Installation Section 2
14
Part Number 000006505 Rev02 12/19
Step 6 Open Lineset and Receiver Valves
You will not hear refrigerant flow when the valves are
opened. Refrigerant will not flow until the toggle switch is
placed in the ice position and the solenoid valve opens.
All valve caps must be reinstalled, tightened and leak
checked to assure no refrigerant leakage exists.
Counterclockwise opens all valves:
A. Refer to chart and open the suction and liquid
line shut off valves the correct number of 360°
turns.
B. Open the receiver service valve until
backseated (two valves on the S3000C/
SF3000C).
.
S0600C/S0800C/S1000C/S1200C
.
IB0600C/IB0800C/IB1000C
S1470C/S1870C/S2170C
S3000C/SF3000C
Valve Tubing Size Number of Turns To Open
3/8” 6
1/2” 5/8” 3/4” 10
7/8” 14
USE ALLEN WRENCH TO OPEN
(TURN COUNTERCLOCKWISE)
LIQUID AND SUCTION LINE
SHUT OFF VALVES
USE ALLEN WRENCH
TO OPEN (TURN
COUNTERCLOCKWISE)
LIQUID AND SUCTION
LINE SHUT OFF
VALVES
!
Caution
After opening suction, discharge and receiver
service valves, refrigerant pressure will not be
detected until the toggle switch is placed in the ice
position and the solenoid valves energize.
USE ALLEN WRENCH
TO OPEN (TURN
COUNTERCLOCKWISE)
LIQUID AND SUCTION
LINE SHUT OFF
VALVES
USE ALLEN WRENCH
TO OPEN (TURN
COUNTERCLOCKWISE)
LIQUID AND SUCTION
LINE SHUT OFF
VALVES