Braeburn 140202 2-Zone Control Panel Model

User Manual - Page 6

For 140202.

PDF File Manual, 36 pages, Read Online | Download pdf file

140202 photo
Loading ...
Loading ...
Loading ...
3.4 Transformer Wiring
Install the transformer using the instructions provided
by the manufacturer. Size the transformer to the damper
requirements. The zone panel has a built-in, self-resetting
fuse. The maximum damper power per panel is 35 VA at
24 VAC.
Connect the transformer to the zone panel as shown.
Note: Additional dampers or dampers with a higher current draw will require the use of a separate
slave relay.
24V
24C
CC
HOT
Dedicated
Zoning Transformer
Zone
Panel
6
3.5 Conventional System Wiring
Note: For a heat pump system, see Section 3.6.
Connect a conventional heating system to
the zone panel as shown.
For a single stage heating and cooling
system, the 2nd stage connections are
not used.
For a system using a dual transformer,
open jumper J1 (see Configuration
section, Figure 4). Make sure the neutrals
(common) are connected.
RH
RC
Y
G
W1
EH
W2
O/B
C
C
HOT
1st stage
compressor
control
1st stage
fan
control
1st stage
heat
control
2nd stage
heat
control
24 VAC