This thermostat is compatible with the following systems:
1) Turn power off at the heating/cooling system.

2) Remove old thermostat, but leave wallplate with wires attached.

If any wires are not attached to your old thermostat or are attached to a terminal marked C or C1, they will not be connected to your new thermostat. Wrap the bare metal end of each of these wires with electrical tape, so it cannot touch and short other wires.

Disconnect wires and remove the old wallplate only after all wires are labeled. Wrap the wires around a pencil to prevent them from falling though the wall opening.
1) Loosen the locking screw at the bottom of the thermostat. Note that the screw is captive and cannot be removed from the wallplate.
2) Separate the thermostat from the wallplate as per Figure 1.
3) Position the wallplate against the wall and mark hole positions with a pencil.
NOTE: Levelling is for esthetics only and will not affect the performance of the thermostat.
4) Drill holes at the marked positions and insert supplied wall anchors.
5) Pass the wires through the large opening located at the bottom center of the wallplate as per Figure 2.
6) Secure the wallplate to the wall with supplied mounting screws as per Figure 3.
7) Connect the wires to the terminals.

Conventional Systems (Typical Wiring)

Connect Wires (cont’d)
Conventional Systems (Alternate Wiring)

Heat Pump Systems with Auxiliary/Backup Heat (Typical Wiring)

Labels don’t match? See page 8.
Heat Pump Systems with Auxiliary/Backup Heat (Alternate Wiring)

Set jumper JP1, on the back of the thermostat, if you have connected a wire to the G terminal.

HG Leave the jumper in this factory-set position if you have a gas or oil furnace.
HE Place the jumper to this position if you have an electric furnace.
Incorrect jumper setting: An incorrect setting is noticeable in a gas or oil heating system. When heating starts, you will initially feel cold air coming out of the vents as the fan is running before the furnace has enough time to heat up the air.
Set jumper JP2, on the back of the thermostat, if you have a heat pump.

O Leave the jumper in this factory-set position if you have connected O wire to the O/B terminal.
B Place the jumper to this position if you have connected B wire to the O/B terminal.
Incorrect jumper setting: The heat pump operation will be reversed, i.e., it will cool in Heat mode and will heat in Cool mode.

Follow the procedure below to personalize and configure the thermostat according to the heating/ cooling system.

NOTE: If you do not press any button for 60 seconds while you are in the setup menu, the thermostat automatically saves any changes made and exits the menu. At any time you can save the changes and exit by pressing the Run button.
System Setup (cont’d)

1 Damage can occur if the compressor is restarted too soon after shutdown. This feature forces the compressor to wait 5 minutes before restarting. During the wait time, the message Cool On or Heat On flashes on the screen. When the safe wait time has elapsed, the message stops flashing and the compressor turns on.
2 Adaptive Intelligent RecoveryTM allows the thermostat to “learn” how long your furnace or air conditioner takes to reach the set temperature. Simply program the desired times and desired temperatures into the schedule. The thermostat will determine when to activate heating or cooling so that the desired temperature is attained at the desired time.
Reference file: Honeywell RTH2410B1001 5-1-1 Day Programmable Thermostat
Additionally, the document applies to other Honeywell models: RTH2410