182 Part Number: 000015430 Rev 02 5/20
SELF-CONTAINED MODEL PROCEDURE
Do not purge refrigerant to the atmosphere. Capture
refrigerant using recovery equipment. Follow the
manufacturers recommendations.
Notice
Manitowoc assumes no responsibility for the use of
contaminated refrigerant. Damage resulting from the
use of contaminated refrigerant is the sole responsibility
of the servicing company.
Notice
Replace the liquid line drier after recovering the
refrigerant and before evacuating and recharging. Use
only a Manitowoc (OEM) liquid line filter-drier to prevent
voiding the warranty.
Connections
Manifold gauge sets must utilize low loss fittings to comply
with local rules and regulations.
Make these connections:
Suction side of the compressor through the suction
access valve.
Discharge side of the compressor through the
discharge access valve.
Liquid side through the liquid line drier.