Rear discharge
This range hood can be vented directly out the back using the
3¼" x 10" (8.3 cm x 25.4 cm) rectangular damper (supplied) along
with a 3¼" x 10" (8.3 cm x 25.4 cm) rectangular vent system (not
supplied). See “Install Range Hood” section for details for
installing the damper.
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
3¹⁄
4
" x 10" (8.3 cm x 25.4 cm) Vent System
Vent Piece
3¹⁄
4
" x 10" (8.3 cm x 25.4 cm)
90° elbow
5.0 ft
(1.5 m)
3¹⁄
4
" x 10" (8.3 cm x 25.4 cm)
at elbow
12.0 ft
(3.7 m)
3¹⁄
4
" x 10" (8.3 cm x 25.4 cm) wall
cap
0.0 ft
(0.0 m)
Example vent system
Maximum Recommended Length = 35 ft (10.7 m)
1 - 90° elbow = 5.0 ft (1.5 m)
8 ft (2.4 m) straight = 8.0 ft (2.4 m)
1 - wall cap = 0.0 ft (0.0 m)
Length of 3¹⁄
4
" x 10" (8.3 cm x 25.4 cm)
system
= 13.0 ft (3.9 m)
Electrical Requirements
Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70 (latest
edition), or CSA Standards C22.1-94, Canadian Electrical Code,
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes
and ordinances.
If codes permit and a separate ground wire is used, it is
recommended that a qualied electrician determine that the
ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
A 120 V, 60 Hz, AC only, 15 A, fused electrical circuit is
required.
If the house has aluminum wiring, follow the procedure
below:
Connect the aluminum wiring using special connectors and/or
tools designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended
procedure. Aluminum/copper connection must conform with local
codes and industry accepted wiring practices.
Wire sizes and connections must conform with the rating of
the appliance as specied on the model/serial/rating plate.
The model/serial/rating plate is located behind the left lter on
the rear wall of the range hood.
Wire sizes must conform to the requirements of the National
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA
Standards C22. 1-94, Canadian Electrical Code, Part 1 and
C22.2 No. 0-M91 (latest edition) and all local codes and
ordinances.
Roof Venting Wall Venting
(top or re
ar discharge)
A
B
A
B
A. Roof cap
B. 3¹⁄
4
" x 10" (8.3 x 25.4 cm)
rectangular metal vent
A. Wall cap
B. 3¹⁄
4
" x 10" (8.3 x 25.4 cm)
rectangular metal vent
Wall cap
3
¹⁄₄" x 10"
(8.3 x 25.4 cm)
elbow
2 ft
(0.6 m)
6 ft (1.8 m)