LG Electronics ARUN096DT2

User Manual - Page 60

For ARUN096DT2.

PDF File Manual, 91 pages, Download pdf file

Loading ...
Loading ...
Loading ...
60 Outdoor Unit
Connection method of the connecting cable (Example)
1. Make a hole appropriate for the passage of connection cable through on cap by tool.
2. After knocking out the holes, we recommend you paint the edges and areas around the edges using
the repair paint to prevent rusting
3. Pass the connecting cable through the hole.
4. Properly connect the cable on the terminal block.
5. Fix the connection cable with the cord clamp providing on the unit not to have strain at the terminal.
6. Finally, Fix the cap to the conduit panel.
WARNING
• Loose wiring may cause the terminal to overheat or result in unit malfunction.
• A fire hazard may also exist.
• Therefore, be sure all wiring is tightly connected.
Model name ARUN076DT2 ARUN096DT2 ARUN115DT2 ARUN134DT2 ARUN154DT2
AWG 14 14 14 12 12
Conduit (inch) 1/2 1/2 1/2 1/2 1/2
Knockout Diameter (inch) 7/8 7/8 7/8 7/8 7/8
Model name ARUN173DT2 ARUN192DT2 ARUN211DT2 ARUN230DT2 ARUN250DT2 ARUN270DT2 ARUN290DT2 ARUN310DT2
AWG 12 12 12 10 8 8 6 6
Conduit (inch) 1/2 1/2 1/2 1/2 1 1 1 1
Knockout Diameter (inch) 7/8 7/8 7/8 7/8 1-23/64 1-23/64 1-23/64 1-23/64
Model name ARUN330DT2 ARUN350DT2 ARUN370DT2 ARUN390DT2 ARUN410DT2 ARUN430DT2 ARUN450DT2 ARUN470DT2
AWG 6 6 6 6 4 4 4 4
Conduit (inch) 1 1 1 1 1-1/4 1-1/4 1-1/4 1-1/4
Knockout Diameter (inch) 1-23/64 1-23/64 1-23/64 1-23/64 1-23/32 1-23/32 1-23/32 1-23/32
Model name ARUN076BT2 ARUN096BT2 ARUN115BT2 ARUN154BT2 ARUN173BT2 ARUN192BT2 ARUN211BT2 ARUN230BT2
AWG 10 10 8 6 6 4 4 4
Conduit (inch) 1/2 1/2 1 1 1 1-1/4 1-1/4 1-1/4
Knockout Diameter (inch) 7/8 7/8 1-23/64 1-23/64 1-23/64 1-23/32 1-23/32 1-23/32
Model name ARUN250BT2 ARUN270BT2 ARUB290BT2 ARUB310BT2 ARUN330BT2 ARUN350BT2
AWG 2 2 2 2 2 2
Conduit (inch) 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4
Knockout Diameter (inch) 1-23/32 1-23/32 1-23/32 1-23/32 1-23/32 1-23/32