SERVICE MANUAL
MODELS:
DIY-*-HP-MUAH-230D25-O
DIY-*-HP-C-230D25-O
This product utilizes R-454B refrigerant
Read this manual carefully before installation and keep it where
the operator can easily nd it for future reference.
Due to updates and constantly improving performance, the
information and instructions within this manual are subject to
change without notice.
Version Date: March 20, 2025
Please visit www.mrcool.com/documentation
to ensure you have the latest version of this manual.
background
mrcool.com1
CONTENTS
SYSTEM OVERVIEW ............................................................................................................................................ 2
MODEL REFERENCE ......................................................................................................................................... 10
INDOOR UNIT .................................................................................................................................................. 11
3.1 Dimensional Drawing ...................................................................................................................... 11
3.2 Fan Performance .............................................................................................................................. 13
3.3 Noise Curves ..................................................................................................................................... 17
3.4 Electrical Wiring Diagrams .............................................................................................................. 18
OUTDOOR UNIT............................................................................................................................................... 28
4.1 Dimensional Drawing ...................................................................................................................... 28
4.2 Install Location ................................................................................................................................. 29
4.3 Capacity Correction for Height Dierence.................................................................................... 29
4.4 Noise Curves .................................................................................................................................... 59
4.5 Refrigerant Cycle Diagram .............................................................................................................. 32
4.6 Electrical Wiring Diagram ................................................................................................................ 33
Installation ...................................................................................................................................................... 41
5.1 Installation Overview....................................................................................................................... 41
5.2 Location Selection ............................................................................................................................ 42
5.3 Indoor Unit Installation ................................................................................................................... 44
5.4 Outdoor Unit Installation ................................................................................................................ 49
5.5 Refrigerant Pipe Installation ........................................................................................................... 50
5.6 Vacuum Drying & Leakage Testing ................................................................................................ 53
5.7 Additional Refrigerant Charge ........................................................................................................ 54
5.8 Piping Insulation .............................................................................................................................. 54
5.9 Auxiliary Heat ................................................................................................................................... 55
5.10 Electrical Wiring .............................................................................................................................. 57
5.11 Test Operation ................................................................................................................................ 59
REFRIGERANT RECHARGE ............................................................................................................................... 60
PRODUCT FEATURES ....................................................................................................................................... 61
7.1 24V Signal Chart ............................................................................................................................... 61
7.2 Safety Features ................................................................................................................................. 62
7.3 Basic Functions ................................................................................................................................. 62
7.4 Installation Overview....................................................................................................................... 41
TROUBLESHOOTING ....................................................................................................................................... 67
8.1 Error Display (Indoor Unit) .............................................................................................................. 67
8.2 Error Display (Outdoor Unit With Auxiliary Board) ...................................................................... 69
8.3 Outdoor Unit Point Check Function ............................................................................................... 70
8.4 Information Inquiry ......................................................................................................................... 72
8.5 Error Diagnosis Without Error Code .............................................................................................. 85
8.6 Quick Maintenance by Error Code ................................................................................................. 85
8.7 Troubleshooting by Error Code ...................................................................................................... 89
8.8 Check Procedures .......................................................................................................................... 126
TEMPERATURE SENSOR RESISTANCE TABLE .............................................................................................. 127
SYSTEM PRESSURE TABLE............................................................................................................................. 129
1
2
3
4
5
Contents
6
7
8
9
10
background
mrcool.com 2 2
Indicates the possibility of personal injury or loss of life.
Indicates the possibility of property damage or serious
consequences.
WARNING
CAUTION
WARNINGS FOR PRODUCT INSTALLATION
INSTALLATION MUST BE PERFORMED BY AN AUTHORIZED DEALER OR SPECIALIST. DEFECTIVE
INSTALLATION CAN CAUSE WATER LEAKAGE, ELECTRICAL SHOCK, OR FIRE.
****ELECTRICAL WORK MUST BE COMPLETED BY A QUALIFIED ELECTRICAL TECHNICIAN****
DO NOT install the unit in a location that may be exposed to combustible gas leaks. If
combustiblegasaccumulatesaroundtheunit,itcouldcausere.
DO NOT turn on the power until the installation and all work has been completed.
DO NOT install a unit equipped with an auxiliary electric heater within 3 ft (1 m) of any
combustible materials.
1. Turn o the unit and disconnect the power before performing any installation or repairs. Failure to do so
can cause electric shock.
2. Installation must be performed according to the installation instructions. Improper installation could cause
water leakage, electrical shock, re, and could void the warranty. Contact an authorized service technician
for repair or maintenance of this unit. This appliance must be installed in accordance with national wiring
regulations.
3. Only use the included accessories, parts, and specied parts for installation. Using non-standard parts can
cause water leakage, electrical shock, re, and/or failure of the unit.
4. Install the unit in a rm location that can support the unit’s weight. If the location cannot support the unit’s
weight, or the installation is not done properly, the unit may drop and cause serious injury and damage.
5. Install the drainage piping according to the instructions in this manual. Improper drainage could cause
water damage to your home and/or property.
6. When moving or relocating the air conditioner, consult experienced service technicians for disconnection
and re-installation of the unit.
7. For detailed information of how to install the indoor and outdoor units to their respective supports, please
refer to the indoor unit installation and outdoor unit installation sections of this manual.
8. For units with a wireless network function, the USB device access, replacement, and maintenance
operations must be carried out by professional sta.
9. Refer to details further in this manual regarding installing the unit to its support.
Incorrect usage may cause serious damage or injury.
The symbols below are used throughout this manual to indicate instructions that should be followed closely
or actions that should be avoided to prevent death, injury, and/or property damage.
Safety Precautions
Read Before Using
1
SAFETY
background
mrcool.com3
WARNINGS FOR PRODUCT USE
DO NOT insertngers,rods,orotherobjectsintotheairinletoroutlet.Thiscouldcauseinjury,
since the fan may be rotating at high speeds.
DO NOT useammablesprayssuchashairspray,lacquerorpaintneartheunit,asthiscould
causereand/oranexplosion.
DO NOT operate the unit in places near or around combustible gases. Emitted gas may collect
around the unit and cause an explosion.
DO NOT allow children to play with the appliance. Children must be supervised around
the unit at all times.
DO NOT operate the unit in a room where it could be exposed to excessive amounts of water,
such as a bathroom or laundry room. Exposure to excessive water amounts can cause the
electrical components to short circuit.
DO NOT exposeyourbodydirectlytodirectcoolairowfromtheunitforaprolongedperiod
of time.
1. If the unit operates abnormally (emits strange noises or a burning smell), immediately turn o the unit
and disconnect the power in order to avoid electric shock, re, and/or injury. Call your local dealer, or
MRCOOL® tech support at (270) 366-0457, for further assistance.
2. If the air conditioner is used together with burners or other heating devices, thoroughly ventilate the room
in order to avoid an oxygen deciency.
3. In certain functional environments (such as kitchens and server rooms etc.), the use of specially designed
air-conditioning units is highly recommended.
4. This appliance can be used by children (8 years and older) and persons with reduced physical, sensory or
mental capabilities, or lack of experience and knowledge if they have been given instruction concerning the
use of the appliance and understand the hazards involved.
5. Improper installation, adjustment, alteration, service, or maintenance can cause property damage,
personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC
installer, service agency, or the gas supplier.
ELECTRICAL WARNINGS
****ELECTRICAL WORK MUST BE COMPLETED BY A QUALIFIED ELECTRICAL TECHNICIAN****
DO NOT share the power supply with other appliances. The unit must be installed on a dedicated
electricalcircuit.Animproperorinsucientpowersupplycouldcausereand/orelectrical
shock.
1. The product must be properly grounded during installation or electrical shock could occur.
2. Appropriate wiring standards, regulations, and the installation manual must be followed for all electrical
work.
3. If connecting power to xed wiring, an all-pole disconnection device must be incorporated in the xed
wiring in accordance with the wiring rules and must meet the following requirements: at least 3 mm of
clearances in all poles, a leakage current that may exceed 10 mA, and a residual current device (RCD)
having a rated residual operating current not exceeding 30 mA.
4. For all electrical work, fuse the specied cables. Connect cables tightly and clamp them securely to prevent
external forces from damaging the terminal. Improper electrical connections could overheat, causing re
and/or electrical shock.
5. All electrical connections must be made according to the Electrical Connection Diagram located on the
panels of the indoor and outdoor units.
6. All wiring must be properly arranged to ensure that the control board cover can close properly. If the
control board cover is not properly closed, it can lead to corrosion and cause the connection points on the
terminal to heat up, catch re, or cause electrical shock.
7. Only use the specied wire. If the wire is damaged, it must be replaced by the manufacturer, its service
agent, or similarly qualied person in order to avoid a hazard.
8. Disconnection must be incorporated in the xed wiring in accordance with the NEC, CEC, or local codes.
SAFETY
1
background
mrcool.com 4
4
WARNINGS FOR CLEANING & MAINTENANCE
DO NOT clean the unit with excessive amounts of water.
DO NOT cleanunitwithcombustiblecleaningagents,asthesecouldcausedeformationand/or
re.
1. Turn o the device and disconnect the power before cleaning. Failure to do this could result in electrical
shock.
CAUTION
DO NOT allow the air conditioner to operate for extended periods of time with the doors or
windows open, or in very high humidity.
DO NOT operate the air conditioner with wet hands, as this could cause electric shock.
DO NOT use device for any other purpose than its intended use.
DO NOT climbontoorplaceobjectsontopoftheoutdoorunit.
1. Make sure that water condensation can drain smoothly and unhindered from the unit.
2. Turn o the unit and disconnect the power if the unit will not be used for an extended period of time.
3. As with any mechanical equipment, contact with sharp metal edges can result in personal injury. Ensure
care is taken when handling the unit and any of its accessories by wearing gloves and protective clothing.
NOTE ON FLUORINATED GASES (NOT APPLICABLE FOR R-290 UNITS):
1. This unit contains uorinated greenhouse gases.
2. For specic information on the type of gas and the amount, please refer to the relevant label on the unit
itself.
3. Service, maintenance, and repair of this unit must be performed by a certied technician.
4. Product un-installation and recycling must be performed by a certied technician.
5. When checking the unit for leaks, maintain proper record-keeping of all checks.
1
SAFETY
background
mrcool.com5
FLAMMABLE REFRIGERANT WARNINGS
1. The installation of pipe-work should be kept to a minimum and should be protected from physical damage.
2. Refrigerant pipes should comply with national gas regulations.
3. All mechanical connections and ventilation openings should be kept clear of obstruction.
4. Utilize proper disposal processes based on national regulations.
5. Any person involved with working on or breaking into a refrigerant circuit should hold a current valid
certicate from an industry-accredited assessment authority, which authorizes their competence to handle
refrigerants safely in accordance with an industry recognized assessment specication.
6. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the
supervision of the person competent in the use of ammable refrigerants.
7. Do not use any means to accelerate the defrosting process or to clean, other than those recommended by
the manufacturer.
8. The appliance shall be stored in a room without continuously operating ignition sources (for example: open
ames, an operating gas appliance, or an operating electric heater).
9. Do not allow foreign matter (oil, water, etc.) to enter the piping, and securely seal the opening by pinching,
taping, etc.
10. Do not pierce or burn.
11. Refrigerants may not contain an odor.
12. Working procedures that aect safety should only be carried out by competent persons.
13. The unit should be stored in a well-ventilated area where the room size corresponds to the room area as
specic for operation, and should be stored so as to prevent potential mechanical damage from occurring.
14. Joints should be tested with detection equipment with a capability of 5 g/year of refrigerant or better, with
the equipment in standstill and under operation or under a pressure of at least these standstill or operation
conditions after installation. Detachable joints should NOT be used in the indoor side of the unit (brazed,
welded joint could be used).
15. A leak detection system is installed. The unit must be powered except for service. For units with a refrigerant
sensor, the indoor unit will display an error code and emit a buzzing sound, the compressor of the outdoor
unit will immediately stop, and the indoor fan will start running. The service life of the refrigerant sensor
is 15 years. When the refrigerant sensor malfunctions, the indoor unit will display the error code "FHCC".
The refrigerant sensor cannot be repaired and can only be replaced by the manufacturer. It should only be
replaced with the sensor specied by the manufacturer.
16. Prior to beginning work on systems containing ammable refrigerants, safety checks are necessary
to ensure that the risk of ignition is minimized. For repairs to the refrigerating system, the following
precautions shall be complied with prior to conducting work on the system.
17. Work should be undertaken under a controlled procedure so as to minimize the risk of a ammable gas or
vapor being present while the work is being performed.
18. All maintenance sta and others working in the local area should be instructed on the nature of work being
carried out. Avoid work in conned spaces.
19. The area should be checked with an appropriate refrigerant detector prior to and during work, to ensure the
technician is aware of potentially ammable atmospheres. Ensure that the leak detection equipment being
used is suitable for use with ammable refrigerants, i.e. no sparking, adequately sealed, or intrinsically safe.
20. If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate re
extinguishing equipment should be on site and readily available. Have a dry power or CO2 re extinguisher
adjacent to the charging area.
21. No person carrying out work in relation to a refrigerating system which involves exposing any pipe work
should use any sources of ignition in such a manner that it may lead to the risk of re or explosion. All
possible ignition sources, including cigarette smoking, should be kept suciently far away from the site
of installation, repairing, removing, and disposal, during which refrigerant can possibly be released to the
surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make
sure that there are no ammable hazards or ignition risks. "No Smoking" signs should be displayed.
22. Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or
conducting any hot work. A degree of ventilation shall continue during the period that the work is carried
out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the
atmosphere.
SAFETY
1
background
mrcool.com 6
FLAMMABLE REFRIGERANT WARNINGS
23. Where electrical components are being changed, they shall be t for the purpose and to the correct
specication. At all times the manfacturer's maintenance ad service guidelines shall be followed. If in
doubt, consult the manufacturer's technical department for assistance. The following checks should be
applied to installations using ammable refrigerants:
• the actual refrigerant charge is in accordance with the room size within which the refrigerant containing
parts are installed;
• the ventilation machinery and outlets are operating adequately and are not obstructed;
• if an indirect refrigerating circuit is being used, the secondary circuits should be checked for the
presence of refrigerant;
• marking to the equipment continues to be visible and legible, marking and signs that are illegible
should be corrected;
• refrigeration pipe or components are installed in a position where they are unlikely to be exposed to
any substance which may corrode refrigerant containing components, unless the components are
constructed of materials which are inherently resistant to being corroded or are suitably protected
against being so corroded.
24. Repair and maintenance to electrical components shall include initial safety checks and component
inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be
connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it
is necessary to continue operation, an adequate temporary solution should be used.
25. Initial safety checks should include:
• that capacitors are discharged: this should be done in a safe manner to avoid the possibility of
sparking;
• that there are no live electrical components and wiring are exposed while charging, recovering, or
purging the system;
• that there is continuity of earth bonding.
26. Sealed electrical components should be replaced if damaged.
27. Intrinsically safe components should be replaced if damaged.
28. Check that wiring will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges, or
any other adverse environmental eects. The check shall also take into account the eects of aging or
continual vibration from sources such as compressors or fans.
29. Under no circumstances should potential sources of ignition be used in the search for or detection of
refrigerant leaks. A halide torch (or any other detector using a naked ame) should not be used.
The following leak detection methods are deemed acceptable for refrigerant systems. Electronic leak detectors
may be used to detect refrigerant leaks but, in the case of ammable refrigerants, the sensitivity may not be
adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) En-
sure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detec-
tion equipment shall be set at a percentage of the LFL of the refrigerant and should be calibrated to the refrig-
erant employed, and the appropriate percentage of gas (25% minimum) is conrmed. Leak detection uids are
also suitable for use with most refrigerants but the use of detergents containing chlorine may react with the
refrigerant and corrode the copper work. Examples of leak detection uids are the bubble method, uorescent
method agents, etc. If a leak is suspected, all naked ames should be removed/extinguished. If a leakage of
refrigerant is found which requires brazing, all of the refrigerant should be recovered from the system, or iso-
lated (by means of shut-o valves) in a part of the system remote from the leak. See the following instructions
of removal of refrigerant.
30. When breaking into the refrigerant circuit to make repairs, or for any other purpose, conventional
procedures should be used. However, for ammable refrigerants, it is even more vital to follow best
practice. The following procedure should be adhered to:
• safely remove refrigerant following local and national regulations;
• evacuate;
• purge the circuit with inert gas;
• evacuate;
• continuously ush or purge with inert gas when using ame to open circuit;
• open the circuit
1
SAFETY
background
mrcool.com7
FLAMMABLE REFRIGERANT WARNINGS
31. The refrigerant charge should be recovered into the correct recovery cylinders if venting is not allowed by
local and national codes. For units containing ammable refrigerants, the system should be purged with
oxygen-free nitrogen to render the appliance safe for ammable refrigerants. This process might need to
be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems.
For appliances containing ammable refrigerants, refrigerant purging should be achieved by breaking the
vacuum in the system with oxygen-free nitrogen and continuing to ll the working pressure is achieved,
then venting to atmosphere, and nally pulling down to a vacuum. This process should be repeated until
no refrigerant is within the system. When the nal oxygen-free nitrogen charge is used, the system should
be vented down to atmospheric pressure to enable work to take place. The outlet for the vacuum pump
should not be close to any potential ignition sources, and ventilation should be available.
32. In addition to conventional charging procedures, the following requirements should be followed:
• Work should be undertaken with appropriate tools only (in case of uncertainty, please consult the
manufacturer of the tools for use with ammable refrigerants).
• Ensure that contamination of dierent refrigerants does not occur when using charging equipment.
Hoses or lines shall be as shot as possible to minimize the amount of refrigerant contained in them.
• Cylinders should be kept upright.
• Ensure that the refrigeration system is grounded prior to charging the system with refrigerant.
• Label the system when charging is complete (if not already).
• Extreme care should be taken not to overll the refrigeration system.
• Prior to recharging the system, it should be pressure tested with oxygen-free nitrogen (OFN). The
system should be leak-tested on completion of charging but prior to commissioning. A follow-up leak
test shall be carried out prior to leaving the site.
33. Before carrying out this procedure, it is essential that the technician is completely familiar with the
equipment and all its detail. It is good recommended practice that all refrigerants are recovered safely.
Prior to the task being carried out, an oil and refrigerant sample should be taken in case analysis is
required prior to re-use of recovered refrigerant. It is essential that electrical power is available before the
task is commenced.
a. Become familiar with the equipment and its operation.
b. Isolate the system electrically.
c. Before attempting the procedure ensure that:
• mechanical handling equipment is available, if required, for handling refrigerant cylinders;
• all personal protective equipment is available and being used correctly;
• the recovery process is supervised at all times by a competent person;
• recovery equipment and cylinders conform to the appropriate standards
d. Pump down refrigerant system, if possible.
e. If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of
the system.
f. Make sure that the cylinder is situated on the scales before recovery takes place.
g. Start the recovery machine and operate in accordance with instructions.
h. Do not overll cylinders (no more than 80% volume liquid charge).
i. Do not exceed the maximum working pressure of the cylinder, even temporarily.
j. When the cylinders have been lled correctly and the process completed, make sure that the cylinders
and equipment are removed from the site promptly and all isolation valves on the equipment are closed
o.
k. Recovered refrigerant should not be charged into another refrigeration system unless it has been
cleaned and checked.
34. Equipment shall be labeled stating that it has been decommissioned and emptied of refrigerant. The
label should be dated and signed. For appliances containing ammable refrigerants, ensure that there are
labels on the equipment stating the equipment contains ammable refrigerant.
SAFETY
1
background
mrcool.com 8
FLAMMABLE REFRIGERANT WARNINGS
35. When removing refrigerant from a system, either for servicing or decommissioning, it is good
recommended practice that all refrigerants are removed safely. When transferring refrigerant into
cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the
correct number of cylinders for holding the total system charge is available. All cylinders to be used should
be designated for the recovered refrigerant and labeled for that refrigerant (i.e. special cylinders for the
recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-o
valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before
recovery occurs. The recovery equipment should be in good working order with a set of instructions
concerning the equipment that is at hand and should be suitable for the recovery of the ammable
refrigerant. If in doubt, the manufacturer should be consulted. In addition, a set of calibrated weighing
scales should be available and in good working order. Hoses should be complete with leak-free disconnect
couplings and in good condition. The recovered refrigerant should be processed according to local
legislation in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix
refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be
removed, ensure that they have been evacuated to an acceptable level to make certain that ammable
refrigerant does not remain within the lubricant. The compressor body should not be heated by an open
ame or other ignition sources to accelerate this process. When oil is drained from a system, it should be
carried out safely.
36. An unventilated area where the appliance using ammable refrigerants is installed should be constructed
so that should any refrigerant leak, it will not stagnate so as to create a re or explosion hazard. If
appliances connected via an air duct system to one or more rooms below the ventilation requirements,
that room should never contain potential ignition sources. A ame-producing device may be installed
in the space if the device is provided with an eective ame arrest. Auxiliary devices which may be a
potential ignition source should not be installed in the duct work. Examples of such are hot surfaces with
a temperature exceeding 1292°F (700°C) and electric switching devices. Only auxiliary devices (such as
a certied heater kit) approved by the manufacturer or declared suitable with the refrigerant should be
installed in connecting ductwork. False or drop ceilings may be used as a return air plenum if a refrigerant
detection system is provided in the appliance and any external connections are also provided with a sensor
immediately below the return air plenum duct joint. Refrigerant sensors for refrigerant detection systems
should only be replaced with sensors specied by the manufacturer. A leak detection system is installed.
The unit must be powered except for service.
37. Transport of equipment containing ammable refrigerants should comply with transportation regulations.
38. Marking of equipment using signs should comply with local regulations.
39. Disposal of equipment using ammable refrigerants should comply with national regulations.
40. Storage of equipment/appliances should be in accordance with the manufacturer's instructions.
41. Storage of packed (unsold) equipment should be constructed so that mechanical damage to the equipment
inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of
equipment permitted to be stored together will be determined by local regulations.
Symbols Displayed on Indoor & Outdoor Unit
WARNING
This symbol shows that this appliance uses a ammable refrigerant. If the refrigerant
is leaked and exposed to an external ignition source, there is a risk of re.
CAUTION This symbol shows that the operation manual should be read carefully.
CAUTION
This symbol shows that a service personnel should be handling this equipment with
reference to the installation manual.
CAUTION
CAUTION
This symbol shows that information is available such as the operating manual or
installation manual.
1
SAFETY
background
mrcool.com9
Room Size Restriction
The units are connected via an air duct to one or more rooms, the bottom of the air outlet of the air duct in the
room should be at a height ≥7.3 ft (2.2m) from the oor. In UL/CSA 60335-2-40, the R454B refrigerant belongs to
mildly ammable refrigerants, which will limit the room area of the system service. Similarly, the total amount
of refrigerant in the system should be less than or equal to the maximum allowable refrigerant charge, which
depends on the room area serviced by the system.
Refrigerant Charge and Room Area Limitations
For the purpose of determination of room area (A) when used to calculate the maximum allowable refrigerant
charge (mmax) in an unventilated space, the following shall apply.
The room area (A) shall be dened as the room area enclosed by the projection to the oor of the walls,
partitions and doors of the space in which the appliance is installed. Spaces connected by only drop ceilings,
ductwork, or similar connections shall not be considered a single space.
For units mounted higher than 6 ft (1.8m), spaces divided by partition walls which are no higher than 5.3ft/1.6m
shall be considered a single space.
For xed appliances, rooms on the same oor and connected by an open passageway between the spaces can
be considered a single room when determining compliance to Amin, if the passageway complies with all of the
following:
• it is a permanent opening
• it extends to the oor
• it is intended for people to walk through
For xed appliances, the areas of the adjacent rooms, on the same oor, connected by a permanent opening
in the walls and/or doors between occupied spaces, including gaps between the wall and the oor, can be
considered a single room when determining compliance to Amin, provided all of the following are met:
• the space shall have appropriate openings
• the minimum opening area for natural ventilation Anvmin shall not be less than the following:
SECTION TERMINOLOGY
Mc: the actual refrigerant charge in the system
A: the actual room area where the appliance is
installed
Amin: the required minimum room area
Mmax: the allowable maximum refrigerant charge in
a room
Qmin: the minimum circulation airow
Anvmin: the minimum opening area for connected
rooms
TAmin: the total area of the conditioned space (for
appliances serving one or more rooms with an air
duct system)
TA: The total area of the conditioned space connected
by air ducts.
HeightofOutlet/m A/m
2
Mc/kg Mmax/kg Anvmin/m
2
2.2 5 5.0 2.685 0.045
2.2 6 5.0 2.941 0.042
2.2 7 5.0 3.177 0.038
2.2 8 5.0 3.396 0.035
2.2 9 5.0 3.602 0.031
2.2 10 5.0 3.797 0.028
2.2 11 5.0 3.983 0.024
2.2 12 5.0 4.160 0.020
2.2 13 5.0 4.330 0.016
2.2 14 5.0 4.493 0.013
2.2 15 5.0 4.651 0.009
2.2 16 5.0 4.803 0.005
2.2 17 5.0 4.951 0.001
SAFETY
1
background
mrcool.com 10
10
MODEL REFERENCE
2
Indoor Unit Model Outdoor Unit Model Capacity(Btu/h)
Power
Supply
DIY-24-HP-MUAH-230D25-O DIY-24-HP-C-230D25-O 24K
208/230V~,
60Hz, 1
Phase
DIY-36-HP-MUAH-230D25-O DIY-36-HP-C-230D25-O 36K
Air Handler Apperance Condenser Apperance
background
mrcool.com11
INDOOR UNIT
3
3.1 Dimensional Drawing
background
mrcool.com 12
INDOOR UNIT
3
Dimensions Model
24K 36K
inch mm inch mm
A Model Height 45 1143 49 1245
B Model Width 17-1/2 445 21 534
C Supply Air Opening Width 15-5/8 397 19-1/8 486
D Return Air Opening Width 15-1/8 384 18-5/8 473
E Model Depth 21 534 21 534
F Supply Air Opening Depth 10-1/4 260 10-1/4 260
G Return Air Opening Depth 18-3/4 476 18-3/4 476
H
Supply Air Opening
Clearance
15/16 24 15/16 24
I
Return Air Opening Side
Clearance
1-1/4 32 1-1/4 32
J
Return Air Opening Front
Clearance
1-1/2 38 1-5/8 41
K
Return Air Opening Back
Clearance
5/8 16 5/8 16
Part Names
background
mrcool.com13
Service Place:
Horizontal Installation
The outlet side pipe length is 4.9ft/m.
Vertical Installation
3.2 Fan Performance
24K Vertical, Horizontal Right, Horizontal Left:
Use the Remote Controller:
1. The indoor unit needs to be turned o for 5 minutes then powered on (all settings need to be
nished within 10 minutes).
2. Push ON/OFF and FAN SPEED together for 7 seconds to enter engineering mode.
3. Choose channel 23 (for cooling) and 25 (for heating) with UP and Down buttons.
4. After choosing channel 23 or 25 push ON/OFF for 2 seconds to select -41,-40,.....,-1,0,1,2,3,....,19,20
(reference the matrix list to identify the relative CFM)
5. Push the OK button to conrm the adjustment value, the display board will display CS (means
success for the setting) then disconnect power after 5 seconds.
INDOOR UNIT
3
background
mrcool.com 14
Cooling Default -1 -2 -3 -4 -5 -6 -7 -8 -9 -10
Turbo 988 804 784 764 744 724 704 684 664 644 624
High 894 739 719 699 679 659 639 619 599 579 559
Medium 806 674 654 634 614 594 574 554 534 514 494
Low 712 609 589 569 549 529 509 489 469 449 429
Cooling Default -11 -12 -13 -14 -15 -16 -17 -18 -19 ~ -40 +1
Turbo 988 604 584 564 544 524 504 484 464 453 844
High 894 539 519 499 479 459 439 435 435 435 799
Medium 806 474 454 434 418 418 418 418 418 418 714
Low 712 409 400 400 400 400 400 400 400 400 649
Cooling Default +2 +3 +4 +5 +6 +7 +8 +9 ~ +20
Turbo 988 853 853 853 853 853 853 853 853
High 894 799 819 835 835 835 835 835 835
Medium 806 734 754 774 794 814 818 818 818
Low 712 669 689 709 729 749 769 789 800
Heating Default -1 -2 -3 -4 -5 -6 -7 -8 -9 -10 -11
Turbo 788 768 748 728 708 688 668 648 628 608 588 568
High 753 733 713 693 673 653 633 613 593 573 553 533
Medium 641 621 601 581 651 541 521 501 481 461 441 421
Low 524 504 484 646 444 424 404 400 400 400 400 400
Heating Default -12 -13 -14 -15 -16 -17 ~ -40 +1 +2 +3 +4 +5
Turbo 788 548 528 508 488 468 453 808 828 848 853 853
High 753 513 493 473 453 435 435 773 793 813 833 835
Medium 641 418 418 418 418 418 418 661 681 701 721 741
Low 524 400 400 400 400 400 400 544 564 584 604 624
Heating Default +6 +7 +8 +9 +10 +11 +12 +13
+14 ~
+20
Turbo 788 853 853 853 853 853 853 853 853 853
High 753 835 835 835 835 835 835 835 835 835
Medium 641 761 781 801 818 818 818 818 818 818
Low 524 644 664 684 704 724 744 764 784 800
INDOOR UNIT
3
background
mrcool.com15
36K Vertical, Horizontal Right, Horizontal Left:
Use the Remote Controller:
1. The indoor unit needs to be turned o for 5 minutes then powered on (all settings need to be
nished within 10 minutes).
2. Push ON/OFF and FAN SPEED together for 7 seconds to enter engineering mode.
3. Choose channel 23 (for cooling) and 25 (for heating) with UP and Down buttons.
4. After choosing channel 23 or 25 push ON/OFF for 2 seconds to select -41,-40,.....,-1,0,1,2,3,....,19,20
(reference the matrix list to identify the relative CFM)
5. Push the OK button to conrm the adjustment value, the display board will display CS (means
success for the setting) then disconnect power after 5 seconds.
Cooling Default -1 -2 -3 -4 -5 -6 -7 -8 -9 -10 -11 -12
Turbo 1188 1168 1148 1128 1108 1088 1068 1048 1028 1008 988 968 948
High 1082 1062 1042 1022 1002 982 962 942 922 902 882 862 842
Medium 971 951 931 911 891 871 851 831 811 971 771 751 731
Low 865 845 825 805 785 765 745 725 705 685 665 645 625
Cooling Default -13 -14 -15 -16 -17 -18 -19 -20 -21 -22 -23 -24
Turbo 118 928 908 888 868 848 828 808 788 768 748 728 708
High 1082 822 802 782 762 742 722 702 682 662 642 622 602
Medium 971 711 691 671 651 631 611 591 571 551 531 511 491
Low 865 605 585 565 454 525 505 485 465 455 425 405 400
Cooling Default -25 -26 -27 -28 -29 -30 -31 -32 -33 -34 -35 -36
Turbo 1188 688 668 648 628 608 588 568 548 528 508 488 468
High 1082 582 562 542 522 502 482 462 442 435 435 435 435
Medium 971 471 451 431 418 418 418 418 418 418 418 418 418
Low 865 400 400 400 400 400 400 400 400 400 400 400 400
INDOOR UNIT
3
background
mrcool.com 16
Cooling Default
-37 ~
-40
+1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11
Turbo 1188 453 1208 1228 1248 1268 1288 1288 1288 1288 1288 1288 1288
High 1082 435 1102 1122 1142 1162 1182 1202 1222 1242 1262 1271 1271
Medium 971 418 991 1011 1031 1051 1071 1091 1111 1131 1151 1171 1191
Low 865 400 885 905 925 945 965 985 1005 1025 1045 1065 1085
Cooling Default +12 +13 +14 +15 +16 +17 +18
+19 ~
+20
Turbo 1188 1288 1288 1288 1288 1288 1288 1288 1288
High 1082 1271 1271 1271 1271 1271 1271 1271 1271
Medium 971 1211 1231 1251 1253 1253 1253 1253 1253
Low 865 1105 1125 1145 1165 1185 1205 1225 1235
Heating Default -1 -2 -3 -4 -5 -6 -7 -8 -9 -10 -11
Turbo 1112 1092 1072 1052 1032 1012 992 972 952 932 912 892
High 1059 1039 1019 999 979 959 939 919 899 879 859 839
Medium 794 774 754 734 714 694 674 654 634 614 594 574
Low 582 400 400 400 400 400 400 400 400 400 400 400
Heating Default -12 -13 -14 -15 -16 -17 -18 -19 -20 -21 -22
Turbo 1112 872 852 832 812 792 772 752 732 712 692 672
High 1059 819 799 779 759 739 719 699 679 659 639 619
Medium 794 554 534 514 494 474 454 434 418 418 418 418
Low 582 400 400 400 400 400 400 400 400 400 400 400
Heating Default -23 -24 -25 -26 -27 -28 -29 -30 -31 -32 -33 ~ -40
Turbo 1112 652 632 612 592 572 553 532 512 492 472 453
High 1059 599 579 559 539 519 499 479 459 439 435 435
Medium 794 418 418 418 418 418 418 418 418 418 418 418
Low 582 400 400 400 400 400 400 400 400 400 400 400
Heating Default +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11
Turbo 1112 1132 1152 1172 1192 1212 1232 1252 1272 1288 1288 1288
High 1059 1079 1099 1119 1139 1159 1179 1199 1219 1239 1259 1271
Medium 794 814 834 854 874 894 914 934 954 974 994 1014
Low 582 602 622 642 662 682 702 722 742 762 782 802
Heating Default +12 +13 +14 +15 +16 +17 +18 +19 +20
Turbo 1112 1288 1288 1288 1288 1288 1288 1288 1288 1288
High 1059 1271 1271 1271 1271 1271 1271 1271 1271 1271
Medium 794 1034 1054 1074 1094 1114 1134 1154 1174 1194
Low 582 822 842 862 882 902 922 942 962 982
INDOOR UNIT
3
background
mrcool.com17
3.3 Noise Curves
Notes:
• Sound is measures at 4.92ft/1.5m (horizontal installation) /3.28ft/1m (vertical installation) away
from the center of the unit.
• Data is valid at free eld condition.
• Reference acoustic pressure OdB=20µPa
• Sound level will vary depending on a range of factors such as the construction (acoustic absorption
coecient) of the room in which the equipment is installed.
• The operating conditions are assumed to be standard.
Horizontal Installation Vertical Installation
(H=0.5x (height of unit+1))
36K24K
INDOOR UNIT
3
background
mrcool.com 18
3.4 Electrical Wiring Diagrams
IDU Model 24K 36K
Power (Indoor)
Phase 1
Frequency and Volt 208/230V,60Hz
Power (Outdoor)
Phase 1
Frequency and Volt 208/230V,60Hz
Max. Fuse
Indoor Unit (A) 15 15
Outdoor Unit (A) 25 35
Outdoor Unit
Power Wire
Line Quantity 3 3
Line Diameter (AWG) 12/4.0mm
2
10/6.0mm
2
Outdoor-Indoor Connect Wire 1
Line Quantity 4 4
Line Diameter (AWG) 14/2.5mm
2
14/2.5mm
2
Outdoor-Indoor Connect Wire 2
Line Quantity 2 2
Line Diameter (AWG) 20/0.5mm
2
20/0.5mm
2
Thermostat Signal Wire
Line Quantity
Line Diameter (AWG) 18/1.0mm
2
18/1.0mm
2
Electrical Characteristics:
Electrical Wiring Diagrams:
Capacity(Btu/h) IDU Wiring Diagram
24K 16023000014232
36K 16023000015672
Abbreviation Paraphrase
Y/G Yellow-Green Conductor
FAN1 Indoor ECM Motor
To CCM Comm.Bus Central Controller
T1 Indoor Room Temperature Sensor
T2 Indoor Coil Temperature Sensor
INDOOR UNIT
3
background
mrcool.com19
Indoor Unit Wiring Diagram: 16023000014232
INDOOR UNIT
3
background
mrcool.com 20
20
Indoor Unit Wiring Diagram: 16023000015672
INDOOR UNIT
3
background
mrcool.com21
Micro-Switches:
For ALARM Terminal Port CN33:
1. Use the terminal port to connect ALARM. (The terminal does not send power and must be supplied
separately).
2. Design voltage can support higher voltage but it is highly recommended to use less than 24v with a
current of less than 0.5A.
3. When a issue occurs the relay will close and the ALARM stops the system.
For Remote Control (ON-OFF) Terminal Port CN2 and Short Connector of JR1:
1. Remove the short connector of JR1 when you use ON-OFF function.
2. When the remote switch is o (OPEN); the unit will be o.
3. When the remote switch in on (CLOSE); the unit will be on.
4. When the switch is triggered the unit will respond to the demand within 2 seconds.
5. When the remote switch is on, you can use the remote controller/wired controller to select the
mode desired, when the remote switch is o the unit will not respond to a demand from the
remote/wire controller.
6. The voltage of the power is 12VDC with a design max. current of 5mA.
INDOOR UNIT
3
background
mrcool.com 22
22
Micro-switch S1 and dial-switch SW8 are for address settings when you want to control this unit by a
central controller.
Range: 00-63
Network address: the address silkscreen is NET address, which is composed of a 16-bit address rotary
code S1 plus a two-digit DIP switch SW8 {Set during engineering installation, no network function needs
to be set].
When SW8 is 00 (The dialing code is not connected), the network address value is the value of S1.
When SW8 is 10 (Corresponding to the switch of the hardware connected to the 10K resistor), the
network address value is S1 plus 16.
Determined by dial code SW8 1-10K, 2-5.1K.
When SW8 is 01 (Corresponding to the dial code of the 5.1K resistor connected to the hardware is
turned on), the network address value is the value of S1 plus 32.
When SW8 is 11 (All dialing codes are on), the network address value is the value of S1 plus 48.
Dial Code Selection Net Address
S1+48
S1+32
S1+16
S1
Dial-Switch ENC1: The indoor PCB is universally designed for whole series units from 12K to 60K. This
ENC1 setting will tell the main program what size the unit is.
Range: AUTO, 12K, 18K, ...60K.
Note: AUTO means the indoor unit is equipped with dierent outdoor units, which can automatically
identify the capacity of the outdoor unit either single or multi zone and match the indoor units
parameters.
INDOOR UNIT
3
background
mrcool.com23
Function DIP Switch Settings:
The 24V Thermostat Mode Needs to Refer to the Following Steps:
No.
Dial
Code
Function ON OFF(Default) Note
Control Scenario 24V Tstat, S1+S2
1 SW1-2
Anti-cold blow
protection option
No [Default] Yes
2 SW1-3
Single cooling/
heating and cooling
options
Cooling [Default] Cooling & Heating
3 SW2-1
Compressor
Running (demand
working with heat
pump+electric
heat)
Compressor slower
speed
[Default] Faster Compressor Only aects compressor and W1
4 SW2-4 Compressor
The operation of
heat pump is limited
by the outdoor
temperature, and
the operation of
auxiliary heat is not
limited. The system
makes judgments
according to the
following rules:
1. The compressor
can be operated
when the outdoor
temperature is
≥S3 DIP switch
temperature =2°C.
2. The compressor
cannot be operated
when the outdoor
temperature is lower
than S3 DIP switch
temperature.
[Default] The operation of the
heat pump is limited by the
outdoor temperature and the
operation of auxiliary heat is
not limited. The system makes
judgments based on the
following rules:
1. The compressor cannot be
operated when the outdoor
temperature is lower than the S3
DIP switch.
2. The compressor can be
operated when the outdoor
temperature is ≥S3 DIP switch
temperature +2°C.
SW2-4 and S3 need to be
working together
5
Rotary
Switch S3
Sets the outdoor
temperature
limitation (for
auxiliary heating or
compressor)
Table A
6 SW3-1
Maximum
continuous
runtime allowed
before the system
automatically
stages up capacity
to satisfy set point.
This adds 1-5°F to
the user set point
in the calculated
control point to
increase capacity
and satisfy user set
point.
30 Minutes [Default] 90 minutes
7 SW3-2
Cooling and
heating Y/Y2
temperature
dierential
adjustment.
Compressor slower
speed
[Default] Faster Compressor Only aects compressor
INDOOR UNIT
3
background
mrcool.com 24
24
No.
Dial
Code
Function ON OFF(Default) Note
Control Scenario 24V Tstat, S1+S2
8 SW3-3
Compressor
running (demand
working with heat
pump+electric
heat)
Compressor slower
speed
[Default] Faster Compressor Only aects compressor and W2
9 SW3-4
Fan speed of
cooling mode when
24V thermostat is
applied for
Turbo High
10
SW4-1
SW4-2
SW4-3
Electric heat
nominal CFM
adjustment
Available settings are 000/001/010/011. Each digit
corresponds to an individual switch position.
For example [SW4-1 OFF, SW4-2 ON, SW4-3 OFF]=010
11 S4-4 Default ON
[Default] For single
stage supplemental
heat, W1 and W2 are
connected
For dual stage supplemental
heat, W1 and W2 are controlled
independently
12 S4-2
DH function
selection
[Default]
Dehumidication
control not available
Dehumidication feature is
enabled through thermostat
13 SW5-3
L or Alarm relay
selection
L output 24V
or alarm relay
close only when
refrigerant sensor
fault or R454B
refrigerant leakage is
detected
[Default] L output 24V or alarm
relay close when any fault is
detected
14 SW5-4 R output selection
R stop output 24v
When refrigerant
sensor fault or
R454B refrigerant
leakage is detected
[Default] R keep output 24V even
when refrigerant sensor fault
or R454B refrigerant leakage is
detected
INDOOR UNIT
3
background
mrcool.com25
No.
Dial
Code
Function ON OFF(Default) Note
Control Scenario Wired Controller
1 SW1-2
Anti-cold blow
protection option
No [Default] Yes
2 SW1-3
Single cooling/
heating and cooling
options
Cooling [Default] Cooling & Heating
3 SW2-1
Temperature
dierential to
activate rst stage
auxiliary heat ( the
GAP of T1 and Ts),
Wire controller
demand with heat
pump+electric heat
working together
26°F (1°C) [Default] 4°F (2°C)
4 SW2-2
Electric heat on
delay
Yes [Default] No
5 SW2-3
Electric auxiliary
heating delay to
start time
30 minutes [Default] No
6 SW2-4 Compressor
The operation of
heat pump is limited
by the outdoor
temperature, and
the operation of
auxiliary heat is not
limited. The system
makes judgments
according to the
following rules:
1. The compressor
can be operated
when the outdoor
temperature is
≥S3 DIP switch
temperature +2°C.
2. The compressor
cannot be operated
when the outdoor
temperature is lower
than S3 DIP switch
temperature.
[Default] Only one heat pump or
auxiliary heat can be operated.
The system makes judgments
according to the following rules:
1. When the outdoor
temperature is lower than the
S3 DIP switch temperature, the
compressor is not allowed to be
operated but auxiliary heat is
allowed.
2. When the outdoor
temperature is ≥S3 DIP
switch temperature +2°C the
compressor can be operated
but auxiliary heat cannot be
operated.
SW2-4 and S3 need to be
working together
7
Rotary
Switch S3
Sets the outdoor
temperature
limitation (for
auxiliary heating or
compressor)
Table A
8 SW3-3
Temperature
dierential to
activate second
stage auxiliary
heating (the GAP
of T1 and Ts)
Wire controller
demand with heat
pump+electric heat
working together
4°F (2°C) [Default] 6°F (3°C)
INDOOR UNIT
3
background
mrcool.com 26
26
No.
Dial
Code
Function ON OFF(Default) Note
Control Scenario Wired Controller
9
SW4-1
SW4-2
SW4-3
Electric heat
nominal CFM
adjustment
Available settings are 000/001/010/011. Each digit
corresponds to an individual switch position.
For example [SW4-1 OFF, SW4-2 ON, SW4-3 OFF]=010
10 SW4-4
Temperature
dierential to
activate third stage
auxiliary heating
(the GAP of T1 and
Ts) Wire controller
demand with heat
pump+electric heat
working together
6°F (3°C) [Default] 8°F (4°C)
Only valid for product which has
three stage auxiliary heating
11 SW5-3
L or Alarm relay
selection
L output 24V
or alarm relay
close only when
refrigerant sensor
fault or R454B
refrigerant leakage is
detected
[Default] R keep output 24v even
when refrigerant sensor fault
or R454B refrigerant leakage is
detected
12 SW5-4 R output selection
R stop output when
refrigerant sensor
fault or R454B
refrigerant leakage is
detected
[Default] R keep output 24v even
when refrigerant sensor fault
or R454B refrigerant leakage is
detected
Control Scenario Full 24V
1 SW1-2
Anti-cold blow
protection option
No [Default] Yes
2 SW1-3
Single cooling/
heating and cooling
options
Cooling [Default] Cooling & Heating
3 SW3-4
Fan speed of
cooling mode when
24V thermostat is
applied for
Turbo High
4
SW4-1
SW4-2
SW4-3
Electric heat
nominal CFM
adjustment
Available settings are 000/001/010/011. Each digit
corresponds to an individual switch position.
For example [SW4-1 OFF, SW4-2 ON, SW4-3 OFF]=010
5 S4-4 Default ON
[Default] For single
stage supplemental
heat, W1 and W2 are
connected
For dual stage supplemental
heat, W1 and W2 are controlled
independently.
6 S4-2
DH function
selection
[Default]
Dehumidication
control not available
Dehumidication feature is
enabled through thermostat
7 SW5-3
L or Alarm relay
selection
L output 24V
or alarm relay
close only when
refrigerant sensor
fault or R454B
refrigerant leakage is
detected
[Default] L output 24V or alarm
relay close when any fault is
detected
8 SW5-4 R output selection
R stop output 24V
when refrigerant
sensor fault or
R454B refrigerant
leakage is detected
[Default] R keep output 24V even
when refrigerant sensor fault
or R454B refrigerant leakage is
detected
INDOOR UNIT
3
background
mrcool.com27
Table A:
S3 S3 (°F) S3 (°C) S3 S3 (°F) S3 (°C)
0 OFF OFF 8 10 -12
1 -22 -30 9 18 -8
2 -18 -28 A 25 -4
3 -15 -26 B 32 0
4 -11 -24 C 36 2
5 -8 -22 D 39 4
6 -4 -20 E 43 6
7 3 -16 F 46 8
SW4-1
000 is default
000/001/010/011/100/101/110/111 , Internal
machines with dierent abilities, electric heating
and PSC classication for use
SW4-2
SW4-3
Function Combination Table of SW1-1 and SW1-4:
SW1 Control Type
IDU and ODU
Connection
Note
Wired Controller / 24V
Thermostat
(S1+S2) / 24V Connection Auto Discovery
Wired Controller S1+S2 Scenario 2
24V Thermostat S1+S2 Scenario 1
24V Thermostat 24V Thermostat Scenario 3
INDOOR UNIT
3
background
mrcool.com 28
28
OUTDOOR UNIT
4
4.1 Dimensional Drawing
Outdoor Unit Model Panel Plate
DIY-24-HP-C-230D25-O
D30
DIY-36-HP-C-230D25-O
Note: Check the corresponding dimensional drawings according to the panel plate.
D30 Platform
DIY-24-HP-C-230D25-O
DIY-36-HP-C-230D25-O
background
mrcool.com29
OUTDOOR UNIT
4
4.2 Install Location
4.3CapacityCorrectionforHeightDierence
Capacity
(Btu/h)
24K PipeLength(Ft/m)
Cooling 24.6/7.5 32.8/10 65.6/20 98.4/30 131.2/40 164/50
Height
dierence H
(ft/m)
Indoor
Higher
than
Outdoor
82/25 0.917 0.898 0.879
65.6/20 0.946 0.926 0.907 0.887
32.8/10 0.975 0.955 0.936 0.916 0.896
0 1.000 0.990 0.970 0.950 0.930 0.910
Outdoor
Higher
than
Indoor
-16.4/-5 1.000 0.990 0.970 0.950 0.930 0.910
-32.8/-10 0.990 0.970 0.950 0.930 0.910
-65.6/-20 0.970 0.950 0.930 0.910
-82/-25 0.950 0.930 0.910
Heating 24.6/7.5 32.8/10 65.6/20 9834/30 131.2/40 164/50
Height
dierence H
(ft/m)
Indoor
Higher
than
Outdoor
82/25 0.984 0.978 0.972
65.6/20 0.991 0.984 0.978 0.972
32.8/10 0.997 0.991 0.984 0.978 0.972
16.4/5 1.000 0.997 0.991 0.984 0.978 0.972
0 1.000 0.997 0.991 0.984 0.978 0.972
Outdoor
Higher
than
Indoor
-16.4/-5 0.992 0.989 0.983 0.977 0.970 0.964
-32.8/-10 0.981 0.975 0.969 0.963 0.957
-65.6/-20 0.967 0.961 0.955 0.949
-82/-25 0.953 0.947 0.941
background
mrcool.com 30
30
Capacity(Btu/h) 36K PipeLength(Ft/m)
Cooling 24.6/7.5 15/49.2 82/25 34/114.8 164/50 246/75
Height dierence
H (ft/m)
Indoor
Higher
than
Outdoor
98.4/30 0.889 0.851 0.787
65.6/20 0.924 0.898 0.859 0.795
32.8/10 0.959 0.933 0.907 0.868 0.803
16.4/5 0.995 0.969 0.942 0.916 0.876 0.811
0 1.000 0.974 0.947 0.921 0.881 0.815
Outdoor
Higher
than
Indoor
-16.4/-5 1.000 0.974 0.947 0.921 0.881 0.815
-32.8/-10 0.974 0.947 0.921 0.881 0.815
-65.6/-20 0.947 0.921 0.881 0.815
-30/-98.4 0.921 0.881 0.815
Heating 24.6/7.5 15/49.2 82/25 35/114.8 164/50 246/75
Height dierence
H (ft/m)
Indoor
Higher
than
Outdoor
98.4/30 0.964 0.945 0.915
65.6/20 0.976 0.964 0.945 0.915
32.8/10 0.988 0.976 0.964 0.945 0.915
16.4/5 1.000 0.988 0.976 0.964 0.945 0.915
0 1.000 0.988 0.976 0.964 0.945 0.915
Outdoor
Higher
than
Indoor
-16.4/-5 0.992 0.980 0.968 0.956 0.938 0.908
-35.8/-10 0.972 0.960 0.948 0.930 0.900
-65.6/-20 0.952 0.941 0.923 0.893
-30/-98.4 0.933 0.915 0.886
OUTDOOR UNIT
4
background
mrcool.com31
4.4 Noise Curves
Note:H= 0.5* height of the outdoor unit.
Notes:
• Sound is measured at 3.25ft (1.0m) Away from
center of the unit.
• Data is valid at free eld condition.
• Data is valid at nominal operation condition.
• Reference acoustic pressure OdB=20µPa.
• Sound level will vary depending on arrange
o factors such as the construction (acoustic
absorption coecient) of particular rooms in
which the equipment is installed.
• The operating conditions are assumed to be
standard.
OUTDOOR UNIT
4
background
mrcool.com 32
32
4.5 Refrigerant Cycle Diagrams
Capacity(Btu/h)
Pipe Size (Diameter:
Ø) inch(mm)
PipingLength(ft/m) Elevation(ft/m)
Additional
Refrigerant
Gas Liquid Rated Max. Rated Max.
24K 5/8 (16) 3/8 (9.52) 24.6/7.5 164/50 0 82/25 0.32oz/ft (30g/m)
Capacity(Btu/h)
Pipe Size (Diameter:
Ø) inch(mm)
PipingLength(ft/m) Elevation(ft/m)
Additional
Refrigerant
Gas Liquid Rated Max. Rated Max.
36K 5/8 (16) 3/8 (9.52) 24.6/7.5 546/75 0 98.4/30 0.32oz/ft (30g/m)
OUTDOOR UNIT
4
background
mrcool.com33
4.6 Electrical Wiring Diagrams
ODU Model ODU Wiring Diagram ODU Main Printed Circuit Board
DIY-24-HP-C-230D25-O 16022000040313 17122000048064
DIY-36-HP-C-230D25-O 16022000040650 17122300007152
OUTDOOR UNIT
4
background
mrcool.com 34
34
Outdoor unit wiring diagram: 16022000040313
OUTDOOR UNIT
4
background
mrcool.com35
Outdoor unit wiring diagram: 16022000040650
OUTDOOR UNIT
4
background
mrcool.com 36
36
Outdoor unit printed circuit board diagram: 17122000048064 & 17122000048066
OUTDOOR UNIT
4
background
mrcool.com37
No. Name NC# Meaning
1 Power Supply
CN6 Earth: Connect to Ground
CN7 N_in: Connect to N-line (230VAC Input)
CN8 L_in: Connect to L-line (230VAC input)
2 S CN2
S: Connect to indoor unit communication (230VAC
input)
3 4-WAY CN60 Connect to 4 way valve (Output: 230VAC)
4 AC-FAN CN5 Connect to AC fan
5 HEAT2 CN19 Connect to chassis heater (Output: 230VAC)
6 TP T4 T3 CN17
Connect to pipe temp. sensor T3, ambient temp. sensor
T4, exhaust temp. sensor TP (Output: 0~5VDC)
7 PMV CN18 Connect to Electric Expansion Valve
8 HEAT1 CN16 Connect to compressor heater (Output: 230VAC)
9 DC-FAN CN414 Connect to DC fan (Output: 0~310VAC)
10 TESTPORT CN23 Used for testing
11 FAN_IPM IPM501 IPM for DC fan
12 COMP_IPM IPM1 IPM for compressor
13
U CN27
Connect to compressor (Output: 0~310VAC)V CN28
W CN29
14 EE_PORT CN505 EEPROM programmer port
Note: This section is for reference only. Please take practicality as standard.
OUTDOOR UNIT
4
background
mrcool.com 38
38
Outdoor unit printed circuit board diagram: 17122300007152
OUTDOOR UNIT
4
background
mrcool.com39
No. Name NC# Meaning
1 COMPRESSOR
W
Connect to compressor (Output: 0~310VAC)V
U
2 DC-FAN1 CN32 Connect to DC fan (Output: 0~310VAC)
3 TESTPORT CN45 Used for testing
4 HEAT_Y CN38 Connect to compressor heater (Output: 230VAC)
5 4-WAY
CN37 Connect to 4 way valve 1 (Output: 230VAC)
CN25 Connect to 4 way valve 2 (Output: 230VAC)
CN42 Connect to 4 way valve 3 (Output: 230VAC)
6 HEAT_D CN24 Connect to chassis heater (Output: 230VAC)
7 POWER SUPPLY
CN11 N_in: connect to N-line (230 VAC input)
CN12 L-in: connect to L-line (230VAC input)
8
S-A
CN43
S: connect to indoor unit communication (230VAC
input)
S-B
S-C
S-D
S-E
S-F
9
TBH-IN TBH-OUT T3B
TF
CN9
Connect to cold plate inlet temp. sensor TBH-IN, cold
plate outlet temp. sensor TBH-OUT, condenser coil
middle temp. sensor T3B, Refrigerant tube inlet temp.
sensor TF
10 OLP TEMP. SENSOR CN30
Connect to compressor top temp. sensor (Output
0~5VDC)
11 T2B CN28
Connect to evaporator coil outlet temperature sensor
T2B
12 / CN27 Connect to key board CN1
13 T3 T4 TP CN26
Connect to condenser coil temp. sensor T3, ambient
temp. sensor T4, exhaust temp. sensor TP (Output:
0~5VDC)
14 H-PRO, L-PRO CN29
Connect to high and low pressure switch (pin1-pin2 &
pin3-pin4: 5VDC pulse wave)
OUTDOOR UNIT
4
background
mrcool.com 40
40
No. Name NC# Meaning
15
EEVA CN17
Connect to electric expansion valve (Output: 0~12VDC)
EEVB CN16
EEVC CN22
EEVD CN14
EEVE CN13
EEVF CN1
EEV1 CN1
EEV2 CN44
EEV3 CN3
16 H_YL CN49 Connect to high pressure sensor
17 DC-FAN2 CN10 Connect to DC fan (Output: 0~310VAC)
Note: This section is for reference only. Please take practicality as standard.
OUTDOOR UNIT
4
background
mrcool.com41
INSTALLATION
5
5.1 Installation Overview
background
mrcool.com 42
42
INSTALLATION
5
5.2 Location Selection
* Unit Location Selection can Refer to the
Installation Manual.
*DO NOT Install the Unit in the Following
Locations:
Indoor Unit:
• DO NOT install the indoor unit in a moist
environment. Excessive moisture can corrode
the equipment, electrical components, and
cause electrical shorts.
• Areas with strong electromagnetic waves.
• Coastal areas with high salt content in the air.
• Areas with oil drilling or fracking.
• Areas that store ammable materials or gas.
• Areas where there may be detergent or other
corrosive gases in the air such as bathroom or
laundry rooms.
• Areas where the air inlet and outlet may be
obstructed.
• Danger of explosion. Keep ammable
materials and vapors, such as gasoline, away
from the air handler.
Outdoor Unit:
• Near an obstacle that will block air inlets and
outlets.
• Near animals or plants that will be harmed by
hot air discharge.
• In a location that is exposed to large amounts
of dust.
• Near any source of combustible gas.
• Near a public street, crowded areas, or where
noise from the unit will disturb others.
Special Considerations for Extreme Weather:
If the Unit is Exposed to Heavy Wind:
• Install the unit so that the air outlet fan is at
a 90° angle to the direction of the wind. If
needed, build a barrier in front of the unit to
protect it from extremely heavy winds.
If the Unit is Frequently Exposed to Heavy
Rain or Snow:
• Build a shelter above the unit to protect
it from the rain or snow. Be careful to not
obstruct airow around the unit.
The Unit Must be Installed in a Location that
Meets the Following Requirements:
Indoor Unit:
background
mrcool.com43
Outdoor Unit:
Firm and solid - the location
can support the unit and will
not vibrate.
Noise from the unit will not
disturb other people.
Good air circulation and
ventilation.
Where snowfall is anticipated,
take appropriate measures to
prevent ice buildup and coil
damage.
The outdoor unit must be installed on risers of at least 15cm
(6in) in height or per local code to get the unit above the local
mean snowfall line.
Meets all spatial requirements shown in the Installation Space
Requirements above.
Rows of Series Installation:
L A
L ≤ H
L ≤ 1/2H
9.8in (25cm) or
more
1/2H < L ≤ H
11.8in (30cm)
or more
L>H Cannot be installed
The Relations Between H, A and L are as
Follows:
• Mark the positions for four expansion bolts
based on the dimensions chart.
• Pre-drill holes for expansion bolts.
• Hammer expansion bolts into the pre-drilled
holes.
• Remove the nuts from the expansion bolts
and place the outdoor unit on the bolts.
• Put a washer on each expansion bolt then
replace the nuts.
• Using a wrench, tighten each nut until snug.
If You Install the Unit on the Ground or
on a Concrete Mounting Platform Do the
Following:
Warning
When drilling into concrete eye protection is
recommended at all times.
If You Install the Unit on a Wall-Mounted
Bracket Do the Following:
• Pre-drill the holes for the expansion bolts.
• Place a washer and nut on the end of each
expansion bolt.
• Thread the expansion bolt through the holes
in the mounting brackets, put the brackets
into position, then hammer the expansion
bolts into the wall.
• Check that the mounting brackets are level.
INSTALLATION
5
background
mrcool.com 44
44
• Carefully lift the unit and place its mounting
feet onto the brackets.
• Install the rubber isolator pads to reduce
vibration and noise.
• Bolt the unit rmly to the brackets.
CAUTION
Make sure that the wall is made of solid brick,
concrete, or similarly strong material. The wall
must be able to support at least four times the
weight of the unit.
5.3 Indoor Unit Installation
Service Space for the Indoor Unit:
Horizontal Installation:
The outlet side pipe length 4.9ft/1.5m.
Vertical Installation:
When installed vertical (up ow or down ow) the
lower end of the air outlet needs to be connected
to the L-Shaped air duct and fastened by screws.
Spacing:
Vertical Installation:
Horizontal Installation:
Installation of the Main Body:
The units can be installed in a vertical (down
ow and up ow) and horizontal (right or left)
conguration.
Vertical Installation:
INSTALLATION
5
background
mrcool.com45
Horizontal Installation:
Note: For horizontal installation, a secondary drain
pan (not supplied) must be installed.
Note: Vertical up and horizontal left installations do
not need the evaporator coil positioned changed.
Follow the Following Steps to Perform Down
Flow and Horizontal Right Installations:
1. Open the upper cover.
2. Open the cover of the electronic control box.
3. Connect the wire according to the wiring
diagram.
4. Connect the piping and install the drainage
pipes.
1.Removethelterdoorandtakethelter
out.
2. Remove the upper cover assembly.
INSTALLATION
5
background
mrcool.com 46
46
3. Remove the evaporator cover plate.
4. Indication of the position of each
temperature sensor sensors of the
evaporator.Conrmyourmodelbelow.
24K
36K
5. Unplug temperature sensors T1,T2,
refrigerant detection sensor from the control
board.
Sensors:
T1: Room temperature
T2: Evaporator central plug
6. Remove T1,T2, refrigerant detection sensor
wire ties.
INSTALLATION
5
background
mrcool.com47
7. Take the evaporator and drain pan and
rotate 180°.
8.Adjustthemountingpartsposition
according to the direction of the equipment.
9. Reinstall the evaporator and drain pan.
10. Reinstall T1 and T2 sensor plugs and tie up
the sensor wires.
Note: The wire body needs to pass through the wire
groove from the drain pan and be stuck on the hook
of the drain pan.
11. The evaporator is assembled in place.
INSTALLATION
5
background
mrcool.com 48
12.Usecabletiestoxtheroomtemperature
sensorasshowninthegure.
13. Reinstall evaporator cover plate
14. Connect the wire according to the wiring
diagram
15. Reassemble the upper cover and reinstall
theltercoverplate.
16. Connect the pipes and install the drainage
pipes.
Notice on Purchasing Pipes:
Installation requires pvc pipe or other suitable
material per local and national codes. Piping can
be purchased at your local hardware store or
dealer.
CAUTION
• Insulate all piping to prevent condensation.
(If not insulated it can lead to water damage).
• The drain pipe is used to drain water away
from the unit. If the drainpipe is bent or
installed incorrectly water may leak and
cause a water-level switch malfunction.
• In HEAT mode, the outdoor unit will
discharge water. Ensure that the drain
hose is placed in an appropriate area to
avoid water damage and icy conditions on
walkways.
• DO NOT pull the drain pipe forcefully. This
can disconnect it.
Note: If installed above a nished living space,
a secondary drain pan (as required by may
building codes) must be installed under the unit
and its condensate drain line must be routed to a
location such that the user will see the condensate
discharge.
Warning
• After removal of drain pan plug(s), check
drain hole(s), to verify that the drain opening
is fully open and free of any debris. Also
check to make sure that no debris have
fallen into the drain pan during installation
that may plug up the drain opening. Seal
around the exiting drain pipe, liquid, and
suction lines to prevent inltration of humid
air.
• On units of this style where the blower
"draws" rather than "blows' air through
the coil, traps must be installed in the
condensate drain lines (primary and
auxiliary, if used). Traps prevent the blower
from drawing air through the drain lines into
the air supply.
Pipe Installation:
INSTALLATION
5
background
mrcool.com49
Vertical Installations:
• These unit operate with a negative pressure
so a drain trap (p-trap) is required. The trap
needs to be installed as close to the unit as
possible. Make sure the top of the trap is
below the connection pan to allow complete
drainage of the pan.
Note: Horizontal runs must also have an anti-siphon
air vent (standpipe) installed ahead of the horizontal
run to eliminate air trapping.
Notes on Drainpipe Installation:
• The gure shows how to trap or plug all drains
during vertical discharge.
• The gure shows how to trap or plug all drains
during right-hand discharge.
• The seal plugs are supplied as accessories and
should be screwed tightly only by hand.
• Incorrect installation could cause water to ow
back into the unit and ood.
CAUTION
The drainpipe outlet should be at least 1.9in
(5cm) above the ground. If it touches the ground
the unit may become blocked and malfunction.
Before bolting the outdoor unit in place, you must
install the drain joint at the bottom of the unit.
Note: There are two dierent types of drain joints
depending on the type of outdoor unit.
If the Drain Joint Comes with a Rubber Seal
(See Fig. A), Do the Following:
1. Fit the rubber seal on the end of the drain
joint that will connect to the outdoor unit.
2. Insert the drain joint into the hole in the base
pan of the unit.
3. Rotate the drain joint 90° until it clicks in place
facing the front of the unit. For some panel
plates you will need to use a tool.
4. Connect a drain hose extension (not included)
to the drain joint to redirect water from the
unit during heating mode.
If the Drain Joint Doesn't Come with a Rubber
Seal (See Fig. B) Do the Following:
1. Insert the drain joint into the hole in the base
pan of the unit. The drain joint will click in
place.
2. Connect a drain hose extension (not included)
to the drain joint to redirect water from the
unit during heating mode.
Installing Drain Joint:
Anchor Outdoor Unit:
The outdoor unit can be anchored to the ground
or to a wall-mounted bracket with bolt (M10).
Prepare the installation base of the unit according
to the dimensions below.
The following is a list of dierent outdoor unit
sizes and the distance between their mounting
feet.
5.4 Outdoor Unit Installation
INSTALLATION
5
background
mrcool.com 50
Platform Unit D A B C
D30
inch 16.14 26.50 15.87 17.9
mm 410 673 403 455
5.5 Refrigerant Pipe Installation
Maximum Length and Drop Height:
Ensure that the length of the refrigerant pipe,
the number of bends, and the drop height
between the indoor and outdoor units meets the
requirements shown in the following table.
Capacity
Max. Length
(ft/m)
Max. Elevation
(ft/m)
24k 164/50 82/25
36k 246/75 98.4/30
CAUTION
1. The capacity test is based on the standard
length and maximum permissive length is
based on the system reliability.
2. Oil traps.
• If oil ows back into the outdoor unit's
compressor, this might cause liquid
compression or deterioration of oil return.
Oil traps in the rising gas piping can
prevent this.
• An oil trap should be installed every 20ft
(6m) of vertical suction line riser (<36kBtu/h
unit).
• An oil trap should be installed every
32.8ft (10m) of vertical suction line riser
(≥36kBtu/h unit).
Connection of Quick Connect
Refrigerant Lines (Indoor Unit):
Important Information
• Closely follow the detailed instructions
for connecting the refrigerant lines to the
indoor and outdoor unit. Failure to install in
accordance with these installation instructions
may void the warranty.
• Do not remove the sealing caps and stoppers
until you are ready to install the line sets.
• To prevent leaks, ensure that the quick-
connector threading and valve body is free
of dirt and contaminates prior to assembly.
Moisture or foreign material may impact
function leading to refrigerant loss or
premature failure.
• Only install refrigerant lines during dry
weather.
• The refrigerant lines cannot be plastered over.
• Care should be taken to prevent the release of
refrigerant to the environment while installing
or servicing the equipment.
• Wear proper PPE when handling refrigerant (
gloves, safety glasses, etc.)
• Do not smoke during installation.
• The equipment must never be operated
without fully completing the refrigerant line
connections.
• Follow the required tightening torques
dened in the table based on the connector
size. Under-tightening may result in a
refrigerant leak while over-tightening could
damage components.
Note:
• The quick-connect installation method is only
used for models that have been pre-charged
with refrigerant and equipped with quick-
connects.
• Before you continue read the following
instructions carefully.
INSTALLATION
5
background
mrcool.com51
Step 1:
• When you are ready to install the refrigerant
line remove the plastic seals/caps from the
indoor unit and the refrigerant line.
• Align the quick connector with the valve of the
indoor unit ensuring that they are the same
size.
• Tighten them with two wrenches (one to x
the valve and another to tighten the quick
connect) according to the torque table.
• Screw the quick connect line onto the quick
connector and hand tighten. Be careful not to
cross thread.
Step 2:
Using two open-ended wrenches, tighten the
quick-connect nut "2" on the line according to the
torque specication in the table below, be careful
to not loosen the connection "1" to the valve
body.
Step 3:
Ensure that the screw connectors do not cross
thread as you tighten them and work quickly.
After completing steps 1-3, check that all the
connections are sealed correctly by using a leak
detection spray or soapy water. If any bubbles
form, the system has a leak and the screw
connectors must be re tightened using an open-
ended wrench.
Note: Since the coupling works with tapping rings, it
may leak if you undo and reconnect the pipes.
Step 4:
Remove the cover on the top valve using a 19mm
open-ended wrench. Open the valve by turning
it counter clockwise as far as it will go using a
5mm Allen key. The valve will now be opened.
If the valve is not fully opened the system can
malfunction and suer damage. Screw the cover
back on to the top valve and tighten it well to
ensure that it is properly sealed.
INSTALLATION
5
background
mrcool.com 52
Connection of Quick Connect
Refrigerant Lines (Outdoor Unit):
Step 1:
First remove the service valve cover on the
outdoor unit as shown below.
Note: Before connecting the quick joint connecting
pipe, use a wrench to conrm the fast joint and the
shut-o valves are securely fastened in the direction
indicated in the diagram. If it is loose at all it needs
to be tightened to prevent leakage. During the
assembly process, if there is reverse disassembly
operation, the above operation needs to be
performed to tighten it.
Step 2:
When you are ready to install the refrigerant line,
remove the plastic seals/caps from the outdoor
unit and refrigerant line.
Step 3:
Align the refrigerant quick-connect line with the
threaded connector on the outdoor unit ensuring
they are the same size. Be careful not to cross
thread, screw the line connector onto the quick-
connect and hand-tighten.
Warning
Before connecting the pipes, ensure that the
quick connectors are tightened.
Note: The refrigerant pipes must be connected with
the valves with as little stress as possible.
Step 4:
Using two open-ended wrenches, tighten the
quick-connect nut "2" on the line according to the
torque specication in the table below, be careful
to not loosen the connection "1" to the valve
body.
Step 5:
Important: The conical ring on the valve has
an important sealing function together with the
sealing seat in the caps. Ensure that you do not
damage the cone and that you keep the cap
free of dirt and dust. After completing steps 1-4,
check that all the connections are sealed correctly
using leak detection spray or soapy water. If any
bubbles form, the system has a leak and the
screw connectors must be re-tightened using an
open-ended wrench.
Step 6:
Remove the cover on the top valve using a 19mm
open-ended wrench. Open the valve by turning
it counter clockwise as far as it will go using a
5mm Allen key. The valve will now be opened.
If the valve is not fully opened the system can
malfunction and suer damage. Screw the cover
back on to the top valve and tighten it well to
ensure that it is properly sealed.
INSTALLATION
5
background
mrcool.com53
Step 7:
Remove the cover on the bottom valve using
a 19mm open-ended wrench. Open the valve
by turning it counter clockwise as far as it will
go using a 5mm Allen key. The valve will now
be opened. If the valve is not fully opened the
system can malfunction and suer damage.
Screw the cover back on to the top valve and
tighten it well to ensure that it is properly sealed.
Step 8:
After completing steps 1-7, check that all
connections are sealed correctly using leak
detection spray or soapy water. If any bubbles
form, the system has a leak and the screw
connectors must be re-tightened using an open-
ended wrench.
Step 9:
With the system now functional, check the system
again for signs of leaks (as in step 7) except
while operating in both cooling and heating
modes to allow proper operating pressures to
be generated. If any bubbles form, the system
has a leak and the screw connectors must be re-
tightened until no leaks exists.
Coupling
Size (Last
2 Part
Numbers)
Pound Force Foot
(Lbs Ft)
Newton Meter
(Nm)
-06 18-20 24.4-27.1
-09 30-35 40.6-47.4
-12 45-50 61.0-67.7
-16 60-65 81.3-88.1
Quick Connect Torque Specs:
5.6 Vacuum Drying & Leakage Testing
Purpose of Vacuum Drying:
• Eliminates moisture in the system to prevent
the phenomena of ice-blockage and copper
oxidation.
-Ice-blockages will cause abnormal operation
of system while copper oxidation will damage
the compressor.
• Eliminating non-condensible gas(air) in the
system will prevent the components from
oxidizing, pressure uctuation, and poor heat
exchange during operation of the system.
Operation Procedure for Vacuum
Drying:
Due to dierent construction environments, two
kinds of vacuum drying ways could be chosen,
namely ordinary vacuum drying and special
vacuum drying.
Ordinary vacuum drying:
1. When conducting rst vacuum drying, connect
a pressure gauge to the infusing mouth of
gas pipe and liquid pipe and keep the vacuum
pump running for 1 hour (vacuum degree of
vacuum pump shall be reached at -755mmHg).
2. If the vacuum degree of the vacuum pump
could not reach -755mmHg after 1 hour of
drying it indicates that there is moisture or
leakage in the pipeline of the system and
needs to go on with drying for half an hour.
3. If the vacuum degree of the vacuum pump still
cannot reach -755mmHg after 1.5 hours of
drying check to see if there is a leak.
4. Leakage test: After the vacuum degree reaches
-755mmHg stop vacuum drying and keep the
pressure for 1 hour. If the indicator of the
vacuum gauge does not go up it is good. If it
does go up it indicates that there is moisture or
a leak.
INSTALLATION
5
background
mrcool.com 54
Special Vacuum Drying:
The special vacuum drying method shall be
adopted when:
1. Finding moisture during ushing refrigerant
pipe.
2. Conducting construction on a rainy day (Rain
water might get into pipeline).
3. Construction period is long (Rain water might
get into pipeline).
Procedures of special vacuum drying are as
follows:
1. Vacuum drying for 1 hour.
2. Vacuum damage, lling nitrogen to reach
0.5Kgf/cm².
-Because nitrogen is a dry gas, vacuum damage
could achieve the of vacuum drying, but this
method cannot achieve drying thoroughly when
there is too much moisture. Therefore special
attention shall be drawn to prevent the entering
of water and the formation of condensate water.
3. Vacuum drying again for half an hour.
-If the pressure reached -755mmHg, start
pressure leakage test. If it cannot reach the value,
repeat vacuum damage and vacuum drying again
for 1 hour.
4. Leakage test: After the vacuum degree reaches
-755mmHg, stop vacuum drying and keep
the pressure for 1 hour. If the indicator of
the vacuum gauge does not go up it is good.
If it keeps going up it indicates that there is
moisture or a leak.
5.7 Additional Refrigerant Charge
• After the vacuum drying process is carried
out, the additional refrigerant charge process
needs to be performed.
• The outdoor unit is factory charged with
refrigerant. The additional refrigerant charge
volume is decided by the diameter and length
of the liquid pipe between the indoor and
outdoor unit. Refer to the following formula to
calculate the charge volume.
Diameter of
liquid pipe
(inch(mm))
Formula
R545B
Ø1/4 (Ø6.35)
V=0.32(30)oz/ft(g/m)x(L-
standard pipe length)
Ø3/8 (Ø9.52)
V=0.7(65)oz/ft(g/m)x(L-
standard pipe length)
V: Additional Refrigerant charge volume.
L: The length of the liquid pipe.
Note:
• Refrigerant may only be charged after the
performed vacuum drying process.
• Use electronic scale or uid infusion apparatus
to weigh the refrigerant to be charged. Be
sure to avoid excess refrigerant charge, it may
cause liquid hammering of the compressor.
• The refrigerant should be charged in a liquid
state.
• After nishing the refrigerant recharge
process, check whether there is refrigerant
leakage at the connection joints(Using a leak
detector or soapy water).
5.8 Piping Insulation
Insulation of Refrigerant Pipe:
1. Operational Procedure of Refrigerant Pipe
Insulation:
Cut the suitable pipe > insulation (except joint
section) > are the piping > piping layout and
connection > vacuum drying > insulate joints.
2. Purpose of Refrigerant Pipe Insulation:
• During operation the temperature of the gas
pipe and liquid pipe will be very hot/cold.
Therefore insulation is necessary as without it
will decrease performance and can cause the
compressor to burnout.
• The gas pipe temperature is low during
cooling operation, if lacking insulation it will
condensate.
• The gas pipe temperature is high (generally
122°F -212°F (50°C-100°C)) in heating
operating. If lacking insulation it can result in
burns.
3. Insulation Material Selection for
Refrigerant Pipes:
• Insulation should withstand 248°F (120°C)
• Choose insulation materials according to local
codes.
• The thickness of the insulation layers
needs to be above 10mm. If in a hot or wet
environment the layer on insulation will need
to be thicker.
4. Highlights of insulation construction:
• The gas pipe and liquid pipe needs to be
insulated separately. (If the gas and liquid pipe
were insulated together it will decrease the
performance of the system).
INSTALLATION
5
background
mrcool.com55
• The insulation material at jointing pipes shall
be 1.96in (5cm)~3.93in (10cm) longer than the
gap of the insulation material.
• Insulation material at the joint needs to
be inserted into the gap of the insulation
material.
• Insulation material at the joint needs to be
banded to the gap and liquid pipe tightly.
• The linking part should by glued together.
• Make sure not to bind the insulation material
tightly, it can extrude air out of the material
causing it to age faster.
Insulation of Drain Line:
1. Operational Procedure of Refrigerant Pipe
Insulation:
Cut the suitable pipe > insulation (except joint
section) > Piping layout and connection >
drainage test > insulate joints.
2. Purpose of Drainage Pipe Insulation:
The temperature of the condensate drainage
water is low. If there is insucient insulation it
will sweat and leak causing damage to structures.
3. Insulation Material Selection for Drainage
Pipe:
• The insulation material should be ame
retardant material and the ame retardant of
the material should be selected according to
the local codes.
• Thickness of the insulation is usually above
0.39in (10mm).
• Use specic glue to paste the seam of
insulation material and then bind with
adhesive tape. The width of the tape shall be
no less than 1.97in (5cm). Make sure it is rm
to avoid sweating.
4. Installation and Highlight of Insulation
Construction:
• A single piece of pipe should be insulated
before connecting to another pipe, the joint
should be insulated after the drainage test.
• There should be no insulation gap between
the insulation material.
5.9 Auxiliary Heat
Note:
Installation must be performed by a licensed
contractor. Please make necessary precaution
when performing the installation operation.
Preparations for Installation:
Before installation, please conrm the electric
auxiliary heat module and supplied accessories
are complete and free of any damage. Do not
attempt to install if there is damage present.
Accessories:
Name Quantity
Manual 2
Foam Gasket 1
Screws 7
Silicone Breaker Cover 1
Electric Auxiliary Heating Diagram 1
Circuit Breaker Label 1
Model size selection:
For installations requiring supplemental heating,
the optional electric heat module is available
in sizes from 5kW to 20kW to accommodate
appropriate sizing given to the specic heat load
and electrical requirements of each installation.
Please refer to the following table below for
selections of available sizes of each model to
avoid improper matching.
Indoor
Unit Model
(Btu/h)
5kW 8kW 10kW 15kW 20kW
24K √ √ √ √ x
36K √ √ √ √ √
1. Open the upper cover.
Auxiliary heat installation and wiring:
INSTALLATION
5
background
mrcool.com 56
2. Use tools to remove the knock-out holes of
the upper cover.
3. Remove the terminal block and power
wires, loosen the screws, and remove the
electric auxiliary heating cover.
4. Install the electric auxiliary heating
assembly and make sure the support rails
lock into the support holes in the back of the
cabinet.
5. Tighten the mounting screws.
6. Wire according to the wiring nameplate.
Note: Apply the wiring diagram to the inside cover
after wiring is completed for future reference and
maintenance.
• Plug the electric heating plugs into CN11 and
CN12 into the main board.
7. Install the upper cover and the silicone
breaker cover.
8. After installing the electric auxiliary heat
module, apply the circuit breaker label near
thesiliconebreakercoverthatwasjust
applied.
INSTALLATION
5
background
mrcool.com57
ConrmationofIndoorUnit:
After the electric heating wiring is connected,
please conrm before powering on:
• Check all wiring and ensure secure connection
of all wiring.
• Ensure that the wire size is properly selected
per NEC or local codes.
Specications
Number
of circuit
breakers
Number
of relays
Number
of power
cord
groups
Number
of power
cord
grounding
screws
5kW 1 1 2 2
8kW 1 1 2 2
10kW 1 2 2 2
15kW 2 3 3 3
20kW 2 4 3 3
Note:
• Electric auxiliary heating wiring diagrams are
packed with the accessory.
• If the branch circuit wire length exceeds
100ft, consult NEC 210-19a to determine the
maximum wire length. Use 2% voltage drop.
5.10 Electrical Wiring
• All eld wiring construction should be nished
by a qualied electrician.
• Air conditioning equipment should be
grounded according to the local electrical
regulations.
• A current leakage protection switch should be
installed.
• Do not connect the power wire to the terminal
of the signal wire.
• When the power wire is parallel with the signal
wire put the wires in their own conduit and
gap them by 11.8in (300mm).
• According to the table in the indoor wiring
make sure the selected wiring is not smaller
than shown in the table.
• Select dierent colors for dierent wire
according to relevant regulations.
• DO NOT use metal conduit in a place with acid
or alkali corrosion. Switch to a plastic wire
tube to replace it.
• DO NOT have a joint in the conduit, if one is
required place into a connection box.
• The wiring with dierent voltage should not be
in the same conduit.
• Ensure that the color of the wires of the
outdoor terminal number and indoor
correspond.
Highlights of Electrical Wiring:
Specicwiringmethod:
Connection Method A:
Refer to the wiring method of internal and
external machine communication:
A.
B.
Connection Method B:
To use a 24V thermostat you need to refer to the
following wiring:
A.
B.
Note: The wiring method of the thermostat and the
internal machine refers to the wiring of the non-
communication scheme.
INSTALLATION
5
background
mrcool.com 58
Optional Function Wiring:
CondensateOverowSwitch:
The unit will accommodate a remote condensate
overow switch. To enable, remove jumper J7
and connect he installer provided condensate
overow device to CN23 per below. When an
overow condition is present the device should
open connection signaling the unit to turn o the
system.
Fault Warning:
Alarm output:
An alarm output (CN33) can be utilized if actions
are required when a fault is present. This is a
passive outlet port so you will need to input a
voltage signal. The relay is normally-open for
normal operation and closed when a fault is
active.
HumidierControl:
To connect a humidier, utilize the passive signal
"WORK" output (CN23) port as well as the G and
C wires on the controller and wire the humidistat
and humidier per the wiring diagram below.
When the fan is running the CN23 relay will be
closed which will allow power to the humidier
when the humidistat is below humidity set point.
If the thermostat or zone controller has a HUM
interface, connect the humidier directly to the
HUM and C ports.
UV, Fresh air, or Negative Ion Wiring:
The WORK port is linked with the fan. When the
fan is running the relay is closed; if an active 24V
signal is required it can be directly connected to
the G and C ports.
Control Logic:
Indoor Unit Connector:
Connector Purpose
R 24V Power Connection
C Common
G Fan Control
Y1 Low Cooling
Y/Y2 High Cooling
B Heating Reversing Valve
W Heating Control
W1 Stage 1 Electric Heating
W2 Stage 2 Electric Heating
E/AUX Emergency Heating
DH/BK Dehumidication/ZoningControl
DS Reserved Signal
L System Fault Signal
KEY1 Instructions (Wired Controller
Only):
• Press KEY1 to enter the forced automatic
mode, press KEY1 again to enter the forced
cooling mode (LED displays FC), and press
KEY1 again to shut down.
• Long press KEY1 under forced cooling mode
(LED displays FC) for 5 seconds to enter forced
cooling mode.
Outdoor Unit Wiring:
1. Remove the wire cover from the unit by
loosening the 3 screws.
2. Remove the caps on the conduit panel.
3. Mount the conduit tubes (not included) on the
conduit panel.
4. Properly connect both the power supply
and low voltage lines to the corresponding
terminals on the terminal block.
5. Ground the unit in accordance with local
codes.
6. Be sure to leave some slack in the wiring for
connections.
INSTALLATION
5
background
mrcool.com59
Warning
Isolate the power supply leads and
communication leads from touching each other
or crossing.
5.11 Test Operation
1. The test operation must be carried out
after the installation has been completed.
2. Pleaseconrmthefollowingpointsbefore
the test operation.
• The indoor and outdoor unit are installed
properly.
• Piping and wiring are properly connected.
• Make sure that there are no obstacles near
the inlet and outlet of the unit that might
cause poor performance or malfunction.
• The refrigerant system has no leaks.
• The drainage system is clear and draining to a
safe location.
• The heating insulation is properly installed.
• The grounding wires are properly connected
• The length of the piping and the added
refrigerant capacity has been recorded.
• Power voltage is correct for the system.
Indoor unit
• Double check to see if the room temperature
is being registered correctly.
• Ensure the manual buttons on the indoor unit
work properly.
• Check to see that the drainage system is clear
and draining smoothly.
• Ensure there is no vibration or abnormal
noise during operation.
Outdoor Unit
• Check to see if the refrigeration system is
leaking.,
• Make sure there is no vibration or abnormal
noise during operation.
• Ensure the wind, noise, and water generated
by the unit do not disturb your neighbors or
pose a safety hazard.
4. Drainage test
A. Ensure the drain pipe ows smoothly. New
buildings should perform this test before
nishing the ceiling.
B. Turn on the main power and run the unit in
COOL mode.
C. Check to see that the water is discharged. It
may take up to one minute before the unit
begins to drain depending on the drain pipe.
D. Stop the unit (turn o power and reinstall the
test cover).
CAUTION
Failure to perform the test run may result in
system damage, property damage, or personal
injury.
3. Test run instructions.
D. Open both the liquid and gas valves.
E. Turn ON the main power and allow the unit to
warm up.
F. Set the air conditioner to COOL mode and
check the following points:
INSTALLATION
5
background
mrcool.com 60
6
REFRIGERANT RECHARGE
1. Close both 2 and 3 way valves.
2. Slightly connect the handle Lo charge hose to
the 3 way service port.
3. Connect the charge hose to the valve at the
bottom of the refrigerant cylinder.
4. If the refrigerant is R410A/R32, invert the
cylinder to ensure a complete liquid charge.
5. Open the valve at the bottom of the cylinder
for 5 seconds to purge the air in the charge
hose, then fully tighten the charge hose with a
push pin Handle Lo to the service port of the
3-way valve.
6. Place the charging cylinder onto an electronic
scale and record the starting weight.
7. Fully open the Handle Lo manifold valve,
2-way and 3-way valves.
Procedure:
8. Operate the air conditioner in cooling mode to
charge the system.
9. When the electronic scale displays the correct
weight (refer to the gauge and the pressure of
the low side to conrm, the value of pressure
refers to chapter System Pressure Table) turn
o the air conditioner then close Lo manifold
valve and cylinder valve and disconnect the
charge hose from the 3-way service port
immediately.
10. Mount the caps back to the 2-way and 3-way
valves.
11. Use a torque wrench to tighten the caps to a
torque spec of 13.28ft. lbs (18Nm).
12. Check for any leaks.
background
mrcool.com61
PRODUCT FEATURES
7
7.1 24V Signal Chart
Mode Priority G Y1 Y/Y2 B W W1 W2 E/AUX DH Fan Speed Display
OFF / 0 0 0 0 0 0 0 0 * OFF 00
FAN 7 1 0 0 * 0 0 0 0 * Low 01
Cooling Stage 1
6
* 1 0 0 0 0 0 0 1 Mid 02
Cooling Stage 2 * * 1 0 0 0 0 0 1 High 03
Dehumidication 1 * 1 0 0 0 0 0 0 0 Low 04
Dehumidication 2 * * 1 0 0 0 0 0 0 Low 05
Heat Pump Stage 1
5
* 1 0 1 0 0 A 0 1 Mid 06
Heat Pump Stage 2 * * 1 1 0 0 A 0 1 High
07
Heat Pump Stage 2 * * * * 1 0 A 0 1 High
Electric Auxiliary Heat
Module 1
3
* 0 0 * 0 1 A 0 * Turbo
08
Electric Auxiliary Heat
Module 2
* 0 0 * 0 0 1 0 * Turbo
Electric Auxiliary Heat
Module 1 & 2
* 0 0 * 0 1 1 0 * Turbo 09
Heat Pump Stage 1 +
Electric Auxiliary Heat
Module 1
1
* 1 0 1 0 1 0 0 1 Turbo
10
Heat Pump Stage 1 +
Electric Auxiliary Heat
Module 2
* * 0 1 0 0 1 0 1 Turbo
Heat Pump Stage 2 +
Electric Auxiliary Heat
Module 1
* * 1 1 0 1 0 0 1 Turbo
Heat Pump Stage 2 +
Electric Auxiliary Heat
Module 1
* * * * 1 1 0 0 1 Turbo
Heat Pump Stage 2 +
Electric Auxiliary Heat
Module 2
* * 1 1 0 0 1 0 1 Turbo
Heat Pump Stage 2 +
Electric Auxiliary Heat
Module 2
* * * * 1 0 1 0 1 Turbo
Heat Pump Stage 1 +
Electric Auxiliary Heat
Module 1 & 2
* 1 0 1 0 1 1 0 1 Turbo
11
Heat Pump Stage 2 +
Electric Auxiliary Heat
Module 1 & 2
* * 1 1 0 1 1 0 1 Turbo
Heat Pump Stage 2 +
Electric Auxiliary Heat
Module 1 & 2
* * * * 1 1 1 0 1 Turbo
Emergency Heat 1 * * * * * * * 1 * Turbo 12
Heating Zone Control
2
* 1 0 1 0 * * 0 0 Low
13Heating Zone Control * * 1 1 0 * * 0 0 Low
Heating Zone Control * * * * 1 * * 0 0 Low
Note:
1: 24V signal
0: No 24V signal
*: 1 or 0
The AHU will turn o if the 24V input cannot meet the table.
background
mrcool.com 62
PRODUCT FEATURES
7
7.2 Safety Features
Compressor Three-Minute Delay at
Start:
Compressor functions are delayed for up to
ten seconds upon the rst startup of the unit,
and are delayed for up to three minutes upon
subsequent unit restarts.
AutomaticShutoBasedonDischarge
Temperature:
If the compressor discharge temperature
exceeds a certain level for nine seconds, the
compressor ceases operation.
Inverter Module Protection:
The inverter module has an automatic shuto
mechanism based on the unit's current, voltage,
and temperature. If the automatic shuto
is initiated, the corresponding error code is
displayed on the indoor unit and the unit ceases
operation.
Indoor Fan Delayed Operation:
If the unit is in heating mode the indoor fan is
regulated by the anti-cold wind function.
Compressor Preheating:
Preheating is automatically activated when the T4
sensor is lower than the setting temperature.
Sensor Redundancy and Automatic
Shuto:
• If one temperature sensor malfunctions,
the air conditioner continues operation
and displays the corresponding error code
allowing for emergency use.
• When more than one temperature sensor
is malfunctioning the system will cease
operation.
7.3 Basic Functions
Abbreviation Element
T1 Indoor room temperature sensor
T2 Evaporator coil temperature sensor
T3 Condenser coil temperature sensor
T4
Outdoor ambient temperature
sensor
TP Compressor discharge temperature
Tsc Adjusted setting temperature
TCDE1 Exit defrost temperature1
TCDE2
Exit defrost temperature2 (maintain
for a period of time)
TIMING_
DEFROST_
TIME
Enter defrost time
Unit Element Abbreviations:
In this manual, such as CDIFTEMP, HDIFTEMP2,
TCDE1, TCDE2,...etc, they are well-setting
parameter of EEPROM.
Fan Mode:
When Fan Mode is Activated:
• Temperature control is disabled and no
temperature setting is displayed.
• The indoor fan speed can be set to low,
medium, high, turbo, and auto.
• The outdoor fan and compressor stop.
• Auto fan: In fan-only mode the system
operates the same as auto fan in cooling
mode with the temperature set at 75°F (24°C).
• Under 24V control, when only G signal is
available when switching from heating mode
or emergency heating mode to fan mode,
T4<50°F (10°C), the heating mode is sent
to the outdoor; when T4>53.6°F (12°C), the
normal outdoor control if resumed, the fan
mode is sent to the outdoor
background
mrcool.com63
Cooling Mode:
Compressor Control:
1. Reach the congured temperature
• If the following conditions are satised the
compressor ceases operation.
• Calculated frequency (fb) is less than 0Hz.
• Reach temperate stop protective time is
more than 10 minutes.
• Indoor room temperature (T1) is lower than
or equal to (Tsc-1°F (-0.5°C)).
2. If one of the following conditions is satised,
not judge protective time.
• Compressor running frequency is more than
test frequency.
• When compressor running frequency is
equal to test frequency, outdoor ambient
temperature (T4) is more than 59°F (15°C),
or outdoor ambient sensor (T4) fault.
• Change in the setting temperature.
• Turning on/o turbo or sleep function.
• Various frequency limit shutdown occurs.
Indoor Fan Control:
1. In cooling mode, the indoor fan operates
continuously. The fan speed can be set to low,
medium, high, turbo, and auto.
2. Auto fan action in cooling mode:
• Descent curve
• When T1-Tsc is lower than 6.3°F (3.5°C), the
fan speed reduces to high.
• When T1-Tsc is lower than 1.8°F (1°C), the fan
speed reduces to medium.
• When T1-Tsc is lower than 0.9°F (0.5°C), the
fan speed reduces to low.
• Rise curve
• When T1-Tsc is higher than or equal to 1.8°F
(1°C), the fan speed increases to medium.
• When T1-Tsc is higher than or equal to 2.7°F
(1.5°C), the fan speed increases to high.
• When T1-Tsc is higher than or equal to 7.2°F
(4°C) the fan speed increases to turbo.
• The outdoor unit will be run at dierent fan
speeds according to T4 and compressor
running frequency.
• For dierent outdoor units, the fan speeds are
dierent.
Outdoor Fan Control:
Condenser Temperature
Protection:
• O: Compressor stops.
• Decrease: Decrease the running frequency to
the lower level at 0.04Hz/s.
• Hold: Keep the current frequency.
• Increase: Increase the running frequency to
the higher level at 1Hz/s.
• Resume: No limitation for frequency.
Evaporator Temperature
Protection:
• O: Compressor stops.
• Decrease: Decrease the running frequency to
the lower level per 1 minute.
• Hold: Keep the current frequency.
• Resume: No limitation for frequency.
PRODUCT FEATURES
7
background
mrcool.com 64
Heating Mode:
Compressor Control:
1. Reach the congured temperature.
• If the following conditions are satised, the
compressor ceases operation.
• Calculated frequency(fb) is less than 0Hz.
• Reach temperature stop protective time is
more than 10 minutes.
• T1 is higher than or equal to Tsc + 1°F (0.5°C).
2. If one of the following conditions is satised,
not judge protective time.
• Compressor running frequency is more than
test frequency.
• Compressor running frequency is equal
to test frequency, outdoor ambient
temperature (T4) is more than 59°F (15°C), or
outdoor ambient sensor (T4) fault.
• Change setting temperature.
• Turning on/o turbo or sleep function.
3. When the current is higher than the
predened safe value, surge protection is
activated causing the compressor to cease
operation.
Indoor Fan Control:
1. In heating mode, the indoor fan operates
continuously. The fan speed can be set to low,
medium, high, turbo, and auto.
• Anti-cold air function
• The indoor fan is controlled by the indoor
temperature T1 and the indoor unit coil
temperature T2.
T1≥66°F (19°C) ΔTE1=0
59°F (15°C)≤T1,66°F
(19°C)
ΔTE1=66°F (19°C)-T1
T1<59°F (15°C) ΔTE1=7.2°F (4°C)
2. Auto fan action in heating mode:
• Rise Curve
• When T1-Tsc is higher than -3°F (-1.5°C), fan
speed reduces to high.
• When T1-Tsc is higher than 0°F (0°C), fan
speed reduces to medium.
• When T1-Tsc is higher than 1°F (0.5°C), fan
speed reduces to low.
• Descent Curve
• When T1-Tsc is lower than or equal to 0°F
(0°C), fan speed increases to medium.
• When T1-Tsc is lower than or equal to -3°F
(-1.5°C), fan speed increases to high.
• When T1-Tsc is lower than or equal to -5°F
(-3°C), fan speed increases to turbo.
Outdoor Fan Control:
• The outdoor unit will be run at dierent fan
speeds according to T4 and compressor
running frequency.
• For dierent outdoor units, the fan speeds
are dierent.
Defrosting Mode:
• The unit enters defrosting mode according
to the temperature value of condenser
temperature (T3) and outdoor ambient
temperature (T4) as well as the compressor
running time.
• In defrosting mode the compressor continues
to run, the indoor and outdoor motor will
cease operation and the defrost light of the
indoor unit will turn on then the " " symbol is
displayed.
• If any one of the following conditions is
satised defrosting ends and the machine
switches to normal heating mode:
• Condenser temperature (T3) rises above
TCDE1.
• Condenser temperature (T3) maintained
above TCDE2 for 80 seconds.
• Unit runs for 15 minutes consecutively in
defrosting mode.
• If the outdoor ambient temperature (T4)
is lower than or equal to -8°F (-22°C) and
the compressor running time is more than
TIMING_DEFROST_TIME, if any one of the
following conditions is satised defrosting
ends and the machine switches to normal
heating mode:
• Unit runs for 10 minutes consecutively in
defrosting mode.
• Condenser temperature (T3) rises above 50°F
(10°C).
PRODUCT FEATURES
7
background
mrcool.com65
• If any one of the following conditions is
satised, the unit enters defrosting mode:
• If the condenser temperature (T3) or outdoor
ambient temperature (T4) is lower than 27°F
(-3°C) for 30 seconds, Ts-T1 is lower than
41°F (5°C) and the compressor running time
is more than EE_TIME_DEFROST7.
• If condenser temperature (T3) or outdoor
ambient temperature (T4) is lower than 27°F
(-3°C) for 30 seconds and the compressor
running time is more than EE_TIME_
DEFROST7 + 30 minutes.
• If any one of the following conditions is
satised, defrosting ends and the machine
switches to normal heating mode:
• Condenser temperature (T3) rises above
TCDE1+7°F (4°C).
• Condenser temperature (T3) maintained
above TCDE2+7°F (4°C) for 80 seconds.
• Unit runs for 15 minutes consecutively in
defrosting mode.
Evaporator Coil Temperature
Protection:
• O: Compressor stops
• Decrease: Decrease the running frequency to
the lower level per 20 seconds.
• Hold: Keep the current frequency.
• Resume: No limitation for frequency.
Auto Mode:
• This mode can be selected with the remote
controller and the temperature setting can be
adjusted between 61°F-86°F (16°C-30°C).
• In auto mode, the machine selects cooling,
heating, or fan-only mode on the basis of ΔT
(Δ=T1-Ts).
ΔT Running mode
ΔT>3.6°F (2°C) Cooling
-5.4°F (-3°C)<ΔT≤3.6°F (2°C) Fan-only
ΔT≤-5.4°F (-3°C) Heating*
Heating*: in auto mode, cooling only models run
the fan.
• Indoor fan will run at auto fan speed.
• If the machine switches modes between
heating and cooling, the compressor will keep
stopping for a certain time and then choose a
mode according to the ΔT.
Drying Mode:
• In drying mode, the system operates the same
as auto fan in cooling mode.
• All protections are activated and operate the
same as they do in cooling mode.
• Low room temperature protection:
If the room temperature is lower than 50°F
(10°C), the compressor ceases operation and
does not resume until the room temperature
exceeds 53.6°F (12°C).
Forced Operation Function:
Press the AUTO/COOL button, the system will run
as below sequence:
• Forced cooling mode:
The compressor and outdoor fan continue
to run and the indoor fan will run at breeze
speed. After running for 30 minutes, the
system will switch to auto mode with a preset
temperature of 76°F (24°C).
• Forced auto mode:
Forced auto mode operates the same as
normal auto mode with a preset temperature
of 76°F (24°C).
• The unit will exit forced operation when it
receives the following signals:
• Switch o
• Receives the remote signal to change the
running mode.
PRODUCT FEATURES
7
background
mrcool.com 66
Timer Function:
• The timing range is 24 hours.
• Time On: The machine turns on automatically
at the preset time.
• Timer O: The machine turns o automatically
at the preset time.
• Timer On/O: The machine turns on
automatically at the preset On time and turns
o automatically at the preset O time.
• Timer O/ON: The machine turns o
automatically at the preset O time and then
turns on automatically at the preset ON time.
• The timer does not change the units operation
mode. If the unit is o it will not start
immediately after the "timer o" function
is set. When the setting time is reached, the
timer LED switches o and the units running
mode remains unchanged.
• The timer uses relative time, not clock time.
Sleep Function:
• The sleep function is available in cooling,
heating, auto mode, or heat pump+electric
heat.
• The operational process for sleep mode is as
follows:
• When cooling, the set temperature rises
by 1.8°F (1°C) (no higher than 86°F (30°C))
every hour. After 2 hours the temperature
stops rising and the indoor fan is xed at low
speed.
• When heating, the set temperature decreases
by 1.8°F (1°C) (no lower than 60.8°F (16°C))
every hour. After 2 hours the temperature
stops decreasing and the indoor fan is xed
at low speed. The anti-cold wind function
takes priority.
• When in auto mode, the fan speed is also
xed at low speed. After 1 hour if the actual
operation mode is cooling mode, the set
temperature will rise by 1.8°F (1°C), if it is
in heating mode the set temperature will
decrease by 1.8°F (1°C), if it is in fan mode the
set temperature will not change and the set
temperature will not change after two hours
of operation.
• The timer setting is available in this mode.
Auto-Restart Function:
• The indoor unit has an auto-restart module
that allows the unit to restart automatically.
The module automatically stores the current
settings and in case of sudden power failure it
will restore those settings automatically within
3 minutes after power returns.
PRODUCT FEATURES
7
background
mrcool.com67
TROUBLESHOOTING
8
8.1 Error Display (Indoor Unit)
When the indoor unit encounters a recognized error, the operation lamp will ash in a corresponding series, the
timer lamp may turn on or begin ashing, and an error code will be displayed. These error codes are described
in the following table:
Display Error Information Solution
EC 07 ODU fan speed out of control TS27
EC 0D ODU malfunction TS44
EC 51 ODU EEPROM parameter error TS23
EC 52 ODU coil temp. sensor (T3) error TS29
EC 53 ODU ambient temp. sensor (T4) error TS29
EC 54 COMP. discharge temp. sensor (TP) error TS29
EC 56 IDU coil outlet temp. sensor (T2B) error (Multi-Zone) TS29
EC C1 Other IDU refrigerant sensor detects leakage (Multi-Zone) TS43
EH 00 IDU EEPROM malfunction TS23
EH 03 IDU fan speed out of control TS27
EH 0A IDU EEPROM parameter error TS23
EH 0B IDU main control board & display board communication error TS45
EH 0E Water-level alarm malfunction TS31
EH 3A External fan DC bus voltage is too low TS41
EH 3B External fan DC bus voltage is too high TS41
EH 60 IDU room temp. sensor (T1) error TS29
EH 61 IDU coil temp. sensor (T2) error TS29
EH 62 / EH 66 Evaporator coil inlet temperature sensor T2B is in open circuit or short circuit TS29
EH 65 Evaporator coil temperature sensor T2A is in open circuit or short circuit TS29
EH BA Communication malfunction between indoor unit and external fan module TS31
EH C1 Refrigerant sensor detects leakage TS43
EH C2 Refrigerant sensor is out of range and leakage is detected TS43
EH C3 Refrigerant sensor is out of range TS42
EL 01 IDU & ODU communication error TS24
EL 0C System lacks refrigerant TS24
EL 16 Communication malfunction between adapter board and outdoor main board TS46
FH CC Refrigerant sensor error TS42
FL 09 Mismatch between the new and old platforms TS49
PC 00 ODU IPM module protection TS32
PC 01 ODU voltage protection TS33
PC 02 Compressor top (or IPM) temp. protection TS38
PC 03 Pressure protection (low or high pressure) TS35
PC 04 Inverter compressor drive error TS34
PC 0l Low ambient temperature protection TS39
---- IDUs mode conict (Multi-Zone) --
EH B3 Communication malfunction between wire & master control (for wired controller) TS40
background
mrcool.com 68
8
TROUBLESHOOTING
WARNING
Besuretoturnoallpowersuppliesordisconnectallwirestoavoidelectricshock.Whilecheckingthe
indoor/outdoorPCB,pleaseequipyourselfwithanti-staticglovesorawriststraptoavoiddamaging
the board.
Electricitywillremainincapacitorsevenwhenthepowersupplyiso.Ensurethecapacitorsarefully
discharged before troubleshooting.
For other errors:
The display board may show a garbled code or a code
undened by the service manual. Ensure that this
code is not a temperature reading.
LED Flash Frequency:
background
mrcool.com69
TROUBLESHOOTING
8
8.2 Error Display (Outdoor Unit with Auxiliary Board)
Display Error Information Solution
DF
Defrost
Normal display, not
error code
FC
Forced cooling
EC 07
ODU Fan Speed Out of Control TS27
EC 51
ODU EEPROM Parameter Error TS23
EC 52
ODU coil temp. sensor (T3) Error TS29
EC 53
ODU ambient temp. sensor (T4) Error TS29
EC 54
COMP. Discharge Temp. Sensor (TP) Error TS29
EC 55
ODU IPM Module Temperature Sensor Malfunction TS33
EC 56
IDU Coil Outlet Temp. Sensor (T2B) Error Multi-Zone TS29
EC 57
Refrigerant Pipe Temperature Sensor Error TS29
EC 71
Over Current Failure of ODU DC Fan Motor TS27
EC 72
Lack Phase Failure of ODU DC Fan Motor TS63
EL 01
IDU & ODU Communication Error TS24
EL 16
Communication Malfunction between Adapter Board and ODU Main Board TS46
PC 00
IPM Module Protection TS32
PC 02
Compressor Top(or IPM) Temp. Protection/ Refrigerant Sensor Error TS38
PC 06
Discharge Temperature protection of compressor TS53
PC 08
Outdoor Over current Protection TS47
PC 0A
High Temperature Protection of Condenser TS54
PC 0F
PFC Module Protection TS52
PC 10
ODU Low AC Voltage Protection TS49
PC11
ODU Main Control Board DC Bus High Voltage Protection TS49
PC 12
ODU Main Control Board DC Bus Low Voltage Protection /341 MCE Error TS49
PC 30
System High Pressure Protection TS55
PC31
System Low Pressure Protection TS57
PC40
Communication Error Between ODU Main Chip and Compressor Driven Chip TS51
PC 41
Compressor Current Sampling Failure TS60
PC 42
Compressor Start Failure of Outdoor Unit TS47
PC 43
ODU Compressor Lack Phase Protection TS59
PC 44
ODU Zero Speed Protection TS47
PC 45
ODU IR Chip Drive Failure TS60
PC 46
Compressor Speed has Been Out of Control TS47
PC 49
Compressor Over current Failure TS47
LC 06
High Temperature Protection of Evaporator TS38
PH 90
High Temperature Protection of Evaporator TS61
PH 91
Low Temperature Protection of Evaporator TS62
background
mrcool.com 70
8
TROUBLESHOOTING
• A check switch is included on the auxiliary board.
• Push SW4 to check the unit's status while running. The digital display shows the following codes
each time the SW4 is pushed.
Number of
Presses
Display Remark
00
Normal display
Displays running frequency, running state, or malfunction code.
Defrosting mode: " dF" or alternative displays between running
frequency and "dF" (ach appears for 0.5s.)
01
Indoor unit capacity demand
code
Actual data*HP*10
If capacity demand code is higher than 99, light the decimal point of
the high digit tube. (For example, the digital display tube show "5.0",
so 5.0 multiplied by 10 to become 50, then added to 100 to become
150, so actual capacity demand=150/10=15. The digital display tube
show "60", so actual capacity demand=60/10=6.0)
GA algorithm models display "--"
02
The frequency after the
capacity requirement transfer
If the value is higher than 99, light the decimal point of the high digit
tube.
03
Room temperature (T1)
If the temp. is lower than 0°C, the digital display tube will show "0".
If the temp. is higher than 70°C, the digital display tube will show
"70".
04
Indoor unit evaporator
temperature (T2)
If the temp. is lower than -9°C, the digital display tube will show
"-9°C". If the temp. is higher than 70°C, the digital display tube will
show "70". If the indoor unit is not connected, the digital display tube
will show: "--".
05
Condenser pipe temp. (T3)
06
Outdoor ambient temp. (T4)
07
Compressor discharge temp.
(TP)
The display value is between 0~199°C. if the temp. is lower than 0°C,
the digital display tube will show "0". If the temp. is higher than 99°C,
light the decimal point of the high digit tube. (For example, the digital
display tube show "0.5", so 0.5 multiplied by 10 to become 5 then
added to 100 to become 105°C).
08
AD value of current
The display value is a hex number.
For example, the digital display tube shows "Cd", so
C*16¹+d*16⁰=12*16+13=205, it meads AD value is 205.
09
AD value of voltage
10
Indoor unit running mode code
Standby:0, Cooling:1, Heating:2, Fan only:3, Drying:4, Forced
cooling:6, Defrost:7, ECO:9, Forced defrosting:A, Self clean:B
11
Outdoor unit running mode
code
12
EXV open angle
Actual data/4
If the value is higher than 99, light the decimal point of the high
digit tube. For example, the digital display tube show "2.0", so 2.0
multiplied by 10 to become 20, then added to 100 to become 120, it
means the EXV open angle is 120x4=480p.
8.3 Outdoor Unit Point Check Function
background
mrcool.com71
TROUBLESHOOTING
8
Number of
Presses
Display Remark
13
Frequency limit symbol
Bit7 Frequency limit caused by IGBT radiator The display value
is hex number.
For example,
the digital
display tube
show 2A, the
corresponding
binary is 101010,
so Bit5=1, Bit3=1,
and Bit1=1.
It means
frequency limit
caused by T3, or
the current.
Bit6 Reserved
Bit5 Reserved
Bit4
Frequency limit caused by low temperature
of T2. (LH00)
Bit3 Frequency limit caused by T3.(LC01)
Bit2 Frequency limit caused by TP.(LC02)
Bit1 Frequency limit caused by current.(LC03)
Bit0 Frequency limit caused by voltage.(LC05)
14
Outdoor unit fan speed
If it is higher than 99, light the decimal point of the high digit tube.
(For example, the digital display tube show "2.0", so 2.0 multiplied
by 10 to become 20, then added to 100 to become 120. This value is
multiplied by 8, and is the current fan speed: 120*8=960.
15
The average value of the
temperature values detected
by the high and low pressure
sensors in the last 10 seconds
of the compressor frequency
calculation period
The displayed value is the actual value plus 60 (that is, when the
displayed value is 10, the actual value is -50). When the displayed
value is higher than 99, light the decimal point of the high digit tube.
(If it displays 2.0, so 2.0 multiplied by 10 to become 20, then added to
100 to become 120, the actual value is 60).
When there is no pressure sensor, it is displayed as --.
16
The temperature value
detected by the high and low
pressure sensor
17
AD value detected by the high
and low pressure sensor
The display value is a hex number.
For example, the digital display tube shows "Cd", so
C*16¹+d*16⁰=12*16+13=205, it meads AD value is 205. When there is
no pressure sensor, it is displayed as --.
18
The currently running
communication protocol
version
00-99
background
mrcool.com 72
8
TROUBLESHOOTING
8.4 Information Inquiry
In order to enter engineering mode and check the data of the system, use the following steps:
• Ensure the unit is in standby status, or working normally in non-locked conditions.
• Press both "Power" and "Fan" buttons together simultaneously for 7 seconds until the remote screen shows
"0". The "Auto", "Cool", "Dry", "Heat", and "Battery" icons will be displayed at the same time.
• Press the "Up" or "Down" button to choose the dierent channel number that you want to check. (from 0-30)
on the remote control, and the display will show the parameter value.
Channel Code Meaning Remark
0 Error Code
Refer to the next list of error codes: Empty means no
error
1 T1 Room Temperature Actual data, °C/°F
2 T2 Indoor Coil Temperature Actual data, °C/°F
3 T3 Outdoor Coil Temperature Actual data, °C/°F
4 T4 Ambient Temperature Actual data, °C/°F
5 TP Discharge Temperature Actual data, °C/°F
6 FT Targeted Frequency Actual data
7 Fr Actual Frequency Actual data
8 dL Running Current 3.2A = 3
9 Ac AC Voltage
10 Sn Reserved
11 nA Reserved
12 Pr Indoor Air Flow Actual Data / 10
13 Lr EXV opening steps Actual Data / 8
14 Ir Indoor fan speed Actual Data / 8
15 Hu Humidity (if sensor is present) Actual Data, %
16 TT Set temperature including compensation Actual Data, °C
17 nA Reserved
18 nA Reserved
19 Uo Outdoor DC bus voltage
20 oT Target Frequency calculated by indoor Without limitation
21~30 nA Reserved
Note:
1. The channel number indicates a certain parameter value (check the table below).
2. The indoor unit display will show the code for 2 seconds, then the parameter value.
3. In engineering mode, the other keys or operations are invalid except for the "Power", "Up", "Down", and "OK"
buttons.
4. To exit from engineering mode, press the "Power" and "Fan" buttons together for 2 seconds to quit and
return to the home screen.
5. The engineering mode will automatically end and return to the home screen if there is no activity for 60
seconds.
background
mrcool.com73
TROUBLESHOOTING
8
Display Error Information
EH 00 IDU EEPROM malfunction
EH 0A IDU EEPROM parameter error
EL 01 IDU & ODU communication error
EH BA Communication error between the indoor unit and external fan module
EH 30 Parameters error of indoor external fan
EH 35 Phase failure of indoor external fan
EH 37 Indoor external fan zero speed failure
EH 38 Indoor external fan stall failure
EH 39 Out of step failure of indoor external fan
EH 3A Low voltage protection of indoor external fan DC bus
EH 3B Indoor external fan DC bus voltage is too high
EH 3E Indoor external fan over current fault
EH 3F Indoor external fan module protection/hardware over current protection
EH 03 IDU fan speed out of control
EC 51 ODU EEPROM parameter error
EC 52 ODU coil temperature sensor (T3) error
EC 53 ODU ambient temperature sensor (T4) error
EC 54 COMP. discharge temperature sensor (TP) error
EC 55 IGBT temperature sensor TH is in open circuit or short circuit
EC 0d Outdoor unit malfunction
EH 60 IDU room temperature sensor (T1) error
EH 61 IDU coil temperature sensor (T2) error
EC 71 Outdoor external fan over current fault
EC 75 Outdoor external fan module protection/hardware over current protection
EC 72 Outdoor external fan phase failure
EC 74 Outdoor external fan current sampling bias fault
EC 73 Zero speed failure of outdoor unit DC fan
EC 07 ODU fan speed out of control
EH B5 Intelligent eye communication failure
EL 0C Refrigerant leak detected
EH 0E Water-level alarm malfunction
EH 0F Intelligent eye malfunction
FH 07 Communication malfunction between indoor unit and auto-lifting panel
PC 00 ODU IPM module protection
PC 10 Over low voltage protection
PC 11 Over voltage protection
PC 12 DC voltage protection
PC 02 Top temperature protection of compressor or High temperature protection of IPM module
PC 40 Communication error between outdoor main chip and compressor driven chip
PC 41 Current Input detection protection
PC 42 Compressor start error
Error Codes of Engineer Mode:
background
mrcool.com 74
8
TROUBLESHOOTING
Display Error Information
PC 43 Lack of phase (3 phase) protection
PC 44 Outdoor unit zero speed protection
PC 45 341 PWM error
PC 46 Compressor speed malfunction
PC 49 Compressor over current protection
PC 06 Compressor discharge temperature protection
PC 08 Outdoor current protection
PH 09 Anti-cold air in heating mode
PC 0f PFC module malfunction
PC 30 System overpressure protection
PC 31 System pressure is too low
PC 03 Pressure protection
PC 0l Outdoor low ambient temperature protection
PH 90 Evaporator coil temperature too high
PH 91 Evaporator coil temperature too low
PC 0A Condenser high temperature protection
PH 0C Indoor unit humidity sensor failure
LH 00 Frequency limit caused by T2
LH 30 Indoor external fan current limit
LH 31 Indoor external fan voltage limit
LC 01 Frequency limit caused by T3
LC 02 Frequency limit caused by TP
LC 05 Frequency limit caused by voltage
LC 03 Frequency limit caused by current
LC 06 Frequency limit caused by PFC
LC 30 Frequency limit caused by high pressure
LC 31 Frequency limit caused by low pressure
LH 07 Frequency limit caused by a remote control
-- IDUs mode conict (match with multi-outdoor unit)
NA No malfunction and protection
background
mrcool.com75
TROUBLESHOOTING
8
In order to enter to Check the Advanced Function Settings and Enter Engineering Mode please follow
these steps:
1. First you will need to disconnect power from the unit and wait for 1 minute.
2. Then connect the power supply again to the unit (the system should enter standby).
3. Press "Power" + "Fan" buttons together for 7s until the remote controller screen shows "0", and also "Auto,
Cool, Dry, Heat, battery" icons will be displayed at the same time.
4. Press the "Up" or "Down" buttons to choose dierent channel numbers that you want to check (from 0-30)
on the remote controller.
5. Then press the "Power" button for 2s until the remote controller screen shows "Ch".
6. Press the "Ok" button to query the current function set value while the remote controller shows "Ch" and the
function set value will be shown on the indoor units display.
If you want to change the Current Functions Set Value:
1. First you will need to disconnect power from the unit and wait for 1 minute.
2. Then connect the power supply again to the unit (the system should enter standby).
3. Press "Power" + "Fan" buttons together for 7s until the remote controller screen shows "0", and also "Auto,
Cool, Dry, Heat, battery" icons will be displayed at the same time.
4. Press the "Up" or "Down" buttons to choose dierent channel numbers that you want to check (from 0-30)
on the remote controller.
5. Then press the "Power" button for 2s until the remote controller screen shows "Ch".
6. Then press the "Up" or "Down" button to choose the desired set value from the screen of the remote
control.
7. The press "Ok" to send the new set value to the indoor unit and the indoor unit will display "CS" which
means that the new set value is uploaded successfully.
8. Finally disconnect the power supply again from the unit and wait for 10 minutes, then connect it again.
Please Note:
1. The channel number indicates a certain function and each number shown on the indoor units screen
indicates the current function set value (Reference table below).
2. In the engineering mode, the other keys or operations are invalid except for the following buttons "Power",
"Up", "Down", and "Ok".
3. In order to set a new set value successfully you need to nish the steps (from 2-7) within 1 minute.
4. The engineering mode will be exited if there is no valid input data for 60s.
5. In order to exit engineering mode, please follow these steps:
• Press "Power" button for 2s until the remote controls screen shows "0".
• Then press "Power" + "Fan" buttons together for 2s to quite the engineering mode and return back to the
home screen.
Advanced Function Setting:
background
mrcool.com 76
8
TROUBLESHOOTING
Channel Function Parameter Value Meaning Remark
0 Capacity setting (Btu/h) 1-100K
1 Auto-restart function
0-Inactive
1-Active
2
Fan control when Ts
reached
1-Fan stop
2-Fan runs at lowest RPM
3-Fan runs at setting RPM
4-Fan stops for 4 mins. and runs for 1 min.
5-Fan stops for 8 mins. and runs for 1 min.
6-Fan stops for 16 mins. and runs for 1 min.
7-Fan stops for 24 mins. and runs for 1 min.
8-Fan stops for 48 mins. and runs for 1 min.
9-Fan stops for 15 mins. and runs for 2.5 min.
10-Fan stops for 30 mins. and runs for 2.5 min.
11-Fan stops for 60 mins. and runs for 2.5 min.
12-Fan runs at setting RPM, but stops if you choose
automatic speed
13-Fan runs at lowest speed, but will stop if you choose
automatic speed
3 Mode lock
CH-Cooling and heating (all modes)
HH-Heating only (heating + fan only)
CC-Cooling only (cooling + drying + fan only)
nU-Cooling and heating without auto
Remote controller
will change as well
4
Lowest setting
temperature
16-24
Remote controller
will change as well
5
Highest setting
temperature
25-30
Remote controller
will change as well
6 Reserved Nothing to set
7 / Nothing to set
8 / Nothing to set
9 / Nothing to set
10 / Nothing to set
11
Min. frequency limitation
in cooling mode
10,11,12,...,49,50,--(Cancel)
12
Min. fequency limitation
in heating mode
10,11,12,...,49,50,--(Cancel)
13
Max. frequency selection
in T4 limitation of Zone6
20,21,22,...,149,150,--(Cancel)
14 / Nothing to set
15
Frequency selection of
outdoor forced-operation
10,11,12,...,249,250,--(Cancel)
16 One button reset rS - Reset
17 nA Nothing to set
18 Capacity setting(kW) 23,26,32,35,51,72,120,--,(Cancel)
background
mrcool.com77
TROUBLESHOOTING
8
Channel Function Parameter Value Meaning Remark
19
Max. frequency selection
in cooling mode
40,41,42,...,83,84,--(Cancel)
20
Max. frequency selection
in heating mode
40,41,42,...,83,84,--(Cancel) Without limitation
21
Cooling temperature
compensation
-3.0,-2.5,-2.0,...,3.0,3.5,--(Cancel)
22
Heating temperature
compensation
-6.5,-6.0,-5.5,...,0.5,1.0,1.5,...,7.0,7.5,--(Cancel
23
Fan volume selection in
cooling
Fan volume will add set data*20cfm
24 Reserved Nothing to set
25
Fan volume selection in
heating
Fan volume will add set data*20cfm
26 Reserved Nothing to set
27 Defrosting type
A0-Normal defrosting
A1-Enhanced defrosting
28
Anti-cold air Stop Fan
Temperature
16~28
29 Reserved Nothing to set
30 Reserved Nothing to set
background
mrcool.com 78
8
TROUBLESHOOTING
8.5 Error Diagnosis Without Error Code
Remote Maintenance:
Suggestion: When troubles occur, please check the following points with the customer before eld maintenance.
WARNING
Besuretoturnounitbeforeanymaintenancetopreventdamageorinjury.
No. Problem Solution
1
Unit will not start TS29-TS15
2
The power switch is on but fans will not start TS29-TS15
3
The temperature on the display board cannot be set TS29-TS15
4
Unit is on but the air is not cold/hot TS29-TS15
5
Unit runs but shortly stops TS29-TS15
6
The unit starts up and stops frequently TS29-TS15
7
Unit runs continuously but insucient cooling/heating TS29-TS15
8
Cool cannot change to heat TS29-TS15
9
Unit is noisy TS29-TS15
Field Maintenance:
No. Problem Solution
1
Unit will not start TS16-TS17
2
Compressor will not start but fans run TS16-TS17
3
Compressor and condenser fan will not start TS16-TS17
4
Air handler fan will not start TS16-TS17
5
Condenser fan will not start TS16-TS17
6
Unit runs but shortly stops TS16-TS17
7
Compressor short-cycles due to overload TS16-TS17
8
High suction pressure TS16-TS17
9
Low discharge pressure TS16-TS17
10
High suction pressure TS16-TS17
11
Low suction pressure TS16-TS17
12
Unit runs continuously but insucient cooling TS16-TS17
13
Too cool TS16-TS17
14
Compressor is noisy TS16-TS17
15
Horizontal louver cannot revolve TS16-TS17
background
mrcool.com79
TROUBLESHOOTING
8
1. Remote
Maintenance
Electrical Circuit Refrigerant Circuit
Possible causes of
trouble
Power failure
The main power tripped
Loose connections
Faulty transformer
The voltage too high or too low
Theremotecontrolispoweredo
Broken the remote control
Dirtyairlter
Dirtycondenserns
Thesettingtemperatureishigher/lower
thantheroom's(cooling/heating)
Theambienttemperatureistoohigh/
lowwhenthemodeiscooling/heating
Fan mode
Silence function is activate
Frosting and defrosting frequency
Unit will not start √ √ √ √ X X X X X X X X X X
The power switch is
on but fans will not
start
X X √ √ √ X X X X X X X X X
The temperature
on the playboard
cannot be set
X X X X X √ √ X X X X X X X
Unit is on but the air
is not cold/hot
X X X X X X X X X √ √ √ X X
Unit runs but shortly
stops
X X X X √ X X X √ √ X X X
The unit startup and
stops frequently
X X X X √ X X X X X √ X X √
Unit runs
continuously but
insucient cooling/
heating
X X X X X X X √ √ √ √ X √ X
Cool cannot change
to heat
X X X X X X X X X X X X X X
Unit is noisy X X X X X X X X X X X X X X
Testmethod/
remedy
Test voltage
Close the power switch
Inspect connections - tighten
Change the transformer
Test voltage
Replace the battery of the
remote control
Replace the remote control
Clean or replace
Clean
Adjustthesettingtemperature
Turn on the unit later
Adjusttocoolmode
Turnothesilencefunction
Turn on the unit later
background
mrcool.com 80
8
TROUBLESHOOTING
1. Remote
Maintenance
Others
Possible causes of
trouble
Heavy load condition
Loosen hold down bolts or screws
Bad airproof
The air inlet or outlet of either unit is
blocked
Interference from cell phone towers and
remote boosters
Shipping plates remain attached
Unit will not start X X X X X X
The power switch is
on but fans will not
start
X X X X √ X
The temperature
on the playboard
cannot be set
X X X X X X
Unit is on but the air
is not cold/hot
X X X X X X
Unit runs but shortly
stops
X X X X X X
The unit startup and
stops frequently
X X X √ X X
Unit runs
continuously but
insucient cooling/
heating
√ X √ √ X X
Cool cannot change
to heat
X X X X X X
Unit is noisy X √ X X X √
Testmethod/
remedy
Check heat load
Tighten bolts and screws
Close all windows and doors
Remove the obstacles
Reconnect the power or press
ON/OFFbuttonontheremoteto
restart operation
Remove item
background
mrcool.com81
TROUBLESHOOTING
8
2. Field
Maintenance
Refrigerant Circuit Others
Possible causes of
trouble
Compressor stuck
Shortage of refrigerant
Restricted liquid line
Dirtyairlter
Dirty evaporator coil
Insucientairthroughevaporator
coil
Overcharge of refrigerant
Dirty or partially blocked condenser
Air or incompressible gas in
refrigerant cycle
Short cycling of condensing air
High temperature condensing
medium
Insucientcondensingmedium
Broken compressor internal parts
Inecientcompressor
Expansion valve obstructed
Expansion valve or capillary tube
close completely
Leaking power element on
expansion valve
Poor installation of feeler bulb
Heavy load condition
Loosenholddownboltsand/or
screws
Shipping plates remain attached
Poor choices of capacity
Contact of piping with other piping
or external plate
Unit will not start X X X X X X X X X X X X X X X X X X X X X X X
Compressor will
not start but fans
run
√ X X X X X X X X X X X X X X X X X X X X X X
Compressor and
condenser fan will
not start
X X X X X X X X X X X X X X X X X X X X X X X
Air handler fan will
not start
X X X X X X X X X X X X X X X X X X X X X X X
Condenser fan will
not start
X X X X X X X X X X X X X X X X X X X X X X X
Unit runs but
shortly stops
X √ √ X X X √ √ X X X X X X X √ √ X X X X X X
Compressor
short-cycles due to
overload
X √ X X X X √ √ X X X X X X X X X X X X X X X
High discharge
pressure
X X X X X X √ √ √ √ √ √ X X X X X X X X X X X
Low discharge
pressure
X √ X X X X X X X X X X X √ X X X X X X X X X
Testmethod/
remedy
Replace the compressor
Leak test
Replace restricted part
Clean or replace
Clean coil
Check fan
Change charged refrigerant volume
Clean condenser or remove obstacle
Purge, evacuate and recharge
Removeobstructiontoairow
Removeobstructioninairorwaterow
Removeobstructioninairorwaterow
Replace compressor
Testcompressoreciency
Replace valve
Replace valve
Replace valve
Fix feeler bulb
Check heat load
Tighten bolts or screws
Remove them
Choose system of larger capacity or add
another system
Rectify piping so as to not contact with
each other or with external plate
background
mrcool.com 82
8
TROUBLESHOOTING
2. Field
Maintenance
Refrigerant Circuit Others
Possible causes of
trouble
Compressor stuck
Shortage of refrigerant
Restricted liquid line
Dirtyairlter
Dirty evaporator coil
Insucientairthroughevaporator
coil
Overcharge of refrigerant
Dirty or partially blocked condenser
Air or incompressible gas in
refrigerant cycle
Short cycling of condensing air
High temperature condensing
medium
Insucientcondensingmedium
Broken compressor internal parts
Inecientcompressor
Expansion valve obstructed
Expansion valve or capillary tube
close completely
Leaking power element on
expansion valve
Poor installation of feeler bulb
Heavy load condition
Loosenholddownboltsand/or
screws
Shipping plates remain attached
Poor choices of capacity
Contact of piping with other piping
or external plate
High suction
pressure
X X X X X X √ X X X X X X √ X X X √ √ X X X X
Low suction
pressure
X √ √ √ √ √ X X X X X X X X √ √ √ X X X X X X
Unit runs
continuously but
insucient cooling
X √ √ √ √ √ X √ √ √ X X X √ X X X X √ X X √ X
Too Cool X X X X X X X X X X X X X X X X X X X X X X X
Compressor is
noisy
X X X X X X √ X X X X X √ X X X X X X √ √ X √
Horizontal louver
cannot revolve
X X X X X X X X X X X X X X X X X X X X X X X
Testmethod/
remedy
Replace the compressor
Leak test
Replace restricted part
Clean or replace
Clean coil
Check fan
Change charged refrigerant volume
Clean condenser or remove obstacle
Purge, evacuate and recharge
Removeobstructiontoairow
Removeobstructioninairorwaterow
Removeobstructioninairorwaterow
Replace compressor
Testcompressoreciency
Replace valve
Replace valve
Replace valve
Fix feeler bulb
Check heat load
Tighten bolts or screws
Remove them
Choose system of larger capacity or add
another system
Rectify piping so as to not contact with
each other or with external plate
background
mrcool.com83
TROUBLESHOOTING
8
2. Field
Maintenance
Electrical Circuit
Possible causes of
trouble
Power Failure
Blown fuse or varistor
Loose connections
Shorted or broken wires
Safety device opens
Faultythermostat/room
temperature sensor
Wrong setting place of
temperature sensor
Faulty transformer
Shorted or open capacitor
Faulty magnetic contactor for
compressor
Faulty magnetic contactor for fan
Low voltage
Faulty stepping motor
Shorted or grounded compressor
Shorted or grounded fan motor
Unit will not start √ √ √ √ √ X X √ X X X X X X X
Compressor will
not start but fans
run
X X X √ X √ X √ √ X X X X √ X
Compressor and
condenser fan will
not start
X X X √ X √ X X X √ X X X X X
Air handler fan will
not start
X X X √ X X X X √ X √ X X X √
Condenser fan will
not start
X X X √ X √ X X √ X √ X X X √
Unit runs but
shortly stops
X X X X X X X X X √ X √ X X X
Compressor
short-cycles due to
overload
X X X X X X X X X √ X √ X X X
High discharge
pressure
X X X X X X X X X X X X X X X
Low discharge
pressure
X X X X X X X X X X X X X X X
Testmethod/
remedy
Test voltage
Inspect fuse type & size
Inspect connections - tighten
Test circuits with tester
Test continuity of safety device
Testcontinuityofthermostat/sensor
& wiring
Place the temperature sensor at the
central of the air inlet grille
Check control circuit with tester
Check capacitor with tester
Test continuity of coil & contacts
Test continuity of coil & contacts
Test voltage
Replace the stepping motor
Check resistance with multimeter
Check resistance with multimeter
background
mrcool.com 84
8
TROUBLESHOOTING
2. Field
Maintenance
Electrical Circuit
Possible causes of
trouble
Power Failure
Blown fuse or varistor
Loose connections
Shorted or broken wires
Safety device opens
Faultythermostat/room
temperature sensor
Wrong setting place of temperature
sensor
Faulty transformer
Shorted or open capacitor
Faulty magnetic contactor for
compressor
Faulty magnetic contactor for fan
Low voltage
Faulty stepping motor
Shorted or grounded compressor
Shorted or grounded fan motor
High suction
pressure
X X X X X X X X X X X X X X X
Low suction
pressure
X X X X X X X X X X X X X X X
Unit runs
continuously but
insucient cooling
X X X X X X X X X X X X X X X
Too cool X X X X X X √ √ X X X X X X X
Compressor is
noisy
X X X X X X X X X X X X X X X
Horizontal louver
can not revolve
X X √ √ X X X X X X X X √ X X
Testmethod/
remedy
Test voltage
Inspect fuse type & size
Inspect connections - tighten
Test circuits with tester
Test continuity of safety device
Testcontinuityofthermostat/sensor
& wiring
Place the temperature sensor at the
central of the air inlet grille
Check control circuit with tester
Check capacitor with tester
Test continuity of coil & contacts
Test continuity of coil & contacts
Test voltage
Replace the stepping motor
Check resistance with multimeter
Check resistance with multimeter
background
mrcool.com85
TROUBLESHOOTING
8
8.6 Quick Maintenance by Error Code
If you do not have the time to test which specic parts are faulty, you can change the required parts according to
the error code. You can nd the parts to replace by error code in the following table.
Part Requiring
Replacement
Error Code
EH00/
EH 0A
EL 01 EH 03 EH 60 EH 61
EH62/
EH 66
EH 65 EL 0C
EHC1/
EH C2
EH 0E EH 0b
Indoor PCB
√ √ √ √ √ √ √ √
X
√ √
Outdoor PCB
X
√
X X X X X X X X X
Indoor fan motor
X X
√
X X X X X X X X
T1 sensor
X X X
√
X X X X X X X
T2 sensor
X X X X
√
X X
√
X
√
X
T2B sensor
X X X X X
√
X X X X X
T2A sensor
X X X X X X
√
X X X X
Reactor
X
√
X X X X X X X X X
Compressor
X X X X X X X X X X X
Additional
refrigerant
X X X X X X X
√ √ √
X
Water-level switch
X X X X X X X X X
√
X
Water pump
X X X X X X X X X
√
X
Display board
X X X X X X X X X X
√
background
mrcool.com 86
8
TROUBLESHOOTING
Part Requiring
Replacement
Error Code
EC 54 EC 51 EC 52 EC 53 EC 56 EC 07 PC 00 PC 01 PC 02 PC 04 PC 03
FH
CC/EH
C3
Indoor PCB
X X X X X X X X X X X
√
Outdoor PCB
√ √ √ √ √ √ √ √ √ √ √
X
Outdoor fan
motor
X X X X X
√ √
X
√ √
X X
T3 sensor
X X
√
X X X X X X X X X
T4 sensor
X X X
√
X X X X X X X X
TP sensor
√
X X X X X X X X X X X
T2B sensor
X X X X
√
X X X X X X X
Refrigerant
sensor
X X X X X X X X X X X
√
Reactor sensor
X X X X X X X
√
X X X X
Compressor
X X X X X X
√
X X
√
X X
IPM module
board
X X X X X X
√ √ √ √
X X
Pressure
protector
X X X X X X X X X X
√
X
Additional
refrigerant
X X X X X X X X X X
√
X
background
mrcool.com87
TROUBLESHOOTING
8
Part Requiring
Replacement
Error Code
PC 06
PC
08/42/44/46/49
PC 0A PC 0F PC 40 EC 71
Outdoor PCB
√ √ √ √ √ √
Outdoor fan motor
X
√ √
X X
√
T3 sensor
X X
√
X X X
TP sensor
√
X X X X X
Pressure Sensor
X X X X X X
Reactor
X
√
X
√
X X
Compressor
X X X X X X
IPM module board
X
√
X X
√
X
High pressure valve
assy.
√
X X X X X
High pressure
protector
X X X X X X
Low pressure protector
X X X X X X
Additional refrigerant
√
X
√
X X X
Electric control box
X X X X
√
X
background
mrcool.com 88
8
TROUBLESHOOTING
Part Requiring
Replacement
Error Code
PC 41 PC 43 PC10/11/12 PC 45 PH 90 PH 91
Outdoor PCB
√ √ √
X X X
Outdoor fan motor
X X X X X X
T3 sensor
X X X X X X
TP sensor
X X X X X X
Pressure Sensor
X X X X X X
Reactor
X X
√
X X X
Compressor
X
√
X X X X
IPM module board
X X
√ √
X X
High pressure valve
assy.
X X X X X X
High pressure
protector
X X X X X X
Low pressure protector
X X X X X X
Additional refrigerant
X X X X X X
Electric control box
X X X X X X
T2 sensor
X X X X
√ √
Indoor PCB
X X X X
√ √
Indoor fan motor
X X X X
√
X
background
mrcool.com89
TROUBLESHOOTING
8
8.7 Troubleshooting by Error Code
EH00/EH0A/EC51:EEPROMMalfunctionErrorDiagnosisandSolution.
Description: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.
Recommended parts to prepare:
• Indoor PCB
• Outdoor PCB
Troubleshooting and repair:
Remarks:
EEPROM: A read-only memory whose contents can be erased and reprogrammed using a puled
voltage. The location of the EEPROM chip on the indoor and outdoor PCB is shown in the following two
images:
Note: These pictures are for reference, actual appearance may vary.
Troubleshooting and repair of the compressor driven chip EEPROM parameter error and communication error
between the outdoor main chip and compressor driven chip are the same as EC 51.
background
mrcool.com 90
8
TROUBLESHOOTING
EL 01: Indoor and Outdoor Unit Communication Error Diagnosis and Solution.
Description: Indoor unit cannot communicate with the outdoor unit.
Recommended parts to prepare:
• Indoor PCB
• Outdoor PCB
• Reactor
Troubleshooting and repair:
Current loop Communication (S Communication)
background
mrcool.com91
TROUBLESHOOTING
8
Remarks:
• Use a multimeter to test the DC voltage between 2 port (or S or L2 port) and 3 port (or N or S port)
of outdoor unit. The red pin of the multimeter connects with 2 port (or S or L2 port) while the black
pin is for 3 port (or N or S port).
• When AC is running normal the voltage will move alternately between -25V to 25V.
• If the outdoor unit has a malfunction, the voltage will alternate with a positive value.
• If the indoor unit has a malfunction the voltage will be a certain value.
• Use a multimeter to test the resistance of the reactor which does not connect with the capacitor.
• The normal value should be around zero ohms. Otherwise the reactor has a malfunction.
Note: The pictures and the values are for reference only, actual condition and specic values may vary.
background
mrcool.com 92
8
TROUBLESHOOTING
485 Communication (S1,S2 Communication):
Recommended parts to prepare:
• Indoor PCB
• Outdoor PCB
• Magnet Ring
• Signal Wires
Troubleshooting and repair:
background
mrcool.com93
TROUBLESHOOTING
8
EH03/EC07/EC71:FanSpeedisOperatingOutsideofNormalRange/Over
Current Failure of ODU DC Fan Motor Diagnosis and Solution.
Description: When the indoor/outdoor fan speed is too low or too high for a certain time, the unit
ceases operation and the LED displays an error code.
Recommended parts to prepare:
• Connection wires
• Fan assembly
• Fan motor
• PCB
Troubleshooting and repair:
background
mrcool.com 94
8
TROUBLESHOOTING
Index:
1. Indoor or Outdoor DC fan motor (control chip is in fan motor)
Power on and make sure the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 on the fan
motor connector. If the value of the voltage is not in the range showing in the tables below the PCB
will have problems and will need to be replaced.
NO. Color Signal Voltage
1 Red Vs/Vm 192V~380V
2 --- --- ---
3 Black GND 0V
4 White Vcc 13.5-16.5V
5 Yellow Vsp 0~6.5V
6 Blue FG 13.5-16.5V
Index:
1. Outdoor DC fan motor (control chip is in outdoor PCB)
Release the UVW connector and measure the resistance of U-V, U-W, V-W. If the resistance is not equal
to each other the fan motor has a problem and needs to be replaced. Otherwise the PCB has a
problem and needs to be replaced.
background
mrcool.com95
TROUBLESHOOTING
8
EH60/EH61/EH62/EH66/EH65/EC53/EC52/EC54/EC56/EC57:OpenCircuitor
Short Circuit of Temperature Sensor Diagnosis and Solution.
Description: If the sampling voltage is lower than 0.06V or higher than 4.94V the LED will display an
error.
Recommended parts to prepare:
• Connection wires
• Sensors
• PCB
Troubleshooting and repair:
Note: The picture and the value are for reference only, actual appearance and values may vary.
background
mrcool.com 96
8
TROUBLESHOOTING
EL 0C: System Lacks Refrigerant Diagnosis and Solution.
Description: Judging the abnormality of the refrigeration system according to the number of
compressor stops and the changes in operating parameters caused by excessive exhaust temperature.
Recommended parts to prepare:
• Indoor PCB
• Additional refrigerant
Troubleshooting and repair:
background
mrcool.com97
TROUBLESHOOTING
8
EH 0E: Water-Level Alarm Malfunction Diagnosis and Solution
Description: If the sampling voltage is not 5V the LED displays an error code.
Recommended parts to prepare:
• Connection wires
• Water-level switch
• Water pump
• Indoor PCB
Troubleshooting and repair:
background
mrcool.com 98
8
TROUBLESHOOTING
PC 00: ODU IPM Module Protection Diagnosis and Solution.
Description: When the voltage signal the IPM sends to the compressor drive chip is abnormal the LED
display shows "PC 00" and the system shuts down.
Recommended parts to prepare:
• Connection wires
• IPM module board
• Outdoor fan assembly
• Compressor
• Outdoor PCB
Troubleshooting and repair:
background
mrcool.com99
TROUBLESHOOTING
8
PC 01: ODU Voltage Protection Diagnosis and Solution.
Description: Abnormal increases or decreases in voltage are detected by checking the specied
voltage detection circuit.
Recommended parts to prepare:
• Power supply wires
• IPM module board
• PCB
• Reactor
Troubleshooting and repair:
background
mrcool.com 100
8
TROUBLESHOOTING
PC 04: Inverter Compressor Drive Error Diagnosis and Solution.
Description: An abnormal inverter compressor drive is detected by a special detection circuit,
including communication signal detection, voltage detection, compressor rotation speed signal
detection and so on.
Recommended parts to prepare:
• Connection wires
• IPM module board
• Outdoor fan assembly
• Compressor
• Outdoor PCB
Troubleshooting and repair:
background
mrcool.com101
TROUBLESHOOTING
8
PC 03: Pressure Protection (Low or High Pressure) Diagnosis and Solution.
Description: Outdoor pressure switch cuts o the system because pressure is higher than 638PSI
(4.4MPa) or the outdoor pressure switch cuts o because pressure is lower than 19PSI (0.13MPa) the
LED displays an error code.
Recommended parts to prepare:
• Connection wires
• Pressure switch
• Outdoor fan
• Outdoor main PCB
• Refrigerant
Troubleshooting and repair:
background
mrcool.com 102
8
TROUBLESHOOTING
background
mrcool.com103
TROUBLESHOOTING
8
PC02/LC06:CompressorTop(orIPM)Temp.ProtectionDiagnosisandSolution.
Description: For some models with an overload protection, if the sampling voltage is not 5V the LED
will display an error. If the temperature of the IPM module is higher than a certain value the LED will
display an error. Models without an overload protector should be diagnosed according to the second
owchart.
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• IPM module board
• High pressure protector
• System blockages
Troubleshooting and repair:
background
mrcool.com 104
8
TROUBLESHOOTING
PC 0L: Low Ambient Temperature Protection.
Description: It is a protection function for the system (when o) that occurs when the outdoor
ambient temperature (T4) is lower than -35°C for 10s which will cause the system to stop and display
an error code.
When the compressor is on and the outdoor ambient temperature is lower than -40°C for 10s, the
system will stop and display an error code.
When the outdoor ambient temperature (T4) is no lower than -32°C for 10s the unit will exit the
protection.
background
mrcool.com105
TROUBLESHOOTING
8
EH b3: Communication Malfunction Between Wire and Master Control Diagnosis
and Solution.
Description: If the indoor PCB does not receive feedback from the wired controller the error will
display on the wired controller.
Recommended parts to prepare:
• Connection wires
• Indoor PCB
• Wired controller
Troubleshooting and repair:
background
mrcool.com 106
8
TROUBLESHOOTING
EH bA: Communication Malfunction Between Indoor Unit and External Fan
Module. EH 3A: External Fan DC Bus Voltage is too Low Protection. EH 3b: External
Fan DC Bus Voltage is too High Diagnosis and Solution.
Description: Indoor unit does not receive the feedback from external fan module during 150 seconds
or the indoor unit receives abnormal increases or decreases in voltage from external fan module.
Recommended parts to prepare:
• Indoor PCB
Troubleshooting and repair:
background
mrcool.com107
FH CC: Refrigerant Sensor Error or EH C3: Refrigerant Sensor is Out of Range
Diagnosis and Solution.
Description: Indoor unit receives a fault signal for 10s or the indoor unit does not receive feedback
from the refrigerant sensor for 150s.
Recommended parts to prepare:
• Connection wires
• Sensors
• Indoor main PCB
Troubleshooting and repair:
TROUBLESHOOTING
8
background
mrcool.com 108
8
TROUBLESHOOTING
EH C1: Refrigerant Sensor Detects Leakage or EH C2: Refrigerant Sensor is Out of
Range and Leakage is Detected Diagnosis and Solution.
Description: The refrigerant sensor detects a concentration higher than or equal to 10%*LFL for 10
seconds or the refrigerant sensor detects a concentration higher than or equal to 20%*LFL or the multi
model receives the refrigerant leakage protection fault sent by the outdoor unit.
Multi-zone: Only the buzzer of the indoor unit that detects refrigerant leakage continues to sound the
alarm, the shortest sound is 10 seconds, and the longest sound is 5 minutes (you can press any key
such as remote control or wire control, app, and so on to eliminate the alarm), and the other non-
refrigerant leakage fault the indoor unit only displays "ECC1" but the buzzer does not sound.
Recommended parts to prepare:
• Additional refrigerant
Troubleshooting and repair:
background
mrcool.com109
TROUBLESHOOTING
8
EC 0d: ODU Malfunction Diagnosis and Solution.
Description: The indoor unit detects the outdoor unit has an error.
Recommended parts to prepare:
• Outdoor unit
Troubleshooting and repair:
background
mrcool.com 110
8
TROUBLESHOOTING
EH 0b: IDU Main Control Board and Display Board Communication Error Diagnosis
and Solution.
Description: Indoor PCB does not receive feedback from the display board.
Recommended parts to prepare:
• Communication wire
• Indoor PCB
• Display board
Troubleshooting and repair:
background
mrcool.com111
TROUBLESHOOTING
8
EL 16: Communication Malfunction Between Adapter Board and Outdoor Main
Board Diagnosis and Solution.
Description: The adapter PCB cannot detect the main control board.
Recommended parts to prepare:
• Connection wires
• Adapter board
• Outdoor main PCB
Troubleshooting and repair:
FL 09: Mismatch Between the New and Old Platforms Diagnosis and Solution.
Description: When the indoor and outdoor units are mismatched the LED will display this code. Please
replace the indoor or outdoor unit to match accordingly.
background
mrcool.com 112
8
TROUBLESHOOTING
PC08:CurrentOverloadProtection/PC42:CompressorStartFailureofOutdoor
Unit/PC44:ODUZeroSpeedProtection/PC46:CompressorSpeedhasbeenOutof
Control/PC49:CompressorOverCurrentFailure.
Description: An abnormal current rise is detected by checking the specied current detection circuit.
Recommended parts to prepare:
• Outdoor PCB
• Connection wires
• Bridge rectier
• PFC circuit or reactor
• Refrigeration piping system
• Pressure switch
• Outdoor fan
• IPM module board
Troubleshooting and repair:
background
mrcool.com113
TROUBLESHOOTING
8
background
mrcool.com 114
8
TROUBLESHOOTING
PC10:ODULowACVoltageProtection/PC11:ODUMainControlBoardDCBus
HighVoltageProtection/PC12:ODUMainControlBoardDCBusLowVoltage
Protection/341MCEErrorDiagnosisandSolution.
Description: Abnormal increases or decreases in voltage are detected by checking the specied
voltage detection circuit.
Recommended parts to prepare:
• Power supply wires
• IPM module board
• Outdoor PCB
• Bridge rectier
• PFC circuit or reactor
Troubleshooting and repair:
background
mrcool.com115
TROUBLESHOOTING
8
PC 40: Communication Error Between ODU Main Chip and Compressor Driven Chip
Diagnosis and Solution.
Description: The main PCB cannot detect the IPM board.
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• IPM module board
• Electric control box
Troubleshooting and repair:
background
mrcool.com 116
8
TROUBLESHOOTING
PC 0F: PFC Module Protection Diagnosis and Solution.
Description: Outdoor PCB detects PFC signal is low voltage or DC voltage is lower than 340V for 6s
when quick check.
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• Inductance
• PFC circuit or IPM module board
Troubleshooting and repair:
background
mrcool.com117
TROUBLESHOOTING
8
PC 06: Discharge Temperature Protection of Compressor Diagnosis and Solution.
Description: When the compressor discharge temperature (TP) is more than 115°C for 10 seconds,
the compressor ceases operation and does not restart until TP is less than 90°C..
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• Discharge temperature sensor
• Refrigerant
Troubleshooting and repair:
background
mrcool.com 118
8
TROUBLESHOOTING
PC 0A: High Temperature Protection of Condenser Diagnosis and Solution.
Description: The unit will stop when condenser temperature is higher than 65°C, and runs again when
it is less than 50°C.
Recommended parts to prepare:
• Connection wires
• Condenser temperature sensor
• Outdoor fan
• Outdoor main PCB
• Refrigerant
Troubleshooting and repair:
background
mrcool.com119
TROUBLESHOOTING
8
PC 30: System High Pressure Protection Diagnosis and Solution.
Description: Outdoor pressure switch cuts o the system because pressure is higher than 638PSI
(4.4MPa).
Recommended parts to prepare:
• Connection wires
• Pressure switch
• Outdoor fan
• Outdoor main PCB
Troubleshooting and repair:
background
mrcool.com 120
8
TROUBLESHOOTING
PC 31: System Low Pressure Protection Diagnosis and Solution.
Description: Outdoor pressure switch cut o the system because low pressure is lower than 18.85PSI
(0.13MPa), the LED displays the failure code.
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• Low pressure protector
• Refrigerant
Troubleshooting and repair:
background
mrcool.com121
TROUBLESHOOTING
8
PC 43: ODU Compressor Lack Phase Protection Diagnosis and Solution.
Description: When the three-phase sampling current of the compressor is abnormal, especially when
the current of one or more phases is always small and almost 0, the LED displays the failure code.
Recommended parts to prepare:
• Connection wires
• Compressor
• Outdoor PCB
Troubleshooting and repair:
background
mrcool.com 122
8
TROUBLESHOOTING
PC 45: ODU IR Chip Drive Failure Diagnosis and Solution.
Description: When the IR chip detects its own parameter error, the LED displays the failure code when
power is on.
Recommended parts to prepare:
• Inverter module PCB
Troubleshooting and repair:
PC 41: Outdoor Compressor Current Sampling Circuit Failure Diagnosis and
Solution.
Description: Three-phase sampling oset voltage error, the static bias voltage is normally 2.5V.
Recommended parts to prepare:
• Outdoor main PCB
Troubleshooting and repair:
background
mrcool.com123
PH 90: High Temperature Protection of Evaporator Diagnosis and Solution.
Description: When evaporator coil temperature is more than 60°C in heating mode, the unit stops. It
starts again only when the evaporator coil temperature is less than 52°C.
Recommended parts to prepare:
• Connection wires
• Evaporator coil temperature sensor (T2)
• Indoor fan
• Indoor main PCB
Troubleshooting and repair:
TROUBLESHOOTING
8
background
mrcool.com 124
8
TROUBLESHOOTING
PH 91: Low Temperature Protection of Evaporator Diagnosis and Solution.
Description: When evaporator coil temperature is lower than 0°C in cooling mode or drying mode, the
unit stops. It starts again only when the evaporator coil temperature is more than 5°C.
Recommended parts to prepare:
• Connection wires
• Evaporator coil temperature sensor (T2)
• Indoor main PCB
background
mrcool.com125
TROUBLESHOOTING
8
EC 71: Lack Phase Failure of ODU DC Fan Motor Diagnosis and Solution.
Description: When the three-phase sampling current of the DC motor is abnormal, especially when
the current of one or more phases is always small and almost 0, the LED displays a fault code.
Recommended parts to prepare:
• Connection wires
• Fan motor
• Outdoor PCB
Troubleshooting and repair:
background
mrcool.com 126
8
TROUBLESHOOTING
8.8 Check Procedures
WARNING
Besuretoturnoallpowersuppliesordisconnectallwirestoavoidelectricshock.Operateonlyafter
thecompressorandcoilhasreturnedtonormaltemperatureincaseofinjury.
1. Disconnect the temperature sensor from the PCB.
2. Measure the resistance value of the sensor using a multi-meter.
3. Check corresponding temperature sensor resistance value table.
Note: The picture and the value are for reference only, actual condition and specic values may vary.
Temperature Sensor Check:
background
mrcool.com127
°C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm
-20 -4 542.7 20 68 68.66 60 140 13.59 100 212 3.702
-19 -2 511.9 21 70 65.62 61 142 13.11 101 214 3.595
-18 0 483 22 72 62.73 62 144 12.65 102 216 3.492
-17 1 455.9 23 73 59.98 63 145 12.21 103 217 3.392
-16 3 430.5 24 75 57.37 64 147 11.79 104 219 3.296
-15 5 406.7 25 77 54.89 65 149 11.38 105 221 3.203
-14 7 384.3 26 79 52.53 66 151 10.99 106 223 3.113
-13 9 363.3 27 81 50.28 67 153 10.61 107 225 3.025
-12 10 343.6 28 82 48.14 68 154 10.25 108 226 2.941
-11 12 325.1 29 84 46.11 69 156 9.902 109 228 2.86
-10 14 307.7 30 86 44.17 70 158 9.569 110 230 2.781
-9 16 291.3 31 88 42.33 71 160 9.248 111 232 2.704
-8 18 275.9 32 90 40.57 72 162 8.94 112 234 2.63
-7 19 261.4 33 91 38.89 73 163 8.643 113 235 2.559
-6 21 247.8 34 93 37.3 74 165 8.358 114 237 2.489
-5 23 234.9 35 95 35.78 75 167 8.084 115 239 2.422
-4 25 222.8 36 97 34.32 76 169 7.82 116 241 2.357
-3 27 211.4 37 99 32.94 77 171 7.566 117 243 2.294
-2 28 200.7 38 100 31.62 78 172 7.321 118 244 2.233
-1 30 190.5 39 102 30.36 79 174 7.086 119 246 2.174
0 32 180.9 40 104 29.15 80 176 6.859 120 248 2.117
1 34 171.9 41 106 28 81 178 6.641 121 250 2.061
2 36 163.3 42 108 26.9 82 180 6.43 122 252 2.007
3 37 155.2 43 109 25.86 83 181 6.228 123 253 1.955
4 39 147.6 44 111 24.85 84 183 6.033 124 255 1.905
5 41 140.4 45 113 23.89 85 185 5.844 125 257 1.856
6 43 133.5 46 115 22.89 86 187 5.663 126 259 1.808
7 45 127.1 47 117 22.1 87 189 5.488 127 261 1.762
8 46 121 48 118 21.26 88 190 5.32 128 262 1.171
9 48 115.2 49 120 20.46 89 192 5.157 129 264 1.674
10 50 109.8 50 122 19.69 90 194 5 130 266 1.632
11 52 104.6 51 124 18.96 91 196 4.849
12 54 99.69 52 126 18.26 92 198 4.703
13 55 95.05 53 127 17.58 93 199 4.562
14 57 90.66 54 129 16.94 94 201 4.426
15 59 86.49 55 131 16.32 95 203 4.294
16 61 82.54 56 133 15.73 96 205 4.167
17 63 78.79 57 135 15.16 97 207 4.045
18 64 75.24 58 136 14.62 98 208 3.927
19 66 71.86 59 138 14.09 99 210 3.812
Temperature Sensor Resistance Value Table for TP (°C-K)
TEMPERATURE SENSOR RESISTANCE TABLE
9
background
mrcool.com 128
Other Temperature Sensor Resistance Value Table (°C-K)
°C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm
-20 -4 115.266 20 68 12.6431 60 140 2.35774 100 212 0.62973
-19 -2 108.146 21 70 12.0561 61 142 2.27249 101 214 0.61148
-18 0 101.517 22 72 11.5 62 144 2.19073 102 216 0.59386
-17 1 96.3423 23 73 10.9731 63 145 2.11241 103 217 0.57683
-16 3 89.5865 24 75 10.4736 64 147 2.03732 104 219 0.56038
-15 5 84.219 25 77 10 65 149 1.96532 105 221 0.54448
-14 7 79.311 26 79 9.55074 66 151 1.89627 106 223 0.52912
-13 9 74.536 27 81 9.12445 67 153 1.89627 107 225 0.51426
-12 10 70.1698 28 82 8.71983 68 154 1.83003 108 226 0.49989
-11 12 66.0898 29 84 8.3356 69 156 1.76647 109 228 0.486
-10 14 62.2756 30 86 7.97078 70 158 1.70547 110 230 0.47256
-9 16 58.7079 31 88 7.62411 71 160 1.64691 111 232 0.45957
-8 18 56.3694 32 90 7.29464 72 162 1.59068 112 234 0.44699
-7 19 52.2438 33 91 6.98142 73 163 1.53668 113 235 0.43482
-6 21 49.3161 34 93 6.68355 74 165 1.48481 114 237 0.42304
-5 23 46.5725 35 95 6.40021 75 167 1.43498 115 239 0.41164
-4 25 44 36 97 6.13059 76 169 1.38703 116 241 0.4006
-3 27 41.5878 37 99 5.87359 77 171 1.34105 117 243 0.38991
-2 28 39.8239 38 100 5.62961 78 172 1.29078 118 244 0.37956
-1 30 37.1988 39 102 5.3689 79 174 1.25423 119 246 0.36954
0 32 35.2024 40 104 5.17519 80 176 1.2133 120 248 0.35982
1 34 33.3269 41 106 4.96392 81 178 1.17393 121 250 0.35042
2 36 31.5635 42 108 4.76253 82 180 1.13604 122 252 0.3413
3 37 29.9058 43 109 4.5705 83 181 1.09958 123 253 0.33246
4 39 28.3459 44 111 4.38736 84 183 1.06448 124 255 0.3239
5 41 26.8778 45 113 4.21263 85 185 1.03069 125 257 0.31559
6 43 25.4954 46 115 4.04589 86 187 0.99815 126 259 0.30754
7 45 24.1932 47 117 3.88673 87 189 0.96681 127 261 0.29974
8 46 22.5662 48 118 3.73476 88 190 0.93662 128 262 0.29216
9 48 21.8094 49 120 3.58962 89 192 0.90753 129 264 0.28482
10 50 20.7184 50 122 3.45097 90 194 0.8795 130 266 0.2777
11 52 19.6891 51 124 3.31847 91 196 0.85248 131 268 0.27078
12 54 18.7177 52 126 3.19183 92 198 0.82643 132 270 0.26408
13 55 17.8005 53 127 3.07075 93 199 0.80132 133 271 0.25757
14 57 16.9341 54 129 2.95896 94 201 0.77709 134 273 0.25125
15 59 16.1156 55 131 2.84421 95 203 0.7537 135 275 0.24512
16 61 15.3418 56 133 2.73823 96 205 0.73119 136 277 0.23916
17 63 14.6181 57 135 2.63682 97 207 0.68844 137 279 0.23338
18 64 13.918 58 136 2.53973 98 208 0.66818 138 280 0.22776
19 66 13.2631 59 138 2.4467 99 210 0.64862 139 282 0.22231
9
TEMPERATURE SENSOR RESISTANCE TABLE
background
mrcool.com129
Pressure Temperature Pressure Temperature
Kpa Bar PSI °C °F Kpa Bar PSI °C °F
58.196 0.58 8.44 -60 -76 935.23 9.35 135.64 8 46.4
61.517 0.62 8.92 -59 -74.2 963.75 9.64 139.78 9 48.2
64.988 0.65 9.43 -58 -72.4 992.93 9.93 14401 10 50
68.615 0.69 9.95 -57 -70.6 1022.8 10.23 148.34 11 51.8
72.402 .072 10.50 -56 -68.8 1053.3 10.53 152.76 12 53.6
76.354 0.76 11.07 -55 -67 1084.5 10.85 157.29 13 55.4
80.478 0.80 11.67 -54 -65.2 1116.4 11.16 161.91 14 57.2
84.776 0.85 12.30 -53 -63.4 1149 11.49 166.64 15 59
89.256 0.89 12.95 -52 -61.6 1182.3 11.82 171.47 16 60.8
93.923 0.94 13.62 -51 -59.8 1216.3 12.16 176.40 17 62.6
98.781 0.99 14.33 -50 -58 1251.1 12.51 181.45 18 64.4
103.84 1.04 15.06 -49 -56.2 1286.6 12.87 186.60 19 66.2
109.1 1.09 15.82 -48 -54.4 1322.8 13.23 191.85 20 68
114.56 1.15 16.61 -47 -52.6 1359.9 13.60 197.23 21 69.8
120.25 1.20 17.44 -46 -50.8 1397.7 13.98 202.71 22 71.6
126.15 1.26 18.30 -45 -49 1436.3 14.36 208.31 23 73.4
132.28 1.32 19.18 -44 -47.2 1475.7 14.76 214.02 24 75.2
138.64 1.39 20.11 -43 -45.4 1515.9 15.16 219.85 25 77
145.24 1.45 21.06 -42 -43.6 1557 15.57 225.82 26 78.8
152.09 1.52 22.06 -41 -41.8 1598.9 15.99 231.89 27 80.6
159.18 1.59 23.09 -40 -40 1641.6 16.42 238.09 28 82.4
166.54 1.67 24.15 -39 -38.2 1685.2 16.85 244.41 29 84.2
174.15 1.74 25.26 -38 -36.4 1729.7 17.30 250.86 30 86
182.04 1.82 26.40 -37 -34.6 1775 17.75 257.43 31 87.8
190.2 1.90 27.59 -36 -32.8 1821.3 18.21 264.15 32 89.6
198.65 1.99 28.81 -35 -31 1868.4 18.68 270.98 33 91.4
207.39 2.07 30.08 -34 -29.2 1916.5 19.17 277.95 34 93.2
216.42 2.16 31.39 -33 -27.4 1965.6 19.66 285.08 35 95
225.76 2.26 32.74 -32 -25.6 2015.5 20.16 292.31 36 96.8
235.41 2.35 34.14 -31 -23.8 2066.5 20.67 299.71 37 98.6
245.37 2.45 35.59 -30 -22 2118.4 21.18 307.24 38 100.4
255.67 2.56 37.08 -29 -20.2 2171.3 21.71 314.19 39 102.2
266.29 2.66 38.62 -28 -18.4 2225.2 22.25 322.73 40 104
277.25 2.77 40.21 -27 -16.6 2280.2 22.80 330.70 41 105.8
288.56 2.89 41.85 -26 -14.8 2336.1 23.36 38.81 42 107.6
300.22 3.00 43.54 -25 -13 2393.2 23.93 347.09 43 109.4
312.24 3.12 45.28 -24 -11.2 2451.3 24.51 355.52 44 111.2
324.63 3.25 47.08 -23 -9.4 2510.4 25.10 364.09 45 113
337.39 3.37 48.93 -22 -7.6 2570.7 25.71 372.84 46 114.8
350.54 3.51 50.84 -21 -5.8 2632.1 26.32 381.74 47 116.6
364.08 3.64 52.80 -20 -4 2694.7 26.95 390.82 48 118.4
378.02 3.78 54.83 -19 -2.2 2758.33 27.58 400.04 49 120.2
392.37 3.92 56.91 -18 -0.4 2823.2 28.23 409.46 50 122
407.13 4.07 59.05 -17 1.4 2889.3 28.89 419.04 51 123.8
System Pressure Table-R454B
SYSTEM PRESSURE TABLE
10
background
mrcool.com 130
Pressure Temperature Pressure Temperature
Kpa Bar PSI °C °F Kpa Bar PSI °C °F
422.31 4.22 61.25 -16 3.2 2956.5 29.57 428.79 52 125.6
437.92 4.38 63.5 -15 5 3025 30.25 438.72 53 127.4
453.98 4.54 65.84 -14 6.8 3094.7 30.95 448.83 54 129.2
470.47 4.70 68.23 -13 8.6 3165.7 31.66 459.13 55 131
487.43 4.87 70.69 -12 10.4 3238.1 32.38 469.63 56 132.8
504.84 5.05 73.22 -11 12.2 3311.7 33.12 480.30 57 134.6
522.73 5.23 75.81 -10 14 3386.7 33.87 491.18 58 136.4
541.1 5.41 78.48 -9 15.8 3463 34.63 502.25 59 138.2
559.95 5.60 81.21 -8 17.6 3540.7 35.41 513.52 60 140
579.31 5.79 84.02 -7 19.4 3619.9 36.20 525.00 61 141.8
599.16 5.99 86.90 -6 21.2 3700.5 37.01 536.69 62 143.6
619.54 6.20 89.85 -5 23 3782.7 37.83 548.61 63 145.4
640.43 6.40 92.88 -4 24.8 3866.3 38.66 560.74 64 147.2
661.86 6.62 95.99 -3 26.6 3951.5 39.52 573.10 65 149
683.82 6.84 99.18 -2 28.4 4038.3 40.38 585.69 66 450.28
706.34 7.06 102.44 -1 30.2 4126.8 41.27 598.52 67 152.6
729.41 7.29 105.79 0 32 4217 42.17 611.60 68 154.4
753.06 7.53 109.22 1 33.8 4309 43.09 624.95 69 156.2
777.28 7.77 112.73 2 35.6 4402.9 44.03 638.56 70 158
802.08 8.02 116.33 3 37.4 4498.7 44.99 652.46 71 159.8
827.47 8.27 120.01 4 39.2 4596.5 45.97 666.64 72 161.6
853.49 8.53 123.78 5 41 4696.5 46.97 681.15 73 163.4
880.11 8.80 127.64 6 42.8 4798.9 47.99 696.00 74 165.5
907.35 9.07 131.60 7 44.6 4904.1 49.04 711.25 75 167
System Pressure Table-R454B Cont.
10
SYSTEM PRESSURE TABLE
background
DIY
®
Series
Hybrid Air Handler
The design and specications of this product and/or manual are subject to change without prior notice.
Consult with the sales agency or manufacturer for details.

Specifications