Installation Guide
69-2198—03 12
ADVANCED CONFIGURATION
Table 5. Advanced Configuration.
Menu Name Menu Title (LCD
top line)
Menu Options (LCD bottom
line; defaults in bold)
Menu option description Notes:
Heat Fan HEAT FAN
CONTROL
[HVAC] PANEL
Fan control by HVAC In heat mode, fan controlled by HVAC or turned
on by panel in call for heat.
HVAC [PANEL] Fan control by Panel
Stage 2 Timer STAGE 2 TIMER
[5 MIN] > – < [60 MIN]
[5 MIN] >
5 minutes–60 minutes Number of minutes to delay before engaging
second stage.
Stage 3 Timer STAGE 3 TIMER
[5 MIN] > – < [60 MIN]
[5 MIN] >
5 minutes–60 minutes Number of minutes to delay before engaging
third stage.
Purge Timer PURGE TIME
[2] 3.5 5 MIN
2.0 minutes Number of minutes panel will purge following
call for heat or cool.
2 [3.5] 5 MIN 3.5 minutes
2 3.5 [5] MIN 5.0 minutes
Purge Fan FAN IN PURGE
[HVAC] PANEL
Fan control by HVAC Fan controlled by HVAC or panel during purge.
HVAC [PANEL] Fan control by Panel
Purge Dampers PURGE DAMPERS
[UNCHANGD] OPEN
Dampers Unchanged Damper position unchanged or all dampers
open during purge.
UNCHANGD [OPEN] Dampers All Open
Auto Changeover Delay CHANGEOVER
DELAY
[15] 20 30 MIN 15 minutes auto changeover timer Number of minutes to delay auto changeover
when one zone is calling for heat and another
is calling for cooling.
15 [20] 30 MIN
20 minutes auto changeover timer
15 20 [30] MIN 30 minutes auto changeover timer
DATS Enabled DISCHARGE
SENSOR
[NO] YES Disabled Enables or disables DATS. If Disabled, the
Multistage DATS Inhibit setting is Disabled.
NO [YES] Enabled
DATS High Limit DAT HIGH LIMIT [110 F] > – < [180 F]
< [160 F] >
110 deg F–180 deg F High temperature limit.
DATS Low Limit DAT LOW LIMIT [30 F] > – < [60 F]
< [40 F] >
30 deg F–60 deg F Low temperature limit.
Multistage DATS Inhibit DAT MSTG INHIBIT
NO [YES]
Enabled Allow panel to downstage multistage equip-
ment when near DATS high or low limit.
[NO] YES Disabled
Dual Fuel Changeover DUALFUEL
CHGOVR
[OT] MULTISTG
Dual Fuel Changeover by OT Temp Allow panel to changeover from heat pump to
fossil fuel based on outdoor temperature, or
allow second stage call to changeover panel
to fossil fuel for a minimum of one hour when
outdoor temperature is above OT balance tem-
perature setting. Multistage changeover is only
available on dual fuel applications configured
for 2 heat pump stages.
OT [MULTISTG] Dual Fuel Changeover by OT Temp +
multistage call
Dual Fuel Mstage
Changeover Time
CHANGEOVER
DELAY
[15 MIN] >< [180 MIN]
[30 MIN] >
Sets fossil fuel changeover delay
time.
Sets number of minutes to delay fossil fuel
when calling for second stage heat.
OT Temp Enabled OT SENSOR
[NO] YES
Disabled Enables or disables outdoor temperature
sensor. If Disabled, the Multistage OT Temp
Lockout setting is Disabled.
NO [YES] Enabled
Multistage OT Temp
Lockout
MSTG OT
LOCKOUT
[NO] YES
Disabled When outdoor temperature is above OT
Lockout temperature, locks out second and
third stage (only for conventional and heat
pump configurations), not dual fuel configura-
tions.
NO [YES] Enabled
OT Balance
Temperature (Dual Fuel)
OT BALANCE
TEMP
[0 F] > – < [50 F]
< [30 F] >
0 deg F–50 deg F Selects the temperature at which a dual fuel
configuration will change from heat pump to
fossil fuel.
OT Trip point for multi-
stage lockout
OT LOCKOUT
TEMP
[0 F] > – < [50 F]
< [50 F] >
0 deg F–50 deg F The temp that locks out second or third stage
(only for conventional and heat pump configu-
rations, not dual fuel systems).
LCD Contrast Adjust LCD CONTRAST [1] > – < [10]
< [5] >
Contrast value 1–10 Sets LCD display contrast for ease of viewing.
Lowest contrast is 1, highest contrast is 10.
Save Changes SAVE CHANGES?
[NO] YES
Disabled Saves or rejects the configuration settings.
NO [YES] Enabled
Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page
10 for instructions on using these buttons. Options/information displayed will vary by system type, control type,
number of zones, and other settings.