Safety Precautions 3
WARNING For Using Flammable Refrigerant
1. Installation(where refrigerant pipes are allowed)
- Any person who is involved with working on or breaking into a
refrigerant circuit should hold a current valid certificate from an
industry-accredited assessment authority, which authorises their
competence to handle refrigerants safely in accordance with an
industry recognised assessment specification.
- Maintenance and repair requiring the assistance of other skilled
personnel shall be carried out under the supervision of the person
competent in the use of flammable refrigerants.
- That the installation of pipe-work shall be kept to a minimum.
- That pipe-work shall be protected from physical damage.
- Where refrigerant pipes shall be compliance with national gas
regulations.
- That mechanical connections shall be accessible for mainte-
nance purposes.
- Be more careful that foreign matter(oil, water,etc) does not
enter the piping.
Also, when storing the piping, securely seal the opening by
pinching, taping, etc.
- Appliance shall be stored in a well ventilated area where the
room size corresponds to the room area as specifiec for opera-
tion.
- Appliance shall be stored in a well ventilated area where the
room size corresponds to the room area as specifiec for opera-
tion.
- Joints shall be tested with detection equipment with a capability
of 5 g/year of refrigerant or better, with the equipment in stand-
still and under operation or under a pressure of at least these
standstill or operation conditions after installation. Detachable
joints shall NOT be used in the indoor side of the unit(brazed,
welded joint could be used).
- In cases that require mechanical ventilation, ventilation open-
ings shall be kept clear of obstruction.
2. When a FLAMMABLE REFRIGERANT is used, the requirements
for installation space of appliance and /or ventilation require-
ments are determined according to
- the mass charge amount(M) used in the appliance,
- the installation location,
- the type of ventilation of the location or of the appliance.
- piping material, pipe routing, and installation shall include pro-
tection from physical damage in operation and service, and be in
compliance with national and local codes and standards, such as
ASHRAE 15, IAPMO Uniform Mechanical Code, ICC International
Mechanical Code, or CSA B52. All field joints shall be acces-
sible for inspection prior to being covered or enclosed.
- that protection devices, piping, and fittings shall be protected as
far as possible against adverse environmental efects, for example,
the danger of water collecting and freezing in relief pipes or the
accumulation of dirt and debris;
- that piping in refrigeration systems shall be so designed and
installed to minimize the likelihood of hydraulic shock damaging
the system;
- that steel pipes and components shall be protected against cor-
rosion with a rustproof coating before applying any insulation;
- that precautions shall be taken to avoid excessive vibration or
pulsation;
- the minimum floor area of the room shall be mentioned in the
form of a table or a single figure without reference to a formula;
- after completion of field piping for split systems, the field pipe-
work shall be pressure tested with an inert gas and then vacuum
tested prior to refrigerant charging, according to the following
requirements:
a. The minimum test pressure for the low side of the system shall
be the low side design pressure and the minimum test pressure
for the high side of the system shall be the high side design pres-
sure, unless the high side of the system can not be isolated from
the low side of the system in which case the entire system shall
be pressure tested to the low side design pressure.
b. The test pressure after removal of pressure source shall be
maintained for at least 1 h with no decrease of pressure indicated
by the test gauge, with test gauge resolution not exceeding 5%
of the test pressure.
c. During the evacuation test, after achieving a vacuum level
specified in the manual or less, the refrigeration system shall be
isolated from the vacuum pump and the pressure shall not rise
above 1500 microns within 10 min. The vacuum pressure level
shall be specified in the manual, and shall be the lessor of 500
microns or the value required for compliance with national and
local codes and standards, which may vary between residential,
commercial,and industrial buildings.
-- field-made refrigerant joints indoors shall be tightness tested
according to the following requirements: The test method shall
have a sensitivity of 5 grams per year of refrigerant or better
under a pressure of at least 0,25 times the maximum allowable
pressure. No leak shall be detected.
-- Any servicing shall be performed only as recommended by the
manufacturer.
3. Qualification of workers
Any maintenance, service and repair operations must be required
qualification of the working personnel. Every working procedure
that afects safety means shall only be carried out by competent
persons that joined the training and achieved competence should
be documented by a certificate. The training of these procedures
is carried out by national training organizations or manufacturers
that are accredited to teach the relevant national competency
standards that may be set in legislation. All training shall follow
the ANNEX HH requirements of UL 60335-2-40 4th Edition.
Examples for such working procedures are:
• breaking into the refrigerating circuit;
• opening of sealed components;
• opening of ventilated enclosures.