Part Number 000015433_02 11/19 53
RFF0620/RNF0620/RNF1100/RFF1300
Troubleshooting
SELF-CONTAINED AIR-COOLED
Normal Operation
When the toggle switch is placed in the ON position the
following controls must be in the closed position before
the ice machine will start:
A. Bin Thermostat
B. High Pressure Cut-out Switch
C. Ice Chute Safety Switch
D. Low Pressure Switch
E. Low Water Level Switch
NOTE: Placing the toggle switch in the ON position starts
the gear motor. After the rotation speed sensor verifies 8
minutes of correct rotation the time delay ends and the
compressor starts. The ice machine will continue to make
ice until ice contacts the bin thermostat. The ice machine
remains off until ice no longer contacts the bin thermostat.
ROTATION SENSOR OPERATION
Light Definition
Yellow Blinking Time Delay Period
Yellow Solid Normal Operation Sensing
Red Blinking 2
Flashes Per Second
Time Delay Period - First 1 To 7 Faults
Red Solid Lockout - 8 Consecutive Faults Due To A
Speed Fault
Remove/Restore Power To Reset
Red Blinking Slowly Lockout - 8 Consecutive Faults Due To A
Short Circuit
See “Rotation Sensor” on page 84 for sequence of operation