ENGLISH
Installation Manual 83
Test Run
Sensor checking function judges whether the current temperature of indoor and outdoor unit sensors is right or
not. 3 indoor temperature sensors, 10 outdoor temperature sensor Note 1), 2 outdoor pressure sensors.
Sensor Checking Function
Note 1. Outdoor Unit number of temperature sensors is different according to each chassis.
Note 2. Please check the sensor that is found abnormal.
Note 3. Each step is displayed on the Main PCB LED.
Note 4. Please refer to the sensor error descriptions on the next page.
@
Start
NO
NO
NO
YES
YES
3 minutes
past after power
reset
DIP switch set
Press black button
for 2 seconds
Sensor Normal
Display Error
Press black button for 2 seconds
Press black button for
5 seconds
End
Data Reset and Wait
All DIP switches OFF and press black
button for 2 seconds
Setting 1 Setting 2 Setting 3 Setting 4
Refrigerant
Auto Recharge
Refrigerant
Auto decide
E: Cooling
F: Heating
Start Inspection of each Function
Setting 1 Setting 2 Setting 3 Setting 4
Note 3)
DIP Switch Settings
Warning : Please reset before starting this function
- Setting1
(Refrigerant Auto Recharge)
- Setting2
(Refrigerant Quantity Auto Decide)
- Setting3
(Integrated Test Run - cooling)
- Setting4
(Integrated Test Run - heating)
WARNING
1. Please confirm if auto addressing function was executed. (Check the number of installed indoor units)
2. Error may occur when the sensor is abnormal according to the installed location and the temperature
conditions. When error occurs, please check each sensor and decide faultiness.
UX2(1 Comp) UX3 (2 Comp)
Heat Pump 6 7