Honeywell SPRD10 10" Round Barometric Damper

User Manual - Page 4

For SPRD10.

PDF File Manual, 4 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
69-1518-2 G.H. Rev. 7-03 www.honeywell.com/yourhome
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario
M1V 4Z9
CHECKOUT
After completing the installation, be sure the equipment
operates correctly:
1. The damper opens fully or partially when the small-
est zone of the system is calling, then closes as the
other zones call.
2. When all zones are calling, the damper is fully
closed.
REPLACEMENT PARTS (FIG. 3)
Both the counterweight arm assembly and the
counterweight are available as replacement parts. See
Fig. 3 for part numbers. If the counterweight arm
assembly is used on the rectangular SPRD, remove the
coupling extension because it is used only for the round
SPRD. Remove the extension from the coupling by
loosening the setscrew nearest the counterweight arm
using a 1/8 in. Allen wrench (not included).
Fig. 3. SPRD replacement parts.
COUNTERWEIGHT ARM ASSEMBLY (INCLUDES WEIGHT)
PART NO. USED WITH
32005981-002
(ASSEMBLY)
SPRD6, SPRD7,
SPRD12X8, SPRD20X8
32005981-003
(ASSEMBLY)
SPRD8, SPRD9,
SPRD12X10, SPRD20X10
32005981-004
(ASSEMBLY)
SPRD10, SPRD12, SPRD14, SPRD16
SPRD12X12, SPRD20X12
32005688-001
(WEIGHT ONLY)
ALL SPRD DAMPERS
M19643