Patents Pending
For questions on this device
please call 1-800-241-4453.
http://www.usa.siemens.com/powerdistribution
12
Wire range per NEC wire-bending requirements
Siemens Industry, Inc.
Norcross, GA 30092 U.S.A.
Assembled in Mexico
HP Ratings
Terminal & Wire Information
Accessories
Description Lug Size Wire Range
12
Wire Tightening Torque
Line / Load Lugs 14 – 2 AWG 14 – 8 AWG 35 lb-in. 14-10 AWG / 40 lb-in. 8 AWG
USE 60°C / 75°C COPPER OR ALUMINUM WIRE
Fuse and Short Circuit Information
This switch is suitable for use on a circuit capable of delivering not more than 100,000
amperes, RMS symmetrical, 240 volts maximum when protected by class J, R or T fuses
rated 30 amperes maximum.
Danger! Unless Class J, R or T fuses are used to protect this switch, it may present a
risk of re and injury to persons if installed on circuits capable of delivering more than
10,000 amperes, RMS symmetrical.
This switch is suitable for use on a circuit capable of delivering not more than
10,000 amperes, RMS symmetrical, 240 volts maximum, when protected by Class K
fuses, Class H fuses or a UL Listed Circuit Breaker rated for 10,000 amperes, RMS
symmetrical, 240 volts maximum.
This switch is suitable for use on a circuit capable of delivering not more than 10,000
amperes, 250 volts DC maximum, when protected by fuses marked with an interrupting
rating of 10,000 amperes, 250 volts DC.
Danger! Unless fuses marked for an interrupting rating of 10,000 amperes at 250 volts
DC are used to protect this switch, this switch may present a risk of re and injury to
persons if installed on circuits capable of delivering more than 10,000 amperes.
Type VBII
240 Volts AC (V ) Maximum
250 Volts AC (V ) Maximum
Cat. No.
Non-Fusible General Duty Safety Switch
30 Amps Maximum
Type
s
Pc. No. R500587G00
GNF321A
1 Indoor
Ground Lug Kit: HG61234
240VAC
1
1Ø
3
Max. HP
240VAC
3Ø
7-1/2
250VDC
1
5
1
Use outer two poles.