8 HR Unit
Installation
CAUTION:
HR Unit should be installed that top side is facing up. If not, it may cause failure of the product.
Ceiling
Top side
Top side
Top side
WARNING:
Before brazing work, remove gas in the HR Unit by cutting the three pipes in the small circles on the figure.
If not, it may cause injuries.
Remove the caps before connecting pipes.
Gas pipe Ø15.88(5/8) – Ø12.7(1/2)
Liquid pipe Ø9.52(3/8) – Ø6.35(1/4)
Brazing Type
Liquid pipe
Liquid pipe
Low pressure gas pipe
Low pressure gas pipe
High pressure gas pipe
High pressure gas pipe
Liquid pipe
Low pressure gas pipe
High pressure gas pipe
(Brazing Type)
CAUTION:
• Whenever connecting the indoor units with the HR unit, install the indoor units in numerical order
from No.1.
Ex) In case of installing 3 indoor units : No. 1, 2, 3 (O), No. 1, 2, 4 (X), No.1, 3, 4 (X), No.2, 3, 4 (X).
• Take care of no thermal damage on the valves of the HR uint.
(Especially packing part of valve) Wrap the valve with a wet towel when brazing it.
After considering the indoor unit capacity,
determine the pipe sizes and cut the pipes connected to the indoor unit.
Cutting
Ø15.88 Ø12.7
Ø9.52 Ø6.35
Liquid Pipe
Gas pipe