3.4 Transformer Wiring
Install the transformer using the instructions provided
by the manufacturer. Size the transformer to the damper
requirements. The zone panel has a built-in, self-resetting
fuse. The maximum damper power per panel is 35 VA at
24 VAC.
Connect the transformer to the zone panel as shown.
Note: Additional dampers or dampers with a higher current draw will require the use of a separate
slave relay.
24V
24C
CC
HOT
Dedicated
Zoning Transformer
Zone
Panel
6
3.5 Conventional System Wiring
Note: For a heat pump system, see Section 3.6.
Connect a conventional heating system to
the zone panel as shown.
For a single stage heating and cooling
system, the 2nd stage connections are
not used.
For a system using a dual transformer,
open jumper J1 (see Configuration
section, Figure 4). Make sure the neutrals
(common) are connected.
RH
RC
Y
G
W1
EH
W2
O/B
C
C
HOT
1st stage
compressor
control
1st stage
fan
control
1st stage
heat
control
2nd stage
heat
control
24 VAC