54
Deluxe Line: 2500,
Dry Air 25 & 3500 Series -
Models are manufactured with fixed heater
wattages with the appropriate power cord
attached (all 265 volt models are
permanently connected). 5.0 KW heaters
are not available on 7,000 BTUH models.
Zoneline
®
Chassis Nomenclature
The Zoneline chassis is identified by a model number defining the type of unit, cooling capacity, electrical information and optional features
included on the unit. When specifying or ordering the Zoneline chassis the use of this nomenclature will assure receiving the correct unit.
Example
A Z 2 5 E 0 9 E 4 P
A Z 5 5 H 1 2 D A D
Zoneline
®
Packaged Terminal Chassis
Chassis Series
25 - Deluxe Line Cool/Electric Heat
35 - Deluxe Line Heat Pump
55 - Premium Line Heat Pump
Unit Type
E - Cooling with Electric Resistance Heat
H - Heat Pump with Electric Resistance Heat
Nominal Cooling Capacity
07 - 7,000 BTUH Cooling 12 - 12,000 BTUH Cooling
09 - 9,000 BTUH Cooling 15 - 15,000 BTUH Cooling
Special Features
B - Base Unit
C - Corrosion Treated
D - Internal Condensate Removal
(ICR) System (Heat Pump Models Only)
P - Dry Air 25
5500 Universal Power Connection
(see Premium Series Models - see page 53)
2500, Dry Air 25 & 3500 Numeric
Designator of Heater Size
(see Heater Table Below)
Voltage/Phase/Frequency
D - 230/208 Volt Single Phase 60 Hz
E - 265 Volt Single Phase 60 Hz
Heater Heater Minimum
Voltage Amps Designator Watts KWH Ampacity BTUH
230/208 11.1/10.0 2 2550/2090 2.55/2.09 15 8,600/7,100
230/208 15.0/13.6 3 3450/2820 3.45/2.82 20 11,700/9,600
230/208 21.7/19.7 5 5000/4090 5.00/4.09 30 17,000/13,900
265 9.6 3 2550 2.55 15 8,600
265 14.0 4 3700 3.7 20 12,600
265 18.9 5 5000 5.0 30 17,000
Heater Table
2500 Series Units Dry Air 25
230/208V Models AZ25E07D AZ25E09D AZ25E12D AZ25E15D AZ25E07D*P AZ25E09D*P AZ25E12D*P
Capacity
Cooling BTUH 7,100/6,900 9,000/8,800 11,700/11,500 14,600/14,300 6,800/6,600 8,600/8,400 11,200/11,000
EER (BTU/Watt) 11.8/11.8 11.5/11.5 10.9/10.9 9.6/9.6 11.1/11.1 10.8/10.8 10.2/10.2
Dehumidification Pts/Hr 1.7 2.7 3.6 4.5 2.2 3.4 4.5
Sensible Heat Ratio @ 230 Volts 75% 68% 67% 67% 66% 58% 57%
CFM, Indoor Fan High 240 260 270 310 230 230 240
CFM, Indoor Fan Low 210 230 240 280 200 200 210
Vent CFM 40/35 65/60 70/65 70/65 40/35 65/60 70/65
Power/Ratings
Power Factor 95 96 97 94 95 96 97
Watts 600/585 785/765 1075/1055 1520/1490 600/585 785/765 1075/1055
Amperes, F.L. 2.8/3.0 3.6/3.9 4.9/5.3 7.0/7.5 2.8/3.0 3.6/3.9 4.9/5.3
Amperes, L.R. 19.0 21.0 33.0 38.0 19.0 21.0 33.0
Weight (Net/Ship)** 92/108 93/109 101/117 111/127 98/114 99/115 107/123
Sound Transmission Class (STC) 28 28 28 28 28 28 28
265V Models AZ25E07E AZ25E09E AZ25E12E AZ25E15E AZ25E07E*P AZ25E09E*P AZ25E12E*P
Capacity
Cooling BTUH 7,100 9,000 11,700 14,600 6,800 8,600 11,200
EER (BTU/Watt) 11.8 11.5 10.9 9.6 11.1 10.8 10.2
Dehumidification Pts/Hr 1.7 2.7 3.6 4.5 2.2 3.4 4.5
Sensible Heat Ratio @ 265 Volts 75% 68% 67% 67% 66% 58% 57%
CFM, Indoor Fan High 240 260 270 310 230 230 240
CFM, Indoor Fan Low 210 230 240 280 200 200 210
Vent CFM 40 65 70 70 40 65 70
Power/Ratings
Power Factor 96 94 94 96 96 94 94
Watts 600 785 1075 1520 600 785 1075
Amperes, F.L. 2.4 3.2 4.4 6.0 2.4 3.2 4.4
Amperes, L.R. 16.0 18.0 24.0 31.0 16.0 18.0 24.0
Weight (Net/Ship)** 92/108 93/109 101/117 111/127 98/114 99/115 107/123
Sound Transmission Class (STC) 28 28 28 28 28 28 28
*For Dry Air 25 model number, designate respective heater number using chart above, followed by the letter P.
** ICR adds 3 pounds to unit weight
Deluxe Series - Cooling & Electric Heat Dry Air 25