54
ENGLISH
Compressor Input Current Limit
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn20” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”~”op10” Push the ‘’ button
Compressor Input Current Limit mode is set
Mode Compressor Input Current Limit
oFF 100 %
op1 95 %
op2 90 %
op3 85 %
op4 80 %
op5 75 %
op6 70 %
op7 65 %
op8 60 %
op9 55 %
op10 50 %
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn16” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“Fn19” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“on”,“oFF” Push the ‘’ button
Central Control Connection at Indoor
Unit side Mode is set
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn23” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“on” Push the ‘’ button
Base pan Heater operation mode is set
Base pan Heater operation (Fn 23)
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn21” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn22” Push the ‘’ button
Overall Defrost Operating in Low Mode is set
Setting Detail of function
Defualt OFF
Setting ON/OFF Control
Overall Defrost Operating in Low temperature
(Heating) (Fn 22)
Mode setting method
Compressor Input Current Limit Mode (Fn 20)
System Input Current Control
Mode setting method
Central Control Connection at Indoor Unit side (Fn 19)
Mode setting method
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, capacity may go down.
CAUTION
!
• Function to prevent freezing of ODU base pan in a cold area.
• Heater is accesory.(Sold separately)