Loading ...
Loading ...
Loading ...
Part Number 000015433_03 5/20 39
Thermostat Settings
Bin Thermostat:
The bin thermostat sensing bulb is located in the ice chute
on modular models and in the bin thermostat holder on
the right side of the bin on self storage models. The bin
thermostat turns the ice machine on and off as the level
of ice in the bin changes. Use the indicator on the ice
machine label as the initial setting and adjust as required.
Evaporator Low Temperature Safety Thermostat:
The evaporator low temperature safety thermostat
protects the ice machine if the evaporator temperature is
too cold. Refer to chart for correct setting.
1
2
3
4
5
6
7
1
2
3
4
5
6
7
Bin Thermostat
Small Numbers = Less ice in bin
Large Numbers = More ice in bin
Start at Chart Setting, then adjust
as required
Evaporator Low Temperature
Safety Thermostat
Refer to chart for setting
Incorrect settings will cause ice
machine to shut off prematurely
Loading ...
Loading ...
Loading ...