect two to one
side.
It is forbidden to
connect wiring of
different thicknesses.
Connect same thickness
wiring to both sides.
- For wiring, use the designated power wire
and connect firmly, then secure to prevent
outside pressure being exerted on the
terminal block.
- Use an appropriate screwdriver for tightening
the terinal screws. A screwdriver with a
small head will strip the head and make
proper tighterning impossible.
- Over-tightening the terminal screws may
break them.
CAUTION
The connecting cable connected to the
indoor and outdoor unit should be
complied with the following specifications
(This equipment shall be provided with a
cord set complying with the national
regulation).
!
NORMAL
CROSS-SECTIONAL
AREA 0.75 mm
2
20 mm
35±5 mm
GN/YL
10±3 mm
If the supply cord is damaged, it must be
replaced by a special cord or assembly
available from the manufacturer of its
service agent.
Connecting cables to the
Outdoor Unit
- Remove the side panel from the unit by
loosing screws.
Connect the wires to the terminals on the
control board individually as previous page.
- Secure the cable onto the control board with
the holder (clamp).
- Refix the cover control to the original
position with the screw.
Connecting cable
terminal
Power cord terminal
Cord clamp
Cord clamp
* Make sure the rubber
bushes are Properly used
in knock-out holes after
connecting main Power
cable
CST Duct
Capacity (kBtu/h) 24 36 48 24 36
CMM 13 20 47 14.5 24
* Minimum Rated Air Flow