Rinnai INF32N50M N/G 32 Ltr Continuous Flow 50°C Hot Water System

User Manual - Page 27

For INF32N50M.

PDF File Manual, 40 pages, Download pdf file

Loading ...
Loading ...
Loading ...
Rinnai Australia 24 Installation Manual
GENERAL INSTALLATION INSTRUCTIONS
HORIZONTAL FLUE TERMINAL CLEARANCES
Extract from AS/NZS 5601
Flue terminal Fan assisted flue appliance only Gas meter Electricity meter or fuse box Mechanical air inlet
Min. Clearances
(mm)
Fan-Assisted
Appliances up to 50 MJ/h input
200
Appliances over 50 MJ/h input
300
b From the ground, above a balcony or other surface * 300
c Front a return wall or external corner * 300
d
From a gas meter (M) (see 5.11.5.9 for vent terminal location of regulator )
(see Table 6.6 for New Zealand requirements)
1000
e
From an electricity meter or fuse box (P) †
500
f From a drain pipe or soil pipe 75
g
Horizontally from any building structure* = or obstruction facing a terminal
500
h
From any other flue terminal , cowl, or combustion air intake †
300
Appliances up to 150 MJ/h input *
300
Appliances over 150 MJ/h input up to 200 MJ/h input *
300
Appliances over 200 MJ/h input up to 250 MJ/h input *
500
Appliances over 250 MJ/h input *
1500
• All fan-assisted flue appliances , in the direction of discharge
1500
k From a mechanical air inlet, including a spa blower 1000
• Space heaters up to 50 MJ/hr input 150
• Other appliances up to 50 MJ/hr input
500
Appliances over 50 MJ/h input and up to 150 MJ/h input
1000
Appliances over 150 MJ/h input
1500
1
Where dimensions c, j or k cannot be achieved an equivalent horizontal distance
measured diagonally from the nearest discharge point of the terminal to the opening
may be deemed by the Technical Regulator to comply.
2
See Clause 6.9.4 for restrictions on a flue terminal under a covered area.
3
See Figure J3 for clearances required from a flue terminal to an LP Gas cylinder.
A flue terminal is considered to be a source of ignition.
4
For appliances not addressed above acceptance should be obtained from the
Technical Regulator.
Ref. Item
a
Below eaves, balconies and other projections:
FIGURE 6.2 (in-part) MINIMUM CLEARANCES REQUIRED FOR FAN-ASSISTED FLUE TERMINALS, ROOM-
SEALED APPLIANCE TERMINALS AND OPENINGS OF OUTDOOR APPLIANCES
* - unless appliance is certified for closer installation
n
j
Horizontally from an openable window, door, non-mechanical air inlet, or any other opening into a
building with the exception of sub-floor ventilation:
Vertically below an openable window, non-mechanical air inlet, or any other opening into a
building with the exception of sub-floor ventilation:
NOTES:
† - Prohibited area below electricity meter or fuse box extends to ground level.