This is the main product document for model SENA-36HF-F99999. Additionally, the document applies to other Senville models: SENA-36HF-F99999, SENA-36HF-F66666, SENA-36HF-F66666-1X25, SENA-36HF-F66666-2X25, SENA-36HF-F66666-3X25, SENA-36HF-F66666-4X25, SENA-36HF-F66666-5X25, SENA-36HF-F66666-1X50, SENA-36HF-F66666-2X50, SENA-36HF-F66666-3X50, SENA-36HF-F66666-4X50, SENA-36HF-F66666-5X50, SENA-36HF-F66669, SENA-36HF-F66669-1X25, SENA-36HF-F66669-2X25, SENA-36HF-F66669-3X25, SENA-36HF-F66669-4X25, SENA-36HF-F66669-5X25, SENA-36HF-F66669-1X50, SENA-36HF-F66669-2X50, SENA-36HF-F66669-3X50, SENA-36HF-F66669-4X50, SENA-36HF-F66669-5X50, SENA-36HF-F666612, SENA-36HF-F666612-1X25, SENA-36HF-F666612-2X25, SENA-36HF-F666612-3X25, SENA-36HF-F666612-4X25, SENA-36HF-F666612-5X25, SENA-36HF-F666612-1X50, SENA-36HF-F666612-2X50, SENA-36HF-F666612-3X50, SENA-36HF-F666612-4X50, SENA-36HF-F666612-5X50, SENA-36HF-F666618, SENA-36HF-F666618-1X25, SENA-36HF-F666618-2X25, SENA-36HF-F666618-3X25, SENA-36HF-F666618-4X25, SENA-36HF-F666618-5X25, SENA-36HF-F666618-1X50, SENA-36HF-F666618-2X50, SENA-36HF-F666618-3X50, SENA-36HF-F666618-4X50, SENA-36HF-F666618-5X50, SENA-36HF-F99999-1X25, SENA-36HF-F99999-2X25, SENA-36HF-F99999-3X25, SENA-36HF-F99999-4X25, SENA-36HF-F99999-5X25, SENA-36HF-F99999-1X50, SENA-36HF-F99999-2X50, SENA-36HF-F99999-3X50, SENA-36HF-F99999-4X50, SENA-36HF-F99999-5X50, SENA-36HF-F999912, SENA-36HF-F999912-1X25, SENA-36HF-F999912-2X25, SENA-36HF-F999912-3X25, SENA-36HF-F999912-4X25, SENA-36HF-F999912-5X25, SENA-36HF-F999912-1X50, SENA-36HF-F999912-2X50, SENA-36HF-F999912-3X50, SENA-36HF-F999912-4X50, SENA-36HF-F999912-5X50, 48K

The file format is pdf, 160 pages, you can download this manual here .

background
MULTI OUTDOOR UNIT INVERTER SERIES
SM_ODUMULTI_R454B_3D INV_US1_NA_2403
SERVICE MANUAL
background
background
Table of Contents
1. Safety Precautions
1. Precautions
2. Information servicing(For flammable materials)
2. Specifications
1. Model Reference
2. Pipe Length and Drop Height
3. Indoor units combination
4. Refrigeration Cycle Diagrams
5. Electrical Wiring Diagrams
3. Electronic Functions
1 Abbreviation
2 Main Protection
4. Outdoor Unit Disassembly
1. Outdoor Unit Table
2. Dimension
3. Outdoor Unit Disassembly
5. Troubleshooting
1. Safety Caution
2. General Troubleshooting
3. Outdoor Unit Point Check Function
4. Quick Maintenance by Error Code
5. Troubleshooting by Error Code
6. Check Procedures
Appendix
i) Temperature Sensor Resistance Value Table for TP (°C – K)
ii) Other Temperature Sensor Resistance Value Table (°C – K)
iii) Pressure On Service Port
background
background
Contents
1. Precautions .............................................................................................................2
2. Information servicing(For flammable materials) .................................................4
Safety Precautions
background
Safety Precautions 2
1. Precautions
To prevent personal injury, or property or unit damage,
adhere to all precautionary measures and instructions
outlined in this manual. Before servicing a unit, refer to this
service manual and its relevant sections.
Failure to adhere to all precautionary measures listed in this
section may result in personal injury, damage to the unit or
to property, or in extreme cases, death.
WARNING indicates a potentially hazardous
situation which if not avoided could result in serious
personal injury, or death.
CAUTION indicates a potentially hazardous situation
which if not avoided could result in minor or
moderate personal injury, or unit damage.
1.1 In case of Accidents or Emergency
WARNING
• If a gas leak is suspected, immediately turn off the
gas and ventilate the area if a gas leak is suspected
before turning the unit on.
• If strange sounds or smoke is detected from the unit,
turn the breaker off and disconnect the power supply
cable.
• If the unit comes into contact with liquid, contact an
authorized service center.
• If liquid from the batteries makes contact with skin or
clothing, immediately rinse or wash the area well with
clean water.
• Do not insert hands or other objects into the air inlet
or outlet while the unit is plugged in.
• Do not operate the unit with wet hands.
• Do not use a remote controller that has previously
been exposed to battery damage or battery leakage.
CAUTION
• Clean and ventilate the unit at regular intervals when
operating it near a stove or near similar devices.
• Do not use the unit during severe weather conditions.
If possible, remove the product from the window
before such occurrences.
1.2 Pre-Installation and Installation
WARNING
• Use this unit only on a dedicated circuit.
• Damage to the installation area could cause the unit
to fall, potentially resulting in personal injury, prop-
erty damage, or product failure.
• Only qualified personnel should disassemble, install,
remove, or repair the unit.
• Only a qualified electrician should perform electri-
cal work. For more information, contact your dealer,
seller, or an authorized service center.
CAUTION
• While unpacking be careful of sharp edges around
the unit as well as the edges of the fins on the con-
denser and evaporator.
1.3 Operation and Maintenance
WARNING
• Do not use defective or under-rated circuit breakers.
• Ensure the unit is properly grounded and that a
dedicated circuit and breaker are installed.
• Do not modify or extend the power cable. Ensure
the power cable is secure and not damaged during
operation.
• Do not unplug the power supply plug during
operation.
• Do not store or use flammable materials near the
unit.
• Do not open the inlet grill of the unit during
operation.
• Do not touch the electrostatic filter if the unit is
equipped with one.
• Do not block the inlet or outlet of air flow to the unit.
• Do not use harsh detergents, solvents, or similar items
to clean the unit. Use a soft cloth for cleaning.
• Do not touch the metal parts of the unit when
removing the air filter as they are very sharp.
• Do not step on or place anything on the unit or
outdoor units.
• Do not drink water drained from the unit
• Avoid direct skin contact with water drained from the
unit.
• Use a firm stool or step ladder according to
manufacturer procedures when cleaning or
maintaining the unit.
CAUTION
• Do not install or operate the unit for an extended
period of time in areas of high humidity or in an
environment directly exposing it to sea wind or salt
spray.
• Do not install the unit on a defective or damaged
installation stand, or in an unsecure location.
• Ensure the unit is installed at a level position
• Do not install the unit where noise or air discharge
created by the outdoor unit will negatively impact the
environment or nearby residences.
• Do not expose skin directly to the air discharged by
the unit for prolonged periods of time.
• Ensure the unit do not operate in areas water or
other liquids.
• Ensure the drain hose is installed correctly to ensure
proper water drainage.
• When lifting or transporting the unit, it is
recommended that two or more people are used for
this task.
• When the unit is not to be used for an extended time,
disconnect the power supply or turn off the breaker.
background
Safety Precautions 3
WARNING For Using Flammable Refrigerant
1. Installation(where refrigerant pipes are allowed)
- Any person who is involved with working on or breaking into a
refrigerant circuit should hold a current valid certificate from an
industry-accredited assessment authority, which authorises their
competence to handle refrigerants safely in accordance with an
industry recognised assessment specification.
- Maintenance and repair requiring the assistance of other skilled
personnel shall be carried out under the supervision of the person
competent in the use of flammable refrigerants.
- That the installation of pipe-work shall be kept to a minimum.
- That pipe-work shall be protected from physical damage.
- Where refrigerant pipes shall be compliance with national gas
regulations.
- That mechanical connections shall be accessible for mainte-
nance purposes.
- Be more careful that foreign matter(oil, water,etc) does not
enter the piping.
Also, when storing the piping, securely seal the opening by
pinching, taping, etc.
- Appliance shall be stored in a well ventilated area where the
room size corresponds to the room area as specifiec for opera-
tion.
- Appliance shall be stored in a well ventilated area where the
room size corresponds to the room area as specifiec for opera-
tion.
- Joints shall be tested with detection equipment with a capability
of 5 g/year of refrigerant or better, with the equipment in stand-
still and under operation or under a pressure of at least these
standstill or operation conditions after installation. Detachable
joints shall NOT be used in the indoor side of the unit(brazed,
welded joint could be used).
- In cases that require mechanical ventilation, ventilation open-
ings shall be kept clear of obstruction.
2. When a FLAMMABLE REFRIGERANT is used, the requirements
for installation space of appliance and /or ventilation require-
ments are determined according to
- the mass charge amount(M) used in the appliance,
- the installation location,
- the type of ventilation of the location or of the appliance.
- piping material, pipe routing, and installation shall include pro-
tection from physical damage in operation and service, and be in
compliance with national and local codes and standards, such as
ASHRAE 15, IAPMO Uniform Mechanical Code, ICC International
Mechanical Code, or CSA B52. All field joints shall be acces-
sible for inspection prior to being covered or enclosed.
- that protection devices, piping, and fittings shall be protected as
far as possible against adverse environmental efects, for example,
the danger of water collecting and freezing in relief pipes or the
accumulation of dirt and debris;
- that piping in refrigeration systems shall be so designed and
installed to minimize the likelihood of hydraulic shock damaging
the system;
- that steel pipes and components shall be protected against cor-
rosion with a rustproof coating before applying any insulation;
- that precautions shall be taken to avoid excessive vibration or
pulsation;
- the minimum floor area of the room shall be mentioned in the
form of a table or a single figure without reference to a formula;
- after completion of field piping for split systems, the field pipe-
work shall be pressure tested with an inert gas and then vacuum
tested prior to refrigerant charging, according to the following
requirements:
a. The minimum test pressure for the low side of the system shall
be the low side design pressure and the minimum test pressure
for the high side of the system shall be the high side design pres-
sure, unless the high side of the system can not be isolated from
the low side of the system in which case the entire system shall
be pressure tested to the low side design pressure.
b. The test pressure after removal of pressure source shall be
maintained for at least 1 h with no decrease of pressure indicated
by the test gauge, with test gauge resolution not exceeding 5%
of the test pressure.
c. During the evacuation test, after achieving a vacuum level
specified in the manual or less, the refrigeration system shall be
isolated from the vacuum pump and the pressure shall not rise
above 1500 microns within 10 min. The vacuum pressure level
shall be specified in the manual, and shall be the lessor of 500
microns or the value required for compliance with national and
local codes and standards, which may vary between residential,
commercial,and industrial buildings.
-- field-made refrigerant joints indoors shall be tightness tested
according to the following requirements: The test method shall
have a sensitivity of 5 grams per year of refrigerant or better
under a pressure of at least 0,25 times the maximum allowable
pressure. No leak shall be detected.
-- Any servicing shall be performed only as recommended by the
manufacturer.
3. Qualification of workers
Any maintenance, service and repair operations must be required
qualification of the working personnel. Every working procedure
that afects safety means shall only be carried out by competent
persons that joined the training and achieved competence should
be documented by a certificate. The training of these procedures
is carried out by national training organizations or manufacturers
that are accredited to teach the relevant national competency
standards that may be set in legislation. All training shall follow
the ANNEX HH requirements of UL 60335-2-40 4th Edition.
Examples for such working procedures are:
• breaking into the refrigerating circuit;
• opening of sealed components;
• opening of ventilated enclosures.
background
Safety Precautions 4
2. Information servicing(For
flammable materials)
2.1 Checks to the area
• Prior to beginning work on systems containing flammable
refrigerants, safety checks are necessary to ensure that the
risk of ignition is minimized. For repair to the refrigerating
system, the following precautions shall be complied with
prior to conducting work on the system.
2.2 Work procedure
• Work shall be undertaken under a controlled procedure so
as to minimise the risk of a flammable gas or vapour being
present while the work is being performed.
2.3 General work area
• All maintenance staff and others working in the local area
shall be instructed on the nature of work being carried out.
Work in confined spaces shall be avoided.
2.4 Checking for presence of refrigerant
• The area shall be checked with an appropriate refrigerant
detector prior to and during work, to ensure the technician
is aware of potentially flammable atmospheres.
• Ensure that the leak detection equipment being used is
suitable for use with flammable refrigerants, i.e. no sparking,
adequately sealed or intrinsically safe.
2.5 Presence of fire extinguisher
• If any hot work is to be conducted on the refrigeration
equipment or any associated parts, appropriate fire
extinguishing equipment shall be available to hand. Have
a dry powder or CO2 fire extinguisher adjacent to the
charging area.
2.6 No ignition sources
• No person carrying out work in relation to a REFRIGERATING
SYSTEM which involves exposing any pipe work shall use
any sources of ignition in such a manner that it may lead
to the risk of fire or explosion. All possible ignition sources,
including cigarette smoking, should be kept sufciently far
away from the site of installation, repairing, removing and
disposal, during which refrigerant can possibly be released to
the surrounding space. Prior to work taking place, the area
around the equipment is to be surveyed to make sure that
there are no flammable hazards or ignition risks.
• “No Smoking” signs shall be displayed.
2.7 Ventilated area
• Ensure that the area is in the open or that it is adequately
ventilated before breaking into the system or conducting any
hot work. A degree of ventilation shall continue during the
period that the work is carried out. The ventilation should
safely disperse any released refrigerant and preferably expel
it externally into the atmosphere.
2.8 Checks to the refrigeration equipment
• Where electrical components are being changed, they shall
be fit for the purpose and to the correct specification. At all
times the manufacturer’s maintenance and service guidelines
shall be followed. If in doubt consult the manufacturer’s
technical department for assistance. The following
checks shall be applied to installations using FLAMMABLE
REFRIGERANTS:
• the actual refrigerant charge is in accordance with the
room size within which the refrigerant containing parts
are installed;
• the ventilation machinery and outlets are operating
adequately and are not obstructed;
• if an indirect refrigerating circuit is being used, the
secondary circuits shall be checked for the presence of
refrigerant;
• marking to the equipment continues to be visible and
legible, marking and signs that are illegible shall be
corrected;
• refrigeration pipe or components are installed in a
position where they are unlikely to be exposed to any
substance which may corrode refrigerant containing
components, unless the components are constructed of
materials which are inherently resistant to being corroded
or are suitably protected against being so corroded.
2.9 Checks to electrical devices
• Repair and maintenance to electrical components shall
include initial safety checks and component inspection
procedures. If a fault exists that could compromise safety,
then no electrical supply shall be connected to the circuit
until it is satisfactorily dealt with. If the fault cannot be
corrected immediately but it is necessary to continue
operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment so all
parties are advised.
Initial safety checks shall include:
• that capacitors are discharged: this shall be done in a safe
manner to avoid possibility of sparking;
• that there no live electrical components and wiring
are exposed while charging, recovering or purging the
system;
• that there is continuity of earth bonding.
2.10 Sealed electrical components shall be
replaced
2.11 Intrinsically safe components must be
replaced
background
Safety Precautions 5
2.12 Cabling
• Check that cabling will not be subject to wear, corrosion,
excessive pressure, vibration, sharp edges or any other
adverse environmental effects. The check shall also take
into account the effects of aging or continual vibration from
sources such as compressors or fans.
2.13 Detection of flammable refrigerants
• Under no circumstances shall potential sources of ignition be
used in the searching for or detection of refrigerant leaks. A
halide torch (or any other detector using a naked flame) shall
not be used.
• The following leak detection methods are deemed
acceptable for refrigerant systems. Electronic leak detectors
may be used to detect refrigerant leaks but, in the case
of FLAMMABLE REFRIGERANTS, the sensitivity may not be
adequate, or may need re-calibration. (Detection equipment
shall be calibrated in a refrigerant-free area.) Ensure that
the detector is not a potential source of ignition and is
suitable for the refrigerant used. Leak detection equipment
shall be set at a percentage of the LFL of the refrigerant
and shall be calibrated to the refrigerant employed, and
the appropriate percentage of gas (25 % maximum) is
confirmed. Leak detection fluids are also suitable for use
with most refrigerants but the use of detergents containing
chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
NOTE Examples of leak detection fluids are
- bubble method,
- fluorescent method agents.
• If a leak is suspected, all naked flames shall be removed/
extinguished.
• If a leakage of refrigerant is found which requires brazing,
all of the refrigerant shall be recovered from the system, or
isolated (by means of shut of valves) in a part of the system
remote from the leak. See the following instructions of
removal of refrigerant.
2.14 Removal and evacuation
• When breaking into the refrigerant circuit to make repairs
or for any other purpose, conventional procedures shall be
used. However, it is important that best practice is followed
since flammability is a consideration.
• The following procedure shall be adhered to:
• safely remove refrigerant following local and national
regulations;
• evacuate;
• purge the circuit with inert gas(optional for A2L);
• evacuate(optional for A2L);
• continuously flush or purge with inert gas when using
flame to open circuit; and open the circuit;
• The refrigerant charge shall be recovered into the correct
recovery cylinders if venting is not allowed by local and
national codes. For appliances containing flammable
refrigerants, the system shall be purged with oxygen-
free nitrogen to render the appliance safe for flammable
refrigerants. This process might need to be repeated several
times. Compressed air or oxygen shall not be used for
purging refrigerant systems.
• For appliances containing flammable refrigerants,
refrigerants purging shall be achieved by breaking the
vacuum in the system with oxygen-free nitrogen and
continuing to fill until the working pressure is achieved, then
venting to atmosphere, and finally pulling down to a vacuum
(optional for A2L). This process shall be repeated until no
refrigerant is within the system (optional for A2L). When the
final oxygen-free nitrogen charge is used, the system shall
be vented down to atmospheric pressure to enable work to
take place.
• The outlet for the vacuum pump shall not be close to any
potential ignition sources, and ventilation shall be available.
2.15 Charging procedures
• In addition to conventional charging procedures, the
following requirements shall be followed:
• Works shall be undertaken with appropriate tools only (In
case of uncertainty, please consult the manufacturer of
the tools for use with flammable refrigerants)
• Ensure that contamination of different refrigerants does
not occur when using charging equipment. Hoses or lines
shall be as short as possible to minimize the amount of
refrigerant contained in them.
• Cylinders shall be kept upright.
• Ensure that the refrigeration system is earthed prior to
charging the system with refrigerant.
• Label the system when charging is complete(if not
already).
• Extreme care shall be taken not to overfill the
refrigeration system.
• Prior to recharging the system it shall be pressure tested
with OFN. The system shall be leak tested on completion
of charging but prior to commissioning. A follow up
leak test shall be carried out prior to leaving the site.
2.16 Decommissioning
Before carrying out this procedure, it is essential that the
technician is completely familiar with the equipment and all its
detail. It is recommended good practice that all refrigerants are
recovered safely. Prior to the task being carried out, an oil and
refrigerant sample shall be taken in case analysis is required prior
to re-use of recovered refrigerant. It is essential that electrical
power is available before the task is commenced.
• Become familiar with the equipment and its operation.
• Isolate system electrically.
• Before attempting the procedure ensure that:
• mechanical handling equipment is available, if required,
for handling refrigerant cylinders;
• all personal protective equipment is available and being
background
Safety Precautions 6
used correctly;
• the recovery process is supervised at all times by a
competent person;
• recovery equipment and cylinders conform to the
appropriate standards.
• Pump down refrigerant system, if possible.
• If a vacuum is not possible, make a manifold so that
refrigerant can be removed from various parts of the system.
• Make sure that cylinder is situated on the scales before
recovery takes place.
• Start the recovery machine and operate in accordance with
manufacturer’s instructions.
• Do not overfill cylinders. (No more than 80 % volume liquid
charge).
• Do not exceed the maximum working pressure of the
cylinder, even temporarily.
• When the cylinders have been filled correctly and the process
completed, make sure that the cylinders and the equipment
are removed from site promptly and all isolation valves on
the equipment are closed off.
• Recovered refrigerant shall not be charged into another
refrigeration system unless it has been cleaned and checked.
2.17 Labelling
• Equipment shall be labelled stating that it has been de-
commissioned and emptied of refrigerant. The label shall be
dated and signed. For appliances containing FLAMMABLE
REFRIGERANTS, ensure that there are labels on the
equipment stating the equipment contains FLAMMABLE
REFRIGERANT.
2.18 Recovery
• When removing refrigerant from a system, either for
servicing or decommissioning,
• it is recommended good practice that all refrigerants are
removed safely.
• When transferring refrigerant into cylinders, ensure that
only appropriate refrigerant recovery cylinders are employed.
Ensure that the correct number of cylinders for holding the
total system charge is available. All cylinders to be used
are designated for the recovered refrigerant and labelled
for that refrigerant (i. e. special cylinders for the recovery
of refrigerant). Cylinders shall be complete with pressure-
relief valve and associated shut-of valves in good working
order. Empty recovery cylinders are evacuated and, if
possible,cooled before recovery occurs.
• The recovery equipment shall be in good working order
with a set of instructions concerning the equipment that
is at hand and shall be suitable for the recovery of the
flammable refrigerant. If in doubt the manufacturer should
be consulted. In addition, a set of calibrated weighing scales
shall be available and in good working order. Hoses shall be
complete with leak-free disconnect couplings and in good
condition.
• The recovered refrigerant shall be processed according
to local legislation in the correct recovery cylinder, and
the relevant waste transfer note arranged. Do not mix
refrigerants in recovery units and especially not in cylinders.
• If compressors or compressor oils are to be removed,
ensure that they have been evacuated to an acceptable
level to make certain that flammable refrigerant does not
remain within the lubricant. The compressor body shall not
be heated by an open flame or other ignition sources to
accelerate this process. When oil is drained from a system, it
shall be carried out safely.
2.19 Transportation, marking and storage
for units
1. Transport of equipment containing flammable refrigerants
Compliance with the transport regulations
2. Marking of equipment using signs
Compliance with local regulations
3. Disposal of equipment using flammable refrigerants
Compliance with national regulations
4. Storage of equipment/appliances
The storage of equipment should be in accordance with the
manufacturer’s instructions.
5. Storage of packed (unsold) equipment
Storage package protection should be constructed such that
mechanical damage to the equipment inside the package will
not cause a leak of the refrigerant charge. The maximum number
of pieces of equipment permitted to be stored together will be
determined by local regulations.
background
Contents
1. Model Reference ....................................................................................................2
2. Pipe Length and Drop Height ...............................................................................3
3. Indoor units combination .....................................................................................6
4. Refrigeration Cycle Diagrams .............................................................................18
5. Electrical Wiring Diagrams ..................................................................................20
Specifications
background
Specifications 2
1. Model Reference
Refer to the following table to determine the specific outdoor unit model.
Outdoor Unit Model Capacity (Btu/h) Power Supply
M3OX430-18HFN10-M1 18k
208/230V~, 60Hz, 1Phase
M3OD31-18HFN10-M1X
18k Hyper
M3OD31-18HFN10-M1XD
M4OD31-24HFN10-M1XD 24k Hyper
M4OD30-27HFN10-M1
27k
M4OD30-27HFN10-M1D
M4OD31-27HFN10-M1X
27k Hyper
M4OD31-27HFN10-M1XD
M5OX631-30HFN10-M1XD 30k Hyper
M5OD30-36HFN10-M1
36k
M5OD30-36HFN10-M1D
M5OX631-36HFN10-M1X
36k Hyper
M5OX631-36HFN10-M1XD
M6OE30-48HFN10-M1
48k
M6OE30-48HFN10-M1D
M6OE31-48HFN10-M1X
48k Hyper
M6OE31-48HFN10-M1XD
M6OE30-60HFN10-M1
60k
M6OE30-60HFN10-M1D
M6OE31-53HFN10-M1X
55k Hyper
M6OE31-53HFN10-M1XD
background
Specifications 3
2. Pipe Length and Drop Height
Ensure that the length of the refrigerant pipe and the drop height between the indoor and outdoor units meets the
requirements shown in the following table.
1 drive 2 1 drive 3 1 drive 4 1 drive 5 1 drive 6
Max. length for all rooms (ft/m) 131/40 197/60 262/80 262/80 262/80
Max. length for one IU (ft/m) 82/25 98/30 115/35 115/35 115/35
Max. height difference between IU and OU (ft/m) 49/15 49/15 49/15 49/15 49/15
Max. height difference between IUs (ft/m) 33/10 33/10 33/10 33/10 33/10
Caution:
• Refrigerant pipe diameter is different according to indoor unit to be connected. When using the extension pipe, refer
to the tables below.
• When refrigerant pipe diameter is different from that of outdoor unit union , additional transfer connector needs to
be used on outdoor unit.
Indoor unit
Model Pipe diameter (inch(mm))
6k,9k,12k
Liquid Φ1/4(Φ6.35)
Gas Φ3/8(Φ9.52)
18k
Liquid Φ1/4(6.35)
Gas Φ1/2(Φ12.7)
24k,30k,36k
Liquid Φ3/8(Φ9.52)
Gas Φ5/8(Φ16)
background
Specifications 4
Outdoor unit
Model Pipe diameter (inch(mm)) Adaptor(inch(mm)) Qty
M3OD31-18HFN10-M1XD
Liquid Φ1/4(Φ6.35)*3
Φ3/8(Φ9.52)-->Φ1/2(Φ12.7)
Φ1/2(Φ12.7)-->Φ5/8(Φ16)
2
1
Gas Φ3/8(Φ9.52)*3
M3OD31-18HFN10-M1X
Liquid Φ1/4(Φ6.35)*3
Φ3/8(Φ9.52)-->Φ1/2(Φ12.7) 1
Gas Φ3/8(Φ9.52)*3
M3OX430-18HFN10-M1
Liquid Φ1/4(Φ6.35)*3
Φ3/8(Φ9.52)-->Φ1/2(Φ12.7) 2
Gas Φ3/8(Φ9.52)*3
M4OD31-24HFN10-M1XD
M4OD31-27HFN10-M1XD
M4OD31-27HFN10-M1X
Liquid Φ1/4(6.35)*4
Φ1/4(Φ6.35)-->Φ3/8(Φ9.52)
Φ1/2(Φ12.7)-->Φ5/8(Φ16)
Φ3/8(Φ9.52)-->Φ1/2(Φ12.7)
Φ1/2(Φ12.7)-->Φ3/8(Φ9.52)
1
1
1
1
Gas
Φ3/8(Φ9.52)*3
Φ1/2(Φ12.7)*1
M4OD30-27HFN10-M1D
Liquid Φ1/4(6.35)*4
Φ3/8(Φ9.52)-->Φ1/2(Φ12.7)
Φ1/2(Φ12.7)-->Φ3/8(Φ9.52)
3
1
Gas
Φ3/8(Φ9.52)*3
Φ1/2(Φ12.7)*1
M4OD30-27HFN10-M1
Liquid Φ1/4(6.35)*4
Φ3/8(Φ9.52)-->Φ1/2(Φ12.7)
Φ1/2(Φ12.7)-->Φ3/8(Φ9.52)
Φ1/2(Φ12.7)-->Φ5/8(Φ16)
1
1
1
Gas
Φ3/8(Φ9.52)*3
Φ1/2(Φ12.7)*1
M5OX631-30HFN10-M1XD
M5OX631-36HFN10-M1XD
Liquid Φ1/4(6.35)*5
Φ1/4(Φ6.35)-->Φ3/8(Φ9.52)
Φ1/2(Φ12.7)-->Φ5/8(Φ16)
Φ3/8(Φ9.52)-->Φ1/2(Φ12.7)
Φ1/2(Φ12.7)-->Φ3/8(Φ9.52)
2
2
1
2
Gas
Φ3/8(Φ9.52)*3
Φ1/2(Φ12.7)*2
M5OD30-36HFN10-M1D
Liquid Φ1/4(6.35)*5
Φ1/4(Φ6.35)-->Φ3/8(Φ9.52)
Φ1/2(Φ12.7)-->Φ5/8(Φ16)
Φ3/8(Φ9.52)-->Φ1/2(Φ12.7)
Φ1/2(Φ12.7)-->Φ3/8(Φ9.52)
1
1
3
1
Gas
Φ3/8(Φ9.52)*4
Φ1/2(Φ12.7)*1
M5OD30-36HFN10-M1
Liquid Φ1/4(6.35)*5
Φ1/4(Φ6.35)-->Φ3/8(Φ9.52)
Φ1/2(Φ12.7)-->Φ5/8(Φ16)
Φ3/8(Φ9.52)-->Φ1/2(Φ12.7)
Φ1/2(Φ12.7)-->Φ3/8(Φ9.52)
1
1
1
1
Gas
Φ3/8(Φ9.52)*4
Φ1/2(Φ12.7)*1
M5OX631-36HFN10-M1X
Liquid Φ1/4(6.35)*5
Φ1/4(Φ6.35)-->Φ3/8(Φ9.52)
Φ1/2(Φ12.7)-->Φ5/8(Φ16)
Φ3/8(Φ9.52)-->Φ1/2(Φ12.7)
Φ1/2(Φ12.7)-->Φ3/8(Φ9.52)
2
2
2
2
Gas
Φ3/8(Φ9.52)*4
Φ1/2(Φ12.7)*1
background
Specifications 5
M6OE31-48HFN10-M1XD
M6OE31-53HFN10-M1XD
M6OE30-48HFN10-M1D
M6OE30-60HFN10-M1D
M6OE31-48HFN10-M1X
M6OE31-53HFN10-M1X
M6OE30-48HFN10-M1
M6OE30-60HFN10-M1
Liquid Φ1/4(6.35)*6
Φ1/4(Φ6.35)-->Φ3/8(Φ9.52)
Φ1/2(Φ12.7)-->Φ5/8(Φ16)
Φ3/8(Φ9.52)-->Φ1/2(Φ12.7)
Φ1/2(Φ12.7)-->Φ3/8(Φ9.52)
2
2
1
2
Gas
Φ3/8(Φ9.52)*4
Φ1/2(Φ12.7)*2
background
Specifications 6
3. Indoor units combination
3.1 Indoor unit combination for M3OX430-18HFN10-M1
Available Indoor One unit Two units Three units
Wall mounted(AG/EP):6K/9K/12K/18K;
Cassette/Duct/Console:6K/9K/12K/18K
12 6+6 9+9 6+6+6
18 6+9 9+12 6+6+9
6+12 12+12 6+9+9
6+18
Mid-static duct:9K/12K
9 9+9 12+12
12 9+12
3.2 Indoor unit combination for M3OD31-18HFN10-M1X& M3OD31-18HFN10-M1XD
Available Indoor
One unit Two units Three units
Wall mounted(AG/EP): 6K/9K/12K/18K/24K;
Cassette/Duct/ console: 6K/9K/12K/18K/24K;
18 6+6 9+18 6+6+6 6+12+12
24 6+9 9+24 6+6+9 6+12+18
6+12 12+12 6+6+12 9+9+9
6+18 12+18 6+6+18 9+9+12
6+24 12+24 6+6+24 9+9+18
9+9 18+18 6+9+9 9+12+12
9+12 6+9+12 12+12+12
6+9+18
Wall mounted(AG/EP): 6K/9K/12K;
Cassette/Duct/Console: 6K/9K/12K;
AHU:18K/24K (At least one AHU)
18 6+18 6+6+18
24 9+18 6+9+18
12+18 9+9+18
Mid-static duct:9K/12K/18K/24K
9 9+9 12+12
12 9+12 12+18
18 9+18 12+24
24 9+24
background
Specifications 7
3.3 Indoor unit combination for M4OD30-27HFN10-M1&M4OD30-27HFN10-M1D
Available Indoor
One unit Two units Three units
Four units
Wall mounted(AG/EP):
6K/9K/12K/18K/24K;
Cassette/Duct/ console:
6K/9K/12K/18K/24K;
18 6+6 9+18 6+6+6 6+12+12 6+6+6+6
24 6+9 9+24 6+6+9 6+12+18 6+6+6+9
6+12 12+12 6+6+12 9+9+9 6+6+6+12
6+18 12+18 6+6+18 9+9+12 6+6+9+9
6+24 12+24 6+6+24 9+9+18 6+6+9+12
9+9 18+18 6+9+9 9+12+12 6+9+9+9
9+12 6+9+12 12+12+12 6+9+9+12
6+9+18 9+9+9+9
Wall mounted(AG/EP):
6K/9K/12K;
Cassette/Duct/Console:
6K/9K/12K;
AHU:18K/24K (At least
one AHU)
18 6+18 6+6+18
24 9+18 6+9+18
12+18 9+9+18
Mid-static
duct:9K/12K/18K/24K
9 9+9 12+12
12 9+12 12+18
18 9+18 12+24
24 9+24
background
Specifications 8
3.4 Indoor unit combination for M4OD31-24HFN10-M1XD, M4OD31-27HFN10-
M1X&M4OD31-27HFN10-M1XD
Available Indoor
One unit Two units Three units
Wall mounted(AG/EP): 6K/
9K/12K/18K/24K/30K;
Cassette/Duct/Console:
6K/9K/12K/18K/24K;
24 6+18 6+6+6 6+12+12 9+12+12
30 6+24 6+6+9 6+12+18 9+12+18
9+9 6+6+12 6+12+24 9+12+24
9+12 6+6+18 6+18+18 9+18+18
9+18 6+6+24 6+18+24 12+12+12
9+24 6+9+9 9+9+9 12+12+18
12+12 6+9+12 9+9+12 12+12+24
12+18 6+9+18 9+9+18 12+18+18
12+24 6+9+24 9+9+24
18+18
Four units
6+6+6+6 6+6+9+12 6+6+18+18 6+9+12+18 9+9+9+18
6+6+6+9 6+6+9+18 6+9+9+9 6+12+12+12 9+9+12+12
6+6+6+12 6+6+9+24 6+9+9+12 6+12+12+18 9+9+12+18
6+6+6+18 6+6+12+12 6+9+9+18 9+9+9+9 9+12+12+12
6+6+6+24 6+6+12+18 6+9+9+24 9+9+9+12 12+12+12+12
6+6+9+9 6+6+12+24 6+9+12+12
Mid-static
duct:9K/12K/18K/24K
One unit Two units Three units
18 9+9 12+12 9+9+9 9+12+18
24 9+12 12+18 9+9+12 9+12+24
9+18 12+24 9+9+18 12+12+12
9+24 9+9+24 12+12+18
9+12+12 12+12+24
Available Indoor One unit Two units Three units Four units
Wall mounted(AG/EP):
6K/9K/12K/18K;
Cassette/Duct/Console:
6K/9K/12K/18K;
AHU: 18K/24K/30K (At least one
AHU)
24 6+18 6+6+18 6+6+6+18
30 6+24 6+6+24 6+6+6+24
9+18 6+9+18 6+6+9+18
9+24 6+9+24 6+6+9+24
12+18 6+12+18 6+9+9+18
12+24 6+12+24 6+9+9+24
18+18 9+9+18 9+9+9+18
9+9+24
9+12+18
9+12+24
12+12+18
12+12+24
background
Specifications 9
3.5 Indoor unit combination for M5OD30-36HFN10-M1& M5OD30-36HFN10-M1D
Available Indoor One unit Two units Three units
Wall mounted(AG/EP): 6K/9K/12K/
18K/24K/30K;
Cassette/Duct/Console:
6K/9K/12K/18K/24K;
24 6+18 6+6+6 6+12+12 9+12+12
30 6+24 6+6+9 6+12+18 9+12+18
9+9 6+6+12 6+12+24 9+12+24
9+12 6+6+18 6+18+18 9+18+18
9+18 6+6+24 6+18+24 12+12+12
9+24 6+9+9 9+9+9 12+12+18
12+12 6+9+12 9+9+12 12+12+24
12+18 6+9+18 9+9+18 12+18+18
12+24 6+9+24 9+9+24
18+18
Four units Five units
6+6+6+6 6+6+12+18 6+12+12+18 6+6+6+6+6 6+6+9+9+12
6+6+6+9 6+6+12+24 9+9+9+9 6+6+6+6+9 6+6+9+9+18
6+6+6+12 6+6+18+18 9+9+9+12 6+6+6+6+12 6+9+9+9+9
6+6+6+18 6+9+9+9 9+9+9+18 6+6+6+6+18 6+9+9+9+12
6+6+6+24 6+9+9+12 9+9+12+12 6+6+6+9+9 6+9+9+9+18
6+6+9+9 6+9+9+18 9+9+12+18 6+6+6+9+12 9+9+9+9+9
6+6+9+12 6+9+9+24 9+12+12+12 6+6+6+9+18 9+9+9+9+12
6+6+9+18 6+9+12+12 12+12+12+12 6+6+9+9+9
6+6+9+24 6+9+12+18
6+6+12+12 6+12+12+12
Mid-static duct:9K/12K/18K/24K
One unit Two units Three units
18 9+9 9+9+9 9+12+12 12+12+12
24 9+12 9+9+12 9+12+18 12+12+18
9+18 9+9+18 9+12+24 12+12+24
9+24 9+9+24
12+12
12+18
12+24
Available Indoor One unit Two units Three units Four units Five units
Wall mounted(AG/EP): 6K/9K/1
2K/18K;
Cassette/Duct/Console:
6K/9K/12K/18K;
AHU: 18K/24K/30K (At least one
AHU)
24 6+18 6+6+18 6+6+6+18 6+6+6+6+18
30 6+24 6+6+24 6+6+6+24 6+6+6+9+18
9+18 6+9+18 6+6+9+18 6+6+9+9+18
9+24 6+9+24 6+6+9+24 6+9+9+9+18
12+18 6+12+18 6+6+12+18
12+24 6+12+24 6+6+12+24
18+18 9+9+18 6+9+9+18
9+9+24 6+9+9+24
9+12+18 6+9+12+18
9+12+24 6+12+12+18
12+12+18 9+9+9+18
12+12+24 9+9+12+18
background
Specifications 10
3.6 Indoor unit combination for M5OX631-30HFN10-M1XD, M5OX631-36HFN10-M1X&
M5OX631-36HFN10-M1XD
Available Indoor One unit Two units Three units
Wall mounted(AG/
EP): 6K/9K/12K/1
8K/24K/30K/36K;
Cassette/
Duct/Console:
6K/9K/12K/18K/24K
30 6+24 12+18 6+6+12 6+12+18 9+12+18
36 6+30 12+24 6+6+18 6+12+24 9+12+24
6+36 12+30 6+6+24 6+12+30 9+18+18
9+18 12+36 6+6+30 6+18+18 9+18+24
9+24 18+18 6+6+36 6+18+24 12+12+12
9+30 18+24 6+9+9 9+9+9 12+12+18
9+36 18+30 6+9+12 9+9+12 12+12+24
12+12 24+24 6+9+18 9+9+18 12+18+18
6+9+24 9+9+24 12+18+24
6+9+30 9+9+30 18+18+18
6+12+12 9+12+12
Four units Five units
6+6+6+6 6+6+18+18 6+12+12+18 9+9+18+18 6+6+6+6+6 6+6+9+9+12
6+6+6+9 6+6+18+24 6+12+12+24 9+9+18+24 6+6+6+6+9 6+6+9+9+18
6+6+6+12 6+9+9+9 6+12+18+18 9+12+12+12 6+6+6+6+12 6+6+9+12+12
6+6+6+18 6+9+9+12 6+12+18+24 9+12+12+18 6+6+6+6+18 6+6+12+12+12
6+6+6+24 6+9+9+18 6+18+18+18 9+12+12+24 6+6+6+9+9 6+9+9+9+9
6+6+9+9 6+9+9+24 9+9+9+9 9+12+18+18 6+6+6+9+12 6+9+9+9+12
6+6+9+12 6+9+12+12 9+9+9+12 9+18+18+18 6+6+6+9+18 6+9+9+12+12
6+6+9+18 6+9+12+18 9+9+9+18 12+12+12+12 6+6+6+12+12 9+9+9+9+9
6+6+9+24 6+9+12+24 9+9+9+24 12+12+12+18 6+6+6+12+18 9+9+9+9+12
6+6+12+12 6+9+18+18 9+9+12+12 12+12+12+24 6+6+9+9+9
6+6+12+18 6+9+18+24 9+9+12+18 12+12+18+18
6+6+12+24 6+12+12+12 9+9+12+24
Available
Indoor
One unit Two units Three units Four units
Mid-static duct:
9K/12K/18K/24K
18 9+9 12+18 9+9+9 9+12+18 9+9+9+9 9+12+12+12
24 9+12 12+24 9+9+12 9+12+24 9+9+9+12 9+12+12+18
9+18 18+18 9+9+18 12+12+12 9+9+9+18 9+12+12+24
9+24 18+24 9+9+24 12+12+18 9+9+9+24 12+12+12+12
12+12 24+24 9+12+12 12+12+24 9+9+12+12 12+12+12+18
9+9+12+18 12+12+12+24
9+9+12+24
background
Specifications 11
Available Indoor One unit Two units Three units
Wall mounted(AG/EP):
6K/9K/12K/18K/24K/30K/36K;
Cassette/Duct/Console:
6K/9K/12K/18K/24K;
AHU: 18K/24K/30K/36K (At
least one AHU)
30 6+18 12+18 6+6+18 6+12+30
36 6+24 12+24 6+6+24 9+9+18
6+30 12+30 6+6+30 9+9+24
6+36 12+36 6+6+36 9+9+30
9+18 18+18 6+9+18 9+12+18
9+24 18+24 6+9+24 9+12+24
9+30 18+30 6+9+30 12+12+18
9+36 24+24 6+12+18 12+12+24
6+12+24
Four units Five units
6+6+6+18 6+6+12+24 6+12+12+18 9+9+12+24 6+6+6+6+18
6+6+6+24 6+9+9+18 6+12+12+24 9+12+12+18 6+6+6+9+18
6+6+9+18 6+9+9+24 9+9+9+18 9+12+12+24 6+6+9+9+18
6+6+9+24 6+9+12+18 9+9+9+24 12+12+12+18
6+6+12+18 6+9+12+24 9+9+12+18 12+12+12+24
background
Specifications 12
3.7 Indoor unit combination for M6OE30-48HFN10-M1& M6OE30-48HFN10-M1D
Available Indoor One unit Two units Three units
Wall mounted(AG/
EP): 6K/9K/12K/
18K/24K/30K/36K;
Cassette/Duct/
Console: 6K/9K/12K/
18K/24K;
30 6+24 12+30 6+6+18 6+12+30 9+9+30 9+18+36
36 6+30 12+36 6+6+24 6+12+36 9+9+36 12+12+12
6+36 18+18 6+6+30 6+18+18 9+12+12 12+12+18
9+18 18+24 6+6+36 6+18+24 9+12+18 12+12+24
9+24 18+30 6+9+12 6+18+30 9+12+24 12+12+30
9+30 18+36 6+9+18 6+18+36 9+12+30 12+12+36
9+36 24+24 6+9+24 9+9+9 9+12+36 12+18+18
12+12 24+30 6+9+30 9+9+12 9+18+18 12+18+24
12+18 24+36 6+9+36 9+9+18 9+18+24 12+18+30
12+24 6+12+18 9+9+24 9+18+30 18+18+18
6+12+24
Four units
6+6+6+6 6+6+9+24 6+9+9+12 6+9+18+24 9+9+9+12 9+9+18+18 9+12+18+24
6+6+6+9 6+6+12+12 6+9+9+18 6+12+12+12 9+9+9+18 9+9+18+24 9+18+18+18
6+6+6+18 6+6+12+18 6+9+9+24 6+12+12+18 9+9+9+24 9+12+12+12 12+12+12+12
6+6+6+24 6+6+12+24 6+9+12+12 6+12+12+24 9+9+12+12 9+12+12+18 12+12+12+18
6+6+9+9 6+6+18+18 6+9+12+18 6+12+18+18 9+9+12+18 9+12+12+24 12+12+12+24
6+6+9+12 6+6+18+24 6+9+12+24 6+12+18+24 9+9+12+24 9+12+18+18 12+12+18+18
6+6+9+18 6+9+9+9 6+9+18+18 9+9+9+9
Five units
6+6+6+6+6 6+6+6+9+24 6+6+9+9+18 6+6+12+12+18 6+6+12+12+18 6+12+12+12+18 9+9+9+12+24
6+6+6+6+9 6+6+6+12+12 6+6+9+9+24 6+6+12+12+24 6+6+12+12+24 9+9+9+9+9 9+9+9+18+18
6+6+6+6+12 6+6+6+12+18 6+6+9+12+12 6+6+12+18+18 6+6+12+18+18 9+9+9+9+12 9+9+12+12+12
6+6+6+6+18 6+6+6+12+24 6+6+9+12+18 6+9+9+9+9 6+9+9+9+9 9+9+9+9+18 9+9+12+12+18
6+6+6+6+24 6+6+6+18+18 6+6+9+12+24 6+9+9+9+12 6+9+9+9+12 9+9+9+9+24 9+12+12+12+12
6+6+6+9+9 6+6+6+18+24 6+6+9+18+18 6+9+9+9+18 6+9+9+9+18 9+9+9+12+12 9+12+12+12+18
6+6+6+9+12 6+6+9+9+9 6+6+9+18+24 6+9+9+9+24 6+9+9+9+24 9+9+9+12+18 12+12+12+12+12
6+6+6+9+18 6+6+9+9+12 6+6+12+12+12 6+9+9+12+12 6+9+9+12+12
Six units
6+6+6+6+6+6 6+6+6+6+6+6 6+6+6+9+9+12 6+6+6+12+12+18 6+6+9+9+12+18 6+9+9+9+9+18 9+9+9+9+9+12
6+6+6+6+6+9 6+6+6+6+6+9 6+6+6+9+9+18 6+6+9+9+9+9 6+6+9+12+12+12 6+9+9+9+12+12 9+9+9+9+9+18
6+6+6+6+6+12 6+6+6+6+6+12 6+6+6+9+12+12 6+6+9+9+9+12 6+6+9+12+12+18 6+9+9+9+12+18 9+9+9+9+12+12
6+6+6+6+6+18 6+6+6+6+6+18 6+6+6+9+12+18 6+6+9+9+9+18 6+9+9+9+9+9 6+9+9+12+12+12 9+9+9+12+12+12
6+6+6+6+9+9 6+6+6+6+9+9 6+6+6+12+12+12 6+6+9+9+12+12 6+9+9+9+9+12 9+9+9+9+9+9
Available Indoor One unit Two units Three units Four units
Mid-static
duct:9K/12K/18K/24K
18 9+9 12+18 9+9+9 9+12+18 9+9+9+9 9+12+12+12
24 9+12 12+24 9+9+12 9+12+24 9+9+9+12 9+12+12+18
9+18 18+18 9+9+18 12+12+12 9+9+9+18 9+12+12+24
9+24 18+24 9+9+24 12+12+18 9+9+9+24 12+12+12+12
12+12 24+24 9+12+12 12+12+24 9+9+12+12 12+12+12+18
9+9+12+18 12+12+12+24
9+9+12+24
background
Specifications 13
Available Indoor One unit Two units Three units
Wall mounted(AG/EP):
6K/9K/12K/18K/24K/30K/36K;
Cassette/Duct/Console:
6K/9K/12K/18K/24K;
AHU: 18K/24K/30K/36K (At least
one AHU)
30 6+18 12+30 6+6+18 9+9+18
36 6+24 12+36 6+6+24 9+9+24
6+30 18+18 6+6+30 9+9+30
6+36 18+24 6+6+36 9+9+36
9+18 18+30 6+9+18 9+12+18
9+24 18+36 6+9+24 9+12+24
9+30 24+24 6+9+30 9+12+30
9+36 24+30 6+9+36 9+12+36
12+18 24+36 6+12+18 12+12+18
12+24 6+12+24 12+12+24
6+12+30 12+12+30
6+12+36
Four units
6+6+6+18 6+6+12+18 6+9+12+18 9+9+9+18 9+12+12+18
6+6+6+24 6+6+12+24 6+9+12+24 9+9+9+24 9+12+12+24
6+6+9+18 6+9+9+18 6+12+12+18 9+9+12+18 12+12+12+18
6+6+9+24 6+9+9+24 6+12+12+24 9+9+12+24 12+12+12+24
Five units Six units
6+6+6+6+18 6+6+6+12+24 6+9+12+12+18 9+9+9+12+24 6+6+6+6+6+18
6+6+6+6+24 6+9+9+9+18 6+9+12+12+24 9+9+9+12+18 6+6+6+6+9+18
6+6+6+9+18 6+9+9+9+24 6+12+12+12+18 9+9+12+12+18 6+6+6+9+9+18
6+6+6+9+24 6+9+9+12+18 9+9+9+9+18 9+12+12+12+18 6+6+9+9+9+18
6+6+6+12+18 6+9+9+12+24 9+9+9+9+24 6+9+9+9+9+18
9+9+9+9+9+18
background
Specifications 14
3.8 Indoor unit combination for M6OE31-48HFN10-M1X, M6OE31-48HFN10-M1XD,
M6OE31-53HFN10-M1X & M6OE31-53HFN10-M1XD
Available Indoor One unit Two units Three units
Wall mounted(AG/
EP): 6K/9K/12K/
18K/24K/30K/36K;
Cassette/
Duct/Console:
6K/9K/12K/
18K/24K;
30 6+24 12+30 6+6+18 6+12+18 9+9+24 9+18+36
36 6+30 12+36 6+6+24 6+12+24 9+9+30 12+12+12
6+36 18+18 6+6+30 6+12+30 9+9+36 12+12+18
9+18 18+24 6+6+36 6+12+36 9+12+12 12+12+24
9+24 18+30 6+9+9 6+18+18 9+12+18 12+12+30
9+30 18+36 6+9+12 6+18+24 9+12+24 12+12+36
9+36 24+24 6+9+18 6+18+30 9+12+30 12+18+18
12+12 24+30 6+9+24 6+18+36 9+12+36 12+18+24
12+18 24+36 6+9+30 9+9+9 9+18+18 12+18+30
12+24 6+9+36 9+9+12 9+18+24 12+18+36
6+12+12 9+9+18 9+18+30 18+18+18
Four units
6+6+6+6 6+6+9+24 6+9+9+18 6+12+12+12 9+9+9+9 9+9+18+18 9+18+18+18
6+6+6+9 6+6+12+12 6+9+9+24 6+12+12+18 9+9+9+12 9+9+18+24 12+12+12+12
6+6+6+12 6+6+12+18 6+9+12+12 6+12+12+24 9+9+9+18 9+12+12+12 12+12+12+18
6+6+6+18 6+6+12+24 6+9+12+18 6+12+18+18 9+9+9+24 9+12+12+18 12+12+12+24
6+6+6+24 6+6+18+18 6+9+12+24 6+12+18+24 9+9+12+12 9+12+12+24 12+12+18+18
6+6+9+9 6+6+18+24 6+9+18+18 6+18+18+18 9+9+12+18 9+12+18+18 12+12+18+24
6+6+9+12 6+9+9+9 6+9+18+24 6+18+18+24 9+9+12+24 9+12+18+24 12+18+18+18
6+6+9+18 6+9+9+12
Five units
6+6+6+6+6 6+6+6+12+24 6+6+9+18+24 6+9+9+9+24 6+9+12+18+24 9+9+9+9+24 9+9+12+18+24
6+6+6+6+9 6+6+6+18+18 6+6+12+12+12 6+9+9+12+12 6+9+18+18+18 9+9+9+12+12 9+9+18+18+18
6+6+6+6+12 6+6+6+18+24 6+6+12+12+18 6+9+9+12+18 6+12+12+12+12 9+9+9+12+18 9+12+12+12+12
6+6+6+6+18 6+6+9+9+9 6+6+12+12+24 6+9+9+12+24 6+12+12+12+18 9+9+9+12+24 9+12+12+12+18
6+6+6+6+24 6+6+9+9+12 6+6+12+18+18 6+9+9+18+18 6+12+12+12+24 9+9+9+18+18 9+12+12+12+24
6+6+6+9+9 6+6+9+9+18 6+6+12+18+24 6+9+9+18+24 6+12+12+18+18 9+9+9+18+24 9+12+12+18+18
6+6+6+9+12 6+6+9+9+24 6+6+18+18+18 6+9+12+12+12 6+12+18+18+18 9+9+12+12+12 12+12+12+12+12
6+6+6+9+18 6+6+9+12+12 6+6+18+18+24 6+9+12+12+18 9+9+9+9+9 9+9+12+12+18 12+12+12+12+18
6+6+6+9+24 6+6+9+12+18 6+9+9+9+9 6+9+12+12+24 9+9+9+9+12 9+9+12+12+24 12+12+12+12+24
6+6+6+12+12 6+6+9+12+24 6+9+9+9+12 6+9+12+18+18 9+9+9+9+18 9+9+12+18+18 12+12+12+18+18
6+6+6+12+18 6+6+9+18+18 6+9+9+9+18
Six units
6+6+6+6+6+6 6+6+6+6+12+12 6+6+6+9+12+24 6+6+9+9+12+18 6+9+9+9+9+12 6+9+12+12+12+12 9+9+9+9+12+18
6+6+6+6+6+9 6+6+6+6+12+18 6+6+6+12+12+12 6+6+9+9+12+24 6+9+9+9+9+18 6+9+12+12+12+18 9+9+9+9+12+24
6+6+6+6+6+12 6+6+6+6+12+24 6+6+6+12+12+18 6+6+9+12+12+12 6+9+9+9+9+24 6+12+12+12+12+12 9+9+9+12+12+12
6+6+6+6+6+18 6+6+6+9+9+9 6+6+6+12+12+24 6+6+9+12+12+18 6+9+9+9+12+12 6+12+12+12+12+18 9+9+9+12+12+18
6+6+6+6+6+24 6+6+6+9+9+12 6+6+9+9+9+9 6+6+9+12+12+24 6+9+9+9+12+18 9+9+9+9+9+9 9+9+12+12+12+12
6+6+6+6+9+9 6+6+6+9+9+18 6+6+9+9+9+12 6+6+12+12+12+12 6+9+9+9+12+24 9+9+9+9+9+12 9+9+12+12+12+18
6+6+6+6+9+12 6+6+6+9+9+24 6+6+9+9+9+18 6+6+12+12+12+18 6+9+9+12+12+12 9+9+9+9+9+18 9+12+12+12+12+12
6+6+6+6+9+18 6+6+6+9+12+12 6+6+9+9+9+24 6+6+12+12+12+24 6+9+9+12+12+18 9+9+9+9+9+24 12+12+12+12+12+12
6+6+6+6+9+24 6+6+6+9+12+18 6+6+9+9+12+12 6+9+9+9+9+9 6+9+9+12+12+24 9+9+9+9+12+12
background
Specifications 15
Available Indoor One unit Two units Three units Four units
Mid-static duct:
9K/12K/18K/24K
18 9+9 12+18 9+9+9 9+18+24 9+9+9+9 9+12+12+18 9+9+9+9+9
24 9+12 12+24 9+9+12 9+24+24 9+9+9+12 9+12+12+24 9+9+9+9+12
9+18 18+18 9+9+18 12+12+12 9+9+9+18 9+12+18+18 9+9+9+12+12
9+24 18+24 9+9+24 12+12+18 9+9+9+24 9+12+18+24 9+9+12+12+12
12+12 24+24 9+12+12 12+12+24 9+9+12+12 12+12+12+12 9+12+12+12+12
9+12+18 12+18+18 9+9+12+18 12+12+12+18 12+12+12+12+12
9+12+24 12+18+24 9+9+12+24 12+12+12+24
9+18+18 12+24+24 9+9+18+18 12+12+18+18
9+9+18+24 12+12+18+24
9+12+12+12
Available Indoor One unit Two units Three units
Wall mounted(AG/EP):
6K/9K/12K/18K/24K/30K/36K;
Cassette/Duct/Console:
6K/9K/12K/18K/24K;
AHU: 18K/24K/30K/36K (At least
one AHU)
30 6+18 12+30 6+6+18 9+9+18
36 6+24 12+36 6+6+24 9+9+24
6+30 18+18 6+6+30 9+9+30
6+36 18+24 6+6+36 9+9+36
9+18 18+30 6+9+18 9+12+18
9+24 18+36 6+9+24 9+12+24
9+30 24+24 6+9+30 9+12+30
9+36 24+30 6+9+36 9+12+36
12+18 24+36 6+12+18 12+12+18
12+24 6+12+24 12+12+24
6+12+30 12+12+30
6+12+36
Four units
6+6+6+18 6+6+12+18 6+9+12+18 9+9+9+18 9+12+12+18
6+6+6+24 6+6+12+24 6+9+12+24 9+9+9+24 9+12+12+24
6+6+9+18 6+9+9+18 6+12+12+18 9+9+12+18 12+12+12+18
6+6+9+24 6+9+9+24 6+12+12+24 9+9+12+24 12+12+12+24
Five units Six units
6+6+6+6+18 6+9+9+9+24 6+9+12+12+24 9+9+9+12+24 6+6+6+6+6+18
6+6+6+6+24 6+9+9+12+18 6+12+12+12+18 9+9+9+12+18 6+6+6+6+9+18
6+6+6+12+18 6+9+9+12+24 9+9+9+9+18 9+9+12+12+18 6+6+6+9+9+18
6+6+6+12+24 6+9+12+12+18 9+9+9+9+24 9+12+12+12+18 6+6+9+9+9+18
6+9+9+9+18 6+9+9+9+9+18
9+9+9+9+9+18
background
Specifications 16
3.9 Indoor unit combination for M6OE30-60HFN10-M1& M6OE30-60HFN10-M1D
Available Indoor One unit Two units Three units
Wall mounted(AG/
EP): 6K/9K/12K/
18K/24K/30K/36K;
Cassette/
Duct/Console:
6K/9K/12K/
18K/24K;
30 6+24 12+30 6+6+18 6+12+18 9+9+24 9+18+36
36 6+30 12+36 6+6+24 6+12+24 9+9+30 12+12+12
6+36 18+18 6+6+30 6+12+30 9+9+36 12+12+18
9+18 18+24 6+6+36 6+12+36 9+12+12 12+12+24
9+24 18+30 6+9+9 6+18+18 9+12+18 12+12+30
9+30 18+36 6+9+12 6+18+24 9+12+24 12+12+36
9+36 24+24 6+9+18 6+18+30 9+12+30 12+18+18
12+12 24+30 6+9+24 6+18+36 9+12+36 12+18+24
12+18 24+36 6+9+30 9+9+9 9+18+18 12+18+30
12+24 6+9+36 9+9+12 9+18+24 12+18+36
6+12+12 9+9+18 9+18+30 18+18+18
Four units
6+6+6+6 6+6+9+24 6+9+9+18 6+12+12+12 9+9+9+9 9+9+18+18 9+18+18+18
6+6+6+9 6+6+12+12 6+9+9+24 6+12+12+18 9+9+9+12 9+9+18+24 12+12+12+12
6+6+6+12 6+6+12+18 6+9+12+12 6+12+12+24 9+9+9+18 9+12+12+12 12+12+12+18
6+6+6+18 6+6+12+24 6+9+12+18 6+12+18+18 9+9+9+24 9+12+12+18 12+12+12+24
6+6+6+24 6+6+18+18 6+9+12+24 6+12+18+24 9+9+12+12 9+12+12+24 12+12+18+18
6+6+9+9 6+6+18+24 6+9+18+18 6+18+18+18 9+9+12+18 9+12+18+18 12+12+18+24
6+6+9+12 6+9+9+9 6+9+18+24 6+18+18+24 9+9+12+24 9+12+18+24 12+18+18+18
6+6+9+18 6+9+9+12
Five units
6+6+6+6+6 6+6+6+12+24 6+6+9+18+24 6+9+9+9+24 6+9+12+18+24 9+9+9+9+24 9+9+12+18+24
6+6+6+6+9 6+6+6+18+18 6+6+12+12+12 6+9+9+12+12 6+9+18+18+18 9+9+9+12+12 9+9+18+18+18
6+6+6+6+12 6+6+6+18+24 6+6+12+12+18 6+9+9+12+18 6+12+12+12+12 9+9+9+12+18 9+12+12+12+12
6+6+6+6+18 6+6+9+9+9 6+6+12+12+24 6+9+9+12+24 6+12+12+12+18 9+9+9+12+24 9+12+12+12+18
6+6+6+6+24 6+6+9+9+12 6+6+12+18+18 6+9+9+18+18 6+12+12+12+24 9+9+9+18+18 9+12+12+12+24
6+6+6+9+9 6+6+9+9+18 6+6+12+18+24 6+9+9+18+24 6+12+12+18+18 9+9+9+18+24 9+12+12+18+18
6+6+6+9+12 6+6+9+9+24 6+6+18+18+18 6+9+12+12+12 6+12+18+18+18 9+9+12+12+12 12+12+12+12+12
6+6+6+9+18 6+6+9+12+12 6+6+18+18+24 6+9+12+12+18 9+9+9+9+9 9+9+12+12+18 12+12+12+12+18
6+6+6+9+24 6+6+9+12+18 6+9+9+9+9 6+9+12+12+24 9+9+9+9+12 9+9+12+12+24 12+12+12+12+24
6+6+6+12+12 6+6+9+12+24 6+9+9+9+12 6+9+12+18+18 9+9+9+9+18 9+9+12+18+18 12+12+12+18+18
6+6+6+12+18 6+6+9+18+18 6+9+9+9+18
Six units
6+6+6+6+6+6 6+6+6+6+12+12 6+6+6+9+12+24 6+6+9+9+12+18 6+9+9+9+9+12 6+9+9+12+12+24 9+9+9+9+12+12
6+6+6+6+6+9 6+6+6+6+12+18 6+6+6+12+12+12 6+6+9+9+12+24 6+9+9+9+9+18 6+9+12+12+12+12 9+9+9+9+12+18
6+6+6+6+6+12 6+6+6+6+12+24 6+6+6+12+12+18 6+6+9+12+12+12 6+9+9+9+9+24 6+9+12+12+12+18 9+9+9+9+12+24
6+6+6+6+6+18 6+6+6+9+9+9 6+6+6+12+12+24 6+6+9+12+12+18 6+9+9+9+12+12 6+12+12+12+12+12 9+9+9+12+12+12
6+6+6+6+6+24 6+6+6+9+9+12 6+6+9+9+9+9 6+6+9+12+12+24 6+9+9+9+12+18 6+12+12+12+12+18 9+9+9+12+12+18
6+6+6+6+9+9 6+6+6+9+9+18 6+6+9+9+9+12 6+6+12+12+12+12 6+9+9+9+12+24 9+9+9+9+9+9 9+9+12+12+12+12
6+6+6+6+9+12 6+6+6+9+9+24 6+6+9+9+9+18 6+6+12+12+12+18 6+9+9+9+18+18 9+9+9+9+9+12 9+9+12+12+12+18
6+6+6+6+9+18 6+6+6+9+12+12 6+6+9+9+9+24 6+6+12+12+12+24 6+9+9+12+12+12 9+9+9+9+9+18 9+12+12+12+12+12
6+6+6+6+9+24 6+6+6+9+12+18 6+6+9+9+12+12 6+9+9+9+9+9 6+9+9+12+12+18 9+9+9+9+9+24 12+12+12+12+12+12
Available Indoor One unit Two units Three units Four units Six units
Mid-static
duct:9K/12K/18K/24K
18 9+9 12+18 9+9+9 9+12+18 9+9+9+9 9+12+12+12 9+9+9+9+9
24 9+12 12+24 9+9+12 9+12+24 9+9+9+12 9+12+12+18 9+9+9+9+12
9+18 18+18 9+9+18 12+12+12 9+9+9+18 9+12+12+24 9+9+9+12+12
9+24 18+24 9+9+24 12+12+18 9+9+9+24 12+12+12+12 9+9+12+12+12
12+12 24+24 9+12+12 12+12+24 9+9+12+12 12+12+12+18 9+12+12+12+12
9+9+12+18 12+12+12+24 12+12+12+12+12
9+9+12+24
background
Specifications 17
Available Indoor One unit Two units Three units
Wall mounted(AG/EP):
6K/9K/12K/18K/24K/30K/36K;
Cassette/Duct/Console:
6K/9K/12K/18K/24K;
AHU: 18K/24K/30K/36K (At least
one AHU)
30 6+18 12+30 6+6+18 9+9+18
36 6+24 12+36 6+6+24 9+9+24
6+30 18+18 6+6+30 9+9+30
6+36 18+24 6+6+36 9+9+36
9+18 18+30 6+9+18 9+12+18
9+24 18+36 6+9+24 9+12+24
9+30 24+24 6+9+30 9+12+30
9+36 24+30 6+9+36 9+12+36
12+18 24+36 6+12+18 12+12+18
12+24 6+12+24 12+12+24
6+12+30 12+12+30
6+12+36
Four units
6+6+6+18 6+6+12+18 6+9+12+18 9+9+9+18 9+12+12+18
6+6+6+24 6+6+12+24 6+9+12+24 9+9+9+24 9+12+12+24
6+6+9+18 6+9+9+18 6+12+12+18 9+9+12+18 12+12+12+18
6+6+9+24 6+9+9+24 6+12+12+24 9+9+12+24 12+12+12+24
Five units Six units
6+6+6+6+18 6+9+9+9+24 6+9+12+12+24 9+9+9+12+24 6+6+6+6+6+18
6+6+6+6+24 6+9+9+12+18 6+12+12+12+18 9+9+9+12+18 6+6+6+6+9+18
6+6+6+12+18 6+9+9+12+24 9+9+9+9+18 9+9+12+12+18 6+6+6+9+9+18
6+6+6+12+24 6+9+12+12+18 9+9+9+9+24 9+12+12+12+18 6+9+9+9+9+18
6+9+9+9+18 9+9+9+9+9+18
background
Specifications 18
4. Refrigeration Cycle Diagrams
4.1 Refrigeration Cycle Diagram of M3OD31-18HFN10-M1X, M3OX430-18HFN10-M1
4.2 Refrigeration Cycle Diagram of M4OD31-27HFN10-M1X, M4OD30-27HFN10-M1
background
Specifications 19
4.3 Refrigeration Cycle Diagram of M5OD30-36HFN10-M1
4.4 Refrigeration Cycle Diagram of M5OX631-36HFN10-M1X
background
Specifications 20
4.5 Refrigeration Cycle Diagram of M6OE30-48HFN10-M1, M6OE30-60HFN10-M1
4.6 Refrigeration Cycle Diagram of M6OE31-48HFN10-M1X, M6OE31-53HFN10-M1X
background
Specifications 21
4.7 Refrigeration Cycle Diagram of M3OD31-18HFN10-M1XD
4.8 Refrigeration Cycle Diagram of M4OD31-24HFN10-M1XD, M4OD31-27HFN10-M1XD,
M4OD30-27HFN10-M1D
background
Specifications 22
4.9 Refrigeration Cycle Diagram of M5OD30-36HFN10-M1D
4.10 Refrigeration Cycle Diagram of M5OX631-30HFN10-M1XD& M5OX631-36HFN10-M1XD
background
Specifications 23
4.11 Refrigeration Cycle Diagram of M6OE30-48HFN10-M1D, M6OE30-60HFN10-M1D
4.12 Refrigeration Cycle Diagram of M6OE31-48HFN10-M1XD, M6OE31-53HFN10-M1XD
background
Specifications 24
5. Electrical Wiring Diagrams
Outdoor unit wiring diagram
Outdoor Unit
ODU Model ODU Wiring Diagram
M3OX430-18HFN10-M1 16022000040630
M3OD31-18HFN10-M1X 16022300005693
M3OD31-18HFN10-M1XD 16022300005874
M4OD31-27HFN10-M1X
16022300005674
M4OD30-27HFN10-M1
M4OD31-27HFN10-M1XD
16022300005875
M4OD30-27HFN10-M1D
M5OX631-36HFN10-M1XD
16022300005713
M5OX631-36HFN10-M1X
M5OD30-36HFN10-M1 16022300005774
M5OD30-36HFN10-M1D 16022300005893
M6OE31-48HFN10-M1X
16022000040750
M6OE30-48HFN10-M1
M6OE30-60HFN10-M1
M6OE31-53HFN10-M1X
M6OE31-48HFN10-M1XD
16022000041470
M6OE31-53HFN10-M1XD
M6OE30-48HFN10-M1D
M6OE30-60HFN10-M1D
background
Specifications 25
Outdoor unit printed circuit board diagram
Outdoor Unit
ODU Model ODU Printed Circuit Board
M3OX430-18HFN10-M1
17122000062845
M3OD31-18HFN10-M1X
M3OD31-18HFN10-M1XD
17122300008875
M4OD31-27HFN10-M1X
17122000062845
M4OD30-27HFN10-M1
M4OD31-27HFN10-M1XD
17122300008875
M4OD30-27HFN10-M1D
M5OX631-36HFN10-M1XD
M5OX631-36HFN10-M1X
17122300007152
M5OD30-36HFN10-M1
17122000062845
M5OD30-36HFN10-M1D
17122300008875
M6OE31-48HFN10-M1X
17122300007152
M6OE30-48HFN10-M1
M6OE30-60HFN10-M1
M6OE31-53HFN10-M1X
M6OE31-48HFN10-M1XD
17122300008875
M6OE31-53HFN10-M1XD
M6OE30-48HFN10-M1D
M6OE30-60HFN10-M1D
background
background
background
background
background
background
background
background
background
background
background
Outdoor unit printed circuit board diagram: 17122300008875
background
No. Name CN# Meaning
1 COMPRESSOR
W
connect to compressor; 0V AC (standby); 10-310V AC (running)V
U
2 DC-FAN CN32 connect to DC fan
3 TESTPORT CN45 used for testing
4 HEAT_Y CN38 connect to compressor heater, 208-230V AC when is ON
5 4-WAY
CN37 connect to 4 way valve 1, 208-230V AC when is ON.
CN25 connect to 4 way valve 2, 208-230V AC when is ON.
6 HEAT_D CN24 connect to chassis heater, 208-230V AC when is ON
7 Power Supply
CN11 N_in: connect to N-line (208-230V AC input)
CN12 L_in: connect to L-line (208-230V AC input)
8
S-A
CN43
S: connect to indoor unit communication(pin1-pin2: 24VDC Pulse
wave; pin2-pin3: 208-230V AC input)
S-B
S-C
S-D
S-E
S-F
9 TBH-IN TBH-OUT T3B TF CN9
connect to cold plate inlet temp. sensor TBH-IN, cold plate outlet temp.
sensor TBH-OUT, condenser coil middle temp. sensor T3B, refrigerant
tube inlet temp. sensor TF
10 OLP TEMP. SENSOR CN30 connect to compressor top temp. sensor (5VDC Pulse wave)
11 T2B CN28 connect to evaporator coil outlet temperature sensor T2B
12 / CN27 connect to key board CN1
13 T3 T4 TP CN26
connect to condenser coil temp. sensor T3, ambient temp. sensor T4,
exhaust temp. sensor TP
14 H-PRO,L-RPO CN29
connect to high and low pressure switch(pin1-pin2&pin3-pin4:5VDC
pulse wave)
background
No. Name CN# Meaning
15
EEVA CN17
connect to electric expansion valve
EEVB CN16
EEVC CN22
EEVD CN14
EEVE CN13
EEVF CN1
EEV1 CN53
EEV2 CN44
EEV3 CN3
Note: This section is for reference only. Please take practicality as standard.
background
Outdoor unit printed circuit board diagram: 17122000062845
5
1
3
4
7
8 9
10
12
14
13
2
6
11
background
No. Name CN# Meaning
1 Power Supply
CN11 L_in: connect to N-line (208-230V AC input)
CN12 N_in: connect to L-line (208-230V AC input)
2
S-A CN4
S: connect to indoor unit communication(pin1-pin2: 24VDC Pulse wave;
pin2-pin3: 208-240V AC input)
S-B CN2
S-C CN34
S-D CN5
S-E CN10
3
EEV-A CN10
connect to electric expansion valve
EEV-B CN13
EEV-C CN3
EEV-D CN15
EEV-E CN17
4 HEAT_D CN39 connect to chassis heater, 208-240V AC when is ON
5 4-WAY CN38 connect to 4 way valve, 208-240V AC when is ON.
6 HEAT_Y CN40 connect to compressor heater, 208-240V AC when is ON
7 T2B CN28 connect to evaporator coil outlet temperature sensor T2B
8 T3 T4 TP CN26
connect to pipe temp. sensor T3, ambient temp. sensor T4, exhaust
temp. sensor TP
9 OLP TEMP. SENSOR CN30 connect to compressor top temp. sensor (5VDC Pulse wave)
10 H-PRO,L-RPO CN29
connect to high and low pressure swtich(pin1-pin2&pin3-pin4:5VDC
pulse wave)
11 / CN27 connect to key board CN1
background
No. Name CN# Meaning
12 TESTPORT
CN24/
CN14
used for testing
13 COMPRESSOR
U
connect to compressor; 0V AC (standby), 10-200V AC (running)V
W
14 DC-FAN CN32 connect to DC fan
Note: This section is for reference only. Please take practicality as standard.
background
Outdoor unit printed circuit board diagram: 17122300007152
background
No. Name CN# Meaning
1 COMPRESSOR
W
connect to compressor(Output: 0~310V AC)V
U
2 DC-FAN1 CN32 connect to DC fan(Output: 0~310V AC)
3 TESTPORT CN45 used for testing
4 HEAT_Y CN38 connect to compressor heater(Output: 230V AC)
5 4-WAY
CN37 connect to 4 way valve 1(Output: 230V AC)
CN25 connect to 4 way valve 2(Output: 230V AC)
CN42 connect to 4 way valve 3(Output: 230V AC)
6 HEAT_D CN24 connect to chassis heater(Output: 230V AC)
7 Power Supply
CN11 N_in: connect to N-line (230V AC input)
CN12 L_in: connect to L-line (230V AC input)
8
S-A
CN43 S: connect to indoor unit communication(230V AC input)
S-B
S-C
S-D
S-E
S-F
9 TBH-IN TBH-OUT T3B TF CN9
connect to cold plate inlet temp. sensor TBH-IN, cold plate outlet temp.
sensor TBH-OUT, condenser coil middle temp. sensor T3B, refrigerant
tube inlet temp. sensor TF
10 OLP TEMP. SENSOR CN30 connect to compressor top temp. sensor (Output: 0~5V DC)
11 T2B CN28 connect to evaporator coil outlet temperature sensor T2B
12 / CN27 connect to key board CN1
13 T3 T4 TP CN26
connect to condenser coil temp. sensor T3, ambient temp. sensor T4,
exhaust temp. sensor TP(Output: 0~5V DC)
14 H-PRO,L-RPO CN29
connect to high and low pressure switch(pin1-pin2&pin3-pin4:5VDC
pulse wave)
background
No. Name CN# Meaning
15
EEVA CN17
connect to electric expansion valve(Output: 0~12V DC)
EEVB CN16
EEVC CN22
EEVD CN14
EEVE CN13
EEVF CN1
EEV1 CN53
EEV2 CN44
EEV3 CN3
16 H_YL CN49 connect to high pressure sensor
17 DC-FAN2 CN10 connect to DC fan(Output: 0~310V AC)
Note: This section is for reference only. Please take practicality as standard.
background
Contents
1 Abbreviation ..........................................................................................................2
2 Main Protection .....................................................................................................2
Electronic Functions
background
Product Features 2
1. Abbreviation
Unit element abbreviations
Abbreviation Element
T1 Indoor room temperature
T2 Middle indoor heat exchanger coil
temperature
T2B Indoor heat exchanger exhaust coil
temperature (located on the outdoor
unit)
T3 Coil temperature of condenser
T4 Outdoor ambient temperature
T3B Condenser middle temperature
T5 Refrigerant pipe inlet temperature
T6A Economizer branch inlet temperature
T6B Economizer branch outlet temperature
TP Compressor discharge temperature
NOTE: T3B, T5,T6A&T6B are only for hyper heat models.
2. Main Protection
2.1 Sensor redundancy and automatic
shutoff
• If one temperature sensor(T3, T4, T2B or TP)
malfunctions, the unit ceases operation and displays
the corresponding error code.
2.2 Automatic shutoff based on fan
If the outdoor fan speed is operating outside of the normal
range, fan lack of phase or fan zero speed failure, the unit
ceases operation.
2.3 Inverter module protection
The inverter module has an automatic shutoff mechanism
based on the unit’s current and temperature. If automatic
shutoff is initiated, the corresponding error code is
displayed and the unit ceases operation.
2.4 Indoor / Outdoor Units Communication
Protection
If the indoor units do not receive the feedback signal from
the outdoor units for 2 consecutive minutes or the outdoor
units do not receive the feedback signal from any one of
indoor units for 3 consecutive minutes, the unit ceases
operation. The unit displays the failure code.
2.5 EEPROM parameter error
If main chip does not receive feedback from EEPROM chip
or parameter check error, the unit ceases operation.
2.6 Automatic shutoff based on
compressor
If the compressor speed has been out of control,
compressor lack of phase or voltage too low failure, the
unit ceases operation.
2.7 Temperature Protection of Compressor
Discharge
When the discharge temperature of the compressor rises,
the running frequency is limited. If discharge temperature
is too high, the compressor stops and then restart until
discharge temperature reduced to normal range.
2.8 Evaporator Anti-Freezing Protection
The T2 sent from the indoor unit to the outdoor unit is
low, and the unit limits the compressor to run at a low
frequency.
2.9 Oil Return
1) If the unit runs at low frequency for a long time,
the unit will run the oil return program to increase the
frequency of the compressor;
2) After the unit runs continuously for a period of time,
the unit will run the oil return program to increase the
compressor frequency;
background
Contents
1. Outdoor Unit Table ................................................................................................2
2. Dimension ..............................................................................................................3
3. Outdoor Unit Disassembly ....................................................................................8
3.1 Panel Plate .....................................................................................................8
3.2 Electrical Parts .............................................................................................20
3.3 Fan Assembly ..............................................................................................43
3.4 Fan Motor ...................................................................................................44
3.5 Sound blanket .............................................................................................45
3.6 Four-way valve .............................................................................................46
3.7 Compressor .................................................................................................47
Outdoor Unit Disassembly
background
Outdoor Unit Disassembly 2
1. Outdoor Unit Disassembly
1.1 Outdoor Unit Table
Outdoor Unit Model Panel Plate PCB Board
M3OD31-18HFN10-M1XD D30 PCB board 9
M4OD31-27HFN10-M1XD D30 PCB board 9
M5OX631-36HFN10-M1XD D30 PCB board 9
M6OE31-48HFN10-M1XD E30 PCB board 10
M6OE31-53HFN10-M1XD E30 PCB board 10
M4OD30-27HFN10-M1D D30 PCB board 9
M5OD30-36HFN10-M1D D30 PCB board 9
M6OE30-48HFN10-M1D E30 PCB board 10
M6OE30-60HFN10-M1D E30 PCB board 10
M3OD31-18HFN10-M1X D30 PCB board 6
M4OD31-27HFN10-M1X D30 PCB board 6
M5OX631-36HFN10-M1X X630 PCB board 9
M6OE31-48HFN10-M1X E30 PCB board 10
M6OE31-53HFN10-M1X E30 PCB board 10
M3OX430-18HFN10-M1 X430 PCB board 6
M4OD30-27HFN10-M1 D30 PCB board 6
M5OD30-36HFN10-M1 D30 PCB board 6
M6OE30-48HFN10-M1 E30 PCB board 10
M6OE30-60HFN10-M1 E30 PCB board 10
background
Outdoor Unit Disassembly 3
2. Dimension
2.1. Panel Plate X430 (1 drive 2 & 1 drive 3)
background
Outdoor Unit Disassembly 4
2.2. Panel Plate D30 (1 drive 3, 1 drive 4 &1 drive 5)
background
Outdoor Unit Disassembly 5
2.3. Panel Plate X630 (1 drive 5)
background
Outdoor Unit Disassembly 6
2.4. Panel Plate E30 (1 drive 4&1 drive 5)
background
Outdoor Unit Disassembly 7
2.4. Panel Plate E30 (1 drive 6)
background
Outdoor Unit Disassembly 8
3. Outdoor Unit Disassembly
3.1 Panel Plate
4. X430
Procedure Illustration
1) Turn off the air conditioner and the
power breaker.
2) Remove the screws of big handle
assembly and water collector then
remove them.(6 screws) (see CJ_Multi_
X430_001).
3) Remove the screws of the top cover
and then remove the top cover (3
screws). One of the screws is located
underneath the big handle (see CJ_
Multi_X430_002).
CJ_Multi_X430_001
CJ_Multi_X430_002
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 9
Procedure Illustration
4) Remove the screws of the front panel
and then remove the front panel (7
screws) (see CJ_Multi_X430_003).
5) Remove the screws of the right panel
and then remove the right panel
(14 screws, two of them are used to fix
the optional rear net) (see CJ_Multi_
X430_004).
CJ_Multi_X430_003
CJ_Multi_X430_004
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 10
5. X630
Procedure Illustration
1) Turn off the air conditioner and the
power breaker.
2) Remove the screws of the top cover
and then remove the top cover (7
screws). (see CJ_Multi X630_001).
3) Remove the screws of the front right
panel and then remove the front
right panel (2 screws) (see CJ_Multi
X630_002).
CJ_Multi X630_001
CJ_Multi X630_002
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 11
Procedure Illustration
4) Remove the screws of the front panel
and then remove the front panel (8
screws) (see CJ_Multi X630_003).
5) Remove the screws of big handle
assembly and water collector then
remove them.(7 screws) (see CJ_Multi
X630_004).
CJ_Multi X630_003
CJ_Multi X630_004
Note: This section is for reference only. Actual unit appearance may vary.
Water collecting cover
Big Handle
background
Outdoor Unit Disassembly 12
Shield
Procedure Illustration
6) Remove 4 screws of rear net and
11 screws of right-rear panel, and
remove the rear net and right-rear
panel. (The rear net is for some
models)(see CJ_Multi X630_005).
CJ_Multi X630_005
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 13
3. D30
Procedure Illustration
1) Turn off the air conditioner and the
power breaker.
2) Remove four screws and then remove
the big handle.
3) Remove three screws and then remove
the water collecting cover. (see CJ_
Multi_D30-001.
4) Remove the screws of the top cover
and then remove the top cover (4
screws). Two of the screws is located
underneath the big handle (see CJ_
Multi_D30-002).
CJ_Multi_D30-001
CJ_Multi_D30-002
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 14
Procedure Illustration
5) Remove the screws of the front right
panel and then remove the front right
panel (2 screws) (see CJ_Multi_D30-
003).
CJ_Multi_D30-003
Note: This section is for reference only. Actual unit appearance may vary.
Front Right Panel
background
Outdoor Unit Disassembly 15
Procedure Illustration
6) Remove the screws of the front panel
and then remove the front panel (9
screws) (see CJ_Multi_D30-004).
7) Remove the screws of the rear net and
then remove the rear net (6 screws)
(see CJ_Multi_D30-005). (for some
models)
CJ_Multi_D30-004
CJ_Multi_D30-005
Note: This section is for reference only. Actual unit appearance may vary.
Right Panel
Front Panel
background
Outdoor Unit Disassembly 16
Procedure Illustration
8) Remove the screws of the right panel
and then remove the right panel
(12 screws) (see CJ_multi_D30-006
and CJ_Multi_D30-007).
CJ_Multi_D30-006
CJ_Multi_D30-007
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 17
4. E30
Procedure Illustration
1) Turn off the air conditioner and the
power breaker.
2) Remove the screws of the big handle
and then remove it.(3 screws) (see
CJ_Multi_E30-001).
3) Remove the screws of the water
collecting cover and then remove it.(3
screws) (see CJ_Multi_E30-001).
4) Unfix the four screws of the top cover
and then remove it. (see CJ_Multi_
E30-002).
CJ_Multi_E30-001
CJ_Multi_E30-002
Note: This section is for reference only. Actual unit appearance may vary.
Big Handle
water collectng cover
background
Outdoor Unit Disassembly 18
Procedure Illustration
5) Remove the two screws of the right
front pannel and then push it down
to unhook the right fornt pannel from
the nine hooks.(see CJ_Multi_E30-
003).
6) Remove the seven screws of the front
panel and then remove the front panel
(see CJ_Multi_E30-004).
CJ_Multi_E30-003
CJ_Multi_E30-004
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 19
Procedure Illustration
7) Unfix the screws on the right side of
the right panel.(9 screws)(see CJ_
Multi_E30-005).
8) Remove the screws on the back of
the right panel and then remove the
right panel and rear net.(9 screws).(see
CJ_Multi_E30-006).
CJ_Multi_E30-005
CJ_Multi_E30-006
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 20
3.2 Electrical parts
WARNING: Antistatic gloves must be worn when you disassemble the electronic box.
Note: Remove the air outlet grille(refer to 1.1 Panel Plate) before disassembling electrical parts.
PCB Board 1
Procedure Illustration
1) Remove the screws of the ground
wirings. (3 screws) (CJ_Multi-
PCB_001-1).
2) Unfix the hooks and screw and then
open the electronic control box cover
(5 hooks and 1 screw)(see CJ_Multi-
PCB_001-2).
CJ_Multi-PCB_001-1
CJ_Multi-PCB_001-2
Note: This section is for reference only. Actual unit appearance may vary.
Top Cover
background
Outdoor Unit Disassembly 21
Procedure Illustration
3) Disconnect the connector for outdoor
DC fan from the electronic control
board (see CJ_Multi-PCB_001-3).
4) Remove the connector for the
compressor (see CJ_Multi-
PCB_001-3).
5) Pull out the two blue wires connected
with the four way valve (see CJ_Multi-
PCB_001-3).
6) Pull out connectors of the condenser
coil temp. sensor(T3),outdoor ambient
temp. sensor(T4) and discharge temp.
sensor(TP) (see CJ_Multi-PCB_001-3).
7) Disconnect the electronic expansion
valve wire (see CJ_Multi-PCB_001-3).
8) Disconnect the communication
wire indoor PCB (see CJ_Multi-
PCB_001-3).
9) Disconnect the PFC inductor (see
CJ_Multi-PCB_001-3).
10) Then remove the electronic control box
(see CJ_Multi-PCB_001-3).
:6
6U]KX=OXK
)USS[TOIGZOUT=OXK=OZN/TJUUX6)(
+RKIZXOI+^VGTYO\K<GR\K
=G_<GR\K
*),GT
)USVXKYYUX
6,)/TJ[IZUX
::
'),GT
CJ_Multi-PCB_001-3
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 22
PCB Board 2
Procedure Illustration
1) Remove the screws of the top cover.
(2 screws) (CJ_Multi-PCB_002-1).
2) Unfix the screws and then turn over
the IPM board (4 screws ) (see CJ_
Multi-PCB_002-2).
CJ_Multi-PCB_002-1
CJ_Multi-PCB_002-2
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 23
Procedure Illustration
3) Disconnect the connector for outdoor
DC fan from the electronic control
board (see CJ_Multi-PCB_002-3).
4) Remove the connector for the
compressor (see CJ_Multi-
PCB_002-4).
5) Pull out the two blue wires connected
with the four way valve (see CJ_Multi-
PCB_002-4).
6) Pull out connectors of the condenser
coil temp. sensor(T3),outdoor ambient
temp. sensor(T4) and discharge temp.
sensor(TP) (see CJ_Multi-PCB_002-4).
7) Disconnect the electronic expansion
valve wire (see CJ_Multi-PCB_002-4).
8) Disconnect the communication
wire indoor PCB (see CJ_Multi-
PCB_002-4).
9) Disconnect the PFC inductor (see
CJ_Multi-PCB_002-4).
10) Then remove the electronic control box
(see CJ_Multi-PCB_002-4).
CJ_Multi-PCB_002-3
CJ_Multi-PCB_002-4
Note: This section is for reference only. Actual unit appearance may vary.
4-Way Valve
Reactor
T3/T4
TP
Terminal
Compressor
background
Outdoor Unit Disassembly 24
PCB board 3
Procedure Illustration
1) Remove the screws of the top
cover. (2 screws) (see CJ_Multi-
PCB_003-1).
2) Unfix the hooks and then open the
electronic control box cover (4 hooks)
(see CJ_Multi-PCB_003-2).
3) Disconnect the connector for fan
motor from the electronic control
board (see CJ_Multi-PCB_003-3).
4) Remove the connector for the
compressor (see CJ_Multi-
PCB_003-3).
5) Pull out the two blue wires
connected with the four way valve
(CJ_Multi-PCB_003-3).
6) Pull out connectors of the condenser
coil temp. sensor(T3),outdoor
ambient temp. sensor(T4) and
discharge temp. sensor(TP) (CJ_
Multi-PCB_003-3).
7) Disconnect the electronic expansion
valve wire (CJ_Multi-PCB_003-3).
8) Then remove the electronic control
board.
CJ_Multi-PCB_003-1
CJ_Multi-PCB_003-2
CJ_Multi-PCB_003-3
Note: This section is for reference only. Actual unit appearance may vary.
Compressor
T3, T4, TP
Electronic Expansion Valve
4-Way Valve
background
Outdoor Unit Disassembly 25
PCB board 3
Procedure Illustration
1) Unfix the hooks and then remove the
electronic installing box . (2 screws)
(see CJ_Multi_PCB_003-4).
2) Remove one screw of module board.
(see CJ_Multi_PCB_003-5).
3) Disconnect the connectors of the
module board. (see CJ_Multi_
PCB_003-6).
CJ_Multi-PCB_003-4
CJ_Multi-PCB_003-5
CJ_Multi-PCB_003-6
Note: This section is for reference only. Actual unit appearance may vary.
connected to main board
Electronic expansion
valve
T2B
background
Outdoor Unit Disassembly 26
PCB board 4
Procedure Illustration
1) Remove the screws and then remove
the reactor 1. (2 screws) (see CJ_
Multi_PCB_004-1).
2) Remove the screws and then
remove the reactor 2 (see CJ_Multi_
PCB_004-2).
CJ_Multi-PCB_004-1
CJ_Multi-PCB_004-2
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 27
PCB board 4
Procedure Illustration
1) Unfix five screws and then remove
the radiating pipe. (see CJ_Multi_
PCB_004-3).
2) Unfix two screws on the main board
(see CJ_Multi_PCB_004-3).
3) Disconnect the connectors on the
main board.(see CJ_Multi_PCB_004-
3).
4) Unfix two screws on the upper board
(see CJ_Multi_PCB_004-4).
5) Remove the connectors on the upper
board (see CJ_Multi_PCB_004-4).
CJ_Multi-PCB_004-3
CJ_Multi-PCB_004-4
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 28
PCB board 4
Procedure Illustration
1) Unfix two screws on the bottom
board. (see CJ_Multi_PCB_004-5).
2) Disconnect the connectors on
the bottom board (see CJ_Multi_
PCB_004-5).
CJ_Multi-PCB_004-5
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 29
PCB board 5
Procedure Illustration
1) Disconnect the connector for
compressor and release the ground
wire(1 screw). (see CJ_ODU_Multi_
PCB_005-1).
2) Pull out the wires from electrical
supporting plate and turn over the
electronic control assembly. (see
CJ_ODU_Multi_PCB_005-2).
3) Remove the electronic installing box
subassembly (4 hooks) (see CJ_ODU_
Multi_PCB_005-3).
CJ_ODU_Multi_PCB_005-1
CJ_ODU_Multi_PCB_005-2
CJ_ODU_Multi_PCB_005-3
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 30
Procedure Illustration
4) Remove the fixing board (2 hooks)
(see CJ_ODU_Multi_PCB_005-4).
5) Disconnect the connectors from
the electronic control board (see
CJ_ODU_Multi_PCB_005-5).
6) Then remove the electronic control
board (4 hooks).(see CJ_ODU_Multi_
PCB_005-6).
CJ_ODU_Multi_PCB_005-4
CJ_ODU_Multi_PCB_005-5
CJ_ODU_Multi_PCB_005-6
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 31
Procedure Illustration
7) Unfix the hooks and then remove the
electronic installing box . (2 screws)
(see CJ_Multi_PCB_005-7).
8) Remove one screw of module board.
(see CJ_Multi_PCB_005-8).
9) Disconnect the connectors of the
module board. (see CJ_Multi_
PCB_005-9).
CJ_Multi-PCB_005-7
CJ_Multi-PCB_005-8
CJ_Multi-PCB_005-9
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 32
PCB board 6
Procedure Illustration
1) Remove 5 screws of electrical control
box cover and remove it. (see CJ_
ODU_Multi_PCB_006-1).
2) Cut the ribbon by a shear and
disconnect the 4-way valve
connector. (see CJ_ODU_Multi_
PCB_006-2).
3) Ture over the electronic control box
subassembly. (see CJ_ODU_Multi_
PCB_006-3).
CJ_ODU_Multi_PCB_006-1
CJ_ODU_Multi_PCB_006-2
CJ_ODU_Multi_PCB_006-3
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 33
Procedure Illustration
4) Remove the electronic installing box
subassembly (4 hooks) (see CJ_ODU_
Multi_PCB_006-4).
5) Remove the support of electronic
control box.(see CJ_ODU_Multi_
PCB_006-5).
CJ_ODU_Multi_PCB_006-4
CJ_ODU_Multi_PCB_006-5
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 34
Procedure Illustration
6) Disconnect the connectors from
the electronic control board (see
CJ_ODU_Multi_PCB_006-6).
7) Remove 4 screws and then remove
the electronic control board.(see
CJ_ODU_Multi_PCB_006-6).
8) Pull out the connector, remove one
screw and then remove the key
board subassembly on terminal
board. (see CJ_Multi_PCB_006-7).
CJ_ODU_Multi_PCB_006-6
CJ_Multi-PCB_006-7
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 35
PCB board 7
Procedure Illustration
1) Remove 2 screws to disconnect the
power supply wires. (see CJ_ODU_
Multi_PCB_007-1)
2) Remove 3 screws to disconnect
ground wires. (see CJ_ODU_Multi_
PCB_007-1)
3) Disconnect the wires connected to
main control board. (see CJ_ODU_
Multi_PCB_007-1)
4) Disconnect the wires between main
control board and IPM module board.
(see CJ_ODU_Multi_PCB_007-1)
5) Remove the 4 screws and unfix the
6 hooks and then remove the main
control board.(see CJ_ODU_Multi_
PCB_007-1)
6) Remove 1 screw to remove the fan
motor capacitor(1 screw for each
capacitor).(see CJ_ODU_Multi_
PCB_007-1).
CJ_ODU_Multi_PCB_007-1
Note: This section is for reference only. Actual unit appearance may vary.
Fan motor capacitors
low&high pressure switch
T3&T4
connect to IPM
AC Fan motors
TP
connect to indoor unit
background
Outdoor Unit Disassembly 36
Procedure Illustration
1) Remove 2 screws to disconnect the
power supply wires. (see CJ_ODU_
Multi_PCB_007-2)
2) Remove 3 screws to disconnect the
wires connected to the compressor.
(see CJ_ODU_Multi_PCB_007-2)
3) Remove 3 screws to remove the
radiator.(see CJ_ODU_Multi_
PCB_007-2)
4) Disconnect the wires between IPM
module board and main control
board. (see CJ_ODU_Multi_PCB_007-
2)
5) Remove the 4 screws and unfix the
4 hooks and then remove the IPM
moduel board.(see CJ_ODU_Multi_
PCB_007-2)
CJ_ODU_Multi_PCB_007-2
Note: This section is for reference only. Actual unit appearance may vary.
DC Fan motors
Compressor
connect to main control board
background
Outdoor Unit Disassembly 37
PCB board 8
Procedure Illustration
1) Disconnect the connector for
compressor and release the ground
wire(1 screw). (see CJ_ODU_Multi_
PCB_008-1).
2) Pull out the wires from electrical
supporting plate and turn over the
electronic control assembly. (see
CJ_ODU_Multi_PCB_008-2).
3) Remove the electronic installing box
subassembly (4 hooks) (see CJ_ODU_
Multi_PCB_008-3).
CJ_ODU_Multi_PCB_008-1
CJ_ODU_Multi_PCB_008-2
CJ_ODU_Multi_PCB_008-3
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 38
Procedure Illustration
4) Remove the fixing board (2 hooks)
(see CJ_ODU_Multi_PCB_008-4).
5) Disconnect the connectors from
the electronic control board (see
CJ_ODU_Multi_PCB_008-5).
6) Then remove the electronic control
board (4 hooks).(see CJ_ODU_Multi_
PCB_008-6).
CJ_ODU_Multi_PCB_008-4
CJ_ODU_Multi_PCB_008-5
CJ_ODU_Multi_PCB_008-6
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 39
Procedure Illustration
7) Remove 3 screws and then remove
the cover of electronic installing box.
(see CJ_Multi_PCB_008-7).
8) Disconnect the connectors of the
module board and then remove
the module board. (see CJ_Multi_
PCB_008-7).
CJ_Multi-PCB_008-7
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 40
PCB board 9
Procedure Illustration
1) Remove the cover of electrical
control box. (see CJ_ODU_Multi_
PCB_009-1).
2) Disconnect the fan motor connector.
(see CJ_ODU_Multi_PCB_009-2).
3) Remove eight fixing screws.
4) Ture over the electronic control box
subassembly. (see CJ_ODU_Multi_
PCB_009-3).
CJ_ODU_Multi_PCB_009-1
CJ_ODU_Multi_PCB_009-2
CJ_ODU_Multi_PCB_009-3
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 41
Procedure Illustration
5) Remove 3 screws and then remove
the bracket. (see CJ_ODU_Multi_
PCB_009-4).
6) Disconnect the connectors from
the electronic control board (see
CJ_ODU_Multi_PCB_009-4).
7) Remove 3 screws and then remove
the electronic control board.(see
CJ_ODU_Multi_PCB_009-4).
8) Pull out the connector, remove one
screw and then remove the key
board subassembly on terminal
board. (see CJ_Multi_PCB_009-5).
CJ_ODU_Multi_PCB_009-4
CJ_ODU_Multi_PCB_009-5
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 42
PCB board 10
Procedure Illustration
9) Disconnect the connectors from
the electronic control board (see
CJ_ODU_Multi_PCB_010-1).
10) Remove 3 screws and then remove
the electronic control board.(see
CJ_ODU_Multi_PCB_010-1).
11) Pull out the connector, remove one
screw and then remove the key
board subassembly on terminal
board. (see CJ_Multi_PCB_010-2).
CJ_ODU_Multi_PCB_010-1
CJ_ODU_Multi_PCB_010-2
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 43
3.3 Fan Assembly
Note: Remove the panel plate (refer to 1.1 Panel Plate) before disassembling fan.
Procedure Illustration
1) Remove the nut securing the fan
with a spanner (see CJ_ODU_
FAN_001-1&2).
2) Remove the fan.
CJ_ODU_FAN_001-1
CJ_ODU_FAN_001-2
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 44
3.4 Fan Motor
Note: Remove the panel plate and the connection of fan motor on PCB (refer to 1.1 Panel Plate and 1.2
Electrical parts) before disassembling fan motor.
Procedure Illustration
3) Remove the fixing screws of the fan motor
(4 screws) (see CJ_ODU_MOTOR_001).
4) Remove the fan motor.
CJ_ODU_MOTOR_001
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 45
3.5 Sound blanket
Note: Remove the panel plate (refer to 1.1 Panel plate) before disassembling sound blanket.
Procedure Illustration
1) Remove the sound blanket (side and
top) (see CJ_ODU_BLANKET_001).
CJ_ODU_BLANKET_001
Note: This section is for reference only. Actual unit appearance may vary.
Sound Blanket(side)
Sound Blanket(top)
background
Outdoor Unit Disassembly 46
3.6 Four-way valve (for heat pump models)
WARNING: Evacuate the system and confirm that there is no refrigerant left in the system before removing the
four-way valve and the compressor. (For R32 & R290, you should evacuate the system with the vacuum pump; flush the
system with nitrogen; then repeat the two steps before heating up the brazed parts. The operations above should be
implemented by professionals.)
Note: Remove the panel plate, connection of four-way valve on PCB (refer to 1.1 Panel plate and 1.2 Electrical
parts) before disassembling sound blanket.
Procedure Illustration
1) Heat up the brazed parts and then detach
the the four-way valve and the pipe (see
CJ_ODU_VALVE_001).
2) Remove the four-way valve assembly with
pliers.
CJ_ODU_VALVE_001
Note: This section is for reference only. Actual unit appearance may vary.
background
Outdoor Unit Disassembly 47
3.7 Compressor
WARNING: Evacuate the system and confirm that there is no refrigerant left in the system before removing the
four-way valve and the compressor. (For R32 & R290, you should evacuate the system with the vacuum pump; flush the
system with nitrogen; then repeat the two steps before heating up the brazed parts. The operations above should be
implemented by professionals.)
Note: Remove the panel plate, connection of compressor on PCB (refer to 1.1 Panel plate and 1.2 Electrical
parts) before disassembling sound blanket.
Procedure Illustration
1) Remove the flange nut of terminal cover
and remove the terminal cover (see CJ_
ODU_COMP_001).
2) Disconnect the connectors (see CJ_ODU_
COMP_002).
CJ_ODU_COMP_001
CJ_ODU_COMP_002
Note: This section is for reference only. Actual unit appearance may vary.
Terminal Cover
background
Outdoor Unit Disassembly 48
Procedure Illustration
3) Remove the hex nuts and washers securing
the compressor, located on the bottom
plate (see CJ_ODU_COMP_003).
4) Heat up the brazed parts and then remove
the the discharge pipe and the suction
pipe (see CJ_ODU_COMP_004).
5) Lift the compressor from the base pan
assembly with pliers.
CJ_ODU_COMP_003
CJ_ODU_COMP_004
Note: This section is for reference only. Actual unit appearance may vary.
Discharge Pipe
Suction Pipe
background
Contents
Troubleshooting
1. Safety Caution ................................................................................................ 3
2. General Troubleshooting .................................................................................. 4
2.1 Error Display (Outdoor unit) ...................................................................................... 4
3. Outdoor Unit Point Check Function ................................................................ 6
4. Quick Maintenance by Error Code ................................................................... 10
5. Troubleshooting by Error Code ......................................................................... 12
5.1 EC 51 (ODU EEPROM parameter error diagnosis and solution) ................................. 12
5.2 EL 01(IDU & ODU communication error diagnosis and solution) ................................ 13
5.3 EC 07 (Fan Speed Is Operating Outside of Normal Range)/EC 71(Over Current Failure of
Outdoor DC Fan Motor) Diagnosis and Solution ........................................................ 16
5.4 EC 52/EC 53/EC 54/EC 56/EC 57/EC 5A/EC 5b/EC 5E/EC 50 (Open circuit or short circuit
of temperature sensor diagnosis and solution) ......................................................... 18
5.5 PC 08(Current overload protection)/PC 44(ODU zero speed protection) /PC
46(Compressor speed has been out of control)/PC 49(Compressor overcurrent failure)
19
5.6 PC 00(IPM malfunction diagnosis and solution) ......................................................... 21
5.7 PC 01(Over voltage or too low voltage protection)/PC 10(ODU low AC voltage
protection)/PC 11(ODU main control board DC bus high voltage protection)/PC 12(ODU
main control board DC bus low voltage protection /341 MCE error) Diagnosis and
Solution .................................................................................................................... 23
5.8 PC 40(Communication error between ODU main chip and compressor driven chip
diagnosis and solution) ............................................................................................ 26
5.9 PC 0F(PFC module protection diagnosis and solution) .............................................. 27
5.10 PC 06(Discharge temperature protection of compressor diagnosis and solution) ....... 29
5.11 PC 0A(High temperature protection of condenser diagnosis and solution) ................ 30
background
Contents
Troubleshooting
5.12 PC 02/LC 06 (Compressor top(or IPM) temp. protection diagnosis and solution) ....... 32
5.13 PC 30 (System high pressure protection diagnosis and solution) ................................ 34
5.14 PC 31 (System low pressure protection diagnosis and solution) ................................. 36
5.15 EC 72 (Lack phase failure of outdoor DC fan motor diagnosis and solution) .............. 38
5.16 PC 43 (ODU compressor lack phase protection diagnosis and solution) ...................... 39
5.17 PC 45 (ODU IR chip drive failure diagnosis and solution) ............................................ 40
5.18 CE (Automatic correction of wiring/piping error) ....................................................... 40
5.19 EH C1(Refrigerant sensor detects leakage diagnosis and solution) ............................. 41
5.20 EC 55(ODU IPM module temperature sensor malfunction diagnosis and solution) ..... 42
5.21 EC 5C(Pressure sensor failure diagnosis and solution) ................................................ 43
5.22 PC 13(The AC power is cut off or the AC voltage detection circuit fails diagnosis and solution) 44
5.23 PC A1(Condensation protection of refrigerant pipe diagnosis and solution) ............... 45
6. Check Procedures
background
Troubleshooting 3
1. Safety Caution
WARNING
Be sure to turn off all power supplies or disconnect all wires to avoid electric shock.
While checking indoor/outdoor PCB, please equip oneself with antistatic gloves or wrist
strap to avoid damage to the board.
WARNING
Electricity remains in capacitors even when the power supply is off.
Ensure the capacitors are fully discharged before troubleshooting.
background
Troubleshooting 4
2. General Troubleshooting
2.1 Error Display
Display Malfunction or Protection Solution
f
Defrosting
Normal
Display, not
error code
FC
Forced cooling
EC 07
ODU fan speed out of control TS16
EC 71
Over current failure of outdoor DC fan motor TS16
EC 72
Lack phase failure of outdoor DC fan motor TS23
EC 50
ODU temp. sensor error(T3,T4.TP) TS18
EC 51
ODU EEPROM parameter error TS12
EC 52
ODU coil temp. sensor(T3) error TS18
EC 53
ODU ambient temp. sensor(T4) error TS18
EC 54
COMP. discharge temp. sensor(TP) error TS18
EC 55
ODU IPM module temperature sensor malfunction TS42
EC 56
IDU coil outlet temp. sensor(T2B) error TS18
EC 57
Refrigerant pipe temperature sensor error TS18
EC 5A
Failure of enthalpy inlet temperature sensor TS18
EC 5
Failure of enthalpy outlet temperature sensor TS18
EC 5E
Condenser temperature sensor(T3B) failure TS18
EC 5C
Pressure sensor failure TS43
EH C1
Refrigerant sensor detects leakage TS41
EL 01
IDU & ODU communication error TS13
PC 00
IPM module protection TS21
PC 02
Compressor top(or IPM) temp. protection TS32
PC 06
Discharge temperature protection of compressor TS29
PC 08
Outdoor overcurrent protection TS19
PC 0A
High temperature protection of condenser TS30
PC 0F
PFC module protection TS27
background
Troubleshooting 5
PC 0L
Low ambient temperature protection --
PC 10
ODU low AC voltage protection TS23
PC 11
ODU main control board DC bus high voltage protection TS23
PC 12
ODU main control board DC bus low voltage protection /341 MCE error TS23
PC 13
The AC power is cut off or the AC voltage detection circuit fails TS44
PC 30
System high pressure protection TS34
PC 31
System low pressure protection TS36
PC 40
Communication error between ODU main chip and compressor driven chip TS26
PC 43
ODU compressor lack phase protection TS39
PC 44
ODU zero speed protection TS19
PC 45
ODU IR chip drive failure TS40
PC 46
Compressor speed has been out of control TS19
PC 49
Compressor overcurrent failure TS19
PC A1
Condensation protection of refrigerant pipe TS45
LC 06
High temperature protection of Inverter module (IPM) TS32
background
Troubleshooting 6
3. Outdoor Unit Point Check Function
• A check switch is included on the auxiliary PCB.
• Push SW1 to check the unit’s status while running. The digital display shows the
following codes each time the SW1 is pushed.
Number of
Presses
Display Remark
0 Normal display Displays running frequency, running state, or malfunction code
1
Quantity of indoor units with
working connection
Display Number of indoor unit
2
Outdoor unit running mode
code
Stanby: 0,Fan only: 1, Cooling/Drying: 2, Heating: 3, Forced
cooling: 6, Forced defrostling: A
3 Indoor unit A capacity
The capacity unit is horse power. If the indoor unit is not
connected, the digital display shows the following: “--”
(6K:0.6HP, 7K:0.8HP, 9K:1.0HP, 12K:1.2HP, 18K:1.5HP,
24K:2.5HP, 30K:3.0HP, 36K:3.2HP)
4 Indoor unit B capacity
5 Indoor unit C capacity
6 Indoor unit D capacity
7 Indoor unit E capacity
8
Indoor unit A capacity demand
code
Norm code*HP
(6K:0.6HP, 7K:0.8HP, 9K:1.0HP, 12K:1.2HP, 18K:1.5HP,
24K:2.5HP, 30K:3.0HP, 36K:3.2HP)
9
Indoor unit B capacity demand
code
10
Indoor unit C capacity demand
code
11
Indoor unit D capacity demand
code
12
Indoor unit E capacity demand
code
13
Outdoor unit amendatory
capacity demand code
14
The frequency corresponding
to the total indoor units'
amendatory capacity demand
15
The frequency after the
frequency limit
16
The frequency sending to
compressor control chip
17
Indoor unit A evaporator outlet
temperature (T2BA)
If the temperature is lower than -9
o
C, the digital display
shows “-9.” If the temperature is higher than 70
o
C, the digital
display shows “70.” If the indoor unit is not connected, the
digital display shows: “--”
18
Indoor unit B evaporator outlet
temperature (T2BB)
19
Indoor unit C evaporator outlet
temperature (T2BC)
20
Indoor unit D evaporator outlet
temperature (T2BD)
21
Indoor unit E evaporator outlet
temperature (T2BE)
background
Troubleshooting 7
22
Indoor unit A room
temperature (T1A)
If the temperature is lower than 0
o
C, the digital display shows
“0.” If the temperature is higher than 70
o
C, the digital display
shows “70.” If the indoor unit is not connected, the digital
display shows: “--”
23
Indoor unit B room
temperature (T1B)
24
Indoor unit C room
temperature (T1C)
25
Indoor unit D room
temperature (T1D)
26
Indoor unit E room
temperature (T1E)
27
Indoor unit A evaporator
temperature (T2A)
If the temperature is lower than -9
o
C, the digital display shows
“-9.” If the temperature is higher than 70
o
C, the digital display
shows “70.” If the indoor unit is not connected, the digital
display shows: “--”
28
Indoor unit B evaporator
temperature (T2B)
29
Indoor unit C evaporator
temperature (T2C)
30
Indoor unit D evaporator
temperature (T2D)
31
Indoor unit E evaporator
temperature (T2E)
32
Condenser pipe temperature
(T3)
33
Outdoor ambient temperature
(T4)
34
Compressor discharge
temperature (TP)
The display value is between 30–129
o
C. If the temperature
is lower than 30
o
C, the digital display shows “30.” If the
temperature is higher than 99
o
C, the digital display shows
single and double digits. For example, If the display shows 0.5,
so 0.5 multipled by 10 to become 5, then added to 100 to
become 105
o
C.
35 AD value of current The display value is a hex number.
For example, the digital display tube shows “Cd”, so
C*16
1
+d*16
0
=12*16+13=205, it means AD value is 205.
AD value is detected by the chip. for M5OX631-36HFN10-
M1XD&M5OX631-36HFN10-M1X, actual AD value is AD value
plus 60
36 AD value of AC voltage
37 AD value of DC voltage
38
EXV open angle for A indoor
unit
Actual data/4.
If the value is higher than 99, the digital display shows single
and double digits.
For example, if the digital display shows “2.0”, so 2.0
multipled by 10 to become 20, then added to 100 to become
120, the EXV open angle is 120×4=480p.
39
EXV open angle for B indoor
unit
40
EXV open angle for C indoor
unit
41
EXV open angle for D indoor
unit
42
EXV open angle for E indoor
unit
43
MVI open angle (for some
models)
44
EXI open angle (for some
models)
background
Troubleshooting 8
45 Frequency limit symbol
Bit7 Reserved The display value is a
hexidecimal number.
For example, the
digital display show
2A, the corresponding
binary is 101010, so
Bit5=1, Bit3=1, and
Bit1=1.
This means that a
frequency limit may be
caused by current, IPM
or T3.
Bit6
Frequency limit caused by
voltage
Bit5
Frequency limit caused by
current.
Bit4 Reserved
Bit3
Frequency limit caused by
IPM.
Bit2
Frequency limit caused
by Compressor discharge
temperature(T5)
Bit1
Frequency limit caused by
Outdoor heat exchanger pipe
temperature(T3)
Bit0
Frequency limit caused by
Middle indoor heat exchanger
coil temperature(T2)
46 T2B fault
00:No fault,01:T2B-A fault, ,02:T2B-B fault ,03:T2B-C
fault,04:T2B-D fault, 05:T2B-E fault, 06:T2B-F fault(The display
priority is A-B-C-D-E-F)
47 Average value of T2
(Sum T2 value of all indoor units)/(number of indoor units in
good connection)( The heating is the average value of T2, and
the cooling is the average value of T2B)
If the temperature is lower than -9
o
C, the digital display shows
“-9”.
48 Outdoor unit fan speed See next list
49 Reason of stop
50~59 Reserved
60
Air injection enthalpy inlet
temperature (for hyper heat
models)
If the temperature is lower than -9
o
C, the digital display shows
“-9”. If the temperature is higher than 70
o
C, the digital display
shows “70.” If the indoor unit is not connected, the digital
display shows: “--”
61
Air injection enthalpy outlet
temperature (for hyper heat
models)
62
Condenser coil middle
temperature (for hyper heat
models)
63
Refrigerant tube inlet
temperature (for hyper heat
models)
64 Target discharge temperature
The display value is between 0–199
o
C. If the temperature
is lower than 30
o
C, the digital display shows “30.” If the
temperature is higher than 99
o
C, the digital display shows
single and double digits. For example, If the display shows 0.5,
so 0.5 multipled by 10 to become 5, then added to 100 to
become 105
o
C..
65 Indoor unit F capacity
The capacity unit is horse power. If the indoor unit is not
connected, the digital display shows the following: “--”
background
Troubleshooting 9
66
Indoor unit F capacity demand
code
Norm code*HP
(9K: 1HP,12K: 1.2HP,18K: 1.5HP)
67
Indoor unit F evaporator outlet
temperature (T2BF)
If the temperature is lower than -9
o
C, the digital display
shows “-9.” If the temperature is higher than 70
o
C, the digital
display shows “70.” If the indoor unit is not connected, the
digital display shows: “--”
68
Indoor unit F room temperature
(T1F)
If the temperature is lower than 0
o
C, the digital display shows
“0.” If the temperature is higher than 70
o
C, the digital display
shows “70.” If the indoor unit is not connected, the digital
display shows: “--”
69
Indoor unit F evaporator
temperature (T2F)
If the temperature is lower than -9
o
C, the digital display
shows “-9.” If the temperature is higher than 70
o
C, the digital
display shows “70.” If the indoor unit is not connected, the
digital display shows: “--”
70
EXV open angle for F indoor
unit
Actual data/4.
If the value is higher than 99, the digital display shows single
and double digits.
71 IPM module temperature
The display value is between 0–199
o
C. If the temperature is
higher than 99
o
C, the digital display shows single and double
digits. For example, If the display shows 5.0, so 5.0 multipled
by 10 to become 50, then added to 100 to become 150
o
C.
72
The high pressure sensor
detects the pressure
corresponding to the
condensation temperature(Tc)
The digital display shows: “--”
73
Reserved
74
Outdoor unit fan speed corresponding table:
Outdoor unit fan speed Display
>600rpm 02
>300rpm &<= 600rpm 03
<=300rpm 04
background
Troubleshooting 10
4. Quick Maintenance by Error Code
If you do not have the time to test which specific parts are faulty, you can directly change the required parts according
the error code. You can find the parts to replace by error code in the following table.
Part requiring
replacement
Error Code
EL 01 EC 50 EC 51 EC 52 EC 53
EC 54
EC 55 EC 56 EC 57 EC 5A EC 5b EC5E
Indoor PCB
x x x x x x x x x x x
Outdoor PCB
ODU coil temp. sensor x x x x x x x x x x
ODU ambient temp.
sensor
x x x x x x x x x x
COMP. discharge temp.
sensor
x x x x x x x x x x
IPM module
temperature sensor
x x x x x x x x x x x
IDU coil outlet temp.
sensor
x x x x x x x x x x x
Refrigerant pipe
temperature sensor
x x x x x x x x x x x
Enthalpy inlet
temperature sensor
x x x x x x x x x x x
Enthalpy outlet
temperature sensor
x x x x x x x x x x x
Condenser
temperature sensor
x x x x x x x x x x x
Reactor x x x x x x x x x x x
IPM module board x x x x x x x x x x x
Part requiring
replacement
Error Code
ec 5c eh c1 EC 07/EC 71 PC 00
PC 01/PC
10/PC 11/
PC 12
PC 02
PC 08/PC
44/ PC
46/ PC 49
PC 13 PC A1 PC 0F
Outdoor PCB x
Outdoor fan motor x x x x x x x
Reactor or inductance x x x x x x
Compressor x x x x x x x x x
IPM module board x x x x x x x
Bridge rectifier x x x x x x x
Pressure sensor x x x x x x x x x
PFC module x x x x x x x x x
Additional refrigerant x x x x x x x x x
Over load protector x x x x x x x x x
ODU ambient temp.
sensor
x x x x x x x x x
Refrigerant pipe
temperature sensor
x x x x x x x x x
background
Troubleshooting 11
Part requiring replacement
Error Code
PC 40 EC 72 PC 43 PC 45 Pc 06 Pc 0a PC 30 pc 31
Outdoor PCB x
Outdoor fan motor x x x x
ODU coil temp. sensor x x x x x x x
COMP. discharge temp. sensor x x x x x x x
Compressor x x x x x x x
IPM module board x x x x x x x
Additional refrigerant x x x x x
Electric control box x x x x x x x
High pressure switch x x x x x x x
Low pressure switch x x x x x x x
background
Troubleshooting 12
5. Troubleshooting by Error Code
5.1 EC 51 (ODU EEPROM parameter error diagnosis and solution)
Description: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.
Recommended parts to prepare:
• Indoor PCB
• Outdoor PCB
Troubleshooting and repair:
Shut off the power supply and
turn it on 2 minutes later.
Shut off the power supply and
turn it on 2 minutes later.
Is it still displaying
the error code?
Is it still displaying
the error code?
YES
Replace the outdoor main
PCB.
Replace the outdoor main
PCB.
The unit is operating normally.
The unit is operating normally. NO
Remarks:
EEPROM: A read-only memory whose contents can be erased and reprogrammed using a pulsed voltage.
The location of the EEPROM chip on the indoor and outdoor PCB is shown in the following two images:
This pictures are only for reference, actual appearance may vary.
background
Troubleshooting 13
5.2 EL 01(IDU & ODU communication error diagnosis and solution)
Description: Indoor unit does not receive the feedback from outdoor unit during 110 seconds and this condition
happens 4 times continuously.
Recommended parts to prepare:
• Indoor PCB
• Outdoor PCB
• IPM module board
• Reactor
Troubleshooting and repair:
background
Troubleshooting 14
Indoor
/ outdoor units communication error
Start
:
Power off ,
then Power on the
A
/C by the Breaker
. (
reconnect the
power wire).
Is it still displaying the
error code?
Yes
No
Replace outdoor main PCB
assembly(include wiring) totally
Check wiring on the outdoor and
indoor terminal follow the wiring
diagram.
Is all connecting correctly
?
Yes
No
Measure Vs, is it moving
alternately between positive
value and negative value? (
Vs is
the voltage between S and N
).
Turn on all indoor unit by remote
controller
. Is all indoor unit
display
Turn off the all indoor units
. Is IPM
power LED or operating
LED lamp
On?
Yes
A:
Is all the wiring
between terminal and
Indoor PCB connect ok?
No
Yes
A
No
Reconnect the wiring
Is indoor units number correct? Check
on the outdoor check point . (2 for
dual zone, 3 for tri zone, 4 for qua
zone
,5 for qui zone).
Yes
No first time
Yes
Yes
Replace the Indoor PCB
Power on by remote
controller, I
Is it still
displaying the error code
after 3 minutes?
Trouble is solved
No second time
No
Yes
Reconnect the wiring
No
Replace IPM board or the
outdoor main PCB
No
Is the reactor connecting
well?
No Reconnect the wiring
Replace the outdoor main
PCB
Yes
No
Is main board“
”
lamp on? .
background
Troubleshooting 15
Remarks:
• Use a multimeter to test the resistance of the reactor which does not connect with capacitor.
• The normal value should be around zero ohm. Otherwise, the reactor must have malfunction.
Note: The picture and the value are only for reference, actual condition and specific value may vary.
background
Troubleshooting 16
5.3 EC 07 (Fan Speed Is Operating Outside of Normal Range)/EC 71(Over Current Failure
of Outdoor DC Fan Motor) Diagnosis and Solution
Description: When indoor / outdoor fan speed keeps too low or too high for a certain time, the LED displays the failure
code and the AC turns off.
Recommended parts to prepare:
• Connection wires
• Fan assembly
• Fan motor
• PCB
Troubleshooting and repair:
YES
Power off, then restart the unit after 2 minutes.
Is it within normal parameters?
Replace the fan motor
Does a problem remain? The unit is operating normallyNO
Shut off the power supply, Rotate
the fan by hand.
YES
Does it turn easily? Find the cause
of the problem and resolve it
NO
Check the wiring of fan motor.
YES
Is it improperly wired?
Ensure proper connections
Measure the voltage for
the fan motor from the PCB.
YES
Replace the manr PCBNO
background
Troubleshooting 17
Index:
1. Outdoor DC Fan Motor(control chip is in fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector. If the
value of the voltage is not in the range showing in below table, the PCB must has problems and need to be replaced.
• DC motor voltage input and output (voltage: 220-240V~):
No. Color Signal Voltage
1 Red Vs/Vm 192V~380V
2 --- --- ---
3 Black GND 0V
4 White Vcc 13.5-16.5V
5 Yellow Vsp 0~6.5V
6 Blue FG 13.5-16.5V
2. Outdoor DC Fan Motor (control chip is in outdoor PCB)
Release the UVW connector. Measure the resistance of U-V, U-W, V-W. If the resistance is not equal to each other, the
fan motor must has problems and need to be replaced. otherwise the PCB must has problems and need to be replaced.
background
Troubleshooting 18
5.4 EC 52/EC 53/EC 54/EC 56/EC 57/EC 5A/EC 5b/EC 5E/EC 50 (Open circuit or short circuit
of temperature sensor diagnosis and solution)
Description: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure code.
Recommended parts to prepare:
• Connection wires
• Sensors
• PCB
Troubleshooting and repair:
Check the connection between
temperature sensor and PCB.
Replace PCB
Is it within acceptable
parameters?
Is it properly wired?
Ensure proper connections.
NO
Measure the resistance value
of the sensor.
YES
Replace the sensor.NO
YES
This picture and the value are only for reference, actual appearance and value may vary
background
Troubleshooting 19
5.5 PC 08(Current overload protection)/PC 44(ODU zero speed protection) /PC
46(Compressor speed has been out of control)/PC 49(Compressor overcurrent failure)
Description: An abnormal current rise is detected by checking the specified current detection circuit.
Recommended parts to prepare:
• Outdoor PCB
• Connection wires
• Bridge rectifier
• PFC circuit or reactor
• Refrigeration piping system
• Pressure switch
• Outdoor fan
• IPM module board
Troubleshooting and repair:
background
Troubleshooting 20
background
Troubleshooting 21
5.6 PC 00(IPM malfunction diagnosis and solution)
Description: When the voltage signal the IPM sends to the compressor drive chip is abnormal, the LED displays the
failure code and the AC turns off.
Recommended parts to prepare:
• Connection wires
• IPM module board
• Outdoor fan assembly
• Compressor
• Outdoor PCB
• Reactor or inductance
• Bridge rectifier
Troubleshooting and repair:
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the
IPM is defective. Otherwise, please follow the procedure below:
background
Troubleshooting 22
IPM module protection
IPM module protection
Yes
Is the power voltage normal?
Is the power voltage normal?
Is the outdoor terminal voltage
normal?
Is the outdoor terminal voltage
normal?
Restart the unit when the power supply
returns to normal
Restart the unit when the power supply
returns to normal
No
Yes
No
Reconnect the
power wires
Reconnect the
power wires
Yes
Is the voltage between L and N
normal?
Is the voltage between L and N
normal?
Yes
Is the input voltage of bridge
rectifier normal?
Is the input voltage of bridge
rectifier normal?
No
No
Are the power wires
connected properly?
Are the power wires
connected properly?
Reconnect L and N
Reconnect L and N
Are L and N wired
correctly?
Are L and N wired
correctly?
Reconnect the
bridge rectifier
Reconnect the
bridge rectifier
Is the bridge rectifier
properly wired?
Is the bridge rectifier
properly wired?
No
No
Yes
Replace the PFC module(If This has not
been done already)
Replace the PFC module(If This has not
been done already)
No
Is the voltage between P and N
properly wired according to
9.Check Procedures
Is the voltage between P and N
properly wired according to
9.Check Procedures
Replace the bridge rectifier
Replace the bridge rectifier
No
Is the bridge rectifier
operating normally?
Is the bridge rectifier
operating normally?
Are the reactor or
Inductance wired
properly?
Are the reactor or
Inductance wired
properly?
Reconnect the wiring
Reconnect the wiring No
Are the reactor or
inductance normal?
Are the reactor or
inductance normal?
Yes
Replace reactor or
inductance
Replace reactor or
inductance
No
Is the connecting wire
between the main board and
the IPM board connected
tightly?
Is the connecting wire
between the main board and
the IPM board connected
tightly?
Reconnect the main board
and IPM board
Reconnect the main board
and IPM board
No
Is the outdoor unit
ventilation in working order?
Is the outdoor unit
ventilation in working order?
Yes
Make sure that the outdoor unit is
ventilating properly
Make sure that the outdoor unit is
ventilating properly
Check whether the refrigerant system is
in working order
Check whether the refrigerant system is
in working order
No
Is the outdoor fan running
properly?
Is the outdoor fan running
properly?
Refer to the solution for
themalfunction of the fan speed
being out of control . Find the cause
and resolve the problem
Refer to the solution for
themalfunction of the fan speed
being out of control . Find the cause
and resolve the problem
No
Yes
No
Yes
Yes
Is the compress is
running normally?
Is the compress is
running normally?
Yes
Replace the compressor
Replace the compressor
No
Replace IPM Board. Is the problem
resolved?
Replace IPM Board. Is the problem
resolved?
Replace the outdoor main PCB. Is
the problem resolved?
Replace the outdoor main PCB. Is
the problem resolved?
No
Is the connecting wire of the
compressor is connected
correctly or tightly
Is the connecting wire of the
compressor is connected
correctly or tightly
Reconnect he connecting
wire of the compressor
Reconnect he connecting
wire of the compressor
No
Yes
Yes
background
Troubleshooting 23
5.7 PC 01(Over voltage or too low voltage protection)/PC 10(ODU low AC voltage
protection)/PC 11(ODU main control board DC bus high voltage protection)/PC
12(ODU main control board DC bus low voltage protection /341 MCE error) Diagnosis
and Solution
Description: Abnormal increases or decreases in voltage are detected by checking the specified voltage detection circuit.
Recommended parts to prepare:
• Power supply wires
• IPM module board
• Outdoor PCB
• Bridge rectifier
• PFC circuit or reactor
Troubleshooting and repair:
background
Troubleshooting 24
background
Troubleshooting 25
Voltage protection
Voltage protection
Check whether the power
voltage is normal
.
Check whether the power
voltage is normal
.
Measure whether o
utdoor
terminal voltage is normal
?
Measure whether outdoor
terminal voltage is normal?
Restart the unit when the power supply
gets normal
Restart the unit when the power supply
gets normal
No
Yes
No
Reconnect it well
Reconnect it well
Yes
Yes
No
Replace the IPM board, If the IPM board and
main board is in a board, replace the
outdoor main PCB
Replace the IPM board, If the IPM board and
main board is in a board, replace the
outdoor main PCB
Yes
Replace the PFC module(If has)
Replace the PFC module(If has)
No
Yes
Measure whether the voltage
between L and N is normal?
Measure whether
the voltage
between L
and N is
normal
?
Yes
Measure whether input voltage
of bridge rectifier is normal?
Measure whether input voltage
of bridge rectifier is normal?
Yes
No
No
Measure whether the voltage
between P and N is normal
refer to 9. Check Procedures
Measure whether the voltage
between P and N is normal
refer to 9. Check Procedures
Replace the bridge rectifier
Replace the bridge rectifier
No
Check whether bridge
rectifier is normal
Check whether bridge
rectifier is normal
Check the wiring of
reactor or inductance
Check the wiring of
reactor or inductance
Reconnect the wiring
Reconnect the wiring No
Check whether reactor
or inductance is normal
Check whether reactor
or inductance is normal
Yes
Replace reactor or
inductance
Replace reactor or
inductance
No
Check the wiring of
power wires well or
correctly
Check the wiring of
power wires well or
correctly
Reconnect it well
Reconnect it well
Check the wiring of
L and N well or
correctly
Check the wiring of
L and N well or
correctly
Reconnect it well
Reconnect it well
Check the wiring of
bridge rectifier well
or correctly
Check the wiring of
bridge rectifier well
or correctly
background
Troubleshooting 26
5.8 PC 40(Communication error between ODU main chip and compressor driven chip
diagnosis and solution)
Description: The main PCB cannot detect the IPM board.
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• IPM module board
• Electric control box
Troubleshooting and repair:
background
Troubleshooting 27
Communication malfunction between
IPM board and outdoor main board
Is there at least one LED in
the IPM board light?
Check the signal wire
between the IPM board and
the main board, is it
connected good?
Reconnect and retry. Is error
still display?
Replace IPM board, and then
check whether the system
can run normally
Replace the electric control
box
No
No
No
No
Yes
Trouble is solved
No
Yes
Replace outdoor main board
,
and then check whether the
system can run normally
No
Yes
Yes
5.9 PC 0F(PFC module protection diagnosis and solution)
Description: Outdoor PCB detects PFC signal is low voltage or DC voltage is lower than 340V for 6s when quick check.
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• Inductance
• PFC circuit or IPM module board
Troubleshooting and repair:
background
Troubleshooting 28
PFC module protection
PFC module protection
Check whether the
connecting line between
main board and the PFC
module is connected tightly
Check whether the
connecting line between
main board and the PFC
module is connected tightly
Yes
Measure whether the voltage
between P and N is normal
refer to the Appendix?
Measure whether the voltage
between P and N is normal
refer to the Appendix?
No
Check whether the
inductance of PFC module is
good? If the inductance is
good, the resistance of the
two ports is 0
Check whether the
inductance of PFC module is
good? If the inductance is
good, the resistance of the
two ports is 0
Yes
Replace the inductance
Replace the inductanceNo
Connect it tightly, check
normal or not
Connect it tightly, check
normal or not
Replace the outdoor main board
Replace the outdoor main boardYes
Yes
No
No
Replace the PFC module
Replace the PFC module
Trouble is solved
Trouble is solved
background
Troubleshooting 29
5.10 PC 06(Discharge temperature protection of compressor diagnosis and solution)
Description: When the compressor discharge temperature (T5) is more than 115
o
C for 10 seconds, the compressor
ceases operation and does not restart until T5 is less than 90
o
C
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• Discharge temperature sensor
• Refrigerant
Troubleshooting and repair:
Temperature protection of compressor
discharge
Temperature protection of compressor
discharge
Check whether the
compressor discharge temp.
is more than 115°C ?
Check whether the
compressor discharge temp.
is more than 115°C
?
Check whether the
connection is right between
compressor discharge temp
.
sensor and PCB according to
wiring diagrams?
Check whether the
connection is right between
compressor discharge temp.
sensor and PCB according to
wiring diagrams?
Measure the resistance value
of compressor discharge
temp. sensor. If the value is
not normal is normal refer to
the Appendix?
Measure the resistance value
of compressor discharge
temp. sensor. If the value is
not normal is normal refer to
the Appendix?
No
Yes
Yes
No
Correct the wiring connection
Correct the wiring connection
Stop leaking and add refrigerant
Stop leaking and add refrigerant
Replace the compressor discharge temp. sensor
Replace the compressor discharge temp. sensor
No
Yes
Replace high pressure valve assy
Replace high pressure valve assy
Yes
No
Replace outdoor main PCB
Replace outdoor main PCB
No
Check whether the
refrigerant is leak
Check whether the
refrigerant is leak
background
Troubleshooting 30
5.11 PC 0A(High temperature protection of condenser diagnosis and solution)
Description: The unit will stop when condenser temperature is higher than 65°C, and runs again when it is less than
52°C
Recommended parts to prepare:
• Connection wires
• Condenser temperature sensor
• Outdoor fan
• Outdoor main PCB
• Refrigerant
Troubleshooting and repair:
background
Troubleshooting 31
High temperature protection of
condenser
High temperature protection of
condenser
Check whether the
condenser temperature is
Higher than 65°C
Check whether the
condenser temperature is
Higher than 65°C
Yes
Check whether the
resistance of condenser
temp. sensor is normal refer
to the Appendix
Check whether the
resistance of condenser
temp. sensor is normal refer
to the Appendix
Replace the temperature sensor
Replace the temperature sensor
No
No
Check whether the outdoor
ambient temperature is
higher than 50℃
Check whether the outdoor
ambient temperature is
higher than 50℃
No
Stop the unit
Stop the unit Yes
Check if the outdoor unit
ventilation is good
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Make the outdoor unit ventilate well
Check whether the heat
exchanger is dirty
Check whether the heat
exchanger is dirty
No
Clean the heat exchanger
Clean the heat exchangerYes
Check whether the refrigerant
system is ok
Check whether the refrigerant
system is ok
Replace outdoor main board
Replace outdoor main board
No
Refrigerant is not enough add the
refrigerant
Refrigerant is not enough add the
refrigerant
No
Check if the outdoor fan
runs properly
Check if the outdoor fan
runs properly
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
No
Yes
No
Correct the connection
Correct the connectionNo
Yes
Check the connection
between temperature
sensor and PCB.
Check the connection
between temperature
sensor and PCB.
Yes
background
Troubleshooting 32
5.12 PC 02/LC 06 (Compressor top(or IPM) temp. protection diagnosis and solution)
Description: For some models with overload protector, If the sampling voltage is not 5V, the LED will display the failure.
If the temperature of IPM module is higher than a certain value, the LED displays the failure code.
Models without overload protector should be diagnosed according to the second flowchart.
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• IPM module board
• High pressure protector
• System blockages
Troubleshooting and repair:
Check if the air flow system
of indoor and outdoor units
are obstructed?
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Turn off the power supply and turn
it on 10 minutes later.
Check if the temperature of
compressor Top
Is more than 90℃?
No
Check if the refrigerant
system
is normal?
Repair the refrigerant
system .
Replace the outdoor control PCB.
Yes
Check if all the connection, especially
the connection of OLP (Over Load
Protector) sensor is good.
Correct the connection.No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.No
Replace the outdoor control PCB.Yes
No
background
Troubleshooting 33
Check the fastening screws on the
PCB and IPM radiator.
Are they
fixed tightly?
Replace the outdoor
control PCB.
Tighten the screws and apply
silicon grease.
NO
YES
background
Troubleshooting 34
5.13 PC 30 (System high pressure protection diagnosis and solution)
Description: Outdoor pressure switch cut off the system because high pressure is higher than 4.4 MPa
Recommended parts to prepare:
• Connection wires
• Pressure switch
• Outdoor fan
• Outdoor main PCB
Troubleshooting and repair:
background
Troubleshooting 35
Are the high pressure switch
and main control boar wired
correctly?
Are the high pressure switch
and main control boar wired
correctly?
Method: Disconnect the plug.
Measure the resistance of the
high pressure protector, if the
protector is normal the value is
o, Does a problem still exist?
Method: Disconnect the plug.
Measure the resistance of the
high pressure protector, if the
protector is normal the value is
o, Does a problem still exist?
Yes
Yes
No
No
Is the high pressure
protector broken?
Is the high pressure
protector broken?
Is the outdoor ambient
temperature is higher than
50℃?
Is the outdoor ambient
temperature is higher than
50℃?
No
Yes
Check if the outdoor unit
ventilation is good
Check if the outdoor unit
ventilation is good
Yes
Is the heat exchanger dirty?
Is the heat exchanger dirty?
No
Yes
Replace outdoor main board. Is
the problem resolved?
Replace outdoor main board. Is
the problem resolved?
No
High pressure protection
High pressure protection
Is the outdoor fan running
properly?
Is the outdoor fan running
properly?
No
Yes
NO
Connect high pressure switch and
mian control board
Connect high pressure switch and
mian control board
Replace high pressure protector
Replace high pressure protector
Stop the unit
Stop the unit
Ensure that the outdoor unit
ventilation is functioning properly
Ensure that the outdoor unit
ventilation is functioning properly
Please refer to the solution of the “Fan
Speed is operating outside of normal
range”malfunction.
Please refer to the solution of the “Fan
Speed is operating outside of normal
range”malfunction.
Clean the heat exchanger
Clean the heat exchanger
Check whether the refrigerant
system is functioning properly
Check whether the refrigerant
system is functioning properly
background
Troubleshooting 36
5.14 PC 31 (System low pressure protection diagnosis and solution)
Description: Outdoor pressure switch cut off the system because low pressure is lower than 0.13 MPa, the LED displays
the failure code.
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• Low pressure protector
• Refrigerant
Troubleshooting and repair:
background
Troubleshooting 37
Low pressure protection
Low pressure protection
Are the low pressure protector
and main control board wired
properly?
Are the low pressure protector
and main control board wired
properly?
Method: Disconnect the plug.
Measure the resistance of the
low pressure protector. If the
protector is normal the value is
o. Does a problem still exist?
Method: Disconnect the plug.
Measure the resistance of the
low pressure protector. If the
protector is normal the value is
o. Does a problem still exist?
Yes
Yes
Replace outdoor main board. Does a
problem still exist?
Replace outdoor main board. Does a
problem still exist?
No
No
Is the low pressure
protector broken?
Is the low pressure
protector broken?
Is the outdoor ambient
temperature too low?
Is the outdoor ambient
temperature too low?
No
Yes
No
Is the valve core of the high
pressure valve fully opened?
Is the valve core of the high
pressure valve fully opened?
Is the indoor fan running
properly in cooling mode?
Is the indoor fan running
properly in cooling mode?
No
Yes
Yes
No
Check whether the refrigerant
system is functioning properly.
Check whether the refrigerant
system is functioning properly.
When the lvel of refrigerant is not
sufficient, doe the system function
properly after more refrigerant is added?
When the lvel of refrigerant is not
sufficient, doe the system function
properly after more refrigerant is added?
No
Reconnect the low pressure protector and main
control board
Reconnect the low pressure protector and main
control board
Replace low pressure protector
Replace low pressure protector
Open the valve core of the high
pressure valve
Open the valve core of the high
pressure valve
Stop the unit
Stop the unit
Please refer to the solution of the “Fan
Speed is operating outside of normal
range”malfunction.
Please refer to the solution of the “Fan
Speed is operating outside of normal
range”malfunction.
background
Troubleshooting 38
5.15 EC 72 (Lack phase failure of outdoor DC fan motor diagnosis and solution)
Description: When the three-phase sampling current of the DC motor is abnormal, especially when the current of one
or more phases is always small and almost 0, the LED displays the failure code.
Recommended parts to prepare:
• Connection wire
• Fan motor
• Outdoor PCB
Troubleshooting and repair:
Check the fan three-phase
output for obvious open circuit
Power off,then restart the unit
2 minutes later.Is it still
displaying the error code
The unit operates
normally
Check the wiring of fan
motor.Are all the connections
good?
Correct the connections
Check whether the three-
phase resistance of the fan is
symmetrical
Replace the fan motor
Yes
Yes
Yes
No
No
No
Replace the main PCB
No
Trobule is solved
Yes
background
Troubleshooting 39
5.16 PC 43 (ODU compressor lack phase protection diagnosis and solution)
Description: When the three-phase sampling current of the compressor is abnormal, especially when the current of one
or more phases is always small and almost 0, the LED displays the failure code
Recommended parts to prepare:
• Connection wire
• Compressor
• Outdoor PCB
Troubleshooting and repair:
Check the compressor three-
phase output for obvious open
circuit
Power off,then restart the unit
2 minutes later.Is it still
displaying the error code
The unit operates
normally
Check both ends of
compressor connecting
line .Are all the connections
good?
Correct the connections
Check whether the three-
phase resistance of the
compressor is symmetrical
Replace the compressor
Yes
Yes
Yes
No
No
No
Replace the main PCB
No
Trobule is solved
Yes
background
Troubleshooting 40
5.17 PC 45 (ODU IR chip drive failure diagnosis and solution)
Description: When the IR chip detects its own parameter error, the LED displays the failure code when power on.
Recommended parts to prepare:
• Inverter module PCB.
Troubleshooting and repair:
Power off,then restart the unit
2 minutes later.
Replace the inverter module
PCB.
Yes
5.18 CE (Automatic correction of wiring/piping error)
Press the “check switch” on the outdoor unit PCB board 5 seconds until LED display “CE”, which mean this function
is working, Approximately 5-10 minutes after the switch is pressed, the “CE” disappear the wiring/piping error will be
corrected, and wiring/piping is properly connected.
background
Troubleshooting 41
5.19 EH C1(Refrigerant sensor detects leakage diagnosis and solution)
Description:
The refrigerant sensor detects a concentration higher than or equal to 10%*LFL for 10 seconds or the refrigerant sensor
detects a concentration higher than or equal to 20%*LFL or the multi model receives the refrigerant leakage protection
fault sent by the outdoor unit.
Recommended parts to prepare:
• Additional refrigerant
Troubleshooting and repair:
Power off, then restart the unit 2 minutes later.
Are any leakages
present?
Check System for blockages and
clear blockages if present.
Does a problem remain?
YES
Check system for leakages.
NO
Repair the leakage and recharge
the refrigerant.
YES
NO
Exit Conditions:
One of the following conditions is met:
1. All connected indoor units have no refrigerant leakage protection signal for more than 2.5 hours;
2. All connected indoor units have no refrigerant leakage protection signal, and receive the signal to clear refrigerant
leakage protection (press and hold SW1 on the auxiliary PCB for 10 seconds).
3. The data of EEPROM is protected by refrigerant leakage when the data is read on power-on, and the recovery time of
the refrigerant leakage protection is more than 2.5 hours.
background
Troubleshooting 42
5.20 EC 55(ODU IPM module temperature sensor malfunction diagnosis and solution)
Description: If the sampling voltage is 0V or 5V, the LED displays the failure code.
Recommended parts to prepare:
• IPM module PCB
• Connection wires
• Sensors
• Outdoor main PCB
Troubleshooting and repair:
If the radiator has no sensor, follow the steps below to resolve,
Power off, then restart the unit after 2 minutes.
Does a problem remain? The unit is operating normallyNO
YES
Check whether the
fastening screws on the
PCB and IPM radiator are
fixed tightly
Tighten the screws and apply
silicon grease
NO
YES
Replace the IPM module PCB
If the radiator has a sensor(TH), follow the steps below to resolve,
Check the connection between
temperature sensor and PCB.
Replace the outdoor main PCB
Is it within acceptable
parameters?
Is it properly wired
?
Ensure proper connections.NO
Measure the resistance value
of the sensor.
YES
Replace the sensor.
NO
YES
background
Troubleshooting 43
5.21 EC 5C(Pressure sensor failure diagnosis and solution)
Description: If the sampling voltage is lower than 2V or higher than 254V
Recommended parts to prepare:
• Connection wires
• Sensor
• Outdoor PCB
Troubleshooting and repair:
Check the connection between
temperature sensor and PCB.
Replace outdoor PCB
Is it lower than 0.5V?
Is it properly wired? Ensure proper connections.NO
Measure the voltage
between pin1 and pin2.
YES
Replace the sensor.Yes
No
background
Troubleshooting 44
5.22 PC 13(The AC power is cut off or the AC voltage detection circuit fails diagnosis and
solution)
Description: The machine equipped with a safety shut-off valve has detected a power outage from the mains.
Recommended parts to prepare:
• Outdoor PCB
Troubleshooting and repair:
Check whether the power
voltage is normal.
Measure whether outdoor
terminal voltage is normal?
Restart the unit when the power
supply gets normal
No
Yes
No
Reconnect it well
Yes
Measure whether the voltage
between L and N is normal?
Yes
No
Replace outdoor PCB
Check the wiring of
power wires well or
correctly
Reconnect it well
Check the wiring of
L and N well or
correctly
Does a problem remain?
Yes
background
Troubleshooting 45
5.23 PC A1(Condensation protection of refrigerant pipe diagnosis and solution)
Description: If outdoor ambient temperature is higher than a certain set value of the refrigerant pipe temperature for a
period of time, the LED displays the failure code.
Recommended parts to prepare:
• T4 sensor
• T5 sensor
• Main EXV
• Outdoor PCB
Troubleshooting and repair:
Check whether there is a large
deviation between the T4 temperature
detected by point check function and
the actual temperature at the T4 sensor
position (measured with a
thermometer).
Check whether there is a large
deviation between the T5 temperature
detected by point check function and
the actual temperature at the T5 sensor
position (measured with a
thermometer).
Yes
No
Yes
No
Check whether there is a large
deviation between the inlet and outlet
of the main EXV.
No
Yes
Replace outdoor PCB
Check
the connection
between T5 sensor and
PCB
.
Replace the main electronic
expansion valve(MVI)
Does a problem remain?
Yes
Direct sunlight or
check
the connection
between T4 sensor and
PCB
Yes
Yes
Is it within acceptable
parameters?
Is it properly wired? Ensure proper connections.
NO
Measure the resistance value
of the sensor.
YES
Replace the sensor.NO
YES
background
Troubleshooting
6. Check Procedures
6.1 Temperature Sensor Check
WARNING
Be sure to turn off all power supplies or disconnect all wires to avoid electric shock.
Operate after compressor and coil have returned to normal temperature in case of injury.
1. Disconnect the temperature sensor from PCB (Refer to Chapter 5&6. Indoor&Outdoor Unit Disassembly).
2. Measure the resistance value of the sensor using a multi-meter.
3. Check corresponding temperature sensor resistance value table (Refer to Chapter Appendix).
Note: The picture and the value are only for reference, actual condition and specific value may vary.
6.2 Compressor Check
1. Disconnect the compressor power cord from outdoor PCB (Refer to Chapter 6. Outdoor Unit Disassembly)).
2. Measure the resistance value of each winding using a multi-meter.
3. Check the resistance value of each winding in the following table.
background
Troubleshooting
Resistance Value
KSK103D33UEZ3 KSN140D58UFZ KTF250D22UMT KTN110D42UFZ KTF420D62UNT
Blue-Red
2.13Ω 1.86Ω 0.75Ω 1.82Ω 0.86ΩBlue-Black
Red-Black
Resistance Value
KTN150D30UFZA KTM240D46UKT2 KTF310D43UMT
ETPQ420D1UMUA
ETPQ440D1UMUB
KTQ420D1UMU
EKPQ440D1UMUB
MTH356UKRC8FQL
Blue-Red
1.02Ω 1.04Ω 0.65Ω 0.37Ω 0.487ΩBlue-Black
Red-Black
Resistance Value
MTH550UKPC8FU
Blue-Red
0.295ΩBlue-Black
Red-Black
Note: The picture and the value are only for reference, actual condition and specific value may vary.
background
Troubleshooting
6.3 IPM Continuity Check
WARNING
Electricity remains in capacitors even when the power supply is off.
Ensure the capacitors are fully discharged before troubleshooting.
1. Turn off outdoor unit and disconnect power supply.
2. Discharge electrolytic capacitors and ensure all energy-storage unit has been discharged.
3. Disassemble outdoor PCB or disassemble IPM board.
4. Measure the resistance value between P and U(V, W, N); U(V, W) and N.
Digital tester Resistance value Digital tester Resistance value
(+)Red (-)Black
∞
(Several MΩ)
(+)Red (-)Black
∞
(Several MΩ)
P
N U
N
U V
V W
W -
Or test the conductivity of IPM with diode mode.
Needle-type Tester
Normal Value
Needle-type Tester
Normal Value
Red Black Red Black
P
U
Open-circuit N
U
0.3-0.5V
V V
W W
Needle-type Tester
Normal Value
Needle-type Tester
Normal Value
Black Red Black Red
P
U
0.3-0.5V N
U
Open-circuit
V V
W W
background
Troubleshooting
Note: The picture and the value are only for reference, actual condition and specific value may vary.
6.4 Normal voltage of P and N
208-230V(1-phase)
In standby
around 310VDC
In operation
With passive PFC module With partial active PFC
module
With fully active PFC
module
>200VDC >310VDC >370VDC
6.5 Reactor Check
Measure the resistance and voltage (to ground) of the reactor. The normal resistance should be around 0.1 ohm. Otherwise,
the reactor must have malfunction.
background
Troubleshooting
6.6 4-way valve Check
1.Power on, use a digital tester to measure the voltage, when the unit operates in cooling, it is 0V. When the unit
operates in heating, it is about equal to power supply voltage.
If the value of the voltage is not in the range, the PCB must have problems and need to be replaced.
2 Turn off the power, use a digital tester to measure the resistance. The value should be 1.8~2.5 KΩ.
6.7 EXV Check
1. Turn off outdoor unit and disconnect power supply.
2. Disconnect the connectors of EXV.
3. Measure the resistance value between Red and Blue(Yellow); Brown and Orange(White).
Resistance to EXV coil
Color of lead wire Normal Value
Red- Blue
About 50Ω
Red - Yellow
Brown-Orange
Brown-White
background
Troubleshooting
background
Contents
i) Temperature Sensor Resistance Value Table for TP (°C --K) ................................2
ii) Other Temperature Sensors Resistance Value Table (°C – K) ..............................3
iii) System Pressure Table ...........................................................................................4
Appendix
background
Appendix 2
i) Temperature Sensor Resistance Value Table for TP (°C --K)
°C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm
°C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm
-20 -4 542.7 20 68 68.66 60 140 13.59 100 212 3.702
-19 -2 511.9 21 70 65.62 61 142 13.11 101 214 3.595
-18 0 483 22 72 62.73 62 144 12.65 102 216 3.492
-17 1 455.9 23 73 59.98 63 145 12.21 103 217 3.392
-16 3 430.5 24 75 57.37 64 147 11.79 104 219 3.296
-15 5 406.7 25 77 54.89 65 149 11.38 105 221 3.203
-14 7 384.3 26 79 52.53 66 151 10.99 106 223 3.113
-13 9 363.3 27 81 50.28 67 153 10.61 107 225 3.025
-12 10 343.6 28 82 48.14 68 154 10.25 108 226 2.941
-11 12 325.1 29 84 46.11 69 156 9.902 109 228 2.86
-10 14 307.7 30 86 44.17 70 158 9.569 110 230 2.781
-9 16 291.3 31 88 42.33 71 160 9.248 111 232 2.704
-8 18 275.9 32 90 40.57 72 162 8.94 112 234 2.63
-7 19 261.4 33 91 38.89 73 163 8.643 113 235 2.559
-6 21 247.8 34 93 37.3 74 165 8.358 114 237 2.489
-5 23 234.9 35 95 35.78 75 167 8.084 115 239 2.422
-4 25 222.8 36 97 34.32 76 169 7.82 116 241 2.357
-3 27 211.4 37 99 32.94 77 171 7.566 117 243 2.294
-2 28 200.7 38 100 31.62 78 172 7.321 118 244 2.233
-1 30 190.5 39 102 30.36 79 174 7.086 119 246 2.174
0 32 180.9 40 104 29.15 80 176 6.859 120 248 2.117
1 34 171.9 41 106 28 81 178 6.641 121 250 2.061
2 36 163.3 42 108 26.9 82 180 6.43 122 252 2.007
3 37 155.2 43 109 25.86 83 181 6.228 123 253 1.955
4 39 147.6 44 111 24.85 84 183 6.033 124 255 1.905
5 41 140.4 45 113 23.89 85 185 5.844 125 257 1.856
6 43 133.5 46 115 22.89 86 187 5.663 126 259 1.808
7 45 127.1 47 117 22.1 87 189 5.488 127 261 1.762
8 46 121 48 118 21.26 88 190 5.32 128 262 1.717
9 48 115.2 49 120 20.46 89 192 5.157 129 264 1.674
10 50 109.8 50 122 19.69 90 194 5 130 266 1.632
11 52 104.6 51 124 18.96 91 196 4.849      
12 54 99.69 52 126 18.26 92 198 4.703      
13 55 95.05 53 127 17.58 93 199 4.562      
14 57 90.66 54 129 16.94 94 201 4.426      
15 59 86.49 55 131 16.32 95 203 4.294      
16 61 82.54 56 133 15.73 96 205 4.167      
17 63 78.79 57 135 15.16 97 207 4.045      
18 64 75.24 58 136 14.62 98 208 3.927      
19 66 71.86 59 138 14.09 99 210 3.812      
background
Appendix 3
ii) Other Temperature Sensors Resistance Value Table (°C – K)
°C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm
-20 -4 115.266 20 68 12.6431 60 140 2.35774 100 212 0.62973
-19 -2 108.146 21 70 12.0561 61 142 2.27249 101 214 0.61148
-18 0 101.517 22 72 11.5 62 144 2.19073 102 216 0.59386
-17 1 96.3423 23 73 10.9731 63 145 2.11241 103 217 0.57683
-16 3 89.5865 24 75 10.4736 64 147 2.03732 104 219 0.56038
-15 5 84.219 25 77 10 65 149 1.96532 105 221 0.54448
-14 7 79.311 26 79 9.55074 66 151 1.89627 106 223 0.52912
-13 9 74.536 27 81 9.12445 67 153 1.83003 107 225 0.51426
-12 10 70.1698 28 82 8.71983 68 154 1.76647 108 226 0.49989
-11 12 66.0898 29 84 8.33566 69 156 1.70547 109 228 0.486
-10 14 62.2756 30 86 7.97078 70 158 1.64691 110 230 0.47256
-9 16 58.7079 31 88 7.62411 71 160 1.59068 111 232 0.45957
-8 18 56.3694 32 90 7.29464 72 162 1.53668 112 234 0.44699
-7 19 52.2438 33 91 6.98142 73 163 1.48481 113 235 0.43482
-6 21 49.3161 34 93 6.68355 74 165 1.43498 114 237 0.42304
-5 23 46.5725 35 95 6.40021 75 167 1.38703 115 239 0.41164
-4 25 44 36 97 6.13059 76 169 1.34105 116 241 0.4006
-3 27 41.5878 37 99 5.87359 77 171 1.29078 117 243 0.38991
-2 28 39.8239 38 100 5.62961 78 172 1.25423 118 244 0.37956
-1 30 37.1988 39 102 5.39689 79 174 1.2133 119 246 0.36954
0 32 35.2024 40 104 5.17519 80 176 1.17393 120 248 0.35982
1 34 33.3269 41 106 4.96392 81 178 1.13604 121 250 0.35042
2 36 31.5635 42 108 4.76253 82 180 1.09958 122 252 0.3413
3 37 29.9058 43 109 4.5705 83 181 1.06448 123 253 0.33246
4 39 28.3459 44 111 4.38736 84 183 1.03069 124 255 0.3239
5 41 26.8778 45 113 4.21263 85 185 0.99815 125 257 0.31559
6 43 25.4954 46 115 4.04589 86 187 0.96681 126 259 0.30754
7 45 24.1932 47 117 3.88673 87 189 0.93662 127 261 0.29974
8 46 22.5662 48 118 3.73476 88 190 0.90753 128 262 0.29216
9 48 21.8094 49 120 3.58962 89 192 0.8795 129 264 0.28482
10 50 20.7184 50 122 3.45097 90 194 0.85248 130 266 0.2777
11 52 19.6891 51 124 3.31847 91 196 0.82643 131 268 0.27078
12 54 18.7177 52 126 3.19183 92 198 0.80132 132 270 0.26408
13 55 17.8005 53 127 3.07075 93 199 0.77709 133 271 0.25757
14 57 16.9341 54 129 2.95896 94 201 0.75373 134 273 0.25125
15 59 16.1156 55 131 2.84421 95 203 0.73119 135 275 0.24512
16 61 15.3418 56 133 2.73823 96 205 0.70944 136 277 0.23916
17 63 14.6181 57 135 2.63682 97 207 0.68844 137 279 0.23338
18 64 13.918 58 136 2.53973 98 208 0.66818 138 280 0.22776
19 66 13.2631 59 138 2.44677 99 210 0.64862 139 282 0.22231
background
Appendix 4
iii) System Pressure Table-R454B
Pressure Temperature Pressure Temperature
Kpa bar PSI °C °F Kpa bar PSI °C °F
58.196 0.58 8.44 -60 -76 935.23 9.35 135.64 8 46.4
61.517 0.62 8.92 -59 -74.2 963.75 9.64 139.78 9 48.2
64.988 0.65 9.43 -58 -72.4 992.93 9.93 144.01 10 50
68.615 0.69 9.95 -57 -70.6 1022.8 10.23 148.34 11 51.8
72.402 0.72 10.50 -56 -68.8 1053.3 10.53 152.76 12 53.6
76.354 0.76 11.07 -55 -67 1084.5 10.85 157.29 13 55.4
80.478 0.80 11.67 -54 -65.2 1116.4 11.16 161.91 14 57.2
84.776 0.85 12.30 -53 -63.4 1149 11.49 166.64 15 59
89.256 0.89 12.95 -52 -61.6 1182.3 11.82 171.47 16 60.8
93.923 0.94 13.62 -51 -59.8 1216.3 12.16 176.40 17 62.6
98.781 0.99 14.33 -50 -58 1251.1 12.51 181.45 18 64.4
103.84 1.04 15.06 -49 -56.2 1286.6 12.87 186.60 19 66.2
109.1 1.09 15.82 -48 -54.4 1322.8 13.23 191.85 20 68
114.56 1.15 16.61 -47 -52.6 1359.9 13.60 197.23 21 69.8
120.25 1.20 17.44 -46 -50.8 1397.7 13.98 202.71 22 71.6
126.15 1.26 18.30 -45 -49 1436.3 14.36 208.31 23 73.4
132.28 1.32 19.18 -44 -47.2 1475.7 14.76 214.02 24 75.2
138.64 1.39 20.11 -43 -45.4 1515.9 15.16 219.85 25 77
145.24 1.45 21.06 -42 -43.6 1557 15.57 225.82 26 78.8
152.09 1.52 22.06 -41 -41.8 1598.9 15.99 231.89 27 80.6
159.18 1.59 23.09 -40 -40 1641.6 16.42 238.09 28 82.4
166.54 1.67 24.15 -39 -38.2 1685.2 16.85 244.41 29 84.2
174.15 1.74 25.26 -38 -36.4 1729.7 17.30 250.86 30 86
182.04 1.82 26.40 -37 -34.6 1775 17.75 257.43 31 87.8
190.2 1.90 27.59 -36 -32.8 1821.3 18.21 264.15 32 89.6
198.65 1.99 28.81 -35 -31 1868.4 18.68 270.98 33 91.4
207.39 2.07 30.08 -34 -29.2 1916.5 19.17 277.95 34 93.2
216.42 2.16 31.39 -33 -27.4 1965.6 19.66 285.08 35 95
225.76 2.26 32.74 -32 -25.6 2015.5 20.16 292.31 36 96.8
235.41 2.35 34.14 -31 -23.8 2066.5 20.67 299.71 37 98.6
245.37 2.45 35.59 -30 -22 2118.4 21.18 307.24 38 100.4
255.67 2.56 37.08 -29 -20.2 2171.3 21.71 314.91 39 102.2
266.29 2.66 38.62 -28 -18.4 2225.2 22.25 322.73 40 104
277.25 2.77 40.21 -27 -16.6 2280.2 22.80 330.70 41 105.8
288.56 2.89 41.85 -26 -14.8 2336.1 23.36 338.81 42 107.6
300.22 3.00 43.54 -25 -13 2393.2 23.93 347.09 43 109.4
312.24 3.12 45.28 -24 -11.2 2451.3 24.51 355.52 44 111.2
324.63 3.25 47.08 -23 -9.4 2510.4 25.10 364.09 45 113
337.39 3.37 48.93 -22 -7.6 2570.7 25.71 372.84 46 114.8
350.54 3.51 50.84 -21 -5.8 2632.1 26.32 381.74 47 116.6
364.08 3.64 52.80 -20 -4 2694.7 26.95 390.82 48 118.4
378.02 3.78 54.83 -19 -2.2 2758.3 27.58 400.04 49 120.2
392.37 3.92 56.91 -18 -0.4 2823.2 28.23 409.46 50 122
407.13 4.07 59.05 -17 1.4 2889.3 28.89 419.04 51 123.8
background
Appendix 5
422.31 4.22 61.25 -16 3.2 2956.5 29.57 428.79 52 125.6
437.92 4.38 63.51 -15 5 3025 30.25 438.72 53 127.4
453.98 4.54 65.84 -14 6.8 3094.7 30.95 448.83 54 129.2
470.47 4.70 68.23 -13 8.6 3165.7 31.66 459.13 55 131
487.43 4.87 70.69 -12 10.4 3238.1 32.38 469.63 56 132.8
504.84 5.05 73.22 -11 12.2 3311.7 33.12 480.30 57 134.6
522.73 5.23 75.81 -10 14 3386.7 33.87 491.18 58 136.4
541.1 5.41 78.48 -9 15.8 3463 34.63 502.25 59 138.2
559.95 5.60 81.21 -8 17.6 3540.7 35.41 513.52 60 140
579.31 5.79 84.02 -7 19.4 3619.9 36.20 525.00 61 141.8
599.16 5.99 86.90 -6 21.2 3700.5 37.01 536.69 62 143.6
619.54 6.20 89.85 -5 23 3782.7 37.83 548.61 63 145.4
640.43 6.40 92.88 -4 24.8 3866.3 38.66 560.74 64 147.2
661.86 6.62 95.99 -3 26.6 3951.5 39.52 573.10 65 149
683.82 6.84 99.18 -2 28.4 4038.3 40.38 585.69 66 150.8
706.34 7.06 102.44 -1 30.2 4126.8 41.27 598.52 67 152.6
729.41 7.29 105.79 0 32 4217 42.17 611.60 68 154.4
753.06 7.53 109.22 1 33.8 4309 43.09 624.95 69 156.2
777.28 7.77 112.73 2 35.6 4402.9 44.03 638.56 70 158
802.08 8.02 116.33 3 37.4 4498.7 44.99 652.46 71 159.8
827.48 8.27 120.01 4 39.2 4596.5 45.97 666.64 72 161.6
853.49 8.53 123.78 5 41 4696.5 46.97 681.15 73 163.4
880.11 8.80 127.64 6 42.8 4798.9 47.99 696.00 74 165.2
907.35 9.07 131.60 7 44.6 4904.1 49.04 711.25 75 167

Specifications