LG Electronics ARWN192DAS4

User Manual - Page 6

For ARWN192DAS4.

PDF File Manual, 34 pages, Download pdf file

Loading ...
Loading ...
Loading ...
6
ENGLISH
Items
pH(25C)
Conductivity[25C](mS/m)
Chlorine ion(mg CI
-
/l)
Sulfuric acid ion(mg SO
2
-
/l)
Acid demand[pH 4.8] (mg SiO
2/l)
Total hardness(mg SiO
2/l)
Ca hardness(mg CaCO
3/l)
Ion silica(mg SiO
2/l)
Fe(mg Fe/l)
Copper(mg Cu/l)
Sulfuric acid ion(mg S
2
/l)
Ammonium ion(mg NH
4/l)
Residual chlorine(mg Cl/l)
Free carbon dioxide(mg CO
2/l)
Stability index
7.0~8.0
Below 30
Below 50
Below 50
Below 50
Below 70
Below 50
Below 30
Below 1.0
Below 1.0
Must not be detected
Below 0.3
Below 0.25
Below 0.4
-
Below 0.3
Below 0.1
Must not be detected
Below 0.1
Below 0.3
Below 4.0
-
7.0~8.0
Below 30
Below 50
Below 50
Below 50
Below 70
Below 50
Below 30
O
O
O
O
-
-
-
-
O
O
O
O
O
O
O
O
-
-
-
-
-
O
O
O
-
O
O
O
O
O
Closed type
Basic Item
Reference Item
Effect
Circulating water Supplemented water Corrosion Scale
4
+
Reference
• The "O" mark for corrosion and scale means that there is possi-
bility of occurrence.
• When the water temperature is 40°C(104°F) or above or when
uncoated iron is exposed to the water, it can result in corrosion.
Therefore adding anti-corrosion agent or removing the air can be
very effective.
• In case of using the closed type cooling tower, the cooling water
and supplementing water must satisfy the water quality criteria
of closed type system in the table.
• Supplementing water and supplied water must be supplied with
tap water, industrial water and underground water excluding fil-
tered water, neutral water, soft water etc.
• 15 items in the table are general causes of corrosion and scale.
Sub line
40° or less
Rope supporter
A
B
The location of the Anchor bolts
• Install at places where it can endure the weight and vibration/noise
of the outside unit .
• The outside unit supports at the bottom shall have width of at least
100mm(3-15/16inch) under the Unit’s legs before being fixed.
• The outside unit supports should have minimum height of 200mm
(7-7/8inch).
• Anchor bolts must be inserted at least 75mm(2-15/16 inch).
At least 100mm
(3-15/16 inch)
At least 100mm
(3-15/16 inch)
At least 100mm
(3-15/16 inch)
At least 100mm
(3-15/16 inch)
The location of
anchor bolt
62(2-7/16)
62(2-7/16)
631(24-27/32)
755(29-23/32)
Unit: mm(inch)
500(19-11/16)
472(18-19/32)
Foundation for Installation
• Fix the unit tightly with bolts as shown below so that unit will not fall
down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is
transferred through the installation part depending on installation sta-
tus. Thus, use anti-vibration materials (cushion pad) fully (The base
pad shall be more than 200mm(7-7/8inch)).
At least
200mm
(7-7/8inch)
INSTALLATION
LIFTING METHOD
- When carrying the unit suspended, pass the ropes under the unit and
use the two suspension points each at the front and rear.
- Always lift the unit with ropes attached at fours points so that impact
is not applied to the unit.
- Attach the ropes to the unit at an angle of 40° or less
CAUTION
Be very careful while carrying the product.
• Do not have only one person carry product if it is more than 20
kg(44lbs).
• PP bands are used to pack some products. Do not use them as a
mean for transportation because they are dangerous.
• Tear plastic packaging bag and scrap it so that children cannot
play with it. Otherwise plastic packaging bag may suffocate chil-
dren to death.
• When carrying in Outdoor Unit, be sure to support it at four
points. Carrying in and lifting with 3-point support may make Out-
door Unit unstable, resulting in a fall.
• Use 2 belts of at least 8m(26.2ft) long.
• Place extra cloth or boards in the locations where the casing
comes in contact with the sling to prevent damage.
• Hoist the unit making sure it is being lifted at its center of gravity.
!