The Braeburn Zoning Reference Guide 12 Part No. RG-0508-001
Braeburn 3-Zone Panel Indicators
Function Color Callout Description
Thermostat 1,2 and 3 R Red 1 Zone thermostats power monitor
Thermostat 1,2 and 3 Y Yellow 1 Zone thermostats compressor call
Thermostat 1,2 and 3 G Green 1 Zone thermostats fan call
Thermostat 1,2 and 3 W White 1 Zone thermostats heating call
Panel Power Green 2 Indicates 24VAC available to panel
Equipment Rh Power Red 3 Indicates Power at equipment Rh terminal
Equipment Rc Power Red 3 Indicates Power at equipment Rc terminal
Equipment Y1 Yellow 4 Indicates a fi rst stage compressor call
Equipment Y2 Yellow 4 Indicates a second stage compressor call
Equipment G Yellow 4 The zone panel has turned on Fan Stage 1
Equipment G2 Yellow 4 The zone panel has turned on Fan Stage 2
W1/E/W3 White 4 Heating call depending on confi guration
W2 / O - B Orange 4 Heating or valve control depending on
confi guration
EM Heat Yellow 5 Indicates Emergency Heat has been
activated
Zone 1 Damper Dual 6 Red when closed; green when open
Zone 2 Damper Dual 6 Red when closed; green when open
Zone 3 Damper Dual 6 Red when closed; green when open
Panel Heartbeat Green 7 Flashing once per second when normal