Loading ...
Installation notes
2 PG 8130 / PG 8131 / PG 8132 / PG 8133
Please read and observe the instructions in the operating in-
struction manual and the service documents regarding install-
ation and setting up of this dishwasher.
Installation re-
quirements
This machine must be installed by a suitably qualified person with
the appropriate electrical and plumbing qualifications in accordance
with the installation instructions supplied.
This machine must be installed in accordance with all applicable
standards and guidelines, including legal requirements and health
and safety regulations.
The machine must be commissioned and operatives trained in its
use by Miele Service or by an approved Miele Service Partner only.
Electrical connec-
tion
Connection to the electrical supply should be in accordance with
valid regulations and safety standards (e.g. BS 7671 in the UK). The
connection cable must be protected from the risk of thermal damage.
We recommend connecting the machine to the power supply via a
suitable plug and socket as this will make it easier to carry out the
electrical safety test during commissioning and after any service
work.
For hard-wired machines, connection should be made via a suitable
mains switch with all-pole isolation, which in the off position ensures
a 3mm gap between all open contacts.
The main switch and socket must be easily accessible after installa-
tion.
Equipotential
bonding and
earthing
For added safety the machine should be protected with a residual
current device with a trip current of 30mA.
Equipotential bonding should be carried out if required. The screw
connection point for equipotential bonding is located at the back of
the machine. Equipotential bonding and earthing must be carried out
before the machine is commissioned.
Water supply
The machine can be plumbed in to the cold water, hot water, demin-
eralised water and drainage points without a backflow protection
device. The stopcock to the water supply must be easily accessible.
The water supply to the machine can be connected to either cold wa-
ter or hot water.
Environmental re-
quirements
Condensate can build up in the area surrounding the machine. Any
furniture and fittings in the room must therefore be suitable for pur-
pose. If the machine is fitted under a suitable worktop (built-under
and integrated models), the stainless steel panel supplied must be fit-
ted above the door aperture to protect the worktop from moisture
damage. A suitable stainless steel vapour plate is available to order
from Miele.
Connecting an ex-
ternal dispensing
system
A dispensing system for liquid detergents and rinsing agents can be
connected to the back of the machine.
Loading ...
Loading ...