Dimplex DAB15W DAB 1.5m High-output Air Barrier Hydronic LPHW

Product's Documents

Below are documents related to this product, you can read online or download:
User Manual Other Documents
  • Commercial Brochure - (English) Download
  • Air Curtain Brochure - (English) Download
  • CAB %26 DAB Air Barrier Instr %28UK%29 Issue 9 - (English) Download
  • CAB DAB Air Curtain FAQs Issue 003 - (English) Download
  • CAB DAB Air Curtain FAQs Issue 002 - (English) Download
  • DAB W Spec Sheet - (English) Download

User Manual

This is the main product document for model DAB15W.

The file format is pdf, 3 pages, you can download this manual here .

background
ContactDetails
Pleasenotethatsomeofthecontactdetailson
thisPDFdocumentmaynotbecurrent.
Pleaseusethefollowingdetailsifyouneedto
contactus:
Telephone:08448793588
Email:[email protected]
Thecustomersupportsectionofourwebsitealsofeaturesawide
rangeofinformationwhichmaybeofusetoyouandisavailable
24hoursaday.Itincludes:
Operatingandinstallationinstructions
Easy‘Howtouse’guidesforstorageheaters
Serviceandrepairs
Where
tobuyourproducts
Literaturedownloads
Heatingrequirementcalculator
Visit‐www.dimplex.co.uk/support
A division of GDC Group Ltd
Millbrook House Grange Drive Hedge End Southampton SO30 2DF
www.dimplex.co.uk
Re
g
istered No: 1313016 En
g
land
VAT GB 287 1315 50004
EEE Producer Registration Number –
WEE/GE0057TS
Paper from sustainable sources
background
Installation and Operating Instructions
Dimplex Air Curtain - Single Phase Conversion Kit - CAB1PN
Suitable for use with the CAB10E, CAB15E & DAB10E (Surface & Recessed)
08/19538/0 Issue 4
THESE INSTRUCTIONS SHOULD BE READ CAREFULLY AND RETAINED FOR FUTURE REFERENCE
IMPORTANT SAFETY ADVICE
ENSURE THE APPLIANCE IS EARTHED.
This work should only be carried out by a competent
electrician.
Always disconnect the supply before working on the
product.
Ensure the supply cables are of adequate current
carrying capacity and are protected by a suitable
fuse.
Ensure all wiring is xed clear of all moving parts and
heat sources.
This kit is not designed for use with DAB15 models.
This conversion kit consists of:
8 x 100mm x 2.5mm tie wraps
4 x Moss Plastic tie wrap clips
2 x Neutral link cable
1 x Live link cable
The instructions for the conversion kit should be
read in conjunction with the ‘Dimplex Air Curtain’
Instructions. All ‘Safety Advice’ to be heeded before
tting this kit.
General
The CAB10E, CAB15E and DAB10E are primarlity
designed for 400V~ 3P&N 50Hz operation, however in
the instance where it is not possible to utilise a 3-phase
supply, the units can be de-rated to a ½ heat stiing for
operation via a 230V~ 1P&N 50Hz supply.
Procedure
1. remove the outlet grille assemblies and, where
necessary, the bottom panel and inlet grille to gain
access to the element banks and terminal blocks as
shown in Fig. 1 below.
2. Remove the rst half heat (H1) star connection link
cable from both sides of each elmenet bank (Fig. 2 shows
the bottom red (H1)) star connection link cable replaced
with the supplied neutral star connection link cable.
3. Fix the push on clips (two on
either side) to the inside of the
pressure plate as shown in Fig.
1 (the supplied push on clips
are a press t into their xing
holes (ø3.5mm). Proceed
to attach the neutral star link
connection cable to the push
on clips using the tie wraps as
shown in Fig. 3 below.
Note: Due to extra cable length (for CAB15E) it is
necessary to loop the slack cable in the pressure plate and
secure it using a supplied tie wrap as shown in Fig. 1.
4. Connect the brass ferrule end of the neutral link cable
into the N of the terminal block (along with the Neutral of
the single phase supply) as shown in Fig. 4.
5. Also shown in Fig. 4 is the supplied (brown) Live link
cable, this should be linked from L1 (with connection of
Live from single phase supply) to L2 & L3.
The earth cable is connected as normal within the
terminal block (ensure the supply cable is xed
appropriately within the back panel using the correct
sized gland).
6. Check all switch settings operate, as stated within
the evaluation table (overleaf). Note: H2 should still be
connected (as per remote switch connection instruction
manual) even though it will not be utilised (this still allows
a ½ heat setting when switched to full heat rather than no
heat at all).
Figure 1.
Figure 2.
Figure 3.
Figure 4.
BLUE
RED
background
Once the above loadings and switch settings have been
con rmed as acceptable, proceed to replace the grille
assemblies, and where necessary, the bottom panel.
For reference purposes a full wiring schematic is detailed
above.
This product complies with European Safety Standard EN 60335-2-30, and European Standards EN 55014, EN 60555-2 and EN60555-3 for Electromagnetic Compatibility.
These cover the essential requirements of the EEC Directives 2006/95/EC and 2004/108/EC.
Please retain your receipt as proof of purchase.
© GDC Group Ltd. All rights reserved.
Material contained in this publication may not be reproduced in whole or in part, without prior permission in writing.
A division of the GDC Group Ltd, Millbrook House, Grange Drive, Hedge End, Southampton SO30 2DF
Dimplex,
Millbrook House,
Grange Drive,
Hedge End,
Southampton, SO30 2DF.
Tel: 0845 600 5111
Fax: 01489 773 050
Web-site www.dimplex.co.uk
Republic of Ireland 01 842 4833

Specifications