1. Point out the regulator’s vent to the customer (or
vent assembly or vent tube), and 

Tell the customer to be sure to check the vent
opening after a freezing rain, sleet storm, or snow to
make sure ice has not formed in the vent.
2. Show the customer the shutoff valve on the
container. The customer should close this valve
immediately if gas can be smelled, appliance pilot
lights fail to stay on or appear higher than usual, or
any other abnormal situation occurs.
3. Tell the customer to call your company to service the
regulator. If the regulator vents gas or a leak
develops in the system, only a qualied gas
serviceman should install or service the regulator.


This instruction manual covers installation and
maintenance for the following high or low-pressure
regulators: Types 912N, 912H, Y200N, Y200H,
and R922N.

The Types 912H and Y200H regulators are designed for
high-pressure (pounds per square inch) vapor service
and are not to be used for liquid service. Both are U.L.
listed, and they are normally painted red.
Types 912N, Y200N, and R922N can be used for either
high-pressure or low-pressure (inches of water column)
service. They are not to be used for liquid service. “N”
sufx regulators are not U.L. listed and are normally
painted gray (low-pressure) or red (high-pressure).

The Specications table lists the specications for the
regulators. Contact the factory if the regulators are to be
used on any service other than LP-Gas, Natural Gas, or
Air. Temperature limits are -20° to 160°F (-29° to 71°C).
Maximum inlet pressure is 250 psig (17,2 bar).






OUTLET






Figure 1. Typical Regulator Congurations
!

!
