Installation Instructions
for *R9S80*U Ultra Low
NOx Gas Furnace
CATEGORY I CATÉGORIE I
IOG-2039B
01/2024
19001 Kermier Rd., Waller, TX 77484
www.goodmanmfg.com • www.amana-hac.com
© 2024 Daikin Comfort Technologies Manufacturing, L.P.
is a registered trademark of Maytag Corporation or its related companies and is used under license.
All rights reserved.
These furnaces comply with requirements embodied
in the American National Standard/National Standard
of Canada ANSI Z21.47·CSA-2.3 Gas Fired Central
Furnaces.
Installer: Ax all manuals
adjacent to the unit.
ATTENTION INSTALLING PERSONNEL
As a professional installer, you have an obligation to know
the product better than the customer. This includes all
safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself
with this Instruction Manual. Pay special attention to all
safety warnings. Often during installation or repair, it is
possible to place yourself in a position which is more
hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product
safely and to know it well enough to be able to instruct a
customer in its safe use.
Safety is a matter of common sense...a matter of thinking
before acting. Most dealers have a list of specic, good
safety practices...follow them.
The precautions listed in this Installation Manual are
intended as supplemental to existing practices. However,
if there is a direct conict between existing practices and
the content of this manual, the precautions listed here take
precedence.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION
NOTE: Please contact your distributor or our website listed
below for the applicable Specication Sheet referred to in
this manual.
WARNING
Do not bypass safety devices.
ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL,
ADJUST, SERVICE, MAINTENANCE OR REPAIR
(HEREINAFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN
THIS MANUAL SHOULD SERVICE THE EQUIPMENT.
THIS EQUIPMENT IS NOT INTENDED FOR USE BY
PERSONS (INCLUDING CHILDREN) WITH REDUCED
PHYSICAL, SENSORY OR MENTAL CAPABILITIES, OR
LACK OF EXPERIENCE AND KNOWLEDGE, UNLESS THEY
HAVE BEEN GIVEN SUPERVISION OR INSTRUCTION
CONCERNING USE OF THE APPLIANCE BY A PERSON
RESPONSIBLE FOR THEIR SAFETY.
CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT
THEY DO NOT PLAY WITH THE EQUIPMENT.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR
ANY INJURY OR PROPERTY DAMAGE ARISING FROM
IMPROPER SUPERVISION, SERVICE OR SERVICE
PROCEDURES. IF YOU SERVICE THIS UNIT, YOU ASSUME
RESPONSIBILITY FOR ANY INJURY OR PROPERTY
DAMAGE WHICH MAY RESULT. IN ADDITION, IN
JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES
TO SERVICE THE EQUIPMENT SPECIFIED IN THIS
MANUAL, ONLY LICENSED PERSONNEL SHOULD
SERVICE THE EQUIPMENT. IMPROPER SUPERVISION,
INSTALLATION, ADJUSTMENT, SERVICING, MAINTENANCE
OR REPAIR OF THE EQUIPMENT SPECIFIED IN THIS
MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE
OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL
WITHOUT PROPER SUPERVISION OR TRAINING MAY
RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
WARNING
WARNING
THIS FURNACE MAY BE PAIRED WITH A COOLING UNIT THAT
USES R-32 REFRIGERANT. IF THE COOLING UNIT PAIRED WITH
THIS FURNACE DOES NOT USE R-32, THE R-32 FUNCTION IN
THE FURNACE CONTROL BOARD NEEDS TO BE TURNED OFF.
PLEASE SEE THE ELECTRICAL AND THE R-32 SECTIONS FOR
MORE DETAILS. REFRIGERANT SYSTEMS OTHER THAN 410A
OR R32 MAY REQUIRE AN ADDITIONAL MITIGATION CONTROL
BOARD. REFER TO THE INSTALLATION MANUAL OF THE
INDOOR EVAPORATOR COIL TO DETERMINE INSTALLATION
REQUIREMENTS FOR THAT SUPPLIER’S REFRIGERANT
DETECTION SYSTEM.

2
TABLE OF CONTENTS
SAFETY CONSIDERATIONS ...........................................2
PRODUCT APPLICATION .................................................6
LOCATION REQUIREMENTS AND CONSIDERATIONS . 7
COMBUSTION AND VENTILATION AIR
REQUIREMENTS ........................................................10
CATEGORY I VENTING (VERTICAL VENTING) ............10
MASONRY CHIMNEYS ...................................................11
ELECTRICAL CONNECTIONS ....................................... 11
GAS SUPPLY AND PIPING .............................................13
CIRCULATING AIR AND FILTERS .................................15
NORMAL SEQUENCE OF OPERATION ........................17
COOLING MODE SEQUENCE OF OPERATION ............17
HEAT PUMP MODE .......................................................17
START-UP PROCEDURE AND ADJUSTMENT ..............18
R-32 FUNCTION ..............................................................20
OPERATIONAL CHECKS ...............................................25
SAFETY CIRCUIT DESCRIPTION ..................................25
TROUBLESHOOTING .....................................................26
MAINTENANCE ...............................................................26
CLEANING (QUALIFIED SERVICER ONLY) ..................27
BEFORE LEAVING AN INSTALLATION .........................27
REPAIR AND REPLACEMENT PARTS ..........................27
COMPONENT ID ..............................................................28
TROUBLESHOOTING CHARTS .....................................29
BLOWER PERFORMANCE DATA ..................................31
WIRING DIAGRAM ..........................................................33
START-UP CHECKLIST ..................................................34
SAFETY CONSIDERATIONS
IMPORTANT NOTE: This unit is designed to meet the
NOX requirement of 14Ng/J maximum as required by
the South Coast Air Quality Management District
and the San Joaquin Valley Air Pollution Control
District, both in the State of California, and is
intended for installation in those districts only.
This unit has a Control System that compensates for
certain installation and environmental conditions. This unit
must:
• Be properly installed, operated, and maintained per
the instructions.
• Be serviced only by properly trained Service
Technicians.
This unit is not approved for use with gases other than
Natural Gas.
Units that are not installed, maintained, or operated
properly may result in “noisy” operation during the Heating
Cycle. If this unit is making unusual or objectionable noises
during the Heating Cycle, turn the heat o at the thermostat
and contact a qualied Service organization right away.
Adhere to the following warnings and cautions when
installing, adjusting, altering, servicing, or operating the
furnace. To ensure proper installation and operation,
thoroughly read this manual for specics pertaining to the
installation and application of this product.
This furnace is manufactured for use with natural gas only.
Install this furnace only in a location and position
as specied in LOCATION REQUIREMENTS &
CONSIDERATIONS section and INSTALLATION
POSITIONS section of this manual.
Provide adequate combustion and ventilation air to the
furnace as specied in COMBUSTION & VENTILATION
AIR REQUIREMENTS section of this manual.
Combustion products must be discharged to the outdoors.
Connect this furnace to an approved vent system only,
as specied in CATEGORY 1 VENTING section of this
manual.
Never test for gas leaks with an open ame. Use a
commercially available soap solution made specically for
the detection of leaks to check all connections, as specied
in GAS SUPPLY AND PIPING section of this manual.
Always install a furnace to operate within the furnace’s
intended temperature-rise range with a duct system which
has external static pressure within the allowable range, as
specied on the furnace rating plate and OPERATIONAL
CHECKS section of these instructions.
When a furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space

3
containing the furnace, the return air shall also be handled
by duct(s) sealed to the furnace casing and terminating
outside the space containing the furnace.
A gas-red furnace for installation in a residential
garage must be installed as specied in the LOCATION
REQUIREMENTS AND CONSIDERATIONS section of
this manual.
This furnace may be used as a construction site heater
only if certain conditions are met. These conditions are
listed in the PRODUCT APPLICATION section of this
manual.
WARNING
To prevent personal injury or death due to improper in-
stallation, adjustment, alteration, service or maintenance,
refer to this manual. For additional assistance or informa-
tion, consult a qualified installer, servicer agency or the
gas supplier.
Failure to follow the safety warnings exactly could re-
sult in serious injury, death or property damage.
Never test for gas leaks with an open flame.
Use a commercially available soap solution made specifi-
cally for the detection of leaks to check all connections.
A fire or explosion may result causing property damage,
personal injury or loss of life.
WARNING
FIRE OR EXPLOSION HAZARD
AVERTISSEMENT
RISQUE D’INCENDIE OU D’EXPLOSION
Si les consignes de sécurité ne sont pas suivies à la lettre,
cela peut entraîner la mort, de graves blessures ou des
dommages matériels.
Ne jamais vérifier la présence de fuites de gaz au moyen
d’une flamme nue. Vérifier tous les raccords en utilisant
une solution savonneuse commerciale conçue spécialement
pour la détection de fuites. Un incendie ou une explosion
risque de se produire, ce qui peut entraîner la mort, des
blessures ou des dommages matériels.
WARNING
If the information in these instructions is not followed
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
– Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
– WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
– Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING
Heating unit should not be utilized without reasonable,
routine, inspection, maintenance and supervision. If the
building in which any such device is located will be vacant,
care should be taken that such device is routinely inspect-
ed, maintained, and monitored. In the event that the building
maybe exposed to freezing temperatures and will be vacant,
all water-bearing pipes should be drained, the building
should be properly winterized, and the water source
closed. In the event that the building may be exposed to
freezing temperatures and will be vacant, any hydronic coil
units should be drained as well and, in such case, alterna-
tive heat sources should be utilized.
WARNING
Should overheating occur or the gas supply fail to shut
off, turn off the manual gas shutoff valve external to the
furnace before turning off the electrical supply.
WARNING
Possible property damage, personal injury or death due to
fire, explosion, smoke, soot, condensation, electrical shock
or carbon monoxide may result from improper installation,
repair operation, or maintenance of this product.
WARNING
To prevent personal injury or death due to asphyxiation,
this furnace must be Category I vented. Do not vent using
Category III venting.
Provisions must be made for venting combustion products
outdoors through a proper venting system. The length of
flue pipe could be a limiting factor in locating the furnace.

4
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each ap-
pliance connected to the venting system being placed into
operation could result in carbon monoxide poisoning or
death.
The following steps shall be followed with each appliance
connected to the venting system placed in operation, while
any other appliances connected to the venting system are
not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizon-
tal pitch, as required by the National Fuel Gas Code,
ANSI Z223.1 or the Natural Gas and Propane Installa-
tion Code, CSA B149.1-15 and these instructions. Deter-
mine that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause an
unsafe condition.
3. As far as practical, close all building doors and win-
dows and all doors between the space in which the ap-
pliance(s) connected to the venting system are located
and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connect-
ed to the venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhausts, so they
shall operate at maximum speed.
Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance shall operate continuously.
7. Test for spillage from draft hood appliances at the
draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in accor-
dance with the National Fuel Gas Code ANSI Z223.1/
NFPA 54 and/or National Gas and Propane Installation
Code CSA B149.1-15.
9. After it has been determined that each appliance con-
nected to the venting system properly vents when test-
ed as outlined above, return doors, windows, exhaust
fans, fireplace dampers and any other gas burning
appliance to their previous conditions of use.
AVERTISSEMENT
RISQUE D’INTOXICATION AU MONOXYDE DE CARBONE
Si les étapes décrites ci-dessous ne sont pas suivies pour
chacun des appareils raccordés au système de ventilation
au moment de sa mise en marche, cela peut entraîner une
intoxication au monoxyde de carbone ou la mort.
Les étapes suivantes doivent être suivies pour chacun des
appareils raccordés au système de ventilation au moment
de sa mise en marche, alors que tous les autres appareils
raccordés au système de ventilation ne sont pas en marche :
1. Sceller toutes les ouvertures inutilisées du système
de ventilation.
2. Inspecter le système de ventilation afin de vérifier si la
taille et l’inclinaison par rapport à l’horizontale sont
conformes aux exigences du National Fuel Gas Code,
ANSI Z223.1/NFPA 54 ou du Code d’installation du gaz
naturel et du propane, CSA B149.1 et à ces instructions.
Vérifier qu’il n’y a pas d’obstruction ou de restriction,
de fuite, de corrosion et d’autres problèmes qui pour-
raient entraîner une situation dangereuse.
3. Si possible, fermer toutes les portes et fenêtres du
bâtiment ainsi que toutes les portes séparant l’endroit
où se trouvent les appareils raccordés au système de
ventilation et les autres zones du bâtiment.
4. Fermer le registre des foyers.
5. Mettre les sécheuses en marche ainsi que tous les au-
tres appareils qui ne sont pas raccordés au système de
ventilation. Mettre en marche tous les ventilateurs de
tirage, comme celui des hottes de cuisine et des salles
de bains, et les régler à la puissance maximale.
Ne pas mettre en marche les ventilateurs d’été.
6. Suivre les instructions d’allumage. Mettre en marche
l’appareil soumis à l’inspection. Régler le thermostat
de manière à ce que l’appareil fonctionne en continu.
7. Vérifier la présence de fuite au niveau de l’ouverture
du coupe-tirage des appareils qui en sont dotés après 5
minutes de fonctionnement du brûleur principal. Utilis-
er la flamme d’une allumette ou d’une bougie.
8. Si un problème de ventilation est observé pendant l’un
des essais décrits ci-dessus, des correctifs doivent
être apportés au système de ventilation conformément
au National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou)
au Code d’installation du gaz naturel et du propane,
CSA B149.1.
9. Une fois qu’il a été déterminé que chaque appareil rac-
cordé au système de ventilation fonctionne correcte-
ment au moyen des essais décrits ci-dessus, les portes,
les fenêtres, les ventilateurs, les registres de foyer
et tous les autres appareils de combustion alimentés
au gaz doivent être remis dans leur état initial.

5
CO can cause serious illness including permanent brain
damage or death.
Advertencia especial para la instalación de calentadores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
El monóxido de carbono puede causar enfermedades severas
como daño cerebral permanente ó muerte.
Las emisiones de monóxido de carbono pueden circular a través
del aparato cuando se opera en cualquier modo.
RISQUE D'EMPOISONNEMENT AU
MONOXYDE DE CARBONE
Le monoxyde de carbone peut causer des maladies graves telles que
des dommages permanents au cerveau et meme la mort.
Cette ventilation est nécessaire pour éviter le danger d'intoxication
au CO pouvant survenir si un appareil produisant du monoxyde
de carbone continue de fonctionner au sein de la zone confinée.
Additional Safety Considerations
• This furnace is approved for Category I Venting only.
• Provisions must be made for venting combustion
products outdoors through a proper venting system.
The length of ue pipe could be a limiting factor in
locating the furnace.
Shipping Inspection
All units are securely packed in shipping containers
tested according to International Safe Transit Association
specications. The carton must be checked upon arrival
for external damage. If damage is found, a request for
inspection by carrier’s agent must be made in writing
immediately.
The furnace must be carefully inspected on arrival for
damage and bolts or screws which may have come loose
in transit. In the event of damage the consignee should:
1. Make a notation on delivery receipt of any visible
damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. With concealed damage, carrier must be notied as
soon as possible - preferably within ve days.
4. File the claim with the following support documents
within a nine month statute of limitations.
• Original or certied copy of the Bill of Lading, or
indemnity bond.
• Original paid freight bill or indemnity in lieu
thereof.
• Original or certied copy of the invoice, showing
trade and other discounts or reductions.
• Copy of the inspection report issued by carrier’s
representative at the time damage is reported to
carrier.
The carrier is responsible for making prompt inspection of
damage and for a thorough investigation of each claim.
The distributor or manufacturer will not accept claims from
dealers for transportation damage.
Keep this literature in a safe place for future refer ence.
Electrostatic Discharge (ESD) Precautions
NOTE: Discharge your body’s static electricity
before touching unit. An electrostatic discharge
can adversely affect electrical components.
Use the following precautions during furnace installation
and servicing to protect the integrated control module
from damage. By putting the furnace, the control, and the
person at the same electrostatic potential, these steps
will help avoid exposing the integrated control module to
electrostatic discharge. This procedure is applicable to both
installed and non-installed (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch
the integrated control module or any wire connected
to the control prior to discharging your body’s
electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of
the furnaces near the control. Any tools held in a
person’s hand during grounding will be discharged.
3. Service integrated control module or connecting
wiring following the discharge process in step 2.
Use caution not to recharge your body with static
electricity; (i.e., do not move or shue your feet, do
not touch ungrounded objects, etc.). If you come in
contact with an ungrounded object, repeat step 2
before touching control or wires.
4. Discharge your body to ground before removing
a new control from its container. Follow steps 1
through 3 if installing the control on a furnace.
Return any old or new controls to their containers
before touching any ungrounded object.

6
To The Installer
Before installing this unit, please read this manual
thoroughly to familiarize yourself with specic items which
must be adhered to, including but not limited to: unit
maximum external static pressure, gas pressures, BTU
input rating, proper electrical connections, circulating air
temperature rise, minimum or maximum CFM, and motor
speed connections, and venting. These furnaces are
designed for Category I venting only.
WARNING
To prevent property damage, personal injury or death due
to fire, do not install this furnace in a mobile home, trailer,
or recreational vehicle.
NOTE: This unit should be installed in a manner so
that it is not accessible to the public.
PRODUCT APPLICATION
This furnace is primarily designed for residential home-
heating applications. It is not designed or certied for use in
mobile homes, trailers or recreational vehicles. Neither is it
designed or certied for outdoor applications. The furnace
must be installed indoors (i.e., attic space, crawl space, or
garage area provided the garage area is enclosed with an
operating door).
This furnace can be used in the following non-industrial
commercial applications:
Schools, Oce buildings, Churches, Retail stores,
Nursing homes, Hotels/motels, Common or oce
areas
In such applications, the furnace must be installed with the
following stipulations:
• It must be installed per the installation instructions
provided and per local and national codes.
• It must be installed indoors in a building constructed
on site.
• It must be part of a ducted system and not used in a
free air delivery application.
• It must not be used as a “make-up” air unit.
• All other warranty exclusions and restrictions apply.
This furnace may be used as a construction site heater
ONLY if the following conditions are met:
• The vent system is permanently installed per these
installation instructions.
• A room thermostat is used to control the furnace.
Fixed jumpers that provide continuous heating
CANNOT be used and can cause long term
equipment damage. Bi-metal thermostats, or any
thermostat aected by vibration must not be used
during construction.
• Return air ducts are provided and sealed to the
furnace.
• A return air temperature range between 60°F (16°C)
and 80°F (27°C) is maintained.
• Air lters are installed in the system and replaced
daily during construction and upon completion of
construction.
• The input rate and temperature rise are set per the
furnace rating plate.
• 100% outside air must be used for combustion
during construction. Temporary ducting may be used
to supply outside air to the furnace for combustion –
do not connect this duct directly to the furnace. Size
this duct according to NFPA 54/ANSI Z223.1 section
for Combustion and Ventilation Air.
• The furnace heat exchanger, components, duct
system, air lters and evaporator coils are thoroughly
cleaned following nal construction clean up by a
qualied person.
• All furnace operating conditions (including ignition,
input rate, temperature rise and venting) are veried
by a qualied person according to these installation
instructions.
• Furnace doors must be in place on the furnace while
the furnace is operating in any mode.
Damage or repairs due to failure to comply with these
requirements are not covered under the warranty.
To ensure proper furnace operation, install, operate
and maintain the furnace in accordance with these
installation and operation instructions, all local
building codes and ordinances. In their absence, follow
the latest edition of the National Fuel Gas Code (NFPA 54/
ANSI Z223.1), local plumbing or waste water codes, and
other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI
Z223.1) can be obtained from any of the following:
American National Standards Institute
25 West 43rd Street, 4th Floor
New York, NY 10036
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley
Cleveland, OH 44131
Additional helpful publications available from the NFPA
are, NFPA 90A - Installation of Air Conditioning and
Ventilating System and NFPA 90B - Warm Air Heating and
Air Conditioning System.
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved
method or in accordance with “ASHRAE Guide” or “Manual
J-Load Calculations” published by the Air Conditioning
Contractors of America.

7
LOCATION REQUIREMENTS AND
CONSIDERATIONS
WARNING
To prevent possible equipment damage, property damage,
personal injury or death, the following bullet points must
be observed when installing this unit.
Follow the instructions listed below when selecting a
furnace location. Refer also to the guidelines provided in
Combustion and Ventilation Air Requirements.
• Centrally locate the furnace with respect to the
proposed or existing air distribution system.
• Ensure the temperature of the return air entering
the furnace is between 55°F and 100°F when the
furnace is heating.
• Provisions must be made for venting combustion
products outdoors through a proper venting system.
The length of ue pipe could be a limiting factor in
locating the furnace.
• Ensure adequate combustion air is available for
the furnace. Improper or insucient combustion air
can expose building occupants to gas combustion
products that could include carbon monoxide. Refer
to Combustion and Ventilation Air Requirements.
• The furnace must be level. If the furnace is to be set
on a oor that may become wet or damp at times,
the furnace should be supported above the oor on a
concrete base sized approximately 1-1/2” larger than
the base of the furnace.
• Ensure upow or horizontal furnaces are not installed
directly on carpeting, or any other combustible
material. The only combustible material allowed is
wood.
• Exposure to contaminated combustion air will result
in safety and performance-related problems. Do
not install the furnace where the combustion air is
exposed to the following substances:
permanent wave solutions
chlorinated waxes or cleaners
chlorine-based swimming pool chemicals
carbon tetrachloride
water softening chemicals
swimming pool chemicals
deicing salts or chemicals
halogen type refrigerants
printing inks
cleaning solutions (such as perchloroethylene)
paint removers
varnishes
hydrochloric acid
cements and glues
antistatic fabric softeners for clothes dryers
masonry acid washing materials
• If the furnace is used in connection with a cooling
unit, install the furnace upstream or in parallel with
the cooling unit coil. Premature heat exchanger
failure will result if the cooling unit coil is placed
ahead of the furnace.
For vertical (upow) applications, the minimum
cooling coil width shall not be less than furnace
width minus 1”. Additionally, a coil installed above
an upow furnace may be the same width as the
furnace or may be one size larger than the furnace.
EXAMPLE: A “C” width coil may be installed with a
“B” width furnace.
For upow applications, the front of the coil and
furnace must face the same direction.
• If the furnace is installed in a residential garage,
position the furnace so that the burners and ignition
source are located not less than 18 inches above the
oor. Protect the furnace from physical damage by
vehicles.
• If the furnace is installed horizontally, ensure access
doors are not on the “up/top” or “down/bottom” side
of the furnace.
• Do not connect this furnace to a chimney ue that
serves a separate appliance designed to burn solid
fuel.
Top - 1"
Side
Clearance - 1"
Back - 0"
Front Clearance - 3"
Vent Pipe Clearance to Combustibles-
6" using Single Wall Connector or 1"
using B1 vent.
Figure 1
• Adequate combustion/ventilation air must be
supplied to the closet. Improper or insucient
combustion air can expose building occupants to
gas combustion products that could include carbon
monoxide.
• Furnace must be completely sealed to oor or
base. Combustion/ventilation air supply pipes must
terminate 12” from top of closet and 12” from oor
of closet. DO NOT remove solid base plate for side
return.
• Return air ducts must be completely sealed to
the furnace and terminate outside the enclosure
surfaces.
Clearances and Accessibility
NOTE: For servicing or cleaning, a 24” front
clearance is required. Unit connections

8
(electrical, flue and drain) may necessitate
greater clearances than the minimum clearances
listed above. In all cases, accessibility clearance
must take precedence over clearances from the
enclosure where accessibility clearances are
greater.
Clearance in accordance with local installation codes, the
requirements of the gas supplier and the manufacturer’s
installation instructions.
Dégaugement conforme aux codes d’installation locaux,
aux exigences du fournisseur de gaz et aux instructions
d’installation du fabricant.
TOP
B1-VENT
SINGLE
(PLENUM)
1" 6" 1" 3" 0" 1"
VENT
SIDES
FRONT
BACK
Top clearance for horizontal configuration - 1”
Table 1
Installations must adhere to the clearances to combustible
materials to which this furnace has been design certied.
The minimum clearance information for this furnace is
provided on the unit’s clearance label. These clearances
must be permanently maintained. Clearances must also
accommodate an installation’s gas, electrical, and drain
line connections.
NOTE: In addition to the required clearances to
combustible materials, a minimum of 24” service
clearance must be available in front of the unit.
Installation Positions
An upow furnace may be installed in an upright position
or horizontal on either the left or right side panel. Do not
install this furnace on its back. For vertically installed
upow furnaces, return air ductwork may be attached
to the side panel(s) and/or basepan. For horizontally
installed upow furnaces, return air ductwork must be
attached to the basepan. Contact your distributor for proper
airow requirements and number of required ductwork
connections. Refer to, “Recommended Installation
Positions” for appropriate installation positions, ductwork
connections, and resulting airow arrangements.
NOTE: Ductwork must never be attached to the
back of the furnace.
Venting for Horizontal Left or Right Installations
Always use a B-vent elbow to vent the ue from the top of
the furnace. The inducer cannot be turned due to limited
space in the cabinet. Do not attempt to do this.
Figure 2
Horizontal Installation
Recommended Installation Positions
Figure 3
For
horizontal installations,
insert the
#8 x 5/8 screw
from the
literature package.
Figure 4

9
Line contact to framing is permitted when installed in the
horizontal conguration. Line contact is dened as the
portion of the cabinet that is formed by the intersection of
the top and side. ACCESSIBILITY CLEARANCE, WHERE
GREATER, SHOULD TAKE PRECEDENCE OVER
MINIMUM FIRE PROTECTION CLEARANCE. A gas-
red furnace for installation in a residential garage must
be installed so that the ignition source and burners are
located not less than eighteen inches (18”) above the oor
and is protected or located to prevent physical damage by
vehicles. A gas furnace must not be installed directly on
carpeting, tile, or other combustible materials other than
wood ooring.
Furnace Suspension
If suspending the furnace from rafters or joist, use 3/8”
threaded rod and 2”x2”x3/8” angle iron as shown below.
The length of rod will depend on the application and the
clearances necessary.
Suspended Furnace
Figure 5
Existing Furnace Removal
NOTE: When an existing furnace is removed from
a venting system serving other appliances, the
venting system may be too large to properly vent
the remaining attached appliances.
The following vent testing procedure is repro duced from
the American National Standard/National Standard of
Canada for Gas-Fired Central Furnaces ANSI Z21.47-
Latest Edition, CSA-2.3-Latest Edition Section 1.23.1.
The following steps shall be followed with each appliance
connected to the venting system placed in operation, while
any other appliances connected to the venting system are
not in operation:
a. Seal any unused openings in the venting system;
b. Inspect the venting system for proper size
and horizontal pitch, as required by the
National Fuel Gas Code, ANSI Z223.1 and
these instructions. Determine that there is no
blockage or restriction, leakage, corrosion and
other deciencies which could cause an unsafe
condition;
c. In so far as practical, close all building doors
and windows and all doors between the space
in which the appliance(s) connected to the
venting system are located and other spaces
of the building. Turn on clothes dryers and any
appliance not connected to the venting system.
Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they shall operate
at maximum speed. Do not operate a summer
exhaust fan. Close replace dampers;
d. Follow the lighting instructions. Place the
appliance being inspected in operation.
Adjust thermostat so appliance shall operate
continuously;
e. Test for draft hood equipped appliance spillage
at the draft hood relief opening after 5 minutes of
main burner operation. Use the ame of a match
or candle;
f. After it has been determined that each appliance
connected to the venting system properly vents
when tested as outlined above, return doors,
windows, exhaust fans, replace dampers and
any other gas burning appliance to their previous
conditions of use;
g. If improper venting is observed during any of the
above tests, the common venting system must
be corrected.
Corrections must be in accordance with the latest edition of
the National Fuel Gas Code NFPA 54/ANSI Z223.1.
If resizing is required on any portion of the venting system,
use the appropriate table in the latest edition of the
National Fuel Gas Code ANSI Z223.1.
Thermostat Location
The thermostat should be placed approximately ve feet
from the oor on a vibration-free, inside wall in an area
having good air circulation. Do not install the thermostat
where it may be inuenced by any of the following:
• Drafts, or dead spots behind doors, in corners, or
under cabinets.
• Hot or cold air from registers.
• Radiant heat from the sun.
• Light xtures or other appliances.
• Radiant heat from a replace.
• Concealed hot or cold water pipes, or chimneys.
• Unconditioned areas behind the thermostat, such as
an outside wall.
Consult the instructions packaged with the thermostat for
mounting instructions and further precautions.
COMBUSTION AND VENTILATION
AIR REQUIREMENTS

10
WARNING
To avoid property damage, personal injury or death, suffi-
cient fresh air for proper combustion and ventilation of
flue gases must be supplied. Most homes require outside air
be supplied into the furnace area.
Improved construction and additional insulation in buildings
have reduced heat loss by reducing air inltration and
escape around doors and windows. These changes have
helped in reducing heating/cooling costs but have created
a problem supplying combustion and ventilation air for
gas red and other fuel burning appliances. Appliances
that pull air out of the house (clothes dryers, exhaust
fans, replaces, etc.) increase the problem by starving
appliances for air.
House depressurization can cause back drafting or
improper combustion of gas-red appliances, thereby
exposing building occupants to gas combustion products
that could include carbon monoxide.
If this furnace is to be installed in the same space with
other gas appliances, such as a water heater, ensure there
is an adequate supply of combustion and ventilation air for
all appliances. Refer to the latest edition of the National
Fuel Gas Code NFPA 54/ANSI Z223.1 or applicable
provisions of the local building codes for determining the
combustion air requirements for the appliances.
This furnace must use indoor air for combustion. It cannot
be installed as a direct vent (i.e., sealed com bustion)
furnace.
Most homes will require outside air be supplied to the
furnace area by means of ventilation grilles or ducts
connecting directly to the outdoors or spaces open to the
outdoors such as attics or crawl spaces. A furnace installed
in a conned space (i.e., a closet or utility room) must
have two ventilation openings with a total minimum free
area of 0.25 square inches per 1,000 BTU/hr of furnace
input rating. Refer to Specication Sheet applicable to your
model for minimum clearances to combustible surfaces.
One of the ventilation openings must be within 12” of the
top; the other opening must be within 12” of the bottom of
the conned space. In a typical construction, the clearance
between the door and door frame is usually adequate to
satisfy this ventilation requirement.
CATEGORY I VENTING
(VERTICAL VENTING)
WARNING
To prevent possible personal injury or death doe to asphyx-
iation, this furnace must be Category I vented. Do not vent
using Category III venting.
Category I Venting is venting at a non-positive pressure. A
furnace vented as Category I is considered a fan-assisted
appliance and the vent system does not have to be “gas
tight”. NOTE: Single stage gas furnaces with induced
draft blowers draw products of combustion through a
heat exchanger allowing, in some instances, common
venting with natural draft appliances (i.e. water heaters).
All installations must be vented in accordance with the
latest edition of the National Fuel Gas Code NFPA 54/ANSI
Z223.1.
NOTE: The vertical height of the category 1
venting system must be at least as great as the
horizontal length of the vertical system.
WARNING
To prevent possible personal injury or death doe to asphyx-
iation, common venting with other manufacturer’s induced
draft appliances is not allowed.
The minimum vent diameter for the Category I venting
system is as shown:
MINIMUM VENT
UPFLOW
40 4 Inch
60 4 Inch
80 4 Inch
MODEL
Table 2
Under some conditions, larger vents than those shown
above may be required or allowed. When an existing
furnace is removed from a venting system serving other
appliances, the venting system may be too large to
properly vent the remaining attached appliances.
MASONRY CHIMNEYS

11
WARNING
Possibility of property damage, personal injury or death
damaging condensation can occur inside masonry chim-
neys when a single fan-assisted Category I appliance (80%
AFUE Furnace) is vented without adequate dilution air. Do
not connect an 80% furnace to a masonry chimney unless
the furnace is common vented with a draft hood equipped
appliance or the chimney is lined with a metal liner or type
B metal vent. All installations using masonry chimneys must
be sized in accordance with the appropriate venting ta-
bles. If an 80% furnace is common vented with a draft hood
equipped appliance, the potential for condensation damage
may still exist with extremely cold conditions, long vent
connectors, exterior chimneys, or any combination of these
conditions. The risk of condensation damage is best avoided
by using masonry chimney as a pathway for properly sized
metal liner or type B metal vent.
Masonry Chimney Termination
A masonry chimney used as a vent for gas red equipment
must extend at least three feet above the highest point
where it passes through the roof. It must extend at least
two feet higher than any portion of a building within a
horizontal distance of 10 feet. In addition, the chimney
must terminate at least 3 feet above any forced air inlet
located within 10 feet. The chimney must extend at least
ve feet above the highest connected equipment draft
hood outlet or ue collar.
ELECTRICAL CONNECTIONS
WARNING
HIGH VOLTAGE!
To avoid personal injury or death due to
electrical shock, disconnect electrical power
before servicing or changing any electrical
wiring.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
WARNING
HIGH VOLTAGE!
To avoid risk of injury, electrical shock or
death, the furnace must be electrically polar-
ized and grounded in accordance with local
codes or their absence, with the latest edition
of the National Electric Code.
Wiring Harness
The wiring harness is an integral part of this furnace. Field
alteration to comply with electrical codes should not be
required. Wires are color coded for identication purposes.
Refer to the wiring diagram for wire routings. If any of
the original wire as supplied with the furnace must be
replaced, it must be replaced with wiring material having
a temperature rating of at least 105°C. Any replacement
wiring must be a copper conductor.
120 Volt Line Connections
Before proceeding with electrical connections, ensure
that the supply voltage, frequency, and phase correspond
to that specied on the unit rating plate. Power supply to
the furnace must be NEC Class 1, and must comply with
all applicable codes. The furnace must be electrically
grounded in accordance with local codes or, in their
absence, with the latest edition of The National Electric
Code, ANSI NFPA 70.
Use a separate fused branch electrical circuit containing
properly sized wire, and fuse or circuit breaker. The fuse
or circuit breaker must be sized in accordance with the
maximum overcurrent protection specied on the unit
rating plate. An electrical disconnect must be provided at
the furnace location.
Line voltage wiring must enter into the junction box
provided with the furnace. Connect hot neutral and ground
wires as shown in the wiring diagram located on the unit’s
blower door. Metal conduit is not considered a substitute
for an actual ground wire to the unit.
Line polarity must be observed when making eld
connections. Line voltage connections can be made
through either the right or left side panel. To relocate the
junction box, follow the steps shown in the Junction Box
Relocation section.
Junction Box Relocation
WARNING
Edges of sheet metal holes may be sharp. Use gloves as a
precaution when removing hole plugs.
Line voltage connections can be made through either the
right or left side panel. The furnace is shipped congured
for a right side electrical connection. To make electrical
connections through the opposite side of the furnace,
the junction box must be relocated to the left side prior to
making electrical connections. To relocate the junction box,
perform the following steps.
WARNING
To prevent personal injury or death due to electric shock,
disconnect electrical power before installing or servicing
this unit.
1. Remove both doors from the furnace.
2. Remove and save the screws holding the junc tion

12
box to the right side of the furnace.
3. Models that have the junction box located in the
burner compartment will need to move the junction
box directly over.
4. Attach the junction box to the left side of the fur nace,
using the screws removed in step 2.
5. Check the location of the wiring. Conrm that it
will not be damaged by heat from the burners or
by the rotation of the fan. Also conrm that wiring
location will not interfere with l ter removal or other
maintenance.
After the junction box is in the desired location, use
washers to connect eld-supplied conduit to the junction
box in accordance with NEC and local codes. Connect hot,
neutral, and ground wires as shown in the furnace wiring
diagram. The wires and ground screw are located in the
furnace junction box.
Low voltage wires may be connected to the terminal strip.
IMPORTANT NOTE: To avoid possible equipment
malfunction, route the low voltage wires to
avoid interference with filter removal or other
maintenance.
WARNING
HIGH VOLTAGE!
To avoid risk of injury, electrical shock or
death, the furnace must be electrically polar-
ized and grounded in accordance with local
codes or their absence, with the latest edition
of the National Electric Code.
To ensure proper unit grounding, the ground wire should
run from the furnace ground screw located inside the
furnace junction box all the way back to the electrical
panel. NOTE: Do not use gas piping as an electrical
ground. To conrm proper unit grounding, turn o the
electrical power and perform the following check.
1. Measure resistance between the neutral (white)
connection and the unpainted surface on the
furnace.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock
switch which interrupts unit voltage when the blower door
is opened for servicing. Do not defeat this switch.
24 Volt Thermostat Wiring
NOTE: Wire routing must not interfere with
circulator blower operation, filter removal, or
routine maintenance.
Low voltage connections can be made through either the
right or left side panel. Thermostat wiring entrance holes
are located in the blower compartment. The following gure
shows connections for a “heat only” system and “heat/cool
system”.
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Single-Stage Cooli
ng)
24 VAC
Thermostat
Y1
Y2
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Two-Stage Cooling)
24 VAC
Thermostat
Y2
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VAC
Thermostat
Heat Pump
R
C
Y
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VAC
Thermostat
Two Stage
Heat Pump
R
C
Y
Y2
Y2
Y1
Y2
Y2
Non-communicating Single Stage A/C
Figure 6A
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Single-Stage Cooling)
24 VAC
Thermostat
Y1
Y2
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Two-Stage Cooling)
24 VAC
Thermostat
Y2
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VAC
Thermostat
Heat Pump
R
C
Y
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VAC
Thermostat
Two Stage
Heat Pump
R
C
Y
Y2
Y2
Y1
Y2
Y2
Non-communicating Two Stage A/C
Figure 6B
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Single-Stage Cooling)
24 VAC
Thermostat
Y1
Y2
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Two-Stage Cooling)
24 VAC
Thermostat
Y2
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VAC
Thermostat
Heat Pum
p
R
C
Y
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VAC
Thermostat
Two Stage
Heat Pump
R
C
Y
Y2
Y2
Y1
Y2
Y2
Non-Communicating Single Stage Heat Pump
Figure 6C
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Single-Stage Cooling)
24 VAC
Thermostat
Y1
Y2
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
C
Y
Remote
Condensing Unit
(Two-Stage Cooling)
24 VAC
Thermostat
Y2
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VAC
Thermostat
Heat Pump
R
C
Y
Y1
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
24 VAC
Thermostat
Two Stage
Heat Pum
p
R
C
Y
Y2
Y2
Y1
Y2
Y2
Non-Communicating Two Stage Heat Pump
Figure 6D
NOTE: Equipment type (Single-stage cooling, Two-
stage cooling, Single-stage heat pump, Two-stage
heat pump) MUST be setup through the OdS menu
by the installer for proper system operation. See
Using Push-Button Switches for instructions on
how to navigate the control menu.
This furnace is equipped with a 40 VA transformer to
facilitate use with most cooling equipment. Consult the

13
wiring diagram, located on the blower compartment door,
for further details of 120 Volt and 24 Volt wiring.
A single-stage thermostat with only one heating stage is
needed to control this furnace.
Low Voltage Ventilation
The Ventilation connections provide dry contact for eld
ventilator wiring connections. These connections are
normally open and energize during the R-32 fault/alarm
condition. A VT IN and a VT OUT connectors are provided
and are shown in the image below.
Low Voltage A2L Alarm
The A2L alarm connection provides 24VAC for eld alarm
wiring connections. These connections are normally open
and energize during the R-32 fault/alarm condition. An A2L
Alarm connector is provided and is shown in the image
below.
Field Installed Accessories (Daughter Board)
Additional accessories that do not have dedicated
terminals on the furnace control board may require an
additional daughter board to be installed. Please refer to
service manual on your product for more information.
R-32 SENSOR
24 VOLT
VENTILATION
(OPTIONAL)
24 VOLT A2L ALARM
(OPTIONAL)
24 VAC Accessories - Accessories WIring
Figure 7
120 Volt Line Connection of Accessories
Humidifier and Electronic Air Cleaner
WARNING
HIGH VOLTAGE!
To avoid personal injury or death due to
electrical shock, disconnect electrical power
before servicing or changing any electrical
wiring.
The furnace integrated control module is equipped with
dedicated ¼ inch EAC and HUM relay terminals for
controlling external power to an optional eld-supplied
humidier and/or electronic air cleaner. Additional line
voltage wiring to the inside of the furnace must conform to
all local codes and have a minimum temperature rating of
105°C. All line voltage wire splices must be made inside
the furnace.
When utilized, the HUM relay will be closed during normal
heating operation and the EAC relay will be closed
during fan operation. 120VAC must be present on the
one terminal from HUM or EAC to take advantage of the
second terminal.
115 VAC EAC
115 VAC
HUM
120 Volt Line Connection of Accessories Humidifier (HUM) &
Electronic Air Cleaner (EAC)
Figure 8
Fossil Fuel Applications
This furnace can be used in conjunction with a heat pump
in a fossil fuel application. A fossil fuel application refers to
a combined gas furnace and heat pump installation which
uses an outdoor temperature sensor to determine the most
cost ecient means of heating heat pump or gas furnace.
A heat pump thermostat with two stages of heat is required
to properly use a furnace in conjunction with a heat pump.
Refer to the fossil fuel kit installation instructions for
additional thermostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit
installation instructions. All furnace connections must be
made to the furnace integrated control module and the
FURNACE terminal strip on the fossil fuel control board.
GAS SUPPLY AND PIPING
The furnace rating plate includes the approved furnace gas
input rating and gas types. The furnace must be equipped
to operate on the type of gas applied.
CAUTION
To prevent unreliable operation or equipment damage, the
inlet gas supply pressure must be as specified on the unit
rating plate with all other household gas fired appliances
operating.
Inlet gas supply pressures must be maintained within the
ranges specied in the following table. The supply pressure
must be constant and available with all other household
gas red appliances operating. The minimum gas supply
pressure must be maintained to prevent unreliable ignition.
The maximum must not be exceeded to prevent unit
overring and damage to gas valve.
NOTE: Do not remove the gas valve inlet plug
before the gas line is installed. Replace if water

14
or debris has been introduced.
Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c.
INLET GAS SUPPLY PRESSURE
Table 4
High Altitude Derate
IMPORTANT NOTE: The furnace, as shipped,
requires no change to run between 0-4500 feet.
Manifold pressure adjustments and combustion
analysis are required for all installations
above 4500 ft. Refer to “Gas Supply Pressure
Measurement” section for instruction on how to
properly measure and adjust manifold “outlet”
pressure. The furnace should operate for a
minimum of 15 minutes before taking a combustion
sample. Combustion samples should be taken
from beyond the furnace exhaust and must be
within provided CO2% range. See Table 5 for
recommended manifold pressure adjustments and
proper CO2% range. Gas heating values can vary;
further pressure adjustment may be necessary
to ensure furnace operates within acceptable
CO2 range. At all altitudes the air temperature
rise must be within the range listed on the
Specification Sheet applicable to your model for
the fuel used.
80%
Model
Manifold
Pressure at
5000 ft
Manifold
Pressure at
7500 ft
CO2%
Natural Gas
040 2.5" w.c. 2.4" w.c. 5.5 - 7.0
060 2.5" w.c. 2.4" w.c. 5.7 - 7.2
080 2.5" w.c. 2.4" w.c. 6.0 - 7.5
Table 5
Gas Piping Connections
WARNING
To avoid possible unsatisfactory operation or equipment
damage due to underfiring of equipment, use the proper size
of natural gas piping needed when running pipe from the
meter to the furnace.
When sizing gas lines, be sure to include all appliances
on the same gas supply line and which will operate
simultaneously.
The gas piping supplying the furnace must be properly
sized based on the gas ow required, specic gravity of the
gas, and length of the run. The gas line installation must
comply with local codes, or in their absence, with the latest
edition of the National Fuel Gas Code, NFPA 54/ANSI
Z223.1.
Natural Gas Capacity of Pipe
In Cubic Feet of Gas Per Hour (CFH)
Length of Nominal Black Pipe Size
Pipe in Feet 1/2" 3/4" 1" 1 1/4" 1 1/2"
10 132 278 520 1050 1600
20 92 190 350 730 1100
30 73 152 285 590 980
40 63 130 245 500 760
50 56 115 215 440 670
60 50 105 195 400 610
70 46 96 180 370 560
80 43 90 170 350 530
90 40 84 160 320 490
100 38 79 150 305 460
(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on
0.60 Specif ic Gravity Gas)
CFH =
BTUH Furnace Input
Heating Value of Gas (BTU/Cubic Foot)
Table 6
To connect the furnace to the building’s gas piping, the
installer must supply a ground joint union, drip leg, manual
shuto valve, and line and ttings to connect to gas valve.
In some cases, the installer may also need to supply a
transition piece from 1/2” pipe to a larger pipe size.
The following stipulations apply when connecting gas
piping.
• Gas piping must be supported external to the furnace
cabinet so that the weight of the gas line does not
distort the burner rack, manifold or gas valve.
• Use black iron or steel pipe and ttings for the
building piping. Where possible, use new pipe that
is properly chamfered, reamed, and free of burrs
and chips. If old pipe is used, be sure it is clean and
free of rust, scale, burrs, chips, and old pipe joint
compound.
• Use pipe joint compound on male threads ONLY.
Always use pipe joint compound (pipe dope) that
is APPROVED FOR ALL GASES. DO NOT apply
compound to the rst two threads.
• Use ground joint unions.
• Install a drip leg to trap dirt and moisture before
it can enter the gas valve. The drip leg must be a
minimum of three inches long.
• Install a 1/8” NPT pipe plug tting, accessible for test
gage connection, immediately upstream of the gas
supply connection to the furnace.
• Always use a back-up wrench when making the
connection to the gas valve to keep it from turning.
The orientation of the gas valve connection is 374 in-
lbs; excessive over-tightening may damage the gas
valve and/or gas manifold assembly.
• Install a manual shuto valve between the gas
meter and unit within six feet of the unit. If a union
is installed, the union must be downstream of the
manual shuto valve, between the shuto valve and
the furnace.
• Tighten all joints securely.
• Protect connectors and semi-rigid tubing against
physical and thermal damage when installed.
Ensure aluminum-alloy tubing and connectors are
coated to protect against external corrosion when

15
in contact with masonry, plaster, or insulation, or
subjected to repeated wetting by liquids such as
water (except rain water), detergents, or sewage.
The gas piping may enter the left or right side of the
furnace cabinet. The installer must supply rigid pipe
long enough to reach the outside of the cabinet to
seal the grommet cabinet penetration. A semi-rigid
connector to the gas piping can be used outside the
cabinet per local codes. 1/2” NPT pipe and ttings
are required. Model requires one 90 deg elbow, one
2” nipple and additional nipple to reach outside the
cabinet. A semi-rigid connector to the gas piping can
be used outside the cabinet per local codes. From
the elbow, the length of pipe and the ttings required
will vary by the side chosen, location of union and
cabinet width. The union may be placed inside or
outside of the cabinet.
Location of Manual Valve
(Installed Ahead of
Ground Joint Pipe Union)
Height Required
By Local Code
Ground Joint Pipe Union
To Be Installed
Ahead of Gas Valve
Drip Leg
OPTIONAL:
Reducing Coupling
1/2” x 1/8” with 1/8”
Pipe Plug to Measure
Line Gas Pressure
General Furnace Layout
Figure 9
Upflow Installations
A ground joint union, drip leg, and manual shuto valve
must also be supplied by the installer. In some cases, the
installer may also need to supply a transition piece from 1/2”
to another pipe size.
When the gas piping enters through the side of the furnace,
the installer must supply the following ttings (starting from
the gas valve nipple elbow):
• Straight pipe to reach the exterior of the furnace.
• A ground joint union, drip leg, and manual shuto
valve must also be supplied by the installer.
Gas Piping Checks
Before placing unit in operation, leak test the unit and gas
connections.
WARNING
To avoid the possibility of explosion or fire, never use a
match or open flame to test for leaks.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector, or
other approved testing methods.
CAUTION
To prevent property damage or personal injury due to fire,
the following instructions must be performed regarding
gas connections, pressure testing, location of shutoff valve
and installation of gas piping.
NOTE: Never exceed specified pressures for
testing. Higher pressure may damage the gas valve
and cause subsequent overfiring, resulting in heat
exchanger failure.
Disconnect this unit and shuto valve from the gas supply
piping system before pressure testing the supply piping
system with pressures in excess of 1/2 psig (3.48 kPa).
This unit must be isolated from the gas supply system by
closing its manual shuto valve before pressure testing of
gas supply piping system with test pressures equal to or
less than 1/2 psig (3.48 kPa).
WARNING
If the gas furnace is installed in a basement, an excavat-
ed area or confined space, it is strongly recommended to
contact a certified contractor to install a gas detecting
warning device in case of a gas leak.
CIRCULATING AIR AND FILTERS
Ductwork - Air Flow
WARNING
Never allow the products of combustion, including carbon
monoxide, to enter the return ductwork or circulation air
supply.
Duct systems and register sizes must be properly designed
for the CFM and external static pressure rat ing of the
furnace. Ductwork should be designed in accor dance
with the recommended methods of “Air Conditioning
Contractors of America” Manual D.
A duct system must be installed in accordance with
Standards of the National Board of Fire Underwriters for
the Installation of Air Conditioning, Warm Air Heating and
Ventilating Systems. Pamphlets No. 90A and 90B.
A closed return duct system must be used, with the
return duct connected to the furnace. NOTE: Ductwork
must never be attached to the back of the furnace. For
installations requiring more than 1800 CFM, use a bottom

16
return or two sided return. Supply and return con nections
to the furnace may be made with exible joints to reduce
noise transmission. To prevent the blower from inter fering
with combustion air or draft when a central return is used, a
connecting duct must be installed between the unit and the
utility room wall. Furnace is shipped with the top anges in
the at position. Before installing a coil or ducts, the anges
must be bent 90°. A room, closet, or alcove must not be
used as a return air chamber.
When the furnace is used in connection with a cooling unit,
the furnace should be installed in parallel with or on the
upstream side of the cooling unit to avoid condensa tion
in the heating element. With a parallel ow arrange ment,
the dampers or other means used to control the ow of
air must be adequate to prevent chilled air from entering
the furnace and, if manually operated, must be equipped
with means to prevent operation of either unit unless the
damper is in the full heat or cool position.
Damper must be in open position when appliance main
burner is operating.
When the furnace is installed without a cooling coil, it is
recommended that a removable access panel be provided
in the outlet air duct. This opening shall be accessible
when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for visual light
inspection or such that a sampling probe can be inserted
into the airstream. The access panel must be made to
prevent air leaks when the furnace is in operation.
NOTE: In a horizontal installation the air
conditioning coil must be adequately supported
by proper brackets and supports. Inadequate coil
support can result in furnace cabinet distortion
and air leakage.
When the furnace is heating, the temperature of the return
air entering the furnace must be between 55°F and 100°F.
When a furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by a duct sealed to the furnace casing and terminating
outside the space containing the furnace.
WARNING
Edges of sheet metal holes may be sharp. Use gloves as
a precaution when removing sheet metal from return air
openings.
Filters - Read This Section Before Installing
The Return Air Ductwork
Filters must be used with this furnace. Discuss lter
maintenance with the building owner. Filters do not ship
with this furnace, but must be provided by the installer.
Filters must comply with UL900 or CAN/ULCS111
standards. Damage or repairs due to failure to install lters
in the furnace are not covered under the warranty.
NOTE: An undersized opening will cause reduced
airflow. Refer to the Filter Sizing Chart to
determine filter area requirements.
Upright Installations
Depending on the installation and/or customer preference,
diering lter arrangements can be applied. Filters can
be installed in the central return register or a side panel
external lter rack kit (upows). As an alternative, a media
air lter or electronic air cleaner can be used as the primary
lter. The following gure shows possible lter locations.
FILTER
AIR FLOW
CENTRAL
RETURN
GRILLE
FILTER
SIDE RETURN
EXTERNAL FILTER
RACK KIT
(EITHER SIDE)
Upright Upflow
Figure 10
Circulation Air Filters
One of the most common causes of a problem in a forced
air heating system is a blocked or dirty lter. Circulating air
lters must be inspected monthly for dirt accumulation and
replaced if necessary. Failure to maintain clean lters can
cause premature heat exchanger failure.
A new home may require more frequent replacement until
all construction dust and dirt is removed. Circulating air
lters are to be installed in the return air duct external to
the furnace cabinet.
Upow /
Horizontal Models
Minimum Recommended Filter Size^
*R9S8000403AU 1 - 16 X 25 Side or 1 -14 X 24 Bottom Return
*R9S800603AU 1 - 16 X 25 Side or 1 -14 X 24 Bottom Return
*R9S800604BU 1 - 16 X 25 Side or 1 - 16 X 25 Bottom Return
*R9S800804BU 1 - 16 X 25 Side or 1 - 16 X 25 Bottom Return
*R9S800805CU
2 - 16 X 25 Side Return or
1 - 20 X 25 Bottom Return
^Larger filters may be used, filters may
also be centrally located
Table 7

17
Horizontal Installations
Filters must be installed in either the central return register
or in the return air duct work.
NORMAL SEQUENCE OF OPERATION
Power Up
• 120 VAC power applied to furnace.
• Integrated ignition control performs internal checks.
• Upon power-up of the control board, all Seven
segments will be illuminated displaying “8 8 8”. After
power-up the displays will show “I d L”, idle, or stand-
by mode.
• The control is now ready to receive demands from
the room thermostat. Refer to Status Menu in this
manual for interpretation of items displayed in the
status menu.
Gas Heating Mode
The normal operational sequence in gas heating mode is
as follows:
• R and W thermostat contacts close, initiating a call
for heat. The control will display heat mode in status
menu: - g h
• Integrated control module performs safety circuit
checks.
• Induced draft blower is energized for 30 second pre-
purge period causing pressure sensor contacts to
close.
• Igniter warm up begins after 30 second prepurge
expires.
• Gas valve opens at end of igniter warm up period,
delivering gas to burners and establishing ame.
• Integrated control module monitors ame presence.
Gas valve will remain open only if ame is detected.
• Circulator blower is energized on user selected heat
speed following a xed thirty second blower on delay.
Electronic air cleaner and humidier terminal relays
are energized with circulator blower.
• Furnace operates; integrated control module
monitors safety circuits continuously.
• R and W thermostat contacts open, completing the
call for heat.
• Gas valve closes, extinguishing ame.
• Induced draft blower is de-energized following a
thirty second post purge.
• HUM terminal relay is de-energized.
• Circulator blower continues running for selected heat
o delay. If required this can be changed in the eld.
• Electronic air cleaner is de-energized.
• Furnace awaits the next call from thermostat.
Cooling Mode
The control board support two stages of cooling. If this
furnace is installed with a single stage cooling unit or heat
pump, the Y1 terminal of the control board must be used.
A Y2 call on the control board will be ignored if a Y1 call is
not present.
COOLING MODE SEQUENCE OF
OPERATION
1st Stage Cooling Mode Sequence:
• On a call for low stage cooling, the Y1 or Y1 and
G thermostat contacts close signaling the furnace
control board with 24 vac. on Y1 or Y1 and G
terminals.
• The 7-Segment will display: 1 A C
• The compressor and condenser fan are energized.
• The circulator fan is energized at low cool speed
after the cool on delay period. The electronic air
cleaner EAC relay will close the EAC contacts.
• After the thermostat is satised, the compressor
is de-energized and the Cool Mode Fan O Delay
period begins.
• Following the Cool Mode Fan O Delay period, the
indoor fan and air cleaner relays are de-energized
2nd Stage Cooling Mode Sequence:
NOTE: A Y1 call must be present or a Y2 call will
be ignored.
• On a call for 2nd stage cooling, the Y2 or Y2 and
G thermostat contacts close signaling the furnace
control board with 24 vac. on Y2 or Y2 and G
terminals.
• The 7-Segment will display: 2 A C
• The compressor and condenser fan are energized.
• The circulator fan is energized at cool speed after a
cool on delay. The electronic air cleaner EAC relay
will close the EAC contacts.
• After the thermostat is satised, the compressor
is de-energized and the Cool Mode Fan O Delay
period begins.
• Following the Cool Mode Fan O Delay period, the
indoor fan and air cleaner relays are de-energized
HEAT PUMP MODE
1st Stage HP Heating Mode Sequence:
• On a call for low stage HP Heating, the Y1 or Y1
and G thermostat contacts close signaling the
furnace control board with 24 vac. on Y1 or Y1 and G
terminals.
• The 7-Segment will display: 1 H P
• The compressor and condenser fan are energized.
• The circulator fan is energized at HP1 fan speed
after the HP on delay period. The electronic air
cleaner, EAC, and humidier, HUM, relays will close
the contacts.
• After the thermostat is satised, the compressor is
de-energized and the electronic air cleaner EAC and
humidier HUM relays de-energize. The HP Heat
Mode Fan O Delay period begins.
• Following the HP Heat Mode Fan O Delay period,
the indoor fan, EAC, & HUM relays are de-energized.

18
2nd Stage HP Heating Mode Sequence:
NOTE: A Y1 call must be present or a Y2 call will
be ignored.
• On a call for 2nd stage HP Heating, the Y2 or Y2
and G thermostat contacts close signaling the
furnace control board with 24 vac. on Y2 or Y2 and G
terminals.
• The 7-Segment will display: 2 H P
• The compressor and condenser fan are energized.
• The circulator fan is energized at HP2 fan speed
after the HP on delay period. The electronic air
cleaner EAC and humidier HUM relays will close
the contacts.
• After the thermostat is satised, the compressor is
de-energized and the electronic air cleaner EAC and
humidier HUM relays de-energize. The HP Heat
Mode Fan O Delay period begins.
• Following the HP Heat Mode Fan O Delay period,
the indoor fan, EAC, & HUM relays are de-energized.
Fan Only Mode
The normal operational sequence in fan only mode is as
follows:
• R and G thermostat contacts close, initiating a call
for fan.
• Integrated control module performs safety circuit
checks.
• Circulator blower is energized on user selected
fan speed. Electronic air cleaner terminal relay is
energized.
• Circulator blower runs, integrated control module
monitors safety circuits continuously.
• R and G thermostat contacts open, completing the
call for fan.
• Circulator blower is de-energized. Electronic air
cleaner terminal relay is de-energized.
• Furnace awaits the next call from thermostat.
Defrost Mode
Defrost call can only be generated with heat pump outdoor
unit properly congured in the OdS menu.
• On a call for Defrost, the Y1 or Y1 with Y2 with/
without O contacts and W thermostat contacts close
signaling the furnace control board to enter defrost.
• If Y with O and W are present simultaneously, the
blower shall be energized at Cooling Speed after
COOL on delay, then, switch the blower speed to the
Greater of (Cooling Speed or Gas Heat speed) after
Gas Heat On Delay expired.
• If Y without O and W are present simultaneously, the
blower shall be energized at HP Heat Speed after
HP Heat On Delay, then, switch the blower speed to
the Greater of (HP Heat Speed or Gas Heat speed)
after Gas Heat On Delay expired.
• The 7-Segment will display: d F t
• The electronic air cleaner EAC and humidier HUM
relays will close the contacts.
• After the thermostat is satised, the gas valve will de-
energize. The Gas Heat Mode Fan O Delay period
begins.
• Following the Gas Heat Mode Fan O Delay period,
the indoor fan, EAC, & HUM relays are de-energized.
START-UP PROCEDURE AND
ADJUSTMENT
NOTE: This furnace is equipped with a control
board that is capable of monitoring for R-32
refrigerant leaks in the indoor refrigeration unit.
Please verify that the R-32 sensor wire is plugged
in to the furnace control board before startup,
if applicable. If furnace is not paired with an R-32
Refirgeration system, the default settings in the
furnace control board will need to be changed.
Please see the R-32 section for additional
information.
Furnace must have a 120 VAC power supply properly
connected and grounded. Proper polarity must be
maintained for correct operation. An interlock switch
prevents furnace oper ation if the blower door is not in
place. Keep the blower access door in place except for
inspection and maintenance.
The integrated furnace control board is equipped with two
push-button switches used to access & navigate menus for
furnace setup & settings. The 3 x Seven Segment Displays
on the control board will show the current selection.
Upon power-up of the control board, all Seven segments
will be illuminated displaying “8 8 8”. After power-up the
displays will show “I d L”, idle, or stand-by mode. The
control is now ready to receive demands from the room
thermostat. Refer to Status Menu in this manual for
interpretation of items displayed in the status menu.
Quick Start
Initial set up of outdoor systems are required to be
congured through the control board. Navigate to OdS
menu using the push buttons to properly congure the
outdoor system. Selections for AC1, AC2, HP1, HP2 must
be made to enable specic fan speeds and thermostat
signals to function.
NOTE: Equipment type (Single-stage cooling, Two-
stage cooling, Single-stage heat pump, Two-stage
heat pump) MUST be setup through the OdS menu
by the installer for proper system operation.
Using Push-Button Switches
All user settings may be accessed by two push-button
switches on the control board. The switches are identied
as “menu” & “option”. To enter the main menu, press the
“menu” switch. Each time the menu switch is pressed the
display will show the next available item in the main menu.
While in the main menu, press the “option” switch to scroll

19
through available options corresponding to the main menu
item displayed. In the option menu, the default option will
be displayed rst. If the default option has been changed
to another option, the current option selection will be
displayed rst.
The option menu will display both adjustable & non-
adjustable options. When an adjustable option is displayed,
the display will ash continuously until a switch is pressed.
If a non-adjustable option is displayed (such as Code
Release Number) the display will not ash.
While navigating the option menus, press the menu switch
to select the displayed option. The displayed selection will
stop ashing indicating the selection was made. Press the
menu button again to nalize the selection and return to
the corresponding main menu.
In the option menu, after the last option has been
displayed, the display will revert to the corresponding main
menu & display the default (or selected) option.
If switches are inactive for 30 seconds the display will
revert to the status menu.
Control Board Main Menu
S EGT
#1
S EGT
#2
S EGT
#3
S EGT
#1
S EGT
#2
S EGT
#3
Active Alaram menu
E r r E
x x Err
( xx: code numbers ) - See chart
for Alarm Code definition
Las t 10 Fau lts
F 1 0 E
x x F10
( xx: code numbers ) - See chart
for Alarm Code definition
Code Release Number
C r
Cr
Code number
Shared data Revision
S r
Sr
Shared Data Number
Reset to Factory Default
r F d
rFd
PCB will revert back to factory
default if selected yes
Outdoor Setting Menu 0 d S OdS
OdS option is used to select
outdoor unit type ( 1 or 2 stage )
Blower Speed for
Continous Fan Mode
F S d
FSd
( xx: Blower Speed Number F01,
F02.. )
Single-Stage Cooling Fan
Speed
A C
AC
( xx: Blower Speed Number F01,
F02.. )
Low-stage Cooling Blower
Speed, Two-Stage
A C 1
AC1
( xx: Blower Speed Number F01,
F02.. )
High-stage Cooling Fan
Speed, Two-Stage
A C 2
AC2
( xx: Blower Speed Number F01,
F02.. )
Cool On Delay
C n d
Cnd
Default set at 7 Secs,
Adjustments can be made in 7
Secs increments from 0 to 35
Secs
Cool Off Delay
C f d
Cfd
Default set at 65 Secs,
Adjustments can be made in 5
Secs increments from 0 to 120
Secs
Gas Heat fan Speed
g A F
gAF
( xx: Blower Speed Number F01,
F02.. )
Gas Heat On Delay
g n d
gnd
Default set at 30 Secs,
Adjustments can be made in 5
Secs increments from 5 to 30
Secs
Gas heat Off Delay
g F d
gFd
Default set at 90 Secs,
Adjustments can be made in 30
Secs increments from 30 to 180
Secs
Single-Stage HP Heat Fan
Speed
H P
HP
( xx: Blower Speed Number F01,
F02.. )
Low-stage HP Heat Fan
Speed, Two-Stage
H P 1
HP1
( xx: Blower Speed Number F01,
F02.. )
High-stage HP Heat Fan
Speed, Two-Stage
H P 2
HP2
( xx: Blower Speed Number F01,
F02.. )
HP Heat off Delay
H F d
HFd
Default set at 60 Secs,
Adjustments can be made in 5
Secs increments from 30 to 120
Secs
HP Heat on Delay
H n d
Hnd
Default set at 5 Secs,
Adjustments can be made in 5
Secs increments from 5 to 30
Secs
Automatic Heat Staging -
For Two Stage Control
A H S
AHS
Refer to Section " CHANGING
HEATING MODE SETTING"
A2L Function Verification A 2 u A2u
A2L Function Enabled A 2 E A2E
no, 10, 20,
30, 60, AUt
Refer to the R-32
Section
Refer to the R-32
Section
Fxx
Del ay, Seconds
Del ay, Seconds
Fxx
Fxx
Fxx
Del ay, Seconds
Del ay, Seconds
Fxx
Fxx
Fxx
Del ay, Seconds
Del ay, Seconds
M enu D escription
None
yes, no
AC1 / AC2 /
HP1 / HP2 /
OF F
Fxx
Additional Info
Main Menu
Option M e nu
Display
Text
None
Control Board Status Menu
S EGT
#1
S EGT
#2
S EGT
#3
All s egments illuminate d =
control powering up
8 8 8
Control in Idle stage
I d l
Constant Fan
F A n
Single-Stage Cooling Fan
Speed
A C
Low Stage Cooling
1 A C
High Stage Cooling
2 A C
Gas Heat
g H
Low Stage HP
1 H P
High Stage HP
2 H P
Defrost
d F t
Main Menu
Description of System
Status

20
Furnace operation
Purge gas lines of air prior to start-up. Do not purge lines
into an enclosed burner compartment. Follow NFPA 54,
National Fuel Gas Code 8.1 for proper purging methods.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector, or
other approved method.
NOTE: An interlock switch prevents furnace
oper ation if the blower door is not in place. Keep
the blower access doors in place except for
inspection and maintenance.
R-32 FUNCTION
This furnace is equipped with a control board that is
capable of shutting o the gas heat and turning on the
blower fan in case of an R-32 refrigerant leak in the indoor
evaporator coil. If the cooling unit that is paired with this
furnace does not utilize R-32 as the refrigerant, the R-32
functionalities in the furnace control board will need to be
turned o for the furnace to run properly.
R-32 function on the control board is ON by default. The
R-32 function can be disabled through the furnace control
by entering the A2L Function Enabled menu and selecting
“no”. If A2L function is disabled, the furnace control will
ignore all A2L functions. If A2L function is enabled, the
control will monitor the R-32 sensor information.
To enter the A2L Function Enabled menu, press the left
or right switch until LED displays “A2E”. Press the center
switch and the LED will display the selected option (yes or
no). Press the left of right switch to select one of the two
options and press the middle switch to conrm the option.
R-32 Sensor Wire Routing
NOTE: Wiring routing must not interfere
with circulator blower operation, filter removal
or routine maintenance. Wire should not be
routed near hot surfaces and should be protected
from sharp edges.
The R-32 Sensor wire coming from the indoor evaporator
coil will need to be routed into the furnace and connected
to the connection point on the furnace control board. This
wire should be routed alongside the thermostat wires
through the low voltage openings in the left or right side of
the furnace blower compartment. Please see the electrical
section for the location of the R-32 Sensor connection on
the control board.
Furnace Start-up
During furnace start up, the furnace control will identify the
connected R-32 sensor and will start monitoring the sensor
communication. A green LED located next to the sensor
connection will indicate if there is communication between
the furnace control and the R-32 sensor. The LED will be
ON during the duration of the startup and then will either
start blinking or turn OFF. The blinking LED signies that
communication with the R-32 sensor is present. The LED
OFF signies that there is no signal with the sensor.
If there are no alarms or faults, the furnace will go into
regular run mode after a warm up period. The furnace
control monitors the R-32 sensor once per second.
R-32 Refrigerant Leak
If the R-32 sensor on the indoor evaporator coil detects
a specied concentration of R-32 refrigerant, the furnace
will enter Mitigation Mode to dilute the refrigerant
concentrations in case of a leak. In Mitigation Mode, the
furnace will do the following:
1. Display the A2L Refrigerant Leakage error code
(EAL)
2. Shut down the gas operation
3. Energize the optional ventilation and alarm outputs.
4. Run the fan at max CFM airow
Once the R-32 sensor stops detecting a leak, the fan will
continue to run for 5 minutes. After the 5 minutes, if there
are no other alarms or faults, the control will de-energize
the optional ventilation and alarm outputs and then go back
to the original operating mode per the thermostat.
A2L Verification
The A2L Function Verication menu allows the installer to
verify if the R-32 function operates properly. This menu
simulates the refrigerant leak process and is only able to
be used when there are no active alarms or faults. To verify
the R-32 functions, enter the A2L Function Verication
menu and select “YES”. To enter the A2L Function
Verication menu, press the left or right switch until LED
displays “A2u”. Press the center switch and the LED will
display the selected option (yes or no). Press the left of
right switch to select one of the two options and press
the middle switch to conrm the option. Once “YES” is
selected, the furnace will do the following:
1. Display the A2L Refrigerant Leakage code (EAL)
2. Shut down the gas operation
3. Energize the optional ventilation and alarm outputs.
4. Run the fan at max CFM airow
The control will exit the verication function if:
1. The 5 minute timeout expires or
2. An alarm or fault is detected or
3. The user turns OFF the A2L Function Verication.
Furnace Start-up
1. Close the manual gas shuto valve external to the
furnace.
2. Turn o the electrical power to the furnace.
3. Set the room thermostat to the lowest possible
setting.
4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition
device which automatically lights the burner. Do
not try to light the burner by hand.

21
5. White-Rodgers valves: Push the switch to the OFF
position.
6. Wait ve minutes then smell for gas. Be sure to
check near the oor, as some types of gas are
heavier than air.
7. If gas can be smelled following the ve minute
waiting peri od in Step 6, immediately follow the
instructions on Page 3 of this manual. If you do not
smell gas after ve minutes:
White-Rodgers valves: Push the switch to the ON
position.
8. Replace the door on the front of the furnace.
9. Open the manual gas valve external to the furnace.
10. Turn on the electrical power supply to the furnace.
11. Adjust the thermostat to a setting above room
temperature.
12. After the burners are lit, set the room thermostat to
the desired temperature.
NOTE: There will be a delay between thermostat
energizing and burner firing.
Furnace Shutdown
1. Set the thermostat to lowest setting. The integrated
control will close the gas valve and extinguish ame.
Following a 30 second delay, the induced draft
blower will be de-energized. The circulation blower
will shut down when the time delay expires. Time
delay is selectable on all models.
2. Turn o the electrical power supply to the furnace.
3. Remove the burner compartment door.
4. White-Rodgers valve: Push switch to the OFF
position.
5. Close manual gas shuto valve external to the
furnace.
6. Replace the door on the unit.
Gas Supply Pressure Measurement
CAUTION
To prevent unreliable operation or equipment damage, the
inlet gas supply pressure must be as specified on the unit
rating plate with all other household gas fired appliances
operating.
The line pressure supplied to the gas valve must be within
the range specied on Table 9. The supply pressure can
be measured at the gas valve inlet pressure tap or at a
hose tting installed in the gas piping drip leg. The supply
pressure must be measured with the unit OFF. To measure
inlet pressure, use the following procedure.
White-Rodgers Model 36J22Y-204
Figure 11
1. Turn OFF gas to furnace at the manual gas shuto
valve external to the furnace.
2. Turn OFF all electrical power to the system.
3. Inlet pressure tap connections:
a. White-Rodgers valve: Back inlet pressure
test screw (inlet pressure tap out one turn
(counterclockwise, not more than one turn).
4. Connect calibrated manometer (or appropriate
pressure gauge) at either the gas valve inlet
pressure tap or the gas piping drip leg. See White-
Rodgers 36J22Y-204 gas valve Figure 13 for location
of inlet pressure tap.
5. Turn ON the gas supply.
6. Turn On power and operate the furnace and all other
gas consuming appliances on the same gas supply
line.
7. Using a leak detection solution or soap suds, check
for leaks at screw (White-Rodgers valve). Bubbles
forming indicate a leak. SHUT OFF GAS AND
REPAIR ALL LEAKS IMMEDIATELY!
8. Measure the gas supply pressure with burners ring.
Adjust supply pressure using the Inlet Gas Supply
Pressure table shown below. If supply pressure
reading diers from the table, make necessary
adjustments to pressure regulator, gas piping size,
etc., and/or consult with local gas utility.
Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c.
INLET GAS SUPPLY PRESSURE
Table 9
9. Turn OFF all electrical power and gas supply to the
system.
10. Remove the manometer hose from the hose barb
tting or inlet pressure tap.
11. Replace inlet pressure tap:
a. White-Rodgers valve: Turn inlet pressure test
screw in to seal pressure port (clockwise, 7 in-lb
minimum).
12. Retest for leaks. If bubbles form, shut down gas and
repair leaks immediately.
13. If there are no leaks, turn ON electrical power and
gas supply to the system.
14. Turn valve switch ON.

22
NOTE: If measuring gas pressure at the drip leg, a
field-supplied hose barb fitting must be installed
prior to making the hose connection. If using
the inlet pressure Tap on the White-Rodgers gas
valve, then use the 36G/J Valve Pressure Check Kit,
Goodman Part No. 0151K00000S.
Mode
10.0
Measuring Inlet Gas Pressure (Alt. Method)
Figure 12
Gas Manifold Pressure Measurement
and Adjustment
CAUTION
To prevent unreliable operation or equipment damage,
the gas manifold pressure must be as specified on the unit
rating plate. Only minor adjustments should be made by
adjusting the gas valve pressure regulator.
Only small variations in gas pressure should be made by
adjusting the gas valve pressure regulator. The manifold
pressure must be measured with the burners operating.
To measure and adjust the manifold pressure, use the
following procedure.
1. Turn OFF gas to furnace at the manual gas shuto
valve external to the furnace.
2. Turn OFF all electrical power to the system.
3. Outlet pressure tap connections:
a. White-Rodgers valve: Back outlet pressure
test screw (outlet pressure Tap) out one turn
(counterclockwise, not more than one turn).
4. Connect calibrated manometer (or appropriate
pressure gauge) at the gas valve outlet pressure tap.
See White-Rodgers 36J22Y-204 gas valve Figure 13
for location of outlet pressure tap.
5. Turn ON the gas supply.
6. Turn ON power and close thermostat “R” and “W”
contacts to provide a call for heat.
7. Using a leak detection solution or soap suds, check
for leaks at outlet pressure tap screw (White-Rodgers
valve). Bubbles forming indicate a leak. SHUT OFF
GAS AND REPAIR ALL LEAKS IMMEDIATELY!
8. Measure the gas manifold pressure with burners
ring. Adjust manifold pressure using the following
Manifold Gas Pressure table.
Natural Gas 2.8" - 3.2" w.c.
Manifold Gas Pressure
Table 10
9. Remove regulator cover screw from the outlet
pressure regulator and turn screw clockwise to
increase pressure or counterclockwise to decrease
pressure. Replace regulator cover screw.
10. Turn OFF all electrical power and gas supply to the
system.
11. Remove the manometer hose from the hose barb
tting or outlet pressure tap.
12. Replace outlet pressure tap:
a. White-Rodgers valve: Turn outlet pressure test
screw in to seal pressure port (clockwise, 7 in-lb
minimum).
13. Turn ON electrical power and gas supply to the
system.
14. Close thermostat contacts to provide a call for heat.
15. Retest for leaks. If bubbles form, SHUT OFF GAS
AND REPAIR ALL LEAKS IMMEDIATELY!
Gas Input Rate Measurement (Natural Gas Only)
The gas input rate to the furnace must never be greater
than that specied on the unit rating plate. To measure
natural gas input using the gas meter, use the following
procedure.
1. Turn OFF the gas supply to all other gas-burning
appliances except the furnace.
2. While the furnace is operating at high re rate, time
and record one complete revolution of the gas meter
dial, measuring the smallest quantity, usually the dial
that indicates 1/2 cu. ft. per revolution. You will use
this number to calculate the quantity of gas in cubic
ft. if the furnace would consume if it ran steadily for
one hour (3600 seconds).
3. If the 1/2 cu. ft. dial was used, multiply your number X
2. EXAMPLE: If it took 23 seconds to complete one
revolution of the 1/2 ft. dial (23 x 2 = 46).
This tells us that at this rate, it would take 46
seconds to consume one cu. ft. of gas. This tells us
that in one hour, the furnace would consume 78 cu.
ft. of gas. (3600/46 = 78) The typical value range for
1 cu. ft. of natural gas is around 1025 BTU. Check
with your gas utility, if possible. In this example, the
furnace is consuming 80,000 BTUH.
NOTE: The nal manifold pressure cannot vary by
more than ± 0.2” w.c. for Natural from the specied
setting. Consult your local gas supplier if additional
input rate adjustment is required.
4. Turn ON gas and relight appliances turned o in step
1. Ensure all the appliances are functioning properly
and that all pilot burners (if applicable) are operating.
Temperature Rise
Air temperature rise is the temperature dierence between
supply and return air. The proper amount of temperature

23
rise is usually obtained when the unit is operated at the
rated input with the “as shipped” blower speed. If the
correct amount of temperature rise is not obtained, it may
be necessary to change the blower speed.
Temperature rise must be within the range specied on the
unit rating plate. An incorrect temperature rise may result
in condensing in or overheating of the heat exchanger.
An airow and temperature rise table is provided in the
Specication Sheet applicable to your model. Determine
and adjust temperature rise as follows:
SUPPLY
AIR
RETURN
AIR
Temperature Rise Measurement
Figure 13
1. Operate furnace with burners ring approximately
15 minutes. Ensure all registers are open and all
duct dampers are in their nal (fully or partially open)
position.
2. Place thermometers in the return and supply ducts
as close to the furnace as possible. Thermometers
must not be inuenced by radiant heat by being able
to “see” the heat exchanger.
3. Subtract the return air temperature from the supply
air temperature to determine the air temperature rise.
Allow adequate time for thermometer readings to
stabilize.
4. Adjust temperature rise by adjusting the circulator
blower speed. Increase blower speed to reduce
temperature rise. Decrease blower speed to increase
temperature rise. Refer to the following section for
speed changing details.
Circulator Blower Speed Adjustment
WARNING
To avoid personal injury or death due to electrical shock,
turn OFF power to the furnace before changing speed taps.
This furnace is equipped with a multi-speed circulator
blower. This blower provides ease in adjusting blower
speeds. The Specication Sheet applicable to your model
provides an airow table, showing the relationship between
airow (CFM) and external static pressure (E.S.P.), for the
proper selection of heating and cooling speeds.
1. Determine the tonnage of the cooling system
installed with the furnace. If the cooling capacity is
in BTU/hr divide it by 12,000 to convert capacity to
tons.
Example: Cooling Capacity of 30,000 BTU/hr.
30,000/12,000 = 2.5 Tons
2. Determine the proper air ow for the cooling system.
Most cooling systems are designed to work with air
volume between 350 and 450 CFM per ton. Most
manufacturers recommend an air ow of about 400
CFM per ton.
Example: 2.5 tons X 400 CFM per ton = 1000 CFM
3. Select the heating speed for your model from the
heating speed chart in the Specication Sheet. The
selected speed must provide a temperature rise
within the rise range listed with the particular model.
Continuous Fan Mode Speed Selection
To change the main blower speed in circulation mode, see
the following steps:
1. Press menu button until LED displays “FSd”. Press
option button and LED will display the currently
selected speed number as Fxx (xx: Blower speed
number from 1 to 9).
2. The control shall cycle through available fan speeds
every time the option button is pressed. All 9 speeds
are available for circulation.
3. When the menu button is pressed, the current
displayed speed shall stop ashing. Press the menu
button again to select the option and the control shall
immediately apply that blower setting and return to
the corresponding main menu.
THERMOSTAT CALL
AVAILABLE SPEEDS
(FSd menu)
G
F01
F02
F03
F04
F05
F06
F07
F08
F09
Circulation Speed Table
Cooling Mode Speed Selection
To change the main blower speed in COOLING mode,
follow the following steps:
NOTE: If Heat Pump system is configured in OdS
menu (HP1 or HP2) COOLING thermostat calls will
include “Y1”/Y2” + “O” terminals energized.
1. Press menu button until LED displays “AC1” (for

24
single stage COOLING) or “AC2” (for Two stage
COOLING). Press option button and the LED will
display the currently selected speed number as Fxx
(xx: Blower speed number from 1 to 9).
2. The control shall cycle through available fan speeds
every time the option button is pressed. All 9 speeds
are available for both Single and Two Stage cooling.
3. When the menu button is pressed, the current
displayed speed shall stop ashing. Press the menu
button again to select the option and the control shall
immediately apply that blower setting and return to
the corresponding main menu.
THERMOSTAT CALL
(OdS: Terminal)
AVAILABLE SPEEDS
(AC1 menu)
1AC: Y1
1HP: Y1 + O
F01
F02
F03
F04
F05
F06
F07
F08
F09
Single Stage Cooling Speed Table
THERMOSTAT CALL
(OdS: Terminal)
AVAILABLE SPEEDS
(AC2 menu)
2AC: Y1 + Y2
2HP: Y1 + Y2 + O
F01
F02
F03
F04
F05
F06
F07
F08
F09
Two Stage Cooling Speed Table
Gas Heating Mode Speed Selection
To change the main blower speed in GAS HEATING mode,
see the following steps:
1. Press menu button until LED displays “gAF”. Press
option button and LED will display the currently
selected fan speed as Fxx (xx: Blower speed
number).
2. The control shall cycle through available speed
number every time the option button is pressed.
3. When the menu button is pressed, the current
displayed speed shall stop ashing. Press the menu
button again to select the option and the control shall
immediately apply that blower setting and return to
the corresponding main menu.
NOTE: Each furnace model contains different
allowable gas heating speeds. Allowable gas
heating speeds will be visible within gAF fan speed
menu.
Heat Pump Heating Mode Speed Selection
To change the main blower speed in Heat Pump HEATING
mode, follow the following steps:
1. Press menu button until LED displays “HP1” (for
single stage HP HEATING) or “HP2” (for Two stage
HP HEATING). Press option button and the LED will
display the currently selected speed number as Fxx
(xx: Blower speed number from 1 to 9).
2. The control shall cycle through available fan speeds
every time the option button is pressed. All 9 speeds
are available for both Single and Two Stage HP
HEATING.
3. When the menu button is pressed, the current
displayed speed shall be selected, and control shall
apply the newly selected speed in next HP HEATING
call.
THERMOSTAT CALL
(OdS: Terminal)
AVAILABLE SPEEDS
(HP1 menu)
1HP: Y1
F01
F02
F03
F04
F05
F06
F07
F08
F09
Single Stage HP Heating Speed Table
THERMOSTAT CALL
(OdS: Terminal)
AVAILABLE SPEEDS
(HP2 menu)
2HP: Y1 + Y2
F01
F02
F03
F04
F05
F06
F07
F08
F09
Two Stage HP Heating Speed Table
Circulator Blower Fan Timing Adjustment
NOTE: Items in this section refer to the air
circulator blower fan, NOT to the induced draft
blower. The induced draft blower timing sequence
is not adjustable.
The integrated control module on all models provides
selectable fan on/o delay adjustments.

25
On/Off Fan Delay Selection
To change the fan on or o delay for COOLING, HP
HEATING & GAS HEATING modes, see the following
steps:
1. Press menu button until LED displays the desired on/
o setting (See MAIN MENU section for selectable
blower on/o delay options). Press option button
and LED will display the selected on/o delay time in
seconds.
2. The control shall cycle through available on/o delay
times every time the option button is pressed.
3. When the menu button is pressed, the current
displayed on/o delay shall stop ashing. Press
the menu button again to select the option and the
control shall immediately apply that delay setting and
return to the corresponding main menu.
OPERATIONAL CHECKS
WARNING
To avoid personal injury or death, do not remove any inter-
nal compartment covers or attempt any adjustment. Elec-
trical components are contained in both compartments.
Contact a qualified service agent at once if an abnormal
operation should develop.
Checking Duct Static
Refer to your furnace rating plate for the maximum ESP
(external duct static) rating.
Total external static refers to everything external to the
furnace cabinet. Cooling coils, lters, ducts, grilles,
registers must all be considered when reading your total
external static pressure. The supply duct pressure must be
read between the furnace and the cooling coil. This reading
is usually taken by removing the “A” shaped block o
plate from the end on the coil; drilling a test hole in it and
reinstalling the block o plate. Take a duct static reading
at the test hole. Tape up the test hole after your test is
complete. The negative pressure must be read between
the lter and the furnace blower.
Too much external static pressure will result in insucient
air that can cause excessive temperature rise. This can
cause limit switch tripping and heat exchanger failure.
To determine total external duct static pressure, proceed as
follows:
1. With clean lters in the furnace, use a manometer to
measure the static pressure of the return duct at the
inlet of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct.
(Positive Pressure)
3. The dierence between the two numbers is .4” w.c.
EXAMPLE:
static reading from return duct = -.1” w.c.
static reading from supply duct = .3” w.c.
total external static pressure on this system = .4” w.c.
NOTE: Both readings may be taken simultaneously
and read directly on the manometer if so
desired. If an air conditioner coil or Electronic
Air Cleaner is used in conjunction with the
furnace, the readings must also include theses
components, as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the maximum
listed on the furnace rating plate, check for closed
dampers, registers, undersized and/or oversized poorly laid
out duct work. The temperature rise of the furnace must
be within the temperature rise range listed on the furnace
rating plate.
CUTAWAY OF DUCTWORK
TO EXPOSE COIL
DIGITAL
MANOMETER
RETURN
AIR
Mode
3.5
SUPPLY
AIR
.50
Checking Static Pressure
(80% Furnace Shown)
Figure 14
SAFETY CIRCUIT DESCRIPTION
General
WARNING
To avoid personal injury or death, do not remove any inter-
nal compartment covers or attempt any adjustment. Elec-
trical components are contained in both compartments.
Contact a qualified service agent at once if an abnormal
operation should develop.
WARNING
Do not bypass safety devices.
A number of safety circuits are employed to ensure safe
and proper furnace operation. These circuits serve to
control any potential safety hazards and serve as inputs
in the monitoring and diagnosis of abnormal function.
These circuits are continuously monitored during furnace
operation by the integrated control module.

26
Integrated Control Module
The integrated control module is an electronic device
which controls all furnace operations. Responding to
the thermostat, the module initiates and controls normal
furnace operation, and monitors and addresses all safety
circuits. If a potential safety concern is detected, the
module will take the necessary precautions and provide
diagnostic information through an LED.
Primary Limit
The primary limit control is located on the partition panel
and monitors heat exchanger compartment temperatures.
It is a normally closed (electrically), automatic reset,
temperature activated sensor. The limit guards against the
overheating resulting from insucient air passing over the
heat exchanger.
Auxiliary Limit
The auxiliary limit control is located either on or near
the circulator blower and monitors heat exchanger
compartment temperatures. The control is a normally
closed (electrically), automatic reset, temperature activated
sensor. It guards against overheating resulting from
insucient air passing over the heat exchanger. The
auxiliary limit control is suitable for both horizontal right and
horizontal left installations. Regardless of airow direction,
it does not need to be relocated.
Burner Temperature Switch
The burner temperature switch is mounted on the burner
assembly to monitor the burner box temperature. It is
normally closed (electrically), auto-reset sensor. This
switch guards against the burner ames not being properly
drawn into the heat exchanger.
Pressure Sensor
The pressure sensor is mounted near induced draft blower.
Its function is to regulate the induced draft blower’s speed
in order to maintain proper air-fuel ratio for clean and
reliable combustion. The pressure sensor also guards
against insucient airow (combustion air and ue
products) through the heat exchanger.
Flame Sensor
The ame sensor is a probe mounted near the burner
assembly which uses the principle of ame rectication to
determine the presence or absence of ame.
TROUBLESHOOTING
Diagnostic Chart
Refer to the troubleshooting chart in the Appendix for
assistance in determining the source of unit operational
problems. The 3 digit diagnostic display provides alarm
codes to assist in troubleshooting the unit.
Fault Code Retrieval
The ignition control is equipped with push buttons that
can be used to the last ve faults detected by the control.
Navigate the L6F by pressing the menu button 2 times,
then select the option button.
Clear Fault Memory
To clear all alarm codes, navigate to the last six faults menu,
L6F, and hold the option button down for 5 seconds.
Resetting From Lockout
Furnace lockout results when a furnace is unable to
achieve ignition after three attempts. It is characterized
by a non-functioning furnace and a fault code will be
displayed. If the furnace is in “lockout”, it will (or can be)
reset in any of the following ways.
1. Automatic reset. The integrated control module will
automatically reset itself and attempt to resume
normal operations following a one hour lockout
period.
2. Manual power interruption. Interrupt 120 volt power
to the furnace.
NOTE: If the condition which originally caused the
lockout still exists, the control will return to
lockout. Refer to the Diagnostic Chart for aid in
determining the cause.
MAINTENANCE
WARNING
To avoid electrical shock, injury or death, disconnect
electrical power before performing any service or mainte-
nance. Only a qualified servicer should service or perform
maintenance.
Annual inspection
The furnace should be inspected by a qualied installer, or
service agency at least once per year. This check should
be performed at the beginning of the heating season.
This will ensure that all furnace components are in proper
working order and that the heating system functions
appropriately. Pay particular attention to the following
items. Repair or service as necessary.
• Flue pipe system: Check for blockage and/or
leakage. Check the outside termination and the
connections at and internal to the furnace.
• Heat exchanger: Check for corrosion and/or buildup
within the heat exchanger passageways.
• Burners: Check for proper ignition, and ame sense.
• Wiring: Check electrical connections for tightness
and/or corrosion. Check wires for damage.
• Filters: Check lters and determine if any need to be
replaced.
• R-32 Sensor Wire: Check R-32 sensor wire
connection for tightness and check wire for damage.

27
Filters
WARNING
To avoid property damage, personal injury or death, dis-
connect electrical power before removing filters. Never
operate furnace without a filter installed because dust
and lint will build up on internal parts resulting in loss of
efficiency, equipment damage and possible fire.
A return air lter is not supplied with this furnace; however,
there must be a means of ltering all of the return air. The
installer will supply lter(s) at the time of installation.
Induced Draft and Circulator Blower Motors
The bearings in the induced draft blower and circulator
blower motors are permanently lubricated by the
manufacturer. No further lubrication is required. Check
motor windings for accumulation of dust which may cause
overheating. Clean as necessary.
Flame Sensor (Qualified Servicer Only)
Under some conditions, the fuel or air supply can create a
nearly invisible coating on the ame sensor. This coating
acts as an insulator causing a drop in the ame sense
signal. If the ame sense signal drops too low the furnace
will not sense ame and will lock out. The ame sensor
should be carefully cleaned by a qualied servicer using
steel wool. The ame sense signal should be 1 to 3
microamps.
Igniter (Qualified Servicer Only)
At room temperature, the igniter ohm reading should be
from 20 - 100 ohms.
Burner
WARNING
To prevent personal injury or death, do not remove any
internal compartment covers or attempt any adjustment.
Electrical components are contained in both compartments.
Contact a qualified service agent at once if an abnormal
operation should develop.
The Ultra low NOx furnace uses a premix burner. The
burner box is sealed to achieve safe and reliable operation.
CLEANING (QUALIFIED SERVICER ONLY)
1. Shut o electric power and gas supply to the furnace.
2. Disconnect the rollout limit wires, ame sensor wire,
and disconnect the igniter plug.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
3. Do not remove burner or other components.
4. Clean cabinet and around the inducer blower, motor
and burner box.
5. Reconnect wiring.
6. Turn on electric power and gas supply to the furnace.
7. Check furnace for proper operation. Refer to
“Operational Checks” section to verify burner ame
characteristics.
BEFORE LEAVING AN INSTALLATION
• Cycle the furnace with the thermostat at least three
times. Verify cooling and fan only operation.
• Review the Owner’s Manual with the homeowner
and discuss proper furnace operation and
maintenance.
• Leave literature packet near furnace.
REPAIR AND REPLACEMENT PARTS
• When ordering any of the listed functional parts, be
sure to provide the furnace model, manufacturing,
and serial numbers with the order.
• Although only functional parts are shown in the parts
list, all sheet metal parts, doors, etc. may be ordered
by description.
• Parts are available from your distributor.
Functional Parts List-
Gas Valve
Natural Gas Orice
Burner Assembly
Hot Surface Igniter
Flame Sensor
Gas Manifold
Ignition Control
Blower Mounting Bracket
Pressure Sensor
Pressure Sensor Hose
Induced Draft Blower
Integrated Control Module
Burner Box Gasket
Blower/Collector Box Gasket
Primary Limit Switch
Burner Temperature Switch
Auxiliary Limit Switch
Heat Exchanger
Door Switch
Transformer
Blower Wheel
Blower Housing
Blower Cuto
Blower Motor
Motor Mount Bracket

28
COMPONENT ID
1 Tubular Heat Exchanger
2 Pressure Switch
3
4 Gas Line Entrance
5 Gas Valve
6 Inducer
7 Gas Manifold Assembly
8 Burner Assembly
9 Integrated Control Module
10 Transformer
11 Blower Door Interlock Switch
12 Circulator Blower
Tubular Heat Exchanger
Pressure Sensor Assembly
Flue Pipe Connection
Gas Line Entrance
Gas Valve
Inducer
Gas Manifold Assembly
Integrated
Control Module
Blower Door
Interlock Switch
Circulator Blower
1
2
3
4
5
6
7
8
Burner Assembly
9
10
Transformer
11
12

29
Symptom
LED
Status
Fault Description Corrective Actions
Normal operation I dL Normal operation None
Furnace fails to operate EEE Internal Faults or IRQ Loss in Control Board Replace integrated control board
Locate and correct gas interruption
Check front cover pressure switch operation and verify proper
drainage (hose, wiring, contact operation), correct if
necessary
Replace or realign igniter
Check flame sense signal, clean sensor if coated or oxidized
Check flue piping for blockage, proper length, elbows, and
termination
Verify proper induced draft blower performance
Pressure switch circuit is closed at start of
heating cycle
Pressure switch contacts sticking
Short in pressure switch circuit wiring
Pressure switch circuit is not closed
Pressure switch hose blocked pinched, or
connected improperly
Inspect flue piping for blockage, proper length, elbows, and
termination
Check drain system, correct as necessary
Check induced draft blower performance, correct as
necessary
Incorrect pressure switch set point or
malfunctioning switch contacts
Check pressure switch operation, replace as needed
Loose or improperly connected wiring Tighten or correct wiring connection
Primary limit circuit is open
Check filters and ductwork for blockage Clean filters or
remove obstruction
Insufficient conditioned air over the heat
exchanger
Check circulator blower speed and performance
Blocked filters, restrictive ductwork, improper
circulator blower speed, or failed circulator
blower motor
Correct speed or replace blower motor if necessary
Loose or improperly connected wiring in high
limit circuit
Tighten or correct wiring connection
Flame sensed with no call for heat Correct short at flame sensor or in flame sensor wiring
Short to ground in flame sense circuit
Lingering burner flame Slow closing gas
valve
Open fuse Replace fuse
Short in low voltage wiring Locate and correct short in low voltage wiring
Flame sense micro amp signal is minimal
Flame sensor is coated/oxidized
Flame sensor incorrectly positioned in burner
fame
Check inlet air piping for blockage, proper length, elbows,
and termination
Compare current gas pressure to rating plate and adjust as
needed
Problem with igniter circuit
Check and correct wiring from intergrated control module to
igniter
Improperly connected or shorted igniter Diagnose and replace shorted igniter as needed
Poor unit ground Verify and correct unit ground wiring if needed
Ingniter relay fault on integrated control
module
Check igniter output from control, replace if necessary
Furnace fails to operate
EE0
Furnace lockout due to an excessive number
of ignition “retries” (3 total)
Failure to establish flame
Loss of flame after establishment
Furnace fails to operate
EE1
Replace low stage pressure switch Repair short in wiring
Induced draft blower
runs continuously with
no furnace operation
EE2
Inspect pressure switch hose, repair/replace if necessary
Blocked flue or weak induced draft blower
Circulator blower runs
continuously
No furnace operation
EE3
Normal furnace
operation
EE6
Clean flame sensor if coated or oxidized Inspect for proper
flame sensor alignment
Lazy burner flame due to improper gas
pressure or combustion air
Furnace fails to operate
EE7
Induced draft blower
and circulator blower
runs continuously
No furnace operation
EE4
Check for lingering or lazy flame Verify proper operation of
gas valve
No furnace operation
EE5
TROUBLESHOOTING CHART

30
TROUBLESHOOTING CHART
Furnace stops heating and only
the fan is operating
EAL
R-32 sensor has detected a refrigerant leak and furnace is in
mitigation mode.
Investigate the indoor coil for a refrigerant leak.
Furnace will resume normal operation once a leak is not detected and the 5 minute
delay period is over.
Furnace stops heating and only
the fan is
operating
EAS
R-32 sensor has detected a fault and the furnace is in
mitigation mode.
Investigate the R-32 sensor. Replace the R-32 sensor.
Furnace stops heating
and only the fan is operating
Ear
A2L relay in the furnace control board has detected a fault and
the furnace is in
mitigation mode.
Investigate A2L relay.
Cycle power on the furnace.
Replace integrated control board.
Furnace fails to operate.
Integrated control module LED
display provides no signal
None
No 115 power to furnace or no 24 volt power to integrated control
module.
Blown fuse or tripped circuit breaker Integrated control module
is non- functional
Restore high voltage power to furnace and integrated control module.
Correct condition which caused fuse to open, replace fuse Replace non-functional
integrated control module.
Furnace fails to
operate and goes to hard
lockout
EbL
Main blower motor is consuming
very little current after heat on delay, below an expected
value
Check for loose motor wiring connections.
Verify if the blower motor is burnt, replace blower motor if found burnt
Furnace fails to operate and goes
to hard lockout
EbU
Main blower motor is consuming too much current during
inducer pre-purge, above an expected value.
Verify wiring connections to and from motor are not loose.
Verify that line voltage wires to the control and the main blower motor are not reversed
at the control.
Furnace fails to operate
Ed0
No Shared data
Populate shared data set using BTPIM01
Furnace stops heating
and only the fan is operating
EAF
Furnace has lost communication with the R- 32 sensor and the
furnace is in mitigation
mode.
Verify wire connection to R-32 sensor is not loose. Verify that the R-32 sensor wire is
not damaged.
Replace R-32 Sensor.
Furnace fails to operate
E1d
Analog Pressure Sensor span error
Check Red, Black, White harness & connections to inducer & control board
Check pressure hoses to pressure sensor and pressure
switch
Furnace fails to operate E1E Analog Pressure Sensor pressure error
Check Red, Black, White harness & connections to inducer & control board
Replace pressure sensor
Furnace fails to operate
E1F
Analog Pressure Sensor input error
Check Red, Black, White harness & connections to inducer & control board
Replace pressure sensor
Twinning feature not
working
EEH
TWIN Error
Check for wiring connections.
Replace integrated control board
Circulator blower runs
continuously
No furnace operation
EEd
Auxiliary limit circuit is open
Blocked filters, restrictive ductwork, improper circulator blower
speed, or failed circulator blower motor
Loose or improperly connected wiring in high
limit circuit
Check filters and ductwork for blockage Clean filters or remove obstruction
Correct speed or replace blower motor if necessary
Tighten or correct wiring connection
Furnace fails to operate
EbF
Inducer communication alarm
Check Red, Black, White harness & connections to inducer &
control board
Furnace fails to operate E1b Analog Pressure Sensor reference error
Check Red, Black, White harness & connections to inducer & control board
Replace pressure sensor
Furnace fails to operate
E1C
Analog Pressure Sensor null error
Check Red, Black, White harness & connections to inducer & control board
Check pressure hoses to pressure sensor and pressure
switch
Furnace fails to operate
E12
Redundant relay open alarm
Lorem ipsum
Replace integrated control board
Furnace fails to operate
E13
Redundant relay stuck closed alarm
Replace integrated control board
Furnace fails to operate
EEb
Gas valve is not energized when it should be External Gas
Valve Error
Check wiring in gas valve circuit Replace integrated control board
Furnace fails to operate
EEC
Gas valve is energized when it should not be Internal gas valve
error
Check wiring in gas valve circuit Replace integrated control board
Symptom
LED
Status
Fault Description
Corrective Actions
Furnace fails to operate
EEA
Polarity of 115 volt AC is reversed
Poor unit ground
Correct polarity, check and correct wiring if necessary
Verify proper ground, correct if necessary
Furnace fails to operate
E10
Grounding fault
Poor neutral connection
Verify neutral wire connection to furnace & continuity to
ground source
Furnace fails to operate E11 Burner limit switch circuit is Open
Check for correct gas pressure
Check for correct burner alignment Check for and correct burner restriction
Check burner temperature switch, replace if necessary

31
0.10 0.20 0.30 0.40
CFM CFM CFM CFM CFM WATTS CFM WATTS CFM WATTS CFM WATTS
F01
590 540 483 429 369 72 311 78 247 84 203 89
F02
690 643 597 547 498 90 443 96 389 102 343 109
F03
750 702 660 618 572 104 525 110 477 116 421 124
F04
876 832 794 758 716 138 678 146 641 152 598 157
F05^
927 881 841 806 771 155 734 161 698 168 662 174
F06
1058 1015 976 945 915 202 881 210 849 218 818 226
F07
1116 1071 1036 1003 975 230 943 236 919 245 884 252
F08^^
1238 1192 1158 1124 1098 291 1070 299 1044 308 1016 318
F09
1398 1357 1320 1293 1269 396 1239 405 1216 411 1194 416
F01
587 542 490 437 382 75 318 82 266 88 207 93
F02
685 638 590 543 498 92 448 98 392 105 339 112
F03
856 814 774 732 693 136 657 142 622 148 581 154
F04^
937 892 855 819 786 163 752 170 715 177 684 184
F05
1060 1017 981 950 921 212 886 219 856 227 828 234
F06^^
1108 1068 1033 1003 972 234 942 243 914 250 882 259
F07
1274 1233 1203 1174 1146 327 1118 337 1089 345 1065 353
F08
1374 1340 1306 1278 1254 399 1227 411 1201 414 1179 421
F09
1437 1395 1362 1332 1305 473 1278 482 1253 492 1228 502
F01
836 774 711 655 596 108 523 116 456 124 397 130
F02
1274 1228 1188 1147 1107 248 1064 256 1027 266 990 276
F03
1295 1256 1214 1181 1140 260 1100 269 1062 279 1024 287
F04
1385 1337 1301 1260 1222 298 1186 308 1149 315 1114 326
F05
1454 1407 1372 1353 1325 349 1291 360 1255 370 1219 379
F06^
1528 1485 1438 1409 1383 382 1349 391 1317 402 1285 412
F07
1619 1579 1551 1523 1495 444 1463 454 1430 464 1402 476
F08^^
1746 1697 1667 1642 1617 534 1593 545 1570 559 1540 571
F09
1772 1735 1698 1674 1645 559 1622 571 1598 584 1574 597
F01
722 658 599 534 458 88 386 94 330 99 268 105
F02
1270 1223 1179 1139 1105 250 1066 259 1029 267 996 277
F03
1304 1254 1212 1173 1135 264
1104 273 1069 282 1032 290
F04
1367 1318 1277 1236 1199 296 1169 306 1135 315 1102 327
F05^
1473 1429 1386 1355 1320 354 1289 365 1258 372 1224 383
F06
1560 1518 1476 1441 1409 409 1382 422 1350 429 1321 439
F07
1647 1605 1562 1531 1497 460 1467 471 1440 481 1408 492
F08^^
1720 1710 1674 1642 1611 544 1581 558 1553 565 1527 579
F09
1796 1759 1721 1687 1655 582 1628 595 1604 607 1578 619
F01
1280 1228 1178 1134 1086 204 1036 214 986 226 936 236
F02
1401 1356 1313 1273 1234 252 1190 262 1145 270 1099 282
F03
1593 1550 1512 1475 1436 332 1399 341 1360 354 1319 364
F04
1706 1662 1621 1586 1550 383 1515 395 1479 407 1444 414
F05^
1821 1775 1736 1703 1669 443 1636 455 1605 468 1576 480
F06
1836 1793 1757 1721 1689 459 1659 472 1628 486 1592 497
F07
1932 1888 1855 1825 1794 517 1762 532 1733 545 1701 560
F08^^
2184 2143 2110 2072 2048 706 2017 724 1989 741 1959 756
F09
2221 2178 2145 2109 2082 731 2053 747 2025 764 1992 780
*R9S800603AU*
Y1/Y2/G
*R9S800604BU*
Y1/Y2/G
THERMOSTAT
CALL
*R9S800403AU*
Y1/Y2/G
TAP #
MODEL
*Models
^ Default Y1 speed
^^ Default Y2 speed
NOTE : Watts provided are blower motor watts.
*R9S800805CU*
Y1/Y2/G
*R9S800804BU*
Y1/Y2/G
AR9S80-U / GR9S80-U COOLING & CIRCULATION AIFLOW
EXTERNAL STATIC PRESSURE (INCHES OF WATER COLUMN)
0.50
0.60
0.70
0.80
BLOWER PERFORMANCE DATA

32
0.60 0.70 0.80
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
F02
690 42 643 46 597 49 547 53 498 55 443 389 343
F03^
750 39 702 42 660 45 618 48 572 52 525 477 421
F04
876 34 832 36 794 37 758 39 716 41 678 641 598
F05
927 32 881 34 841 35 806 37 771 38 734 698 662
F06
1058 28 1015 29 976 30 945 31 915 32 881 849 818
F07
1116 27 1071 28 1036 29 1003 30 975 30 943 919 884
F05
1060 42 1017 44 981 45 950 47 921 48 886 856 828
F06
1108 40 1068 42 1033 43 1003 44 972 46 942 914 882
F07^
1274 35 1233 36 1203 37 1174 38 1146 39 1118 1089 1065
F02
1274 35 1228 36 1188 37 1147 39 1107 40 1064 1027 990
F03
1295 34 1256 35 1214 37 1181 38 1140 39 1100 1062 1024
F04^
1385 32 1337 33 1301 34 1260 35 1222 36 1186 1149 1114
F05
1454 31 1407 32 1372 32 1353 33 1325 34 1291 1255 1219
F02^
1270 47 1223 48 1179 50 1139 52 1105 54 1066 1029 996
F03
1304 45 1254 47 1212 49 1173 51 1135 52 1104 1069 1032
F04
1367 43 1318 45 1277 46 1236 48 1199 49 1169 1135 1102
F01
1280 46 1228 48 1178 50 1134 52 1086 55 1036 986 936
F02^
1401 42 1356 44 1313 45 1273 47 1234 48 1190 1145 1099
AR9S80-U / GR9S80 HEATING AIFLOW
TEMP
RANGE
0.10
0.20
0.30
0.40
0.50
*R9S800403AU*
W/W1
MODEL
THERMOSTAT
CALL
TAP #
EXTERNAL STATIC PRESSURE (INCHES OF WATER COLUMN)
25 - 55
*R9S800603AU*
W/W1
20 - 50
*R9S800805CU*
W/W1
35 - 65
*R9S800604BU*
W/W1
20 - 50
35 - 65
*R9S800804BU*
W/W1
^ Default Heat Speed
BLOWER PERFORMANCE DATA

33
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIGH VOLTAGE!
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
OR
INSTALLING
THIS
UNIT
.
M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
9 8 7 6 5 4 3 2 1
9 8 7 6 5 4 3 2
F
C
D
E
B
A
C
D
E
B
A
SC
3 2
1
F
0140F20034
CC
10.25 .10
FRAME
.25
5.50 .10
FRAME
10.75 .10
LABEL
.25
6.00 .10
LABEL
SPECIAL CHARACTERISTICS: (REFER MSP 822-01 FOR DETAILS)
= CRITICAL CHARACTERISTIC REQUIRES AN INITIAL CPK OF 1.33 AND USE OF STATISTICAL PROCESS CONTROL.
= SIGNIFICANT CHARACTERISTIC REQUIRES AN INITIAL CPK OF 1.00 AND USE OF STATISTICAL PROCESS CONTROL.
INABILITY TO MEET THE REQUIRED INITIAL CPK VALUE WILL REQUIRE 100% INSPECTION.
COMPONENTS AND MATERIALS SPECIFIED HEREIN SHALL COMPLY WITH GOODMAN S4900170 MATERIALS OF CONCERN SPECIFICATION
COMPONENTS AND MATERIALS SPECIFIED HEREIN SHALL CONFORM TO THE APPLICABLE SECTION OF GOODMAN MSP 860-01
WORKMANSHIP STANDARD.
CONFIDENTIAL PROPERTY OF DAIKIN COMFORT TECHNOLOGIES MANUFACTURING, L.P. OR ITS AFFILIATES NOT TO BE DISCLOSED TO
OTHERS, COPIED, OR USED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING. MUST BE RETURNED UPON DEMAND,
ON COMPLETION OF ORDER, OR OTHER PURPOSE FOR WHICH IT WAS LENT
DATEENGCHKDESCRIPTIONREVECN/DR
05-Dec-2023 15:44UQINITIAL RELEASE A1451544-451549
DAIKIN COMFORT TECHNOLOGIES MANUFACTURING, L.P.
DRAWING TO BE INTERPRETED IN
ACCORDANCE WITH ASME Y14.100
TITLE
LABEL, WIRING DIAGRAM
ULN 80% 9 TAP
DIMENSIONS ARE IN INCHES
UNLESS OTHERWISE NOTED.
TOLERANCES UNLESS
OTHERWISE NOTED
ANGLES
1.5
.X .1
.XX
.03
.XXX
.015
HOLES
: .005
TUBE CUT LG:
.063
DWN BY: KS SCALE: NTS
CREATE DATE: 12/05/23 SHEET: 1 OF 1
DWG.
NO.
0140F20034 A
NOTES:
1. MATERIAL: BOPP FILM 3.3 MIL PER SPECIFICATION S4900061 TYPE W
2. TEXT TO BE BLACK ON WHITE BACKGROUND
3. BARCODE MUST ADHERE TO S4900070 (TWO DIMENSIONAL BARCODE STANDARDS AND
CHECK DIGIT ALGORITHM)
4. SUPPLIER PACKAGING MUST COMPLY WITH GOODMAN SPECIFICATION S4900110.
NOTES:
1. MANUFACTUR'S SPECIFIED REPLACEMENT
PARTS MUST BE USED WHEN SERVICING.
2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED
WITH THE FURNACE MUST BE REPLACED, IT
MUST BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERATURE RATING OF AT LEAST
105
C. USE COPPER CONDUCTORS ONLY.
3. BLOWER SPEEDS SHOULD BE ADJUSTED BY
INSTALLER TO MATCH THE INSTALLATION
REQUIREMENTS SO AS TO PROVIDE
THE CORRECT HEATING TEMPRATURE
RISE AND THE CORRECT COOLING CFM.
4. UNIT MUST BE PERMANENTLY GROUNDED
AND CONFORM TO N.E.C. AND LOCAL CODES.
5. EAC. NORMALLY OPEN CONTACTS FOR OPTIONAL
ELECTRONIC AIR CLEANER USE. CONTACTS
CLOSE
WHEN INDOOR BLOWER IS RUNNING. TERMINALS
ARE NOT INTERNALLY POWERED
6. HUM. NORMALLY OPEN CONTACTS FOR OPTIONAL
HUMIDIFIER USE. CONTACTS CLOSE WHEN DRAFT
INDUCER IS RUNNING. TERMINALS ARE NOT
INTERNALLY POWERED
7. WHEN THIS FURNACE IS PAIRED WITH NON R-32
REFRIGERANT SYSTEMS, DEFAULT SETTINGS WILL
NEED TO BE CHANGED. REFER TO INSTALLATIONS
MANUAL FOR FURTHER INSTRUCTIONS.
GR
GND
JUNCTION BOX
WARNING:DISCONNECT
N
TO UNIT MUST BE
AND GROUNDED.
L
SERVICING. WIRING
DISCONNECT
GND
WH
BK
POWER BEFORE
PROPERLY POLARIZED
0140F20034-A
Ø /60 HZ
OVERCURRENT
115 VAC/ 1
TO
POWER SUPPLY WITH
PROTECTION
DEVICE
BURNER COMPARTMENT
BLOWER
COMPARTMENT
DOOR-SWITCH
(OPEN WHEN
DOOR OPEN)
RD
WH
BK
RD
GR
BK
BK
YL
FLAME SENSOR
BR
1
GAS VALVE
2
M
C
GY
BLOWER COMPARTMENT
AUTO RESET AUXILIARY
LIMIT CONTROL
RD
RD
AUTO RESET
PRIMARY
LIMIT CONTROL
RD
BK
GND
BLOWER
DRAFT (ID)
INDUCED
1
2
3
RD
WH
BK
RD
WH
2 CIRCUIT
CONNECTOR
HOT
SURFACE
IGNITER
WH
PU
PU
PK
AUTO RESET
BURNER
BOX LIMIT
BK
RD
WH
2
1
WH
WH
YL
BK
OR
RD
BL
WH
BK
BK
NOTE 5
CR48
SW1
SW2
E28
E32
YL
WH
E23
NEUTRAL
E46
E25
E26
E47
E19
E22
W11
BLW
W12
E5
E4
E35
IN
OUT
E42
EAC
W2
W1
B\C
R
G
Y1
TWIN
Y2
E39
TAP1
TAP2
TAP3
TAP4
TAP5
GND
PSO
BLI
MVH
MVL
GND
HLI
TH
MVC
HLO
PS1
TR
ALI
MOB_PE
FS
E41
U
V
W
LINE
N
H
FUSE
GND
PI
5V
E18
YL
NO
C
ID BLOWER
PRESSURE
SWITCH
YL
PRESSURE TRANSDUCER
BK
RD
GR
2
1
3
4
UNUSED
5V
GND
PI
A2L MODE IS ENABLED BY DEFAULT
REFER TO INSTALLATION MANUAL FOR FURTHER
INSTRUCTIONS.
A2L
A2L
ALARM
HUM
NOTE 6
RD
0
1
12
YL
PK
PU
YL
PK
BR
GR
GY
VENT
PK
COLOR CODES:
RD
GY
WH
PU
OR
YL
BL
BR
BK
GR
BLUE
BROWN
BLACK
GREEN
PINK
GRAY
PURPLE
ORANGE
RED
WHITE
YELLOW
SWITCH (PRESSURE)
FIELD SPLICE
FIELD GROUND
EQUIPMENT GROUND
INTERNAL TO
PROTECTION DEVICE
INTEGRATED CONTROL
PLUG CONNECTION
SWITCH (TEMPERATURE)
JUNCTION
OVERCURRENT
TERMINAL
IGNITER
HIGH VOLTAGE (115V)
HIGH VOLTAGE FIELD
LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
STATUS & FAULT
(SEE INSTALLATION MANUAL FOR COMPLETE LIST OF FAULTS)
SEVEN SEGMENT DISPLAY
Seg. 1 Seg. 2 Seg. 3
IDLE Id L
CONTINIOUS FAN FA n
LOW STAGE COOLING 1A C
HIGH STAGE COOLING 2A C
GAS HEAT gH
HEAT PUMP HEAT, LOW STAGE 1H P
HEAT PUMP HEAT, HIGH STAGE 2H P
DEFROST dF t
LOCKOUT DUE TO EXCESSIVE RETRIES RECYCLE EE 0
PRESSURE SWITCH CLOSED WHEN ECPECTED TO BE OPEN EE 1
PRESSURE SWITCH OPEN WHEN EXPECTED TO BE CLOSED EE 2
OPEN HIGH LIMIT SWITCH EE 3
FLAME DETECTED WHEN NO FLAME SHOULD BE PRESENT EE 4
OPEN FUSE EE 5
LOW FLAME SIGNAL EE 6
IGNITOR FAULT OR IGNITOR RELAY FAULT EE 7
REVERSED LINE POLARITY EE A
GROUNDING ERROR E1 0
INTERNAL GAS VALVE ERROR EE b
EXTERNAL GAS VALVE ERROR EE C
STATUS & FAULT
(SEE INSTALLATION MANUAL FOR COMPLETE LIST OF FAULTS)
SEVEN SEGMENT DISPLAY
Seg. 1 Seg. 2 Seg. 3
AUXILLIARY LIMIT SWITCH OPEN EE d
BURNER LIMIT SWITCH OPEN E 1 I
LOW CIRCULATOR CURRENT E b L
CIRCULATOR CURRENT UNEXPECTED E b U
A2L COMMUNICATION ALARM EA F
A2L LEAKAGE ALARM EA L
A2L INTERNAL ALARM EA S
A2L RELAY ALARM EA r
RD
BLOWER
CIRCULATOR
BK
GR
RD
3
1
WH
2
4
BL
5 4 3
2 1
BL
RD
OR
BK
YL
40 VA
TRANS-
FORMER
115
VAC
24
VAC
WH
BK
GND
GROUND WIRE
CONNECTED
TO CONTROL
MOUNTING PANEL
WIRING DIAGRAM

34
START-UP CHECKLIST

35
THIS PAGE INTENTIONALLY LEFT BLANK

36
19001 Kermier Rd., Waller, TX 77484
www.goodmanmfg.com • www.amana-hac.com
© 2024 Daikin Comfort Technologies Manufacturing, L.P.
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights
reserved.
CUSTOMER FEEDBACK
We are very interested in all product comments.
Please ll out the feedback form on one of the following links:
Goodman
®
Brand Products: (http://www.goodmanmfg.com/about/contact-us).
Amana
®
Brand Products: (http://www.amana-hac.com/about-us/contact-us).
You can also scan the QR code on the right for the product brand
you purchased to be directed to the feedback page.
GOODMAN
®
BRAND
AMANA
®
BRAND
GOODMAN
®
BRAND
AMANA
®
BRAND
PRODUCT REGISTRATION
Thank you for your recent purchase. Though not required to get the protection of
the standard warranty, registering your product is a relatively short process, and
entitles you to additional warranty protection, except that failure by California and
Quebec residents to register their product does not diminish their warranty rights.
The duration of warranty coverages in Texas and Florida diers in some cases.
For Product Registration, please register as follows:
Goodman
®
Brand products: (https://www.goodmanmfg.com/product-registration).
Amana
®
Brand products: (http://www.amana-hac.com/product-registration).
You can also scan the QR code on the right for the product brand
you purchased to be directed to the Product Registration page.