Goodman GPCH36031 GPCH3 Packaged Air Conditioner 5 Ton 13.4 SEER2 Two-Stage

Product's Documents

Below are documents related to this product, you can read online or download:
User Manual Installation Instruction
GPCH36031 photo

User Manual

This is the main product document for model GPCH36031. Additionally, the document applies to other Goodman models: GPCH36031, 24K, 30K, 36K, 42K, 48K

The file format is pdf, 55 pages, you can download this manual here .

background
Service and Troubleshooting
*PCH3 13.4 SEER(2) Cooling,*PHH3 / *PHH5 15.2 SEER(2) Heat Pump
Horizontal Package Unit with R-32
© 2025 Daikin Comfort Technologies Manufacturing, Inc.
RS6300016
April 2025
Brand
®
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
TABLE OF CONTENTS
IMPORTANT INFORMATION ......................................... 2
PRODUCT IDENTIFICATION ......................................... 4
SYSTEM OPERATION .................................................... 6
SCHEDULED MAINTENANCE ..................................... 11
SERVICING .................................................................... 13
CHECKING VOLTAGE ............................................ 13
CHECKING WIRING................................................. 13
CHECKING THERMOSTAT AND WIRING ............ 13
CHECKING TRANSFORMER AND
CONTROL CIRCUIT ................................................. 14
CHECKING CONTACTOR AND/OR RELAYS ........ 15
CHECKING CONTACTOR CONTACTS.................. 15
CHECKING LOW PRESSURE CONTROL ............ 15
CHECKING HIGH PRESSURE CONTROL ............ 15
CHECKING CAPACITOR ......................................... 16
RESISTANCE CHECK ............................................. 17
CAPACITANCE CHECK (MFD) ............................... 18
CHECKING FAN AND BLOWER MOTOR
WINDINGS (PSC MOTORS) .................................... 18
CHECKING ECM MOTORS ..................................... 19
CHECKING ECM MOTOR WINDINGS ................... 20
CHECKING COMPRESSOR ................................... 20
RESISTANCE TEST ................................................. 20
GROUND TEST ........................................................ 21
UNLOADER TEST PROCEDURE .......................... 21
(2 STAGE COMPRESSORS ONLY) ........................ 21
OPERATION TEST ................................................... 22
LOCKED ROTOR TEST .......................................... 22
TESTING CRANKCASE HEATER
(OPTIONAL ITEM) .................................................... 22
CHECKING CRANKCASE HEATER
THERMOSTAT .......................................................... 23
TESTING DEFROST CONTROL ............................. 23
TESTING DEFROST THERMOSTAT ...................... 24
Pride and workmanship go into every product to provide
our customers with quality products. It is possible, however,
that during its lifetime a product may require service.
Products should be serviced only by a qualied service
technician who is familiar with the safety procedures
required in the repair and who is equipped with the proper
tools, parts, testing instruments and the appropriate service
manual. REVIEW ALL SERVICE INFORMATION IN THE
APPROPRIATE SERVICE MANUAL BEFORE
BEGINNING REPAIRS.
WARNING
Do not bypass safety devices.
Only personnel that have been trained to install, adjust,
service, maintenance or repair (hereinafter, “service”)
the equipment specified in this manual should service the
equipment.
This equipment is not intended for use by persons
(including children) with reduced physical, sensory or
mental capacities, or lack of experience and knowledge,
unless they have been given supervision or instruction
concerning use of the appliance by a person responsible
for their safety.
Children should be supervised to ensure that they do not
play with the equipment.
The manufacturer will not be responsible for any injury
or property damage arising from improper supervision,
service or service procedures. If you service this unit, you
assume responsibility for any injury or property damage
which may result. In addition, in jurisdictions that require
one or more licenses to service the equipment specified in
this manual, only licensed personnel should service the
equipment. Improper supervision, installation, adjustment,
servicing, maintenance or repair of the equipment specified
in this manual, or attempting to install, adjust, service
or repair the equipment specified in this manual without
proper supervision or training may result in product
damage, property damage, personal injury or death.
WARNING
NOTE: *PCH3, *PHH3, & *PHH5 models apply to both
Amana® Brand and Goodman products only.
background
IMPORTANT INFORMATION
2
OUTSIDE THE U.S., call 1-713-861-2500.
(Not a technical assistance line for dealers.) Your telephone company will bill you for the call.
SAFE REFRIGERANT HANDLING
While these items will not cover every conceivable
situation, they should serve as a useful guide.
WARNING
• Refrigerants are heavier than air. They can “push out”
the oxygen in your lungs or in any enclosed space. To
avoid possible difficulty in breathing or death:
• Never purge refrigerant into an enclosed room or
space. By law, all refrigerant must be reclaimed.
• If an indoor leak is suspected, thoroughly ventilate the
area before beginning work.
• Liquid refrigerant can be very cold. To avoid possible
frostbite or blindness, avoid contact with refrigerant
and wear gloves and goggles. If liquid refrigerant does
contact your skin or eyes, seek medical help immediately.
• Always follow EPA regulations. Never burn refrigerant,
as poisonous gas will be produced.
WARNING
To avoid possible injury, explosion or death, practice safe
handling of refrigerants.
WARNING
The compressor POE oil for R-32 units is extremely
susceptible to moisture absorption and could cause
compressor failure. Do not leave system open to atmosphere
any longer than necessary for installation.
WARNING
To avoid possible explosion:
• Never apply flame or steam to a refrigerant cylinder. If
you must heat a cylinder for faster charging, partially
immerse it in warm water.
• Never fill a cylinder more than 80% full of liquid
refrigerant.
• Never add anything other than R-22 to an R-22 cylinder
or R-32 to an R-32 cylinder. The service equipment used
must be listed or certified for the type of refrigerant
used.
• Store cylinders in a cool, dry place. Never use a
cylinder as a platform or a roller.
WARNING
To avoid possible explosion, use only returnable (not
disposable) service cylinders when removing refrigerant
from a system.
• Ensure the cylinder is free of damage which could lead
to a leak or explosion.
• Ensure the hydrostatic test date does not exceed 5
years.
• Ensure the pressure rating meets or exceeds 400 lbs.
When in doubt, do not use cylinder.
CHECKING HEATER ELEMENTS .......................... 24
REFRIGERATION REPAIR PRACTICE .................. 24
CHARGING ............................................................... 27
CHECKING COMPRESSOR EFFICIENCY ............ 27
THERMOSTATIC EXPANSION VALVE ................... 27
OVERFEEDING ........................................................ 28
UNDERFEEDING ..................................................... 28
CHECKING EXPANSION VALVE OPERATION ..... 28
FIXED ORIFICE RESTRICTION DEVICES ........... 29
CHECKING RESTRICTED LIQUID LINE ............... 30
REFRIGERANT OVERCHARGE ............................ 30
NON-CONDENSABLES ........................................... 30
COMPRESSOR BURNOUT ..................................... 30
REVERSING VALVE REPLACEMENT ................... 34
CHECKING EXTERNAL STATIC PRESSURE ....... 34
ADJUSTING AIRFLOW ........................................... 34
REFRIGERANT DETECTION SYSTEM ................. 37
TROUBLESHOOTING .................................................. 39
WIRING DIAGRAMS ..................................................... 49
IMPORTANT NOTICES
RECOGNIZE SAFETY SYMBOLS, WORDS AND
LABELS
WARNING
To prevent the risk of property damage, personal injury or
death, do not store combustible materials or use gasoline
or other flammable liquids or vapors in the vicinity of this
appliance.
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or
installing this unit. Multiple power sources
may be present. Failure to do so may cause
property damage, personal injury or death.
WARNING
This unit should not be connected to, or used in conjunction
with, any devices that are not listed in the applicable
product specifications as acceptable for use with thus unit
or have not been tested and approved by the manufacturer.
Serious property damage or personal injury, reduced unit
performance and/or hazardous conditions may result from
the use of devices that have not been approved or certified
by the manufacturer.
background
IMPORTANT INFORMATION
3
WARNING
All maintenance staff and others working in the local area
shall be instructed on the nature of work being carried out.
Work in confined spaces shall be avoided.
WARNING
The area shall be checked with an appropriate refrigerant
detector prior to and during work, to ensure the technician
is aware of potentially toxic or flammable atmospheres.
Ensure that the leak detection equipment being used is
suitable for use with all applicable refrigerants.
WARNING
If any hot work is to be conducted on the refrigerating
equipment or any associated parts, appropriate fire
extinguishing equipment shall be available to hand.
WARNING
Ensure that the area is in the open or that it is adequately
ventilated before breaking into the system or conducting
any hot work. A degree of ventilation shall continue during
the period that the work is carried out. The ventilation
should safely disperse any released refrigerant and
preferably expel it externally into the atmosphere.
WARNING
In the inspection and servicing of the unit, any damaged or
faulty sealed electrical component or intrinsically safe
components are to be replaced.
WARNING
Units not to be installed in a room of less than the minimum
stated area below.
Minimum Room
Area
Ft² 164.5
M² 15.3
WARNING
Before completion of any maintenance, ensure that all
cabling and wiring will not be subject to wear, corrosion,
excessive pressure, vibration, sharp edges or any other
adverse environmental effects.
WARNING
Do not use means to accelerate the defrosting process or to
clean, other than those recommended by the manufacturer.
The appliance shall be stored in a room without
continuously operating ignition sources. Do not pierce or
burn. Be aware that refrigerants may not contain odor.
WARNING
Unit not to be installed in an unventilated area.
WARNING
Work shall be undertaken under a controlled procedure
so as to minimize the risk of flammable gas or vapor
being present while work is being performed. No person
carrying out work in relation to the refrigerant containing
components of the system shall use any sources of ignition
in such a manner that may lead to the risk of fire or
explosion.
background
PRODUCT IDENTIFICATION
4
NOMENCLATURE
The model number is used for positive identication of component parts used in manufacturing. Please use this number
when requesting service or parts information.
G P H H 5 36 3 1 A A
1 2 3 4 5 6,7 8 9
10
11
Brand Minor Revision
G Goodman Brand A
Major Revision
Product Category
A
P Packaged Unit
Electrical
1 208/230 V, 1 Phase, 60 Hz
Unit Type
C
Refrigerant
H Heat Pump
3 R-32
Air Flow Nominal Capacity
H Horizontal 24 2 Tons 42 3½ Tons
M
30 2½ tons 48 4 Tons
36 3 Tons 60 5 Tons
3 13.4 SEER2
5 15.2 SEER2
background
PRODUCT IDENTIFICATION
5
MODEL # DESCRIPTION
(A/G)PCH(3/5)(24, 30, 36, 42, 48, 60)
31 AA
Amana® Brand/Goodman® Brand or Distinctions Package Cooling Unit -
13.4 SEER2 or 15.2 SEER2, 208-230/1/60 Single-Phase Unit with R-32.
(A/G)PHH(3/5)(24, 30, 36, 42, 48, 60)
31 AA
Amana® Brand/Goodman® Brand or Distinctions Package Heat Pump Unit
-13.4 SEER2 or 15.2 SEER2, 208-230/1/60 Single-Phase Unit with R-32.
background
SYSTEM OPERATION
6
Refrigerant Detection System (RDS)
The mitigation system is a stationary device that detects
the presence of R-32 refrigerant above 25% LFL using
refrigerant sensors and then initiates mitigation actions.
The mitigation system’s primary function is to reduce the
concentration of leaked R-32 refrigerant to prevent serious
safety hazards. The mitigation actions are accomplished
by halting HVAC operation and continuing indoor blower
operation to provide airow. Once refrigerant concentration
reaches below a safe threshold, the unit will remain in
mitigation mode for ve minutes to evacuate any remaining
R-32 refrigerant within the unit. Upon completion, the unit
will resume its normal operation.
The mitigation system is controlled by a refrigerant
sensor(s), which is secured to a designated location(s) for
active monitoring. If a leak is detected, HVAC operation
is disabled and the indoor blower fan is activated,
providing airow at or above minimum required airow to
evacuate excess concentration. If a Zone Control system
is installed in the ductwork attached to this system, the
Zone controller must be powered through a Daikin Zoning/
Accessory PCB to ensure that the Zoning Dampers open
during mitigation mode to provide ventilation throughout
all ducting. If the unit is installed with a communicating
thermostat, the thermostat will display relevant alerts/
information concerning mitigation mode. Once sensors
read concentration levels below a safe threshold, a ve-
minute timer will initiate.
Once the time is over, the unit will resume back to
its normal operation. If the sensors detect another
concentration excess, the unit will go back into mitigation
mode and will repeat the same process.
Cooling
The refrigerant used in the system is R-32. It is a clear,
colorless, non-toxic and non-irritating liquid. R-410A is
a 50:50 blend of R-32 and R-125. The boiling point at
atmospheric pressure is -62.9°F.
A few of the important principles that make the refrigeration
cycle possible are: heat always ows from a warmer to a
cooler body. Under lower pressure, a refrigerant will absorb
heat and vaporize at a low temperature. The vapors may
be drawn o󰀨 and condensed at a higher pressure and
temperature to be used again.
The indoor evaporator coil functions to cool and dehumidify
the air conditioned spaces through the evaporative process
taking place within the coil tubes.
NOTE: The pressures and temperatures shown in
the refrigerant cycle illustrations on the following
pages are for demonstration purposes only. Actual
temperatures and pressures are to be obtained from
the "Expanded Performance Chart".
Liquid refrigerant at condensing pressure and
temperatures, (270 psig and 122°F), leaves the outdoor
condensing coil through the drier and is metered into the
indoor coil through the metering device. As the cool, low
pressure, saturated refrigerant enters the tubes of the
indoor coil, a portion of the liquid immediately vaporizes.
It continues to soak up heat and vaporizes as it proceeds
through the coil, cooling the indoor coil down to about 48°F.
Heat is continually being transferred to the cool ns and
tubes of the indoor evaporator coil by the warm system air.
This warming process causes the refrigerant to boil. The
heat removed from the air is carried o󰀨 by the vapor.
As the vapor passes through the last tubes of the coil, it
becomes superheated. That is, it absorbs more heat than
is necessary to vaporize it. This is assurance that only
dry gas will reach the compressor. Liquid reaching the
compressor can weaken or break compressor valves.
The compressor increases the pressure of the gas, thus
adding more heat, and discharges hot, high pressure
super-heated gas into the outdoor condenser coil.
In the condenser coil, the hot refrigerant gas, being
warmer than the outdoor air, rst loses its superheat by
heat transferred from the gas through the tubes and ns
of the coil. The refrigerant now becomes saturated, part
liquid, part vapor and then continues to give up heat until
it condenses to a liquid alone. Once the vapor is fully
liqueed, it continues to give up heat which subcools the
liquid, and it is ready to repeat the cycle.
COOLING CYCLE
Cooling Only Models
When the contacts of the room thermostat close, making
terminals R to Y and R to G, the low voltage circuit to the
contactor is completed starting the compressor and outdoor
fan motor. This also energizes the indoor blower through
the 24V signal from the thermostat.
When the thermostat is satised, breaking the circuit
between R to Y and R to G, the compressor and outdoor
fan motor will stop. The indoor blower will stop after the fan
o󰀨 delay.
If the room thermostat fan selector switch should be set
to the “on” position then the indoor blower would run
continuous rather than cycling with the compressor.
background
SYSTEM OPERATION
7
Heat Pump Models
Any time the room thermostat is switched to cool, the O
terminal is energized. This energizes the 24 volt coil on the
reversing valve and switches it to the cooling position.
When the contacts of the room thermostat close, this
closes the circuit from R to Y and R to G in the unit.
This energizes the compressor contactor and will energize
the indoor blower instantly on models equipped with EEM
blower motor.
When the thermostat is satised, it opens its contacts
breaking the low voltage circuit causing the compressor
contactor to open and indoor fan to stop after the
programmed 60 second o󰀨 delay on models equipped with
EEM blower motors.
If the room thermostat fan selector switch should be set
to the “on” position then the indoor blower would run
continuous rather than cycling with the compressor.
HEATING CYCLE
Cooling Only Units
NOTE: The following only applies if the cooling only
unit has an approved electric heat kit installed for
heating. If auxiliary electric heaters should be used,
they may be controlled by outdoor thermostats (OT18-
60A or OT/EHR18-60A).
*PCH3 EEM Equipped Models
With the thermostat set to the heat position and a call
for heat, R to W will be energized. This will energize the
electric heat sequencers and the EEM motor. The electric
heat will be energized through the normally open contacts
of the electric heat sequencers. The indoor blower will be
energized through W from the thermostat.
When the thermostat is satised, this breaks the circuit
from R to W. This will turn o󰀨 the electric heaters, and the
indoor blower after the programmed 60 second o󰀨 delay.
Single-Stage Heat Pump Units
On a call for rst stage heat, the contacts of the room
thermostat close. This energizes terminals R to Y and R
to G, the low voltage circuit to the contactor is completed
starting the compressor and outdoor fan motor. This also
energizes the indoor blower instantly on models equipped
with EEM blower motors.
When the thermostat is satised, breaking the circuit
between R to Y and R to G, the compressor and outdoor
fan motor will stop after the programmed 60 second o󰀨
delay on models equipped with EEM blower motors.
Two-Stage Heat Pump Units
On a call for rst stage heat, the contacts of the room
thermostat close. This energizes terminals R to Y1 and R
to G, the low voltage circuit to the contactor is completed
starting the compressor and outdoor fan motor. This also
energizes the indoor blower motor.
When the thermostat is satised, breaking the circuit
between R to Y1 and R to G, the compressor and outdoor
fan motor will stop. The indoor blower will stop after the
programmed o󰀨 delay.
During rst stage operation the stat calls for second stage
heat. This energizes terminals R to Y2. This powers voltage
to the compressor solenoid allowing the compressor to
shift to full capacity. When the thermostat is satised,
breaking the circuit between R to Y1, R to Y2 and R to G,
the compressor and outdoor fan motor will stop. The indoor
blower will stop after the programmed o󰀨 delay on the
motor.
When auxiliary electric heaters are used the Aux stage
heating contacts in the room thermostat close, which
would be wired to W1 at the unit low voltage connections,
this would energize the coil(s) of the electric heat
contactor(s)/sequencer(s). Contacts within the contactor(s)/
Sequencer(s) will close, bringing on the electric resistance
heaters. If auxiliary electric heaters should be used, the
may be controlled by outdoor thermostats (OT18-60A or
OT/EHR18-60A).
Emergency Heat Mode (Heat Pumps)
NOTE: The following only applies if the unit has
an approved electric heat kit installed for auxiliary
heating.
*PHC & *PHH EEM Equipped Models
With the thermostat set to the emergency heat position,
R to W1 will be energized. This will energize the electric
heat sequencers and the EEM motor. The electric heat
will be energized through the normally open contacts of
the electric heat sequencers. The indoor blower will be
energized through W from the thermostat.
DEFROST CYCLE
Package Heat Pumps
The defrosting of the outdoor coil is jointly controlled by the
defrost control board and the defrost thermostat.
background
SYSTEM OPERATION
8
Solid State Defrost Control
During operation the power to the circuit board is controlled
by a temperature sensor, which is clamped to a feeder tube
entering the outdoor coil. Defrost timing periods of 30, 60,
or 90 minutes may be selected by setting the circuit board
jumper to 30, 60, or 90 respectively. Accumulation of time
for the timing period selected starts when the sensor closes
(approximately 30° F), and when the room thermostat
calls for heat. At the end of the timing period, the unit’s
defrost cycle will be initiated provided the sensor remains
closed. When the sensor opens (approximately 60° F), the
defrost cycle is terminated and the timing period is reset.
If the defrost cycle is not terminated due to the sensor
temperature, a twelve minute override interrupts the unit’s
defrost period.
FAN OPERATION
Continuous Fan Mode
Models Equipped With EEM Blower Motors
If the thermostat calls for continuous fan, the indoor blower
will be energized from the G terminal of the thermostat to
the EEM blower motor.
If a call for heat or cool occurs during a continuous fan call,
the EEM motor will always recognize the call for the highest
speed and ignore the lower speed call.
If the thermostat is not calling for heat or cool, and the
fan switch on the thermostat is returned to the automatic
position, the fan will stop after the programmed 60 second
o󰀨 delay on units with the EEM motor.
background
SYSTEM OPERATION
9
Indoor
Coil
Outdoor
Coil
Chatleff
Orifice
Assy
In the cooling mode the orice is pushed into its seat forcing refrigerant to ow through the metered hole in the center of
the orice.
Typical Package Cooling
Restrictor Orifice Assembly in Cooling Operation
background
SYSTEM OPERATION
10
Indoor
Coil
Accumulator
Outdoor
Coil
Reversing Valve
(Energized)
Indoor
Coil
Accumulator
Outdoor
Coil
Reversing Valve
(De-Energized)
Typical Heat Pump System in Cooling
Typical Heat Pump System in Heating
background
SCHEDULED MAINTENANCE
11
Package units require regularly scheduled maintenance to
preserve high performance standards, prolong the service
life of the equipment, and lessen the chances of costly
failure.
In many instances the owner may be able to perform some
of the maintenance; however, the advantage of a service
contract, which places all maintenance in the hands of a
trained serviceman, should be pointed out to the owner.
WARNING
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
ONCE A MONTH
1. Inspect the return lters of the evaporator unit and
clean or change if necessary. NOTE: Depending on
operation conditions, it may be necessary to clean
or replace the lters more often. If permanent type
lters are used, they should be washed with warm
water and dried.
2. When operating on the cooling cycle, inspect the
condensate line piping from the evaporator coil.
Make sure the piping is clear for proper condensate
ow.
ONCE A YEAR
Qualified Service Personnel Only
1. Clean the indoor and outdoor coils.
2. Clean the cabinet inside and out.
3. Motors are permanently lubricated and do not require
oiling. TO AVOID PREMATURE MOTOR FAILURE,
DO NOT OIL.
4. Manually rotate the outdoor fan and indoor blower to
be sure they run freely.
5. Inspect the control panel wiring, compressor
connections, and all other component wiring to be
sure all connections are tight. Inspect wire insulation
to be certain that it is good.
6. Check the contacts of the compressor contactor. If
they are burned or pitted, replace the contactor.
7. Using a halide or electronic leak detector, check all
piping and etc. for refrigerant leaks.
TEST EQUIPMENT
Proper test equipment for accurate diagnosis is as
essential as regular hand tools.
The following is a must for every service technician and
service shop:
1. Thermocouple type temperature meter - measure dry
bulb temperature.
2. Sling psychrometer - measure relative humidity and
wet bulb temperature.
3. Volt-Ohm Meter - testing continuity, capacitors, motor
windings and voltage.
4. Accurate Leak Detector - testing for refrigerant leaks.
5. High Vacuum Pump - evacuation.
6. Electric Vacuum Gauge, Manifold Gauges and
high vacuum hoses - to measure and obtain proper
vacuum.
7. Accurate Charging Cylinder or Electronic Scale -
measure proper refrigerant charge.
8. Inclined Manometer - measure static pressure and
pressure drop across coils.
Other recording type instruments can be essential in
solving abnormal problems, however, in many instances
they may be rented from local sources.
Proper equipment promotes faster, more e󰀩cient service,
and accurate repairs with less call backs.
background
SCHEDULED MAINTENANCE
12
NOTES:
1. For Aluminum indoor coil cleaning, the A2L sensor
must be removed from the unit before applying coil
cleaners to avoid damage and contamination.
2. When replacing the A2L sensor, ensure that the
arrows on the A2L sensor and the sensor bracket are
pointing in the same direction.
background
SERVICING
13
Checking Voltage
WARNING
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
1. Remove doors, control panel cover, etc. from unit
being tested.
With power ON:
WARNING
Line voltage now present.
2. Using a voltmeter, measure the voltage across
terminals L1 and L2 of the contactor.
3. No reading - indicates open wiring, open fuse(s) no
power or etc. from unit to fused disconnect service.
Repair as needed.
4. If incoming voltage is within the range listed in the
chart below, energize the unit.
5. Using a voltmeter, measure the voltage with the unit
starting and operating to determine if voltage is within
the range listed in the chart below.
6. If the voltage falls below the minimum voltage, check
the line wire size. Long runs of undersized wire can
cause low voltage. If the wire size is adequate, notify
the local power company regarding either low or high
voltage.
Unit Voltage
Rated
Voltage
Minimum Supply
Voltage
Maximum Supply
Voltage
208/230V 197 253
Checking Wiring
WARNING
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
BRANCH CIRCUIT AMPACITY
15
20
25
30
35
40
45
50
SUPPLY WIRE LENGTH - FEET
200
6
4
4
4
3
3
2
2
150
8
6
6
4
4
4 3 3
100 10 8 8 6 6 6 4 4
50 14 12 10 10 8 8 6 6
1. Check wiring visually for signs of overheating,
damaged insulation and loose connections.
2. Use an ohmmeter to check continuity of any
suspected open wires.
3. If any wires must be replaced, replace with
comparable gauge and insulation thickness.
Checking Thermostat and Wiring
Thermostat Wiring: The maximum wire length for 18 AWG
thermostat wire is 100 feet.
background
SERVICING
14
WARNING
Line voltage now present.
With power ON and thermostat calling for cooling:
1. Use a voltmeter to verify 24 volts present at
thermostat wires C and R.
2. If no voltage present, check transformer and
transformer wiring. If 24 volts present, proceed to
step 3.
3. Use a voltmeter to check for 24 volts at thermostat
wires C and Y.
4. No voltage indicates trouble in the thermostat, wiring
or external transformer source.
5. Check the continuity of the thermostat and wiring.
Repair or replace as necessary.
Indoor Blower Motor
With power ON:
WARNING
Line voltage now present.
1. Use a voltmeter to verify 24 volts present at
thermostat wires C and R.
2. If no voltage present, check transformer and
transformer wiring. If 24 volts present, proceed to
step 3.
3. Set fan selector switch at thermostat to “ON”
position.
4. With voltmeter, check for 24 volts at wires C and G.
5. No voltage, indicates the trouble is in the thermostat
or wiring.
6. Check the continuity of the thermostat and wiring.
Repair or replace as necessary.
Checking Transformer and Control Circuit
A step-down transformer (208/240 volt primary to 24 volt
secondary) is provided with each package unit. This allows
ample capacity for use with resistance heaters.
WARNING
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
1. Remove control panel cover, or etc., to gain access
to transformer.
With power ON:
WARNING
Line voltage now present.
2. Using a voltmeter, check voltage across secondary
voltage side of transformer (R to C).
3. No voltage indicates faulty transformer, bad wiring, or
bad splices.
4. Check transformer primary voltage at incoming line
voltage connections and/or splices.
5. If line voltage available at primary voltage side of
transformer and wiring and splices good, transformer
is inoperative. Replace.
background
SERVICING
15
Transformer
Checking Contactor and/or Relays
The compressor contactor and other relay holding coils are
wired into the low or line voltage circuits. When the control
circuit is energized the coil pulls in the normally open
contacts or opens the normally closed contacts. When the
coil is de-energized, springs return the contacts to their
normal position.
WARNING
Disconnect power supply before servicing.
1. Remove the leads from the holding coil.
2. Using an ohmmeter, test across the coil terminals.
If the coil does not test continuous, replace the relay or
contactor.
Checking Contactor Contacts
WARNING
Disconnect power supply before servicing.
Single Phase
1. Disconnect the wire leads from the terminal (T) side
of the contactor.
2. With power ON, energize the contactor.
WARNING
Line voltage now present.
Testing Compressor Contactor
(Single Phase)
3. Using a voltmeter, test across terminals.
A. L1 - L2 - No voltage. Check breaker or fuses on
main power supply.
B. T1 to T2 - Meter should read the same as L1
to L2 in step A. If voltage readings are not the
same as step A, replace contactor.
Checking Low Pressure Control
(Heat Pump Models)
The low pressure control senses the pressure in the
suction line and will open its contacts on a drop in
pressure. The low pressure control will automatically reset
itself with a rise in pressure.
The low pressure control is designed to cut-out (open) at
approximately 22 PSIG. It will automatically cut-in (close) at
approximately 50 PSIG.
Test for continuity using a VOM and if not as above,
replace the control.
Checking High Pressure Control
WARNING
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
The high pressure control senses the pressure in the liquid
or discharge line. If abnormally high condensing pressures
develop, the contacts of the control open, breaking the
control circuit before the compressor motor overloads. This
control is automatically reset.
1. Using an ohmmeter, check across terminals of
high pressure control, with wire removed. If not
continuous, the contacts are open.
background
SERVICING
16
If the high-pressure switch needs to be replaced, please
follow the instructions below.
The copper tube should absorb all the heating, while the
high-pressure switch is heated solely by conduction. To
prevent overheating, the torch tip should be kept away from
the switch, ensuring the inner cone of the ame does not
make contact. Heating should be achieved using the outer
ame envelope, and the level of the brazing ame should
be kept low. During manual torch brazing, the torch should
remain on the copper tubing and be kept in motion to avoid
localized overheating.
Brazing High Pressure Switch
TORCH: A multi-tip torch is recommended, making heating
faster and more uniform than with a single ame.
2. Attach a gauge to the dill valve port on the base
valve.
With power ON:
WARNING
Line voltage now present.
3. Start the system and place a piece of cardboard in
front of the condenser coil, raising the condensing
pressure.
4. Check pressure at which the high pressure control
cuts-out.
If it cuts-out at 660 PSIG ± 10 PSIG, it is operating normally
(See causes for high head pressure in Service Problem
Analysis Guide). If it cuts out below this pressure range,
replace the control. The control should reset at 420 PSIG ±
25 PSIG.
Checking Internal Overload
Prevents the compressor windings from overheating.
Reacts to both current and temperature Cuts out 302°F.
Cuts in between 146 and 176°F.
1. Using an ohmmeter, test continuity between
terminals, If either winding test continuous, Internal
overload open.
2. Allow time for the compressor to cool, and overload
to close and retest.
Checking Capacitor
Capacitor, Run
A run capacitor is wired across the auxiliary and main
windings of a single phase permanent split capacitor
motor. The capacitors primary function is to reduce the line
current while greatly improving the torque characteristics
of a motor. This is accomplished by using the 90° phase
relationship between the capacitor current and voltage
in conjunction with the motor windings so that the motor
will give two phase operation when connected to a single
phase circuit. The capacitor also reduces the line current to
the motor by improving the power factor.
Capacitor, Start
Scroll Compressor Models
Hard start components are not required on Scroll
compressor equipped units due to a non-replaceable check
valve located in the discharge line of the compressor.
However hard start kits are available and may improve low
voltage starting characteristics.
This check valve closes o󰀨 high side pressure to the
compressor after shut down allowing equalization through
the scroll anks. Equalization requires only about one or
two seconds during which time the compressor may turn
backwards.
Your unit comes with a 180-second anti-short cycle
to prevent the compressor from starting and running
backwards.
Models Equipped With A Hard Start Device
A start capacitor is wired in parallel with the run capacitor
to increase the starting torque. The start capacitor is of the
electrolytic type, rather than metallized polypropylene as
used in the run capacitor.
A switching device must be wired in series with the
capacitor to remove it from the electrical circuit after the
compressor starts to run. Not removing the start capacitor
will overheat the capacitor and burn out the compressor
windings.
These capacitors have a 15,000 ohm, 2 watt resistor
wired across its terminals. The object of the resistor
is to discharge the capacitor under certain operating
conditions, rather than having it discharge across the
background
SERVICING
17
closing of the contacts within the switching device such as
the Start Relay, and to reduce the chance of shock to the
servicer. See the Servicing Section for specic information
concerning capacitors.
Relay, Start
A potential or voltage type relay is used to take the start
capacitor out of the circuit once the motor comes up to
speed. This type of relay is position sensitive. The normally
closed contacts are wired in series with the start capacitor
and the relay holding coil is wired parallel with the start
winding. As the motor starts and comes up to speed, the
increase in voltage across the start winding will energize
the start relay holding coil and open the contacts to the
start capacitor.
Testing Start Relay Kits
Testing Coil Relay
1. Disconnect power to unit.
2. Disconnect all wiring.
3. Measure the resistance of the coil between terminals
2 & 5.
4. If the coil reads open or shorted, replace the relay.
Testing Start Relay Coil Resistance
Testing Relay Contacts
Testing Contacts Resistance
A. Disconnect power to unit
B. Disconnect all wiring to the start relay
C. Measure the resistance of the contacts between
terminals 1 & 2
D. If the contacts read open, replace the relay
Testing Contacts Voltage
A. With power on, provide a call for cool to
energize the compressor
B. With the compressor running, use a voltmeter
to measure the voltage between terminals 1 &
2.
C. Voltage reading of zero indicates that the relay’s
contacts are stuck, replace the relay.
Testing Start Relay Contacts
Two quick ways to test a capacitor are a resistance and a
capacitance check.
Resistance Check
WARNING
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
1. Discharge capacitor and remove wire leads.
WARNING
Discharge capacitor through a 20 to 30 OHM resistor before
handling.
Testing Capacitor Resistance
2. Set an ohmmeter on its highest ohm scale and
connect the leads to the capacitor -
background
SERVICING
18
A. Good Condition - indicator swings to zero and
slowly returns to innity (Start capacitor with
bleed resistor will not return to innity. It will still
read the resistance of the resistor).
B. Shorted - indicator swings to zero and stops
there - replace.
C. Open - no reading - replace (Start capacitor
would read resistor resistance).
Capacitance Check (MFD)
WARNING
Discharge capacitor through a 20 to 30 OHM resistor before
handling.
1. Turn power o󰀨 to unit.
2. Discharge capacitor through a 20Ω - 30Ω resistor.
3. Remove wires from capacitor.
4. Use multi-meter check micro-farads (MFD) of the
capacitor.
5. Place leads from C – HERM.
6. Place leads from C – FAN.
7. Compare to capacitor rating label.
If the reading is within the tolerance listed on rating
label the capacitor is good.
If the reading is lower, the capacitor is bad and must
be replaced.
Testing Capacitance (MFD)
Checking Fan And Blower Motor Windings
(PSC Motors)
The auto reset fan motor overload is designed to protect
the motor against high temperature and high amperage
conditions by breaking the common circuit within the motor,
similar to the compressor internal overload. However, heat
generated within the motor is faster to dissipate than the
compressor, allow at least 45 minutes for the overload to
reset, then retest.
WARNING
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
1. Remove the motor leads from its respective
connection points and capacitor (if applicable).
2. Check the continuity between each of the motor
leads.
3. Touch one probe of the ohmmeter to the motor frame
(ground) and the other probe in turn to each lead.
If the windings do not test continuous or a reading is
obtained from lead to ground, replace the motor.
Checking EEM Motors
Applies only to Units with EEM Motors
The EEM motor is a one piece, fully encapsulated, 3 phase
brushless DC (single phase AC input) motor with ball
bearing construction. The EEM motor features an integral
control module.
NOTE: The GE TECMate will not currently operate the
EEM motor.
1. Using a voltmeter, check for 230 volts to the motor
connections L and N. If 230 volts is present, proceed
to step 2. If 230 volts is not present, check the line
voltage circuit to the motor.
2. Using a voltmeter, check for 24 volts from terminal C
to either terminal 1, 2, 3, 4, or 5, depending on which
tap is being used, at the motor. If voltage present,
proceed to step 3. If no voltage, check 24 volt circuit
to motor.
3. If voltage was present in steps 1 and 2, the motor
has failed and will need to be replaced.
NOTE: When replacing motor, ensure the belly band is
between the vents on the motor and the wiring has the
proper drip loop to prevent condensate from entering
the motor.
background
SERVICING
19
C
L G N
1
2 3
4
5
High Voltage
Connections
3/16"
Low Voltage Connections
1/4”
EEM Motor Connections
Checking ECM Motors
An ECM is an Electronically Commutated Motor which
o󰀨ers many signicant advantages over PSC motors.
The ECM has near zero rotor loss, synchronous machine
operation, variable speed, low noise, and programmable
air ow. Because of the sophisticated electronics within
the ECM motor, some technicians are intimated by the
ECM motor; however, these fears are unfounded. GE/
Regal Beloit o󰀨ers two ECM motor testers, and with a VOM
meter, one can easily perform basic troubleshooting on
ECM motors. An ECM motor requires power (line voltage)
and a signal (24 volts) to operate. The ECM motor stator
contains permanent magnet. As a result, the shaft feels
“rough” when turned by hand. This is a characteristic of the
motor, not an indication of defective bearings.
WARNING
Line voltage now present.
1. Disconnect the 5-pin connector from the motor.
2. Using a volt meter, check for line voltage at terminals
#4 & #5 at the power connector. If no voltage is
present:
3. Check the unit for incoming power.
4. Check the control board.
5. If line voltage is present, reinsert the 5-pin connector
and remove the 16-pin connector.
6. Check for signal (24 volts) at the transformer.
7. Check for signal (24 volts) from the thermostat to the
“G” terminal at the 16-pin connector.
8. Using an ohmmeter, check for continuity from the #1
& #3 (common pins) to the transformer neutral or “C”
thermostat terminal. If you do not have continuity, the
motor may function erratically. Trace the common
circuits, locate and repair the open neutral.
9. Set the thermostat to “Fan-On”. Using a voltmeter,
check for 24 volts between pin # 15 (G) and
common.
10. Disconnect power to compressor. Set thermostat to
call for cooling. Using a voltmeter, check for 24 volts
at pin # 6 and or #14.
11. Set the thermostat to a call for heating. Using a
voltmeter, check for 24 volts at pin #2 and/or #11.
1
2
3
4
5
Lines 1 and 2 will be connected
for 12OVAC Power Connector
applications only
Gnd
AC Line Connection
AC Line Connection
}
11
1 9
2
3
4
5
6
7
8 16
15
14
13
12
10
OUT - OUT +
ADJUST +/-
G (FAN)
Y1 Y/Y2
COOL
EM Ht/W2
DELAY
24 Vac (R)
COMMON2
HEAT
W/W1
BK/PWM (SPEED)
COMMON1 O (REV VALVE)
16-PIN ECM HARNESS CONNECTOR
If you do not read voltage and continuity as described, the
problem is in the control or interface board, but not the
motor. If you register voltage as described, the ECM power
head is defective and must be replaced.
background
SERVICING
20
Checking ECM Motor Windings
WARNING
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
1. Disconnect the 5-pin and the 16-pin connectors from
the ECM power head.
2. Remove the 2 screws securing the ECM power head
and separate it from the motor.
3. Disconnect the 3-pin motor connector from the power
head and lay it aside.
4. Using an ohmmeter, check the motor windings for
continuity to ground (pins to motor shell). If the
ohmmeter indicates continuity to ground, the motor is
defective and must be replaced.
5. Using an ohmmeter, check the windings for continuity
(pin to pin). If no continuity is indicated, the thermal
limit (over load) device may be open. Allow motor to
cool and retest.
16-pin
connector
5-pin
connector
3-pin motor
connector
Checking Compressor
WARNING
Hermetic compressor electrical terminal venting can
be dangerous. When insulating material which supports
a hermetic compressor or electrical terminal suddenly
disintegrates due to physical abuse or as a result of an
electrical short between the terminal and the compressor
housing, the terminal may be expelled, venting the vapor and
liquid contents of the compressor housing and system.
If the compressor terminal PROTECTIVE COVER and
gasket (if required) are not properly in place and secured,
there is a remote possibility if a terminal vents, that the
vaporous and liquid discharge can be ignited, spouting
ames several feet, causing potentially severe or fatal
injury to anyone in its path.
This discharge can be ignited external to the compressor
if the terminal cover is not properly in place and if the
discharge impinges on a su󰀩cient heat source.
Ignition of the discharge can also occur at the venting
terminal or inside the compressor, if there is su󰀩cient
contaminant air present in the system and an electrical arc
occurs as the terminal vents.
Ignition cannot occur at the venting terminal without the
presence of contaminant air, and cannot occur externally
from the venting terminal without the presence of an
external ignition source.
Therefore, proper evacuation of a hermetic system is
essential at the time of manufacture and during servicing.
To reduce the possibility of external ignition, all open
ame, electrical power, and other heat sources should be
extinguished or turned o󰀨 prior to servicing a system.
Resistance Test
Each compressor is equipped with an internal overload.
The line break internal overload senses both motor
amperage and winding temperature. High motor
temperature or amperage heats the disc causing it to open,
breaking the common circuit within the compressor on
single phase units.
Heat generated within the compressor shell, usually due to
recycling of the motor, high amperage or insu󰀩cient gas to
cool the motor, is slow to dissipate. Allow at least three to
four hours for it to cool and reset, then retest.
WARNING
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
1. Remove the leads from the compressor terminals.
WARNING
See warnings before removing compressor terminal cover.
2. Using an ohmmeter, test continuity between
terminals S-R, C-R, and C-S, on single phase units
or terminals T1, T2.
background
SERVICING
21
Testing Compressor Windings
If either winding does not test continuous, replace the
compressor.
NOTE: If an open compressor is indicated, allow ample
time for the internal overload to reset before replacing
compressor.
Ground Test
If fuse, circuit breaker, ground fault protective device, etc.
has tripped, this is a strong indication that an electrical
problem exists and must be found and corrected. The
circuit protective device rating must be checked and its
maximum rating should coincide with that marked on the
equipment nameplate.
With the terminal protective cover in place, it is acceptable
to replace the fuse or reset the circuit breaker ONE TIME
ONLY to see if it was just a nuisance opening. If it opens
again, DO NOT continue to reset.
Disconnect all power to unit, making sure that all
power legs are open.
1. Carefully remove the compressor terminal protective
cover and inspect for loose leads or insulation breaks
in the lead wires.
2. Disconnect the three leads going to the compressor
terminals at the compressor or nearest point to the
compressor.
3. Check for a ground separately between each of the
three terminals and ground (such as an unpainted
tube on the compressor). If there is any reading of
continuity to ground on the meter, the compressor
should be considered defective.
4. If ground is indicated, replace the compressor.
WARNING
Damage can occur to the glass embedded terminals if the
leads are not properly removed. This can result in terminal
and hot oil discharging.
Compressor Ground Test
Unloader Test Procedure
(2 Stage Compressors Only)
A nominal 24-volt direct current coil activates the
compressor internal unloader solenoid. The input control
circuit voltage must be 18 to 28 volt ac. The external
electrical connection is made with a molded plug assembly.
This plug contains a full wave rectier to supply direct
current to the unloader coil. The measured DC voltage at
the connectors in the plug should be 15 to 27 volt dc.
Unloader Test Procedure
If it is suspected that the unloader is not working, the
following methods may be used to verify operation.
1. Operate the system and measure compressor
amperage. Cycle the unloader ON and OFF at 10
second intervals. The compressor amperage should
increase when switching from part-load to full-load
and decrease when switching from full-load to part-
load. The percent change depends on the operating
conditions and voltage, but should be at least 25
percent.
2. If step one does not give the expected results, shut
unit o󰀨. Apply 18 to 28 volt ac to the unloader molded
plug leads and listen for a click as the solenoid pulls
in. Remove power and listen for another click as the
unloader returns to its original position.
3. If clicks can’t be heard, shut o󰀨 power to the unit
and remove the control circuit molded plug from
the compressor and measure the unloader coil
resistance (connections on the compressor).
The solenoid coil should have continuity and not
be grounded or have innite resistance. If the
coil resistance is innite, zero, or grounded, the
compressor must be replaced.
background
SERVICING
22
4. Next check the molded plug.
A. Voltage check: Apply control voltage to the
plug wires (18 to 28 volt ac). The measured dc
voltage at the female connectors in the plug
should be around 15 to 27 vdc.
B. Resistance check: Measure the resistance from
the end of one molded plug lead to either of
the two female connectors in the plug. One of
the connectors should read close to zero ohms
while the other should read innity. Repeat
with other wire. The same female connector
as before should read zero while the other
connector again reads innity. Reverse polarity
on the ohmmeter leads and repeat. The female
connector that read innity previously should
now read close to zero ohms.
C. Replace plug if either of these test methods
doesn’t show the desired results.
Operation Test
If the voltage, capacitor, overload and motor winding test
fail to show the cause for failure:
WARNING
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
1. Remove unit wiring from disconnect switch and wire
a test cord to the disconnect switch.
NOTE: The wire size of the test cord must equal the
line wire size and the fuse must be of the proper size
and type.
2. With the protective terminal cover in place, use the
three leads to the compressor terminals that were
disconnected at the nearest point to the compressor
and connect the common, start and run clips to the
respective leads.
3. Connect good capacitors of the right MFD and
voltage rating into the circuit as shown.
4. With power ON, close the switch.
WARNING
Line voltage now present.
A. If the compressor starts and continues to run,
the cause for failure is somewhere else in the
system.
B. If the compressor fails to start - replace.
The condition of the scroll anks is checked in the following
manner:
1. Attach gauges to the high and low side of the
system.
2. Start the system and run a “Cooling Performance
Test.
If the test shows:
A. Below normal high side pressure.
B. Above normal low side pressure.
C. Low temperature di󰀨erence across coil.
D. Low amp draw at compressor.
and the charge is correct, test the reversing valve if
equipped (heat pump models only). If the reversing
valves test good, the compressor is faulty - replace the
compressor.
Locked Rotor Test
If fuse, circuit breaker, ground fault protective device, etc.
has tripped, this is a strong indication that an electrical
problem exists and must be found and corrected. The
circuit protective device rating must be checked and its
maximum rating should coincide with that marked on the
equipment nameplate.
Before checking for locked rotor, the compressor terminals
should be checked for open windings (see Resistance Test)
and the run capacitor and start capacitor (if used) should
be checked thoroughly (see Checking Capacitor).
With power ON:
WARNING
Line voltage now present.
1. Check the serial data plate for the compressor locked
rotor amps (LRA) rating.
2. Using an ampmeter, measure the amperage reading
for the run and common wires to the compressor.
Since the compressor motor overload will likely
trip soon after drawing locked rotor amps, this
measurement should be taken as soon as the
compressor starts.
3. If the amperage reading roughly equals the
compressor LRA rating and all other checks have
been completed, locked rotor amps has been
veried.
Testing Crankcase Heater (Optional Item)
NOTE: Not all compressors use crankcase heaters.
The crankcase heater must be energized a minimum of
four (4) hours before the condensing unit is operated.
background
SERVICING
23
Crankcase heaters are used to prevent migration or
accumulation of refrigerant in the compressor crankcase
during the o󰀨 cycles and prevents liquid slugging or oil
pumping on start up.
A crankcase heater will not prevent compressor damage
due to a oodback or over charge condition.
WARNING
Disconnect power supply before servicing.
1. Disconnect the heater lead in wires.
2. Using an ohmmeter, check heater continuity - should
test continuous. If not, replace.
Checking Crankcase Heater Thermostat
NOTE: Not all models with crankcase heaters will have
a crankcase heater thermostat.
1. Install a thermocouple type temperature test lead on
the discharge line adjacent to the crankcase heater
thermostat.
2. Check the temperature at which the control closes its
contacts by lowering the temperature of the control.
The crankcase heater thermostat should close at
67°F ± 5°F.
3. Check the temperature at which the control opens
its contacts by raising the temperature of the control.
The crankcase heater thermostat should open at
85°F ± 5°F.
4. If not as above, replace control.
Reversing Valve Troubleshooting
Checking Reversing Valve and Solenoid
Reversing valve used in heat pumps could potentially leak
internally. Discharge gases can leak into the suction inside
the valve. Compound gages will give the same symptoms
as bad compressor valves or broken scroll anks. The
temperature between true suction and the suction line after
the valve should not be greater than 4 degrees.
NOTE: The center tube is always the suction line and
should be cold.
Troubleshooting the Reversing Valve for
Electrical Failure
1. Place unit into the cooling mode. Test for 24 volts at
the solenoid. If there is no voltage present at coil,
check the control voltage.
2. If voltage is present, loosen the nut on the top of
the coil. Remove the coil, there should be slight
resistance.
3. If the slight resistance is felt, remove the coil. As
you remove the coil listen carefully, an audible
click should be detected. The clicking is due to the
movement of the pilot valve plunger. The absence of
a clicking sound indicates the plunger is stuck.
Troubleshooting Mechanical Failures on a
Reversing Valve by Pressure
1. Troubleshooting the reversing valve can be done by
pressure and touch.
2. Raise the head pressure. In the cooling mode block
the fan exhaust. Once head pressure has been
raised, cycle between cooling and heating and see if
the piston can be freed.
Trouble Shooting Mechanical Failures on a
Reversing Valve by Temperature
1. When operating properly the valve contains
refrigerant gases at certain temperatures.
2. The discharge line should be the same temperature
after the valves discharge line.
3. The true suction should be the same as the suction
line after the valve. If there is a 4-degree di󰀨erence,
valve is leaking
When stuck in the mid-position, part of the discharge gas
from the compressor is directed back to the suction side,
resulting in excessively high suction pressure. An increase
in the suction line temperature through the reversing
valve can also be measured. Check operation of the valve
by starting the system and switching the operation from
COOLING to HEATING cycle.
If the valve fails to change its position, test the voltage
(24V) at the valve coil terminals, while the system is on the
COOLING cycle.
If voltage is registered at the coil, tap the valve body lightly
while switching the system from HEATING to COOLING,
etc. If this fails to cause the valve to switch positions,
remove the coil connector cap and test the continuity of
the reversing valve solenoid coil. If the coil does not test
continuous - replace it. If the coil test continuous and 24
volts is present at the coil terminals, the valve is inoperative
- replace it.
Testing Defrost Control
NOTE: PCBDM133 defrost controls have a three (3)
minute compressor o󰀨 cycle delay.
NOTE: The PCBDM133 defrost controls are shipped
from the factory with the compressor delay option
selected. This will de-energize the compressor
contactor for 30 seconds on defrost initiation and
defrost termination. If the jumper is set to Normal,
the compressor will continue to run during defrost
initiation and defrost termination. The control will also
ignore the low pressure switch connected to R-PS1
and PS2 for 5 minutes upon defrost initiation and 5
minutes after defrost termination.
background
SERVICING
24
To check the defrost control for proper sequencing,
proceed as follows: With power ON; unit not running.
1. Jumper defrost thermostat by placing a jumper wire
across the terminals “DFT” and “R”/” R-DFT” at
defrost control board.
2. Remove jumper from timer pins and jump across test
pins on defrost control board. NOTE: Do not use
screwdriver or eld supplied jumper to test the
control.
3. Set thermostat to call for heating. System should go
into defrost within 21 seconds.
4. Immediately remove jumper from test pins.
5. Using VOM check for voltage across terminals “C &
O”. Meter should read 24 volts.
6. Using VOM check for voltage across fan terminals
DF1 and DF2 on the board. You should read line
voltage (208-230 VAC) indicating the relay is open in
the defrost mode
7. Using VOM check for voltage across “W”/”W2” & “C”
terminals on the board. You should read 24 volts.
8. If not as above, replace control board.
9. Set thermostat to o󰀨 position and disconnect power.
Remove jumper from defrost thermostat and replace
timer jumper to the desired defrost time.
NOTE: Remove jumper across defrost thermostat
before returning system to service.
Testing Defrost Thermostat
1. Install a thermocouple type temperature test lead on
the tube adjacent to the defrost control. Insulate the
lead point of contact.
2. Check the temperature at which the control closes its
contacts by lowering the temperature of the control. It
should close at approximately 30°F.
3. Check the temperature at which the control opens its
contacts by raising the temperature of the control. It
should open at approximately 60°F.
4. If not as above, replace control.
Checking Heater Limit Control(s)
(Optional Electric Heaters)
Each individual heater element is protected with an
automatic reset limit control connected in series with
each element to prevent overheating of components in
case of low airow. This limit control will open its circuit at
approximately 150°F. to 160°F and close at approximately
110°F.
WARNING
Disconnect electrical power supply.
1. Remove the wiring from the control terminals.
2. Using an ohmmeter test for continuity across the
normally closed contacts. No reading indicates the
control is open - replace if necessary. Make sure the
limits are cool before testing.
If Found Open - Replace - Do Not Wire Around.
Checking Heater Elements
Optional electric heaters may be added, in the quantities
shown in the spec sheet for each model unit, to provide
electric resistance heating. Under no condition shall more
heaters than the quantity shown be installed.
WARNING
High Voltage!
Disconnect all power before servicing or
installing. Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
1. Disassemble and remove the heating element(s).
2. Visually inspect the heater assembly for any breaks
in the wire or broken insulators.
3. Using an ohmmeter, test the element for continuity -
no reading indicates the element is open. Replace as
necessary.
Refrigeration Repair Practice
DANGER: Always remove the refrigerant charge in a
proper manner before applying heat to the system.
These models use the FasTest Access Fitting System,
with a saddle that is either soldered to the suction and
liquid lines or is fastened with a locking nut to the access
tting box (core) and then screwed into the saddle. Do not
remove the core from the saddle until the refrigerant
charge has been removed. Failure to do so could result
in property damage or personal injury.
background
SERVICING
25
When installing a new core or reinstalling the core after
removal, it is very important to note that before inserting
the core into the saddle, the core and saddle must be
free of debris and the “O” Ring must have a thin coating
of refrigerant oil applied to it. The oil is to prevent the “O”
Ring from being deformed when the core is tightened
completely. The core should be torqued to 8 ft. lb.
When repairing the refrigeration system:
WARNING
Disconnect power supply before servicing.
1. Never open a system that is under vacuum. Air and
moisture will be drawn in.
2. Plug or cap all openings.
3. Remove all burrs and clean the brazing surfaces of
the tubing with sand cloth or paper. Brazing materials
do not ow well on oxidized or oily surfaces.
4. Clean the inside of all new tubing to remove oils and
pipe chips.
5. When brazing, sweep the tubing with dry nitrogen
to prevent the formation of oxides on the inside
surfaces.
6. Complete any repair by replacing the liquid line drier
in the system, evacuate and charge.
At any time the system has been open for repair, the
factory installed liquid line lter drier must be replaced.
Brazing Materials
Copper to Copper Joints - Sil-Fos used without ux
(alloy of 15% silver, 80% copper, and 5% phosphorous).
Recommended heat 1400°F.
Copper to Steel Joints - Silver Solder used without
a ux (alloy of 30% silver, 38% copper, 32% zinc).
Recommended heat - 1200°F.
Standing Pressure Test (Recommended Before
System Evacuation)
WARNING
To avoid the risk of fire or explosion, never use oxygen,
high pressure air or flammable gases for leak testing of a
refrigeration system.
WARNING
To avoid possible explosion, the line from the nitrogen
cylinder must include a pressure regulator and a pressure
relief valve. The pressure relief valve must be set to the
systems maximum allowable pressure. Refer to the serial
plate.
Pressure test the system using dry nitrogen and soapy
water to locate leaks. If leaks are found, repair them.
After repair, repeat the pressure test. If no leaks exist,
proceed to system evacuation.
CAUTION
In addition to conventional charging procedures, the
following requirements shall be followed.
• Ensure that contamination of different refrigerants
does not occur when using charging equipment. Hoses
or lines shall be as short as possible to minimize the
amount of refrigerant contained in them.
• Cylinders shall be kept in an appropriate position
according to the instructions.
• Ensure that the REFRIGERATING SYSTEM is earthed
prior to charging the system with refrigerant.
• Label the system when charging is complete (if not
already).
• Extreme care shall be taken not to overfill the
• REFRIGERATING SYSTEM.
Prior to recharging the system, it shall be pressure-
tested with the appropriate purging gas. The system shall
be leak-tested on completion of charging but prior to
commissioning. A follow up leak test shall be carried out
prior to leaving the site.
CAUTION
When removing refrigerant from a system, either for
servicing or decommissioning, all refrigerants must be
removed safely.
When transferring refrigerant into cylinders, ensure
that only appropriate refrigerant recovery cylinders are
employed. Ensure that the correct number of cylinders for
holding the total system charge is available. All cylinders
to be used are designated for the recovered refrigerant
and labeled for that refrigerant (i.e. special cylinders for
the recovery of refrigerant).
Cylinders shall be complete with pressure-relief valve and
associated shut-off valves in good working order. Empty
recovery cylinders are evacuated and, if possible, cooled
before recovery occurs. All recovery equipment must be
suitable for the recovery of A2L refrigerant and in good
working order. Ensure that you follow the manufacturer’s
instructions carefully. If in doubt, the manufacturer
should be consulted. In addition, a set of calibrated
weighing scales shall be available and in good working
order. Hoses shall be complete with leak-free disconnect
couplings and in good condition.
The recovered refrigerant shall be processed according
to local legislation in the correct recovery cylinder,
and the relevant waste transfer note arranged. Do not
mix refrigerants in recovery units and especially not in
cylinders.
If compressors or compressor oils are to be removed,
ensure that they have been evacuated to an acceptable
level to make certain that flammable refrigerant does not
remain within the lubricant. The compressor body shall not
be heated by an open flame or other ignition sources to
accelerate this process. When oil is drained from a system,
it shall be carried out safely.
Leak test the system using dry nitrogen and soapy water to
identify leaks. If you prefer to us an electronic leak detector,
charge the system to 10 PSIG with the appropriate
background
SERVICING
26
system refrigerant (See Serial Data Plate for refrigerant
identication). Do not use an alternative refrigerant. Using
dry nitrogen, nish charging the system to 450 PSIG.
Apply the leak detector to all suspect areas. When leaks
are discovered, repair the leaks, and repeat the pressure
test. If leaks have been eliminated, proceed to the system
evacuation.
System Evacuation
Condensing unit liquid and suction valves are closed to
contain the charge within the unit. The unit is shipped with
valve stems closed and caps installed. Do not open valves
until the system is evacuated.
WARNING
REFRIGERANT UNDER PRESSURE!
Failure to follow proper procedures may cause property
damage, personal injury or death.
NOTE: Scroll compressors should never be used
to evacuate or pump down a heat pump or air
conditioning system.
CAUTION
Prolonged operation at suction pressures less than 20
PSIG for more than 5 seconds will result in overheating of
the scrolls and permanent damage to the scroll tips, drive
bearings and internal seal.
Evacuation
Deep Vacuum Method (Recommended)
The Deep Vacuum Method requires a vacuum pump
rated 500 microns or less. This method is an e󰀨ective
and e󰀩cient way of assuring the system is free on non-
condensable air and moisture. As an alternative, the Triple
Evacuation Method is detailed in the Service Manual for
this product model.
It is recommended used to remove the Schrader Cores
from the service valves using a core-removal tool to
expedite the evacuation procedure.
1. Connect the vacuum pump, micron gauge,
and vacuum rated hose to both service valves.
Evacuation must use both service valves to eliminate
system mechanical seals.
2. Evacuate the system to less than 500 microns.
3. Isolate the pump from the system and hold vacuum
for 10 minutes (minimum). Typically, pressure will rise
slowly during this period. If the pressure rises to less
than 1000 microns and remains steady, the system
is considered leak-free; proceed to system charging
and startup.
4. If pressure rises above 1000 microns but holds
steady below 2000 microns, non-condensable air
or moisture may remain or a small leak is present.
Return to step 2: If the same result is achieved,
check for leaks and repair. Repeat the evacuation
procedure.
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0 1 2 3 4 5 6 7 8 9
10
LEAK(S)
PRESENT
MINUTES
V
ACUUM
IN
MICRONS
CONDENSIBLES OR SMALL
LEAK PRESENT
NO LEAKS
NO CONDENSIBLES
Triple Evacuation Method (Alternate)
1. Evacuate the system to 4000 microns and hold for 15
minutes. Break the vacuum with dry nitrogen, bring
the system pressure to 2-3 PSIG, and hold for 20
minutes. Release the nitrogen.
2. Evacuate to 1500 microns and hold for 20 minutes.
Break the vacuum with dry nitrogen again, bring the
system pressure back to 2-3 PSIG, and hold for 20
minutes.
3. Evacuate the system to 500 microns and hold for 60
minutes.
4. If the pressure rises to 1000 microns or less and
remains steady the system is considered leak free;
proceed to start-up.
background
SERVICING
27
Charging
WARNING
REFRIGERANT UNDER PRESSURE!
• Do not overcharge system with refrigerant.
• Do not operate unit in a vacuum or at negative pressure.
Failure to follow proper procedures may cause property
damage, personal injury or death.
CAUTION
Only use refrigerant certified to AHRI standards. Used
refrigerant may cause compressor damage. The
manufacturer is not responsible for damage or the need
for repairs resulting from the use of unapproved
refrigerant types or used or recycled refrigerant. Most
portable machines cannot clean used refrigerant to meet
AHRI standards.
Charge the system with the exact amount of refrigerant.
See the unit nameplate for the correct refrigerant charge
amount.
An inaccurately charged system will cause future problems.
1. Using charging scale, weigh in the refrigerant
charge amount listed on unit nameplate. Allow liquid
refrigerant only to enter the high side.
2. After the system will take all it will take, close the
valve on the high side of the charging manifold.
3. Start the system and charge the balance of the
refrigerant through the low side.
NOTE: R32 should be drawn out of the storage
container or drum in liquid form due to its fractionation
properties, but should be “Flashed” to its gas state
before entering the system. There are commercially
available restriction devices that t into the system
charging hose set to accomplish this. DO NOT charge
liquid R32 into the compressor.
4. With the system still running, close the valve on the
charging cylinder. At this time, you may still have
some liquid refrigerant in the charging cylinder hose
and will denitely have liquid in the liquid hose.
Slowly open the high side manifold valve and transfer
the liquid refrigerant from the liquid line hose and
charging cylinder hose into the suction service valve
port. CAREFUL: Watch so that liquid refrigerant does
not enter the compressor.
NOTE: Even though the compressor section of a Scroll
compressor is more tolerant of liquid refrigerant,
continued oodback or ooded start conditions may
wash oil from the bearing surfaces causing premature
bearing failure.
Checking Compressor Efficiency
The reason for compressor ine󰀩ciency is broken or
damaged suction and/or discharge valves, or scroll
anks on Scroll compressors, reducing the ability of the
compressor to pump refrigerant vapor.
The condition of the valves or scroll anks is checked in the
following manner:
1. Attach gauges to the high and low side of the
system.
2. Start the system and run a Cooling Performance
Test.
If the test shows:
A. Below normal high side pressure.
B. Above normal low side pressure.
C. Low temperature di󰀨erence across coil.
D. Low amp draw at compressor.
– and the charge is correct. The compressor is faulty -
replace the compressor.
Thermostatic Expansion Valve
The expansion valve is designed to control the rate of liquid
refrigerant ow into an evaporator coil in exact proportion
to the rate of evaporation of the refrigerant in the coil. The
amount of refrigerant entering the coil is regulated since
the valve responds to temperature of the refrigerant gas
leaving the coil (feeler bulb contact) and the pressure of the
refrigerant in the coil. This regulation of the ow prevents
the return of liquid refrigerant to the compressor.
The illustration below shows typical heat pump TXV/check
valve operation in the heating and cooling modes.
COOLING HEATING
TXV Valves
Some TXV valves contain an internal check valve thus
eliminating the need for an external check valve and
bypass loop. The three forces which govern the operation
of the valve are: (1) the pressure created in the power
assembly by the feeler bulb, (2) evaporator pressure, and
(3) the equivalent pressure of the superheat spring in the
valve.
0% bleed type expansion valves are used on indoor and
outdoor coils. The 0% bleed valve will not allow the system
pressures (High and Low side) to equalize during the
shut down period. The valve will shut o󰀨 completely at
approximately 100 PSIG.
30% bleed valves used on some other models will continue
to allow some equalization even though the valve has shut-
o󰀨 completely because of the bleed holes within the valve.
background
SERVICING
28
This type of valve should not be used as a replacement for
a 0% bleed valve, due to the resulting drop in performance.
The bulb must be securely fastened with two straps to a
clean straight section of the suction line. Application of
the bulb to a horizontal run of line is preferred. If a vertical
installation cannot be avoided, the bulb must be mounted
so that the capillary tubing comes out at the top.
Overfeeding
Overfeeding by the expansion valve results in high suction
pressure, cold suction line, and possible liquid slugging of
the compressor.
If these symptoms are observed:
1. Check for an overcharged unit by referring to the
cooling performance charts in the servicing section.
2. Check the operation of the power element in the
valve as explained in Checking Expansion Valve
Operation.
3. Check for restricted or plugged equalizer tube.
Underfeeding
Underfeeding by the expansion valve results in low system
capacity and low suction pressures.
If these symptoms are observed:
1. Check for a restricted liquid line or drier. A restriction
will be indicated by a temperature drop across the
drier.
2. Check the operation of the power element of the
valve as described in Checking Expansion Valve
Operation.
CAUTION
To prevent personal injury, carefully connect and
disconnect manifold gauge hoses. Escaping liquid
refrigerant can cause burns. Do not vent refrigerant to
atmosphere. Recover during system repair or final unit
disposal.
Checking expansion valve operation
1. Remove the remote bulb of the expansion valve from
the suction line.
2. Start the system and cool the bulb in a container of
ice water, closing the valve. As you cool the bulb,
the suction pressure should fall and the suction
temperature will rise.
3. Next warm the bulb in your hand. As you warm the
bulb, the suction pressure should rise and the suction
temperature will fall.
4. If a temperature or pressure change is noticed, the
expansion valve is operating. If no change is noticed,
the valve is restricted, the power element is faulty, or
the equalizer tube is plugged.
5. Capture the charge, replace the valve and drier,
evacuate and recharge.
Refrigerant Charge Check
(Units with Fixed Orifice Devices)
After completing airow measurements and adjustments
the unit’s refrigerant charge must be checked. All package
units with xed orice devices are charged using the super
heat method at the compressor suction line.
Superheat
Before checking the superheat or replacing the valve,
perform all the procedures outlined under Air Flow,
Refrigerant Charge, Expansion Valve - Overfeeding,
Underfeeding. These are the most common causes for
evaporator malfunction.
Checking Superheat
Refrigerant gas is considered superheated when its
temperature is higher than the saturation temperature
corresponding to its pressure. The degree of superheat
equals the degrees of temperature increase above the
saturation temperature at existing pressure.
Procedure:
1. Run system at least 15 -20 minutes to allow pressure
to stabilize.
2. Install a low side pressure gauge on the suction line
access tting.
3. Temporarily install thermometer on suction (large)
line near compressor with adequate contact and
insulate for best possible reading.
4. Record the gauge pressure corresponding
temperature and the temperature of the suction line.
5. Refer to the superheat table for proper system
superheat. Add charge to lower superheat recover
charge to raise superheat.
100
- - - 10 10
95
- - 10 10 10
90
- - 12 15 18
85
- 10 13 17 20
80
- 10 15 21 26
75 10 13 17 25 29
70 10 17 20 28 32
65 13 19 26 32 35
60 17 25 30 33 37
Ambient Condenser
Inlet Temp (°F
Drybulb)
65
70
75
Return Air Temp. (°F Drybulb)
80
85
Superheat Table
EXAMPLE:
A. Suction Pressure = 143
B. Corresponding Temp. °F = 50
C. Thermometer on Suction Line = 59°F
To obtain the degrees temperature of superheat, subtract
50.0 from 59.0°F. The di󰀨erence is 9° Superheat. The 9°
Superheat would fall in the ± range of allowable superheat.
background
SERVICING
29
SUPERHEAT = SUCTION LINE TEMP - SAT. SUCTION
TEMP.
After superheat is checked, it is recommended to check
unit subcooling at the condenser coil liquid line out.
(Units with TXV Devices)
All package units with TXV devices are charged using the
SUBCOOLING method at the liquid line. After subcooling is
checked it is recommended to check unit superheat at the
evaporator coil suction line.
Checking Subcooling
Refrigerant liquid is considered subcooled when its
temperature is lower than the saturation temperature
corresponding to its pressure. The degree of subcooling
equals the degrees of temperature decrease below the
saturation temperature at the existing pressure.
PROCEDURE:
1. Attach an accurate thermometer or preferably a
thermocouple type temperature tester to the liquid
line close to the pressure switch.
2. Install a high side pressure gauge on the liquid
access tting.
3. Record the gauge pressure and the temperature of
the line.
4. The di󰀨erence between the thermometer reading and
pressure to temperature conversion is the amount of
subcooling.
SUBCOOLING FORMULA = SAT. LIQUID TEMP. -
LIQUID LINE TEMP.
EXAMPLE:
A. Liquid Line Pressure = 417
B. Corresponding Temp. °F = 120°
C. Thermometer on Liquid line = 109°F.
To obtain the amount of subcooling, subtract 109°F from
120°F.
The di󰀨erence is 11° subcooling. See the specication
sheet or technical information manual for the design
subcooling range for your unit.
See R32 Pressure vs. Temperature chart.
Expansion Valve (TXV) System
Two Speed Application (APHH5)
Run the unit on high stage cooling for 15-20 minutes until
refrigerant pressures stabilize. Check charge with unit on
high stage.
Follow checking subcooling instructions.
NOTE: The TXV provided is designed to meet the
specication requirements for optimum product
operation. “NO ADJUSTMENTS NEEDED TO TXV”.
System Charging Heating Mode
The proper method of charging a heat pump in the heat
mode is by weighing the charge according to the total
charge listed on the rating plate.
Measure the hot gas discharge at the compressor to
ensure proper TXV setting. To ensure optimum system
performance in heat mode, the TXV may require
adjustment.
1. Allow the system to operate for at least 20 minutes.
2. Attach and insulate an electronic thermometer to
the hot gas discharge line mid-way between the
compressor and the reversing valve.
NOTE: The thermometer must be well insulated to
prevent ambient inuences.
3. Allow the compressor to operate for about 10
additional minutes and measure the hot gas
discharge temperature.
4. Using an additional electronic thermometer, measure
the ambient temperature.
NOTE: The TXV provided is designed to meet the
specication requirements for optimum product
operation. “NO ADJUSTMENTS NEEDED TO TXV”.
CAUTION
To prevent personal injury, carefully connect and
disconnect manifold gauge hoses. Escaping liquid
refrigerant can cause burns. Do not vent refrigerant to
atmosphere. Recover during system repair or final unit
disposal.
SUBCOOLING = SAT. LIQUID TEMP. - LIQUID LINE
TEMP.
Heat Pump - Heating Cycle
The proper method of charging a heat pump in the heat
mode is by weighing the charge according to the total
charge listed on the rating plate.
Fixed Orifice Restriction Devices
The xed orice restriction device (owrator) used in
conjunction with the indoor coil is a predetermined bore
(I.D.).
It is designed to control the rate of liquid refrigerant ow
into an evaporator coil.
The amount of refrigerant that ows through the xed
orice restriction device is regulated by the pressure
di󰀨erence between the high and low sides of the system.
background
SERVICING
30
In the cooling cycle when the outdoor air temperature rises,
the high side condensing pressure rises. At the same time,
the cooling load on the indoor coil increases, causing the
low side pressure to rise, but at a slower rate.
Since the high side pressure rises faster when the
temperature increases, more refrigerant ows to the
evaporator, increasing the cooling capacity of the system.
When the outdoor temperature falls, the reverse takes
place. The condensing pressure falls, and the cooling loads
on the indoor coil decreases, causing less refrigerant ow.
If a restriction should become evident, proceed as follows:
1. Recover refrigerant charge.
2. Remove the orice assembly and clean or replace.
3. Replace liquid line drier, evacuate and recharge.
Checking Equalization Time
During the “OFF” cycle, the high side pressure bleeds to
the low side through the xed orice restriction device.
Check equalization time as follows:
1. Attach a gauge manifold to the suction and liquid line
access ttings.
2. Start the system and allow the pressures to stabilize.
3. Stop the system and check the time it takes for the
high and low pressure gauge readings to equalize.
If it takes more than seven (7) minutes to equalize, the
restriction device is inoperative. Replace, install a liquid line
drier, evacuate and recharge.
Checking Restricted Liquid Line
When the system is operating, the liquid line is warm to the
touch. If the liquid line is restricted, a denite temperature
drop will be noticed at the point of restriction. In severe
cases, frost will form at the restriction and extend down the
line in the direction of the ow.
Discharge and suction pressures will be low, giving the
appearance of an undercharged unit. However, the unit will
have normal to high subcooling.
If a restriction is located, replace the restricted part, replace
drier, evacuate and recharge.
Refrigerant Overcharge
An overcharge of refrigerant is normally indicated by an
excessively high head pressure.
An evaporator coil, using an expansion valve metering
device, will basically modulate and control a ooded
evaporator and prevent liquid refrigerant return to the
compressor.
An evaporator coil, using a xed orice restrictor device
(owrator) metering device, could allow liquid refrigerant
to return to the compressor under extreme overcharge
conditions.
Also with a xed orice restrictor device (owrator)
metering device, extreme cases of insu󰀩cient indoor air
can cause icing of the indoor coil and liquid refrigerant
return to the compressor, but the head pressure would be
lower.
There are other causes for high head pressure. If other
causes check out normal, an overcharge or a system
containing non-condensables would be indicated.
If overcharging is indicated:
1. Start the system.
2. Remove and capture small quantities of refrigerant
as from the suction line access tting until the head
pressure is reduced to normal.
3. Observe the system while running a cooling
performance test. If a shortage of refrigerant
is indicated, then the system contains non-
condensables.
Non-Condensables
If non-condensables are suspected, shut down the system
and allow the pressures to equalize. Wait at least 15
minutes. Compare the pressure to the temperature of the
coldest coil since this is where most of the refrigerant will
be. If the pressure indicates a higher temperature than that
of the coil temperature, non-condensables are present.
Non-condensables are removed from the system by rst
removing the refrigerant charge, replacing and/or installing
liquid line drier, evacuating and recharging.
Compressor Burnout
When a compressor burns out, high temperature develops
causing the refrigerant, oil and motor insulation to
decompose forming acids and sludge.
If a compressor is suspected of being burned-out, attach
a refrigerant hose to the liquid line dill valve and properly
remove and dispose of the refrigerant.
background
SERVICING
31
NOTICE: Violation of EPA regulations may result in
nes or other penalties.
Now determine if a burn out has actually occurred. Conrm
by analyzing an oil sample using a Sporlan Acid Test Kit,
AK-3 or its equivalent.
Remove the compressor and obtain an oil sample from the
suction stub. If the oil is not acidic, either a burnout has not
occurred or the burnout is so mild that a complete clean-up
is not necessary.
If acid level is unacceptable, the system must be cleaned
by using the clean-up drier method.
CAUTION
Do not allow the sludge or oil to contact the skin. Severe
burns may result.
NOTE: Goodman does NOT approve the ushing
method using R-11 refrigerant.
background
SERVICING
32
background
SERVICING
33
LIQUID PRESSURE
AT SERVICE VALVE (PSIG) 8 10 12 14 16 18
189 58 56 54 52 50 48
195 60 58 56 54 52 50
202 62 60 58 56 54 52
208 64 62 60 58 56 54
215 66 64 62 60 58 56
222 68 66 64 62 60 58
229 70 68 66 64 62 60
236 72 70 68 66 64 62
243 74 72 70 68 66 64
251 76 74 72 70 68 66
259 78 76 74 72 70 68
266 80 78 76 74 72 70
274 82 80 78 76 74 72
283 84 82 80 78 76 74
291 86 84 82 80 78 76
299 88 86 84 82 80 78
308 90 88 86 84 82 80
317 92 90 88 86 84 82
326 94 92 90 88 86 84
335 96 94 92 90 88 86
345 98 96 94 92 90 88
354 100 98 96 94 92 90
364 102 100 98 96 94 92
374 104 102 100 98 96 94
384 106 104 102 100 98 96
395 108 106 104 102 100 98
406 110 108 106 104 102 100
416 112 110 108 106 104 102
427 114 112 110 108 106 104
439 116 114 112 110 108 106
450 118 116 114 112 110 108
462 120 118 116 114 112 110
474 122 120 118 116 114 112
486 124 122 120 118 116 114
499 126 124 122 120 118 116
511 128 126 124 122 120 118
REQUIRED SUBCOOLING TEMPERATURE (°F)
REQUIRED LIQUID LINE TEMPERATURE
background
SERVICING
34
Suction Line Drier Clean-Up Method
The POE oils used with R32 refrigerant is an excellent
solvent. In the case of a burnout, the POE oils will remove
any burnout residue left in the system. If not captured by
the refrigerant lter, they will collect in the compressor
or other system components, causing a failure of the
replacement compressor and/or spread contaminants
throughout the system, damaging additional components.
Install a suction line lter drier. This drier should be
installed as close to the compressor suction tting as
possible. The lter must be accessible and be rechecked
for a pressure drop after the system has operated for a
time. It may be necessary to use new tubing and form as
required.
NOTE: At least twelve (12) inches of the suction line
immediately out of the compressor stub must be
discarded due to burned residue and contaminates.
1. Remove the liquid line drier and expansion valve.
2. Purge all remaining components with dry nitrogen or
carbon dioxide until clean.
3. Install new components including liquid line drier.
4. Braze all joints, leak test, evacuate, and recharge
system.
5. Start up the unit and record the pressure drop across
the drier.
6. Continue to run the system for a minimum of twelve
(12) hours and recheck the pressure drop across the
drier. Pressure drop should not exceed 6 PSIG.
7. Continue to run the system for several days,
repeatedly checking pressure drop across the
suction line drier. If the pressure drop never exceeds
the 6 PSIG, the drier has trapped the contaminants.
Remove the suction line drier from the system.
8. If the pressure drop becomes greater, then it must be
replaced and steps 5 through 9 repeated until it does
not exceed 6 PSIG.
NOTICE: Regardless, the cause for burnout must be
determined and corrected before the new compressor
is started.
Reversing Valve Replacement
Remove the refrigerant charge from the system.
When brazing a reversing valve into the system, it is of
extreme importance that the temperature of the valve does
not exceed 250°F. at any time.
Wrap the reversing valve with a large rag saturated with
water. “Re-wet” the rag and thoroughly cool the valve after
each brazing operation of the four joints involved. The wet
rag around the reversing valve will eliminate conduction of
heat to the valve body when brazing the line connection.
The use of a wet rag sometimes can be a nuisance. There
are commercial grades of heat absorbing paste that may
be substituted.
After the valve has been installed, leak test, evacuate and
recharge.
Checking External Static Pressure
The minimum and maximum allowable duct static pressure
is found in the Technical Information Manual.
Too great of an external static pressure will result in
insu󰀩cient air that can cause icing of the coil, whereas too
much air can cause poor humidity control, and condensate
to be pulled o󰀨 the evaporator coil causing condensate
leakage. Too much air can cause motor overloading and in
many cases this constitutes a poorly designed system. To
determine proper air movement, proceed as follows:
1. Using a manometer measure the static pressure
of the return duct at the inlet of the unit (Negative
Pressure).
Mode
.
Total External Static
2. Measure the static pressure of the supply duct,
(Positive Pressure).
3. Add the two readings together.
NOTE: Both readings may be taken simultaneously and
read directly on the manometer if so desired.
4. Consult proper table for quantity of air.
If the external static pressure exceeds the minimum or
maximum allowable statics, check for closed dampers, dirty
lters, undersized or poorly laid out ductwork.
Adjusting Airflow
EEM Motor
The blower motor speed for the EEM motor is controlled by
three 24V low voltage leads: green, yellow, and white. The
green lead sets the speed for fan-only mode.
background
SERVICING
35
The yellow lead sets the speed for cooling and heat pump
heating mode (if applicable).
EEM Motor Speed Adjustment
The white lead sets the speed for electric heat mode
(emergency heat and second stage heat, if applicable).
The leads are factory connected as follows: Green to
T1,Yellow to T2, and White to T3. T1 is the low speed
setting and is dedicated to fan-only mode. T2 is medium
speed cooling and T3 is medium speed heating. T4 is high
speed cooling and T5 is high speed heating. To adjust the
blower speed, move the yellow and/or white wires to T4
and T5.
NOTE: If more than one lead is energized at the same
time, the motor will use the higher speed setting.
ECM Motor Speed Adjustment
Each ECM blower motor has been preprogrammed for
operation at 4 distinct air ow levels when operating in
Cooling/Heat Pump mode or Electric Heat mode. These 4
distinct levels may also be adjusted slightly lower or higher
if desired. The adjustment between levels and the trim
adjustments are made by changing the dip switch(s) either
to an “OFF” or “ON” position. See Blower Performance
Data tables in installation manual.
DIP Switch Functions
The ECM motor has an electronic control that contains
eight (8) 2-position dip switches. The function of these dip
switches is shown in Table below.
For APHH5[24-36]41 models, dip switch 4 must be set
to ON. Dip switch 4 must be set to OFF for the two-stage
compressor models APHH5[42-60]41. Dip switch 4 ON
energizes Y1 signal to the ECM motor anytime Y/Y2 is
energized. The indoor motor will not operate properly if
switch is not set correctly for the model.
Speed Tap Switch 1 Switch 2
A OFF OFF
B ON OFF
C OFF ON
D ON ON
Electric Heat
DIP Switch Settings
Thermostat Switch 3 Switch 4
Single-Stage N/A ON
Two-Stage N/A OFF
DIP Switch Settings for
Single & Two-Stage Thermostat
Speed Tap Switch 5 Switch 6
A OFF OFF
B ON OFF
C OFF ON
D ON ON
Cooling/HP DIP Switch Settings
CFM Switch 7 Switch 8
Plus 10% ON OFF
Normal OFF OFF
Minus 10% OFF ON
Speed Tap Adjustment
Through DIP Switches
background
SERVICING
36
The below table details the required minimum airow of the unit to ensure proper function of the refrigerant
detection system.
DO NOT set the system that would permit call for a lower airow than the below table identies for the associated
unit.
Model
[ft
3
/min]
(A/G)PHH32431 111
(A/G)PHH33031 129
(A/G)PHH33631 170
(A/G)PHH34231 182
(A/G)PHH34831 231
(A/G)PHH36031 241
(A/G)PHH52431 160
(A/G)PHH53031 162
(A/G)PHH53631 235
(A/G)PHH54231 198
(A/G)PHH54831 211
(A/G)PHH56031 229
Minimum Airflow
background
SERVICING
37
Refrigerant Detection System
DETECTION SYSTEMS shall only be replaced with
sensors specied by the manufacturer. If REFRIGERANT
SENSOR requires replacement, please replace with
Sensata R32 Sensor PN#RGD-00ML12 (Daikin
PN#SER2A08011).
Before servicing, identify the mode of operation of the
system by reading the LED ashing pattern on the PCB
within the control box and matching the LED ashing
pattern with mode of operation in the A2L PCB fault code
table on the wiring diagram which is attached on the back
side of the control box panel.
When replacing the A2L sensor, ensure that the arrows on
the A2L sensor and the sensor bracket are pointing in the
same direction.
warning; flammable materials
service indicator; read technical
manual
operator's manual; operating
instructions
warning; low burning velocity
material
UN GHS flame symbol
MODE
LED FLASHING PATTERN
NORMAL OPERATION
SLOW LED FLASHING PATTERN
(2 SECONDS ON 2 SECONDS OFF)
R-32 LEAK ALARM FAST LED FLASHING PATTERN
DELAY MODE LED WILL BE ON CONTINUOUSLY
SYSTEM
VERIFICATION MODE
FAST LED FLASHING PATTERN
CONTROL BOARD
INTERNAL FAULT
LED WILL FLASH 2 TIMES AND
THEN BE OFF FOR 5 SECONDS
R32 SENSOR
COMMUNICATION FAULT
LED WILL FLASH 3 TIMES AND
THEN BE OFF FOR 5 SECONDS
R32 SENSOR FAULT
LED WILL FLASH 4 TIMES AND
THEN BE OFF FOR 5 SECONDS
LED STATUS
background
SERVICING
38
SYMPTOM POSSIBLE CAUSE REMEDY
High head - low suction a. Restriction in liquid line or
TXV not functioning.
a. Remove or replace with proper size TXV.
High head - high or normal suction a. In Cooling: Dirty condenser coil In Heating:
Dirty lter, Dirty indoor coil
b. Overcharged
c. In Cooling: Condenser fan not running
d. In Heating: Indoor blower not running
a. Clean coil.
b. Correct System charge.
c. Repair or Replace.
Low head - high suction a. Incorrect TXV.
b. Defective compressor valves
c. TXV not functioning properly
d. Incorrect TXV setting
a. Replace with correct TXV.
b. Replace compressor.
c. Check for debris in TXV or deformed TXV. Remove
debris or replace TXV.
d. Check Super Heat
Unit will not run a. Power o󰀨 or loose electrical connection.
b. Thermostat out of calibration set too
high.
c. Defective contactor.
d. Blown fuses or tripped breaker.
e. Transformer defective.
f. High or low pressure control open
(Optional).
g. Compressor overload contacts open.
a. Check for unit voltage at contactor in unit.
b. Reset.
c. Check for 24 volts at contactor coil replace if contacts
are open.
d. Replace fuse or reset breaker.
e. Check wiring - replace transformer.
f. Check high pressure control or check unit charge
High pressure control opens at 610 PSIG. Low
pressure control opens at 22 PSIG.
g. Replace compressor
NOTE: Wait at least 2 hours for overload to
reset.
Condenser fan runs,
compressor doesn’t
a. Loose connection.
b. Compressor stuck, grounded or open winding
open internal overload.
c. Low voltage connection.
d. Capacitor weak, open, or shorted.
a. Check for unit voltage at compressor check & tighten
all connections.
b. Wait at least 2 hours for overload to reset If still open,
replace the compressor.
c. At compressor terminals, voltage must be within 10
% of nameplate volts when unit is operating
d. Check capacitor. If defective, replace.
Low suction - cool compressor
Iced evaporator coil
a. In Cooling: Low indoor airow
In Heating: Dirty outdoor coil, defective
defrost thermostat, defective defrost control
board, outdoor fan not running, low refrigerant
charge.
b. Low airow.
c. Low refrigerant charge.
d. Operating unit in cooling mode below 65°F
outdoor temperature.
a. Increase speed of blower or reduce restriction -
replace air lters.
b. Check - should be approximately 400 CFM per ton,
dirty air lters, all duct outlets open.
c. Properly charge unit.
d. Install or check low ambient control, should be open
below 65°F outdoor temperature.
Compressor short cycles a. Defective overload protector.
b. Unit cycling on low pressure control.
c. High pressure switch cuts out
a. Replace - check for correct voltage.
b. Check refrigerant charge and / or airow.
c. Check airow (indoor & outdoor), check expansion
device.
Registers sweat a. Low airow. a. Increase speed of blower or reduce restriction
replace air lters.
High suction pressure a. Excessive load.
b. Defective compressor.
c. Reversing valve not seating properly.
a. Recheck load calculation.
b. Replace.
c. Replace.
Insu󰀩cient cooling a. Improperly sized unit.
b. Improper airow.
c. Incorrect refrigerant charge.
d. Incorrect voltage.
a. Recalculate load.
b. Check - should be approximately 400 CFM per
ton.
c. Charge per procedure attached to unit service
panel.
d. At compressor terminals, voltage must be within 10%
of nameplate volts when unit is operating.
background
39
background
40
background
41
background
42
background
43
background
44
background
45
background
46
background
47
background
48
Decommissioning
Before carrying out this procedure, it is essential that the
technician is completely familiar with the equipment and
all its detail. It is recommended good practice that all
refrigerants are recovered safely. Prior to the task being
carried out, an oil and refrigerant sample shall be taken
in case analysis is required prior to re-use of recovered
refrigerant. It is essential that electrical power is available
before the task is commenced.
1. Become familiar with the equipment and its
operation.
2. Isolate the system electrically.
3. Before attempting the procedure, ensure that:
A. Mechanical handling equipment is available, if
required, for handling refrigerant cylinders;
B. All personal protective equipment is available
and being used correctly;
C. The recovery process is supervised at all times
by a competent person;
D. Recovery equipment and cylinders conform to
the appropriate standards.
4. Pump down refrigerant system, if possible.
5. If a vacuum is not possible, make a manifold so that
refrigerant can be removed from various parts of the
system.
6. Make sure that cylinder is situated on the scales
before recovery takes place.
7. Start the recovery machine and operate in
accordance with instructions.
8. Do not overll cylinders (no more than 80 % volume
liquid charge).
9. Do not exceed the maximum working pressure of the
cylinder, even temporarily.
10. When the cylinders have been lled correctly and the
process completed, make sure that the cylinders and
the equipment are removed from site promptly and
all isolation valves on the equipment are closed o󰀨.
11. Recovered refrigerant shall not be charged into
another REFRIGERATING SYSTEM unless it has
been cleaned and checked.
12. Upon completion of reclaiming the refrigerant.
Authorized personnel may proceed with the removal
of the unit.
Equipment shall be labeled stating that it has been de-
commissioned and emptied of refrigerant. The label
shall be dated and signed. For appliances containing
FLAMMABLE REFRIGERANTS, ensure that there are
labels on the equipment stating the equipment contains
FLAMMABLE REFRIGERANT".
TROUBLESHOOTING
background
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
49
HIGH VOLTAGE!
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
OR
INSTALLING
THIS
UNIT
.
M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
HERM
FAN
LEAK DETECTION SYSTEM INSTALLED. UNIT MUST BE POWERED EXCEPT FOR SERVICE. SEE USER MANUAL
FOR MORE DETAILS.
RED LED'S STATUS MODE CHECK
1 FLASH STARTUP MODE
-
SLOW LED FLASHING NORMAL OPERATION
-
FAST LED FLASHING
R-32 LEAK ALARM
LEAK DETECTED. FIND AND REPAIR THE
SOURCE OF THE LEAK.
LED ON CONTINUOUSLY DELAY MODE MODE WILL CLEAR AFTER 5 MINUTES.
FAST LED FLASHING
SYSTEM VERIFICATION
MODE
USER ACTIVATED TEST MODE.
2 FLASHES INTERNAL FAULT
REPLACE CONTROL BOARD.
3 FLASHES
R-32 SENSOR
COMMUNICATION FAULT
VERIFY REFRIGERANT SENSOR WIRING.
REPLACE SENSOR. REPLACE CONTROL
BOARD.
4 FLASHES R-32 SENSOR FAULT REPLACE SENSOR.
0140G20037-A
NOTES
:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105°C).
USE COPPER CONDUCTORS ONLY. USE NEC CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.
2. TO CHANGE BLOWER MOTOR SPEED MOVE YELLOW AND GRAY LEADS FROM BM "2" AND "3" TO "4" AND "5".
IF BOTH LEADS ARE ENERGIZED, THE HIGHER SPEED SETTING IS USED.
3. FOR INSTALLATION USING 208V SUPPLY POWER MOVE PRIMARY CONNECTIONS FROM 240V TAP
TO THE 208V TAP.
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED.
5. USE COPPER CONDUCTORS ONLY USE N.E.C. CLASS 2 WIRE.
6. CRANKCASE HEATER FACTORY EQUIPPED WHEN REQUIRED OR OPTIONAL.
7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR COULD BE FACTORY EQUIPPED
AS AN ALTERNATE CONFIGURATION.
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION
BLACK
BLUE
BROWN
GREEN
GRAY
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
YELLOW/
PINK STRIPE
BLUE/PINK STRIPE
WIRE CODE
BK
BL
BR
GR
GY
OR
PK
PU
RD
WH
YL
YL/PK
BL/PK
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
OPTIONAL LOW VOLTAGE
CHASSIS GROUND
FIEL
D WIRING
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
EARTH GROUND
BM
CAP
CC
CH
CHS
CM
COMP
CS
DFT
ECON
EHK
GND
HPS
LPS
LVJB
OWV
PLF
PLM
RDS
RVC
SA
TR
BLOWER MOTOR
CAPACITOR
COMPRESSOR CONTACTOR
CRACKCASE HEATER
CRACKCASE HEATER SWITCH
CONDENSER MOTOR
COMPRESSOR
COMP SOLENOID (2ND STG COOLING)
DEFROST THERMOSTAT
ECONOMIZER
ELECTRIC HEATER KIT
EQUIPMENT GROUND
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
LOW VOLTAGE JUNCTION BOX
ONE WAY VALVE
FEMALE PLUG / CONNECTOR
MALE PLUG / CONNECTOR
REF
RIGERANT DETECTION SYSTEM
REVERSING VALVE COIL
START ASSIST
TRANSFORMER
COM
PONENT LEG
END
240V
CONTROL BOX
RD
BL
GR
WH
BR
R
C
W2
W1
G
SEE NOTE 3
LVJB
COMP
S C R
THERMOSTAT
SEE NOTE 1
SEE NOTE 7
RD
BK
PU
BK
YL
BL
YL RDBK
CM
BR BKPU
LINE
VOLTAGE
208V/230V/1PH/60Hz
SA
SEE NOTE 4
RD
GY
C
L G N
1
2
3
BM
4 5
SEE NOTE 2
GR
GR
BL
BL
BR
WH
BR
WH
YL
GR
YL
TR
BL
GR
COM
C
O
M
CAP
RD
YL
BR
PU
YL
RD
BL
PK
RDS
PLM1
RDS
EEV/10V_IN
EEV/10V_OUT
CTM/OD_OUT
R_ID_OUT
COM
COM
24VAC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
NOT USED
1 C
5V 2
PORT1
R32
SENSOR
ALARM
WH
GY
GY
CC
T1
T2
L1
L2
PU
PU
BK
BK
RD
GY
BL BK
PU
O-RV
R-PS1
R-DFT
PS2
R
O
C-RV
C
C
DFT
DF1
DF2
PCB
W
CNT
Y
DEFROST CONTRO L
PUPUYLYLBK
BK
PU
PU
BK
BK
RD
RD
YL
YL
OR
O
SEE NOTE 5
OR
YL
Y
YL
WH
BL
RD
RD
RD
PU
BR BKPU
BR BK
PU
DFT
BL/PKBL/PK
HPS
RD
LPS
YL/PK
YL/PK
RVC
RD
BK
BK
PU
PURDYL
YL
RDBK
BK
GR
A1A2
YL
GY
GY
BL
GR
RD
RD
BL
BR
WH
WH
WH
BL
PK
PU
PU
BK
CHS
RD
CH
GR
RD
BK
BK
PU
SEE NOTE 6
WH
WH
BL
RD
BK
RD
EHK
PLF
EHK
PLM
5
4
3
2
1
5
4
3
2
1
6
6
8
7
8
7
9
9
BK PU
PUBKBL
GND
GRBK GR
*PHH3**31, GPHH5(24-30)31
background
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
50
HIGH VOLTAGE!
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
OR
INSTALLING
THIS
UNIT
.
M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
LEAK DETECTION SYSTEM INSTALLED. UNIT MUST BE POWERED EXCEPT FOR SERVICE. SEE USER MANUAL
FOR MORE DETAILS.
RED LED'S STATUS MODE CHECK
1 FLASH STARTUP MODE
-
SLOW LED FLASHING NORMAL OPERATION
-
FAST LED FLASHING
R-32 LEAK ALARM
LEAK DETECTED. FIND AND REPAIR THE
SOURCE OF THE LEAK.
LED ON CONTINUOUSLY DELAY MODE MODE WILL CLEAR AFTER 5 MINUTES.
FAST LED FLASHING
SYSTEM VERIFICATION
MODE
USER ACTIVATED TEST MODE.
2 FLASHES INTERNAL FAULT
REPLACE CONTROL BOARD.
3 FLASHES
R-32 SENSOR
COMMUNICATION FAULT
VERIFY REFRIGERANT SENSOR WIRING.
REPLACE SENSOR. REPLACE CONTROL
BOARD.
4 FLASHES R-32 SENSOR FAULT REPLACE SENSOR.
0140G20040-A
NOTES
:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105°C).
USE COPPER CONDUCTORS ONLY. USE NEC CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.
2. TO CHANGE BLOWER MOTOR SPEED MOVE YELLOW AND GRAY LEADS FROM BM "2" AND "3" TO "4" AND "5".
IF BOTH LEADS ARE ENERGIZED, THE HIGHER SPEED SETTING IS USED.
3. FOR INSTALLATION USING 208V SUPPLY POWER MOVE PRIMARY CONNECTIONS FROM 240V TAP
TO THE 208V TAP.
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED.
5. USE COPPER CONDUCTORS ONLY USE N.E.C. CLASS 2 WIRE.
6. CRANKCASE HEATER (OPTIONAL).
7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR COULD BE FACTORY EQUIPPED
AS AN ALTERNATE CONFIGURATION.
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION
240V
CONTROL BOX
RD
BL
GR
WH
BR
R
C
W2
W1
G
SEE NOTE 3
LVJB
COMP
S C R
THERMOSTAT
SEE NOTE 1
SEE NOTE 7
RD
BK
BK PU
PU
BK
YL RDBK
CM
BR BKPU
GND
LINE
VOLTAGE
208V/230V/1PH/60Hz
SA
SEE NOTE 4
RD
BL
BLWHBR
YL
GRGY
C L G N
1 2
3
BM
4
5
SEE NOTE 2
GR
BL PU
BK
GR
BL
BL
BR
WH
BR
WH YL GR
YL
GY
GY
TR
BL
BL GR
COM
FAN
HERM
C
O
M
CAP
RD
YL
BR
YL
RD
BL
PK
RD
WH
GY
GY
CC
T1
T2
L1
L2
BK
PU
PU
BK
BK
RD
BL BK PU
O-RV
R-PS1
R-DFT
PS2
R
O
C-RV
C
C
DFT
DF1
DF2
PCB
W
CNT
Y
DEFROST CONTROL
PU PURDRDYLYLBKBK
PU
BK
BK
RD
RD
YL
YL
OR
O
SEE NOTE 5
OR
PU
Y1
WH
PU
WH
BL
RD
RD
RD
PU
Y2
YL
CSR
1
3
BL
PU
SOL
BL
YL
BL
DFT
BL/PKBL/PK
HPS
RD
LPS
YL/PK
YL/PK
RVC
RD
BK
BK
PU
PURD
YL
YL RDBKBK
GR
A1A2
BR BKPU
BR BKPU
WH
BL
BL
YL
WH
WH
WHWH
BLPK
2
CSR
4
PUYL
YL
BL
BL
PU
OR
BK
BK
YL
YL
RD
RD
WH
PU
WH
BK
BK
PU
PU
BK
YLBLBR BKPU
PU
GR
CHS
RD
CH
RD
BK BKBK
PU
GR
PU
BK
BK PU
BK PU YL RDBK YLBL
CH & CHS OPTIONAL
@ L1,L2, SEE NOTE 6
RD
RD
BM BLOWER MOTOR
CAP CAPACITOR
CC COMPRESSOR CONTACTOR
CH CRANKCASE HEATER
CHS CRANKCASE HEATER SWITCH
CM CONDENSER MOTOR
COMP COMPRESSOR
CSR COMPRESSOR SOLENOID RELAY
DFT DEFROST THERMOSTAT
ECON ECONOMIZER
EHK ELECTRIC HEATER KIT
GND EQUIPMENT GROUND
HPS HIGH PRESSURE SWITCH
LPS LOW PRESSURE SWITCH
LVJB LOW VOLTAGE JUNCTION BOX
LVTB LOW VOLTAGE TERMINAL BLOCK
PLF FEMALE PLUG/CONNECTOR
PLM MALE PLUG/CONNECTOR
RDS REFRIGERANT DETECTION SYSTEM
RVC REVERSI
NG VALVE COIL
SA START ASSIST
SOL SOLENOID
TR TRANSFORMER
COMPONENT LEGEND
BLACK
BLUE
BROWN
GREEN
GRAY
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
YELLOW/PINK STRIPE
BLUE/PINK STRIPE
WIRE COD
E
BK
BL
BR
GR
GY
OR
PK
PU
RD
WH
YL
YL/PK
BL/PK
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
OPTIONAL LOW VOLTAGE
CHASSIS GROUND
FIEL
D WIRING
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
EARTH GROUND
EHK
PLF
EHK
PLM
5
4
3
2
1
5
4
3
2
1
6
6
8
7
8
7
9
9
RDS
PLM1
RDS
EEV/10V_IN
EEV/10V_OUT
CTM/OD_OUT
R_ID_OUT
COM
COM
24VAC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
NOT USED
1 C
5V 2
PORT1
R32
SENSOR
ALARM
GPHH5(36-60)31
background
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
51
HIGH VOLTAGE!
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
OR
INSTALLING
THIS
UNIT
.
M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
VSTBR
LEAK DETECTION SYSTEM INSTALLED. UNIT MUST BE POWERED EXCEPT FOR SERVICE. SEE USER MANUAL
FOR MORE DETAILS.
RED LED'S STATUS MODE CHECK
1 FLASH STARTUP MODE
-
SLOW LED FLASHING NORMAL OPERATION
-
FAST LED FLASHING
R-32 LEAK ALARM
LEAK DETECTED. FIND AND REPAIR THE
SOURCE OF THE LEAK.
LED ON CONTINUOUSLY DELAY MODE MODE WILL CLEAR AFTER 5 MINUTES.
FAST LED FLASHING
SYSTEM VERIFICATION
MODE
USER ACTIVATED TEST MODE.
2 FLASHES INTERNAL FAULT
REPLACE CONTROL BOARD.
3 FLASHES
R-32 SENSOR
COMMUNICATION FAULT
VERIFY REFRIGERANT SENSOR WIRING.
REPLACE SENSOR. REPLACE CONTROL
BOARD.
4 FLASHES R-32 SENSOR FAULT REPLACE SENSOR.
0140G20038-A
NOTES
:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105°C).
USE COPPER CONDUCTORS ONLY. USE NEC CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.
2. REFER TO IO FOR FAN SPEED SETTINGS.
3. FOR INSTALLATION USING 208V SUPPLY POWER MOVE PRIMARY CONNECTIONS FROM 240V TAP
TO THE 208V TAP.
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED.
5. USE COPPER CONDUCTORS ONLY USE N.E.C. CLASS 2 WIRE.
6. CRANKCAS
E HEATER FACTORY EQUIPPED WHEN REQUIRED OR OPTIONAL.
7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR COULD BE FACTORY EQUIPPED
AS AN ALTERNATE CONFIGURATION.
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION
BLACK
BLUE
BROWN
GREEN
GRAY
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
YELLOW/PINK STRIPE
BLUE/PINK STRIPE
TAN
WIRE CODE
BK
BL
BR
GR
GY
OR
PK
PU
RD
WH
YL
YL/PK
BL/PK
TN
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
OPTIONAL LOW VOLTAGE
CHASSIS GROUND
FIEL
D WIRING
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
EARTH GROUND
BM BLOWER MOTOR
CAP CAPACITOR
CC COMPRESSOR CONTACTOR
CH CRANKCASE HEATER
CHS CRANKCASE HEATER SWITCH
CM CONDENSER MOTOR
COMP COMPRESSOR
CSR COMPRESSOR SOLENOID RELAY
DFT DEFROST THERMOSTAT
ECON ECONOMIZER
EHK ELECTRIC HEATER KIT
GND EQUIPMENT GROUND
HPS HIGH PRESSURE SWITCH
LPS LOW PRESSURE SWITCH
LVJB LOW VOLTAGE JUNCTION BOX
LVTB LOW VOLTAGE TERMINAL BLOCK
PLF FEMALE PLUG/CONNECTOR
PLM MALE PLUG/CONNECTOR
RDS REFRIGERANT DE
TECTION SYSTEM
RVC REVERSING VALVE COIL
SA START ASSIST
SOL SOLENOID
TR TRANSFORMER
VSTB VARIABLE SPEED TERMINAL BOARD
VSTBR VARIABLE SPEED TERMINAL BOARD RELAY
COM
PONENT LEGEND
CONTROL BOX
RD
BL
GR
WH
BR
R
C
W2
W1
G
LVJB
COMP
S C R
THERMOSTAT
YL RDBK
CM
BR BKPU
SA
SEE NOTE 4
RD
BM
BL
BL
BR
WH
BRWH
FAN
HERM
C
O
M
CAP
RD
YL
BR
PU
YL
RD
BL
PK
RD
YL
TN
TN
O-RV
R-PS1
R-DFT
PS2
R
O
C-RV
C
C
DFT
DF1
DF2
PCB
W
CNT
Y
DEFROST CONTROL
PU
PU
BK
BK
RD
RD
YL
YL
OR
O
SEE NOTE 5
OR
YL
Y1
PU
WH
BL
RD
RD
RD
PU
BR BKPU
BR BKPU
BL
VSTB
SWITCH
8 7 6 5 4 3 2 1
W1
OT1
OT2
HUM
PJ6
PJ2
PJ4
W2
C
R
9
HEATER
W1 W 2 C R
24 VAC
C
R
8
C
R
7
C
R
6
J3
C
R5
C
2
4
1
J2
CR
2
DS1
CR
1
R5
OFF
ON
DIP
E
F
1
3
A
M
P
C
R1
0
R
3
PN. PCB00102
(CFM)
CONFIGURATION.
DIP SWITCH
FOR PROPER
TO MANUAL
PLEASE REFER
R
1
R
2
MOC O 2W DER NOCY
HEATPUMP
CONDENSER
OUTDOOR
THERMOSTATS
HUMIDISTAT
HUM2TO C R 1Y G 2Y/YOT12W/W O CTOE\W1
J1
1
Y1
5
240V
SEE NOTE 3
SEE NOTE 1
SEE NOTE 7
RD
BK
PU
BK
LINE
VOLTAGE
208V/230V/1PH/60Hz
TR
BL
GR
PK
COM
CC
T1
T2
L1
L2
BK
PU
PU
BK
BK
RD
PU
BK
WH
BR
OR
TN
GR
GY
BR
RD OR
GY
HUM
VSTBR
1
3
RD
RD
BL
BK
2
4
BK
PU
BL
PK
GRGR
A1
A2
BL
BL
BR
BL
WH
GND
EHK
PLF
EHK
PLM
5
4
3
2
1
5
4
3
2
1
6
6
8
7
8
7
9
9
RDS
PLM1
RDS
EEV/10V_IN
EEV/10V_OUT
CTM/OD_OUT
R_ID_OUT
COM
COM
24VAC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
NOT USED
1
C
5V 2
PORT1
R32
SENSOR
ALARM
GR
CHS
RD
CH
GR
RD
BK
BK
PU
SEE NOTE 6
PU BK GR
WH W H
PU PURDRDYLYLBKBK
DFT
BL/PKBL/PK
HPS
RD
LPS
YL/PKYL/PK
RVC
RDBKBK
PU PURDYLYL RDBKBK
L2 GL1
PU BK GR GR
PU BK
PU
BK
BL
BL
BL
PU
APHH5(24-30)31
background
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
52
HIGH VOLTAGE!
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
OR
INSTALLING
THIS
UNIT
.
M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
VSTBR
BL
LEAK DETECTION SYSTEM INSTALLED. UNIT MUST BE POWERED EXCEPT FOR SERVICE. SEE USER MANUAL
FOR MORE DETAILS.
RED LED'S STATUS MODE CHECK
1 FLASH STARTUP MODE
-
SLOW LED FLASHING NORMAL OPERATION
-
FAST LED FLASHING
R-32 LEAK ALARM
LEAK DETECTED. FIND AND REPAIR THE
SOURCE OF THE LEAK.
LED ON CONTINUOUSLY DELAY MODE MODE WILL CLEAR AFTER 5 MINUTES.
FAST LED FLASHING
SYSTEM VERIFICATION
MODE
USER ACTIVATED TEST MODE.
2 FLASHES INTERNAL FAULT
REPLACE CONTROL BOARD.
3 FLASHES
R-32 SENSOR
COMMUNICATION FAULT
VERIFY REFRIGERANT SENSOR WIRING.
REPLACE SENSOR. REPLACE CONTROL
BOARD.
4 FLASHES R-32 SENSOR FAULT REPLACE SENSOR.
0140G20039-A
NOTES
:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105°C).
USE COPPER CONDUCTORS ONLY. USE NEC CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.
2. REFER TO IO FOR FAN SPEED SETTINGS.
3. FOR INSTALLATION USING 208V SUPPLY POWER MOVE PRIMARY CONNECTIONS FROM 240V TAP
TO THE 208V TAP.
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED.
5. USE COPPER CONDUCTORS ONLY USE N.E.C. CLASS 2 WIRE.
6. CRANK
CASE HEATER FACTORY EQUIPPED WHEN REQUIRED OR OPTIONAL.
7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR COULD BE FACTORY EQUIPPED
AS AN ALTERNATE CONFIGURATION.
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION
BLACK
BLUE
BROWN
GREEN
GRAY
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
YELLOW/PINK STRIPE
BLUE/PINK STRIPE
TAN
WIRE CODE
BK
BL
BR
GR
GY
OR
PK
PU
RD
WH
YL
YL/PK
BL/PK
TN
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
OPTIONAL LOW VOLTAGE
CHASSIS GROUND
FIEL
D WIRING
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
EARTH GROUND
CONTROL BOX
R
C
W2
W1
G
LVJB
COMP
S C R
THERMOSTAT
YL RD
BK
CM
BR
BKPU
SA
SEE NOTE 4
L2
GL1
BM
BL
BL
BR
WH
BRWH
FAN
HERM
C
O
M
CAP
RD
YL
BR
PU
YL
RD
BL
PK
RD
YL
TN
TN
PUBK
EHK
PLF
EHK
PLM
PU
O
SEE NOTE 5
Y1
RD
BR BKPU
BR
BKPU
Y2
BL
SOL
VSTB
SWITCH
8 7 6 5 4 3 2 1
W1
OT1
OT2
HUM
PJ6
PJ2
PJ4
W2
CR
9
HEATER
W1 W2 C R
24 VAC
CR
8
CR
7
CR
6
J3
C
R5
C2
4
1
J2
C
R2
DS1
C
R
1
R5
OFF
ON
DIP
E
F
1
3
A
M
P
C
R1
0
R
3
PN. PCB00102
(CFM)
CONFIGURATION.
DIP SWITCH
FOR PROPER
TO MANUAL
PLEASE REFER
R
1
R
2
MOC O 2W DER NOCY
HEATPUMP
CONDENSER
OUTDOOR
THERMOSTATS
HUMIDISTAT
HUM2TO C R 1Y G 2Y/YOT12W/W O CTOE\ W1
J1
1
Y1
5
GR
240V
SEE NOTE 3
SEE NOTE 1
SEE NOTE 7
RD
BK
PU
BK
LINE
VOLTAGE
208V/230V/1PH/60Hz
TR
BL GRPK
COM
CC
T1
T2
L1
L2
BK
PU
PU
BK
BK
RD
PU
BK
2
CSR
4
PUYL
WH
BR
OR
PU
GR
GY
TN
BR
RD
OR
WH
HUM
BL
YL
VSTBR
1
3
RD
RD
BL
BK
2
4
BKPU
CSR
1
3
BL
YL
CHS
RD
CH
GR
RD
BK
BK
PU
BL
PK
YL
GRGR
A1A2
BL
BL
PU
GR
BR
BL
WH
GR
SEE NOTE 6
BM BLOWER MOTOR
CAP CAPACITOR
CC COMPRESSOR CONTACTOR
CH CRANKCASE HEATER
CHS CRANKCASE HEATER SWITCH
CM CONDENSER MOTOR
COMP COMPRESSOR
CSR COMPRESSOR SOLENOID RELAY
DFT DEFROST THERMOSTAT
ECON ECONOMIZER
EHK ELECTRIC HEATER KIT
GND EQUIPMENT GROUND
HPS HIGH PRESSURE SWITCH
LPS LOW PRESSURE SWITCH
LVJB LOW VOLTAGE JUNCTION BOX
LVTB LOW VOLTAGE TERMINAL BLOCK
PLF FEMALE PLUG/CONNECTOR
PLM MALE PLUG/CONNECTOR
RDS REFRIGERANT DETECTION SYSTEM
RVC REVERSING VAL
VE COIL
SA START ASSIST
SOL SOLENOID
TR TRANSFORMER
VSTB VARIABLE SPEED TERMINAL BOARD
VSTBR VARIABLE SPEED TERMINAL BOARD RELAY
CO
M
PONENT LEGEND
WH WH
RDS
PLM1
RDS
EEV/10V_IN
EEV/10V_OUT
CTM/OD_OUT
R_ID_OUT
COM
COM
24VAC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
NOT USED
1 C
5V 2
PORT1
R32
SENSOR
ALARM
PK
PK BL
BL
BL PU PU
BKPU
TN
PK
WH
BR
BL
PU
YL
RD
RD
BL
GR
WH
BR
OR
PU
YL
GY
PU
BK
BK
RD
RD
YL
YL
OR
PU
WH
BL
RD
RD
PU
PU
PU
RD
RDYL
YL
BKBK
DFT
BL/PK
BL/PK
HPS
RD
LPS
YL/PKYL/PK
RVC
RD
BK
BK
PU
PURD
YL
YL
RDBKBK
BK
BK
YL
YL
RD
RD
PU
BK
PU BK GR
5
4
3
2
1
5
4
3
2
1
6
6
8
7
8
7
9
9
PU
WH
PU
GND
O-RV
R-PS1
R-DFT
PS2
R
O
C-RV
C
C
DFT
DF1
DF2
PCB
W
CNT
Y
DEFROST CONTROL
APHH5(36-60)31
background
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
53
HIGH VOLTAGE!
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
OR
INSTALLING
THIS
UNIT
.
M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
0140G20034-A
REFRIGERANT DETECTION SYSTEM
TROUBLESHOOTING GUIDE
RED STATUS
LIGHT
EQUIPMENT
STATUS
CHECK
1 FLASH STARTUP MODE -
HEARTBEAT
FLASH
NORMAL
OPERATION
-
2 FLASHES ALARM MODE
LEAK DETECTED. FIND AND
REPAIR THE SOURCE OF THE
LEAK.
2 FLASHES
SYSTEM
VERIFICATION
MODE
-
ON EOL TEST MODE
REMOVE 24VAC FROM THE EOL
TERMINAL.
3 FLASHES INTERNAL FAULT
REPLACE CONTROL BOARD
4 FLASHES
SENSOR
COMMUNICATION
FAULT
VERIFY REFRIGERANT SENSOR
WIRING. REPLACE SENSOR.
REPLACE CONTROL BOARD.
5 FLASHES SENSOR FAULT REPLACE SENSOR
3S ON; 1S OFF
MITIGATION DELAY
TIME
MODE WILL CLEAR AFTER 5
MINUTES.
BK
GR
RD
N
G
L
C
4
3
2
1
5
BL
Y
W1 CW2
NOT
ES
REPLACEMENT WIRE MUST BE SAME SIZE
AND TYPE OF INSULATION AS ORIGINAL (AT
LEAST 105° C). USE COPPER CONDUCTORS
ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL
LOW VOLTAGE FIELD CONNECTIONS.
TO CHANGE BLOWER MOTOR SPEED MOVE
YELLOW AND GRAY LEADS FROM BM "2" AND
"3" TO "4" AND "5". IF BOTH LEADS ARE
ENERGIZED, THE HIGHER SPEED SETTING IS
USED. SEE INSTALLATION MANUAL FOR
INSTRUCTIONS.
TR PRIMARY (HIGH VOLTAGE) CONNECTIONS:
RED WIRE CONNECTED TO 240V T
AP AT THE
FACTORY AND BLACK WIRE TO COM
TERMINAL. FOR 208V SUPPLY POWER, MOVE
RED WIRE FROM 240V TAP TO THE 208V TAP.
DOUBLE POLE CONTACTOR SHOWN. SINGLE
POLE CONTACTOR COULD BE FACTORY
EQUIPPED AS AN ALTERNATE
CONFIGURATION.
WIR
E
CO
D
E
BK
BLACK
BL
BLUE
BL/PK
BLUE WITH PINK STRIPE
BR BROWN
GR GREEN
GY
GRAY
OR
ORANGE
PK PINK
PU
PURPLE
RD RED
TN
TAN
WH
WHITE
YL YELLOW
YL/PK
YELLOW WITH PINK STRIPE
CO
MPO
N
E
NT LEGEN
D
BC
BLOWER CONTACTOR
BM
BLOWER MOTOR
CAP CAPACITOR
CC
COMPRESSOR CONTACTOR
CM
CONDENSER MOTOR
COMP COMPRESSOR
ECON
ECONOMIZER
EHK
ELECTRIC HEATER KIT
GND
EQUIPMENT GROUND
HPS
HIGH PRESSURE SW ITCH
LVJB
LOW VOLTAGE JUNCTION BOX
PLF FEMALE PLUG/CONNECTOR
PLM
MALE PLUG/CONNECTOR
RDS REFRIGERANT DETECTION SYSTEM
TR
TRANSFORMER
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
OPTIONAL LOW VOLTAGE
CHASSIS GROUND
F
I
E
L
D WI
R
ING
FA
CTORY WI
R
ING
HIGH VOLTAGE
LOW VOLTAGE
EARTH GROUND
R
YL
G
COMP
BK
C
R
S
CM
BR
CAP
RD
YL
BR
BK
PU
COM
PU
BK
BK
GR
M
1~
M
1~
HERM
FAN
BM
GR
PLM2
BM
M
1~
PLM1
BM
LINE
VOLTAGE
208-230V/1PH/60Hz
LVJB
BL
BR
WH
BK
TR
GR
WH
GY
GY
RD
BL
PK
GR
RD
THERMOSTAT
HPS
BL/PK
BL
WH
BR
YLRD
GR
BL
PK
GR
YL
GY
YL PK
BL GYWHRD
BL/PK
WH
BL
PK
RD
PU
BL/PK
BK RD
COM
1
2
3
4
5
6
7
8
9
GND
L1
CC
L2
T2
T1
1
C
RDS
PLM1
RDS
EEV_IN
EEV_OUT
CTM_OUT
R_OUT
C
C
R
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
5V 2
PORT
SENSOR
NOT USED
ALARM
1
2
3
4
5
6
7
8
9
2
3
4
EHK
PLF
PLM
2
3
4
1
BL
CC
A1 A2
YL
BL
BL
BL
GR
*PCH3(24-48)31
background
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
54
HIGH VOLTAGE!
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
OR
INSTALLING
THIS
UNIT
.
M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
*PCH36031
0140G20035-A
REFRIGERANT DETECTION SYSTEM
TROUBLESHOOTING GUIDE
RED STATUS
LIGHT
EQUIPMENT
STATUS
CHECK
1 FLASH
STARTUP MODE -
HEARTBEAT
FLASH
NORMAL
OPERATION
-
2 FLASHES
ALARM MODE
LEAK DETECTED. FIND AND
REPAIR THE SOURCE OF THE
LEAK.
2 FLASHES
SYSTEM
VERIFICATION
MODE
-
ON
EOL TEST MODE
REMOVE 24VAC FROM THE EOL
TERMINAL.
3 FLASHES INTERNAL FAULT REPLACE CONTROL BOARD
4 FLASHES
SENSOR
COMMUNICATION
FAULT
VERIFY REFRIGERANT SENSOR
WIRING. REPLACE SENSOR.
REPLACE CONTROL BOARD.
5 FLASHES SENSOR FAULT REPLACE SENSOR
3S ON; 1S OFF
MITIGATION DELAY
TIME
MODE WILL CLEAR AFTER 5
MINUTES.
BK
GR
RD
N
G
L
C
4
3
2
1
5
BL
Y1
W1
C
W2
N
OTE
S
REPLACEMENT WIRE MUST BE SAME SIZE
AND TYPE OF INSULATION AS ORIGINAL (AT
LEAST 105° C). USE COPPER CONDUCTORS
ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL
LOW VOLTAGE FIELD CONNECTIONS.
TO CHANGE BLOWER MOTOR SPEED MOVE
YELLOW AND GRAY LEADS FROM BM "2" AND
"3" TO "4" AND "5". IF BOTH LEADS ARE
ENERGIZED, THE HIGHER SPEED SETTING IS
USED. SEE INSTALLATION MANUAL FOR
INSTRUCTIONS.
TR PRIMARY (HIGH VOLTAGE) CONNECTIONS:
RED WIRE CONNECTED TO 240V TAP AT
THE
FACTORY AND BLACK WIRE TO COM
TERMINAL. FOR 208V SUPPLY POWER, MOVE
RED WIRE FROM 240V TAP TO THE 208V TAP.
DOUBLE POLE CONTACTOR SHOWN. SINGLE
POLE CONTACTOR COULD BE FACTORY
EQUIPPED AS AN ALTERNATE
CONFIGURATION.
WI
RE
C
OD
E
BK BLACK
BL
BLUE
BL/PK
BLUE WITH PINK STRIPE
BR BROWN
GR
GREEN
GY GRAY
OR
ORANGE
PK PINK
PU PURPLE
RD
RED
TN
TAN
WH
WHITE
YL YELLOW
YL/PK YELLOW WITH PINK STRIPE
C
OM
PON
ENT
L
EG
END
BC BLOWER CONTACTOR
BM
BLOWER MOTOR
CAP CAPACITOR
CC COMPRESSOR CONTACTOR
CM CONDENSER MOTOR
COMP COMPRESSOR
CS COMPRESSOR SOLENOID
CSR COMPRESSOR SOLENOID RELAY
ECON ECONOMIZER
EHK ELECTRIC HEATER KIT
GND EQUIPMENT GROUND
HPS HIGH PRESSURE SWITCH
LVJB LOW VOLTAGE JUNCTION BOX
PLF FEMALE PLUG/CONNECTOR
PLM
MALE PLUG/CONNECTOR
RDS REFRIGERANT DETECTION SYSTEM
TR TRANSFORMER
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
OPTIONAL LOW VOLTAGE
CHASSIS GROUND
FI
E
L
D W
I
R
ING
FA
CTO
R
Y WI
R
ING
HIGH VOLTAGE
LOW VOLTAGE
EARTH GROUND
R
PU
G
COMP
BK
C
R
S
CM
BR
CAP
RD
YL
BR
BK
PU
COM
PU
BK
BK
GR
M
1~
M
1~
HERM
FAN
BM
GR
PLM2
BM
M
1~
PLM2
BM
LINE
VOLTAGE
208-230V/1PH/60Hz
LVJB
BL
BR
WH
BK
TR
GR
WH
GY
GY
RD
BL
PK
GR
RD
THERMOSTAT
HPS
BL/PK
BL
WH
BR PU
RD GR
BL
PK
GR
YL
GY
PK BL GYWHRD
BL/PK
WH
BL
PK
RD
PU
BL/PK
BK
RD
COM
1
2
3
4
5
6
7
8
9
GND
L1
CC
L2
T2
T1
1
C
RDS
PLM1
RDS
EEV_IN
EEV_OUT
CTM_OUT
R_OUT
C
C
R
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
5V 2
PORT
SENSOR
NOT USED
ALARM
1
2
3
4
5
6
7
8
9
2
3
4
EHK
PLF
PLM
2
3
4
1
BL
CC
A1 A2
PU BL
BL
GR
Y2
YL
YL
BL
CSR
1 3
YL
BL
4
CSR
2
YL
CS
V1 V2
YL BL
YL
YL PU
background
55
CUSTOMER FEEDBACK
We are very interested in all product comments.
Please ll out the feedback form on one of the following links:
Goodman
®
Brand Products: (http://www.goodmanmfg.com/about/contact-us).
Amana
®
Brand Products: (http://www.amana-hac.com/about-us/contact-us).
You can also scan the QR code on the right for the product brand
you purchased to be directed to the feedback page.
GOODMAN
®
BRAND
AMANA
®
BRAND
© 2025 Daikin Comfort Technologies Manufacturing, Inc.
Brand
®
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.

Specifications

Goodman GPCH36031 Questions and Answers

Questions and Answers

Related Products