AO Smith BL-80 100 Conservationist 74-Gallon Ultra-Low NOx High Recovery Commercial Gas Water Heater

Product's Documents

Below are documents related to this product, you can read online or download:
User Manual Specification
  • Spec Sheet - CONSERVATIONIST® ULTRA-LOW NOX Spec Sheet (AOSCG10601) - (English) Download
BL-80 100 photo

Manual - CONSERVATIONIST® ULTRA-LOW NOX Manual (100228342)

This is the main product document for model BL-80 100. Additionally, the document applies to other AO Smith models: BL-80

The file format is pdf, 36 pages, you can download this manual here .

background
1
Instruction Manual
PRINTED 1215 324258-002
KEEP THIS MANUAL IN THE POCKET ON HEATER FOR FUTURE REFERENCE
WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.
ULTRA LOW NOX COMMERCIAL GAS WATER HEATERS
For Your Safety
AN ODORANT IS ADDED TO THE GAS USED
BY THIS WATER HEATER.
MODELS BL-80/BL-100
Series 100
INSTALLATION - OPERATION - SERVICE
- MAINTENANCE - LIMITED WARRANTY
PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
background
2
SAFE INSTALLATION, USE AND SERVICE...................... 3
APPROVALS ...................................................................... 3
GENERAL SAFETY INFORMATION .................................. 4
INTRODUCTION ................................................................ 5
Abbreviations Used ..................................................... 5
QualiedInstallerorServiceAgency........................... 5
PreparingfortheNewInstallation ............................... 5
INSTALLATION CONSIDERATIONS ................................. 6
RoughInDimensions .................................................. 6
Thermometers ............................................................. 7
FactstoConsiderAboutTheLocation ........................ 7
HighAltitude ................................................................ 8
Clearances .................................................................. 8
Insulation Blankets ...................................................... 9
Hard Water .................................................................. 9
CirculationPumps ....................................................... 9
INSTALLATION REQUIREMENTS .................................. 10
GasSupplySystems ................................................. 10
GasPressureRequirements ..................................... 10
SupplyGasRegulator ............................................... 10
MixingValves ............................................................ 10
WaterPiping .............................................................. 11
ClosedWaterSystems .............................................. 11
ThermalExpansion ................................................... 11
Temperature-PressureReliefValve ......................... 11
FillingtheWaterHeater ............................................. 12
AirRequirements....................................................... 12
UnconnedSpace ..................................................... 13
ConnedSpace ......................................................... 13
FreshAirOpeningsforConnedSpaces .................. 13
OutdoorAirThroughTwoOpenings .......................... 13
OutdoorAirThroughOneOpening ........................... 13
OutdoorAirThroughTwoHorizontalDucts ............... 14
OutdoorAirThroughTwoVerticalDucts ................... 14
AirFromOtherIndoorSpaces .................................. 14
Venting ...................................................................... 14
GasPiping ................................................................. 16
SedimentTraps ......................................................... 17
LIGHTING & OPERATING INSTRUCTIONS ................... 18
TEMPERATURE REGULATION ...................................... 19
FOR YOUR INFORMATION ............................................. 19
Start Up Conditions ................................................... 19
Operational Conditions .............................................. 20
PERIODIC MAINTENANCE ............................................. 21
VentingSystemInspection ........................................ 21
BurnerInspection ...................................................... 21
BurnerCleaning ........................................................ 21
Housekeeping ........................................................... 21
AnodeRodInspection ............................................... 22
Temperature-PressureReliefValveTest ................... 22
RECOMMENDED PROCEDURE FOR PERIODIC
REMOVAL OF LIME DEPOSITS FROM TANK
TYPE COMMERCIAL WATER HEATERS ........................ 22
DelimingSolvents...................................................... 23
TankCleanoutProcedure .......................................... 23
DelimingUsingFlo-JugMethod ................................ 23
DrainingandFlushing ............................................... 24
Service ...................................................................... 24
LEAKAGE CHECKPOINTS .............................................. 25
TROUBLESHOOTING GUIDELINES ............................... 26
WATER PIPING DIAGRAMS ............................................ 27
NOTES ............................................................................. 33
WARRANTY ..................................................................... 35
TABLE OF CONTENTS
background
3
SAFE INSTALLATION, USE AND SERVICE
Theproperinstallation,useandservicingofthiswaterheaterisextremelyimportanttoyoursafetyandthesafetyofothers.
Manysafety-relatedmessagesandinstructionshavebeenprovidedinthismanualandonyourownwaterheatertowarnyouand
othersofapotentialinjuryhazard.Readandobeyallsafetymessagesandinstructionsthroughoutthismanual.Itisveryimportant
thatthemeaningofeachsafetymessageisunderstoodbyyouandotherswhoinstall,use,orservicethiswaterheater.
Allsafetymessageswillgenerallytellyouaboutthetypeofhazard,whatcanhappenifyoudonotfollowthesafetymessage,and
howtoavoidtheriskofinjury.
DANGER
WARNING
CAUTION
CAUTION
DANGER indicates an imminently
hazardous situation which, if not avoided,
will result in injury or death.
This is the safety alert symbol. It is used to alert you to
potential personal injury hazards. Obey all safety
messages that follow this symbol to avoid possible
injury or death.
WARNING indicates a potentially hazardous
situation which, if not avoided, could result
in injury or death.
CAUTION indicates a potentially hazardous
situation which, if not avoided, could result in
minor or moderate injury.
CAUTION used without the safety alert
symbol indicates a potentially hazardous
situation which, if not avoided, could result in
property damage.
APPROVALS
Low Lead Content
background
4
GENERAL SAFETY INFORMATION
background
5
ThankYouforpurchasingthiswaterheater.Properlyinstalledand
maintained,itshouldgiveyouyearsoftroublefreeservice.
ABBREVIATIONS USED
AbbreviationsFoundInThisInstructionManual:
• UL-UnderwritersLaboratoriesInc.
• ANSI-AmericanNationalStandardsInstitute
• NFPA-NationalFireProtectionAssociation
• ASME-AmericanSocietyofMechanicalEngineers
• AHRI-Air-Conditioning,HeatingandRefrigerationInstitute
CAN - Canada
• EPACT-EnergyPolicyAct
• CSA-CanadianStandardsAssociation
This gas-fired water heater is design certified by Underwriters
LaboratoriesInc.underAmericanNationalStandard/CSAStandard
forGasWaterHeatersANSIZ21.10.3•CSA4.3(currentedition).
QUALIFIED INSTALLER OR SERVICE AGENCY
Installationandserviceofthiswaterheaterrequiresabilityequivalent
tothatofaQualiedAgency(asdenedbyANSIbelow)intheeld
involved. Installation skills such as plumbing, air supply, venting,
gassupplyandelectricalsupplyarerequiredinadditiontoelectrical
testingskillswhenperformingservice.
ANSIZ223.12006Sec.3.3.83:“QualiedAgency”-“Anyindividual,
rm, corporation or company that either in person or through a
representativeisengagedinandisresponsiblefor(a)theinstallation,
testingorreplacementofgaspipingor(b)theconnection,installation,
testing, repair or servicing of appliances and equipment; that is
experiencedinsuchwork;thatisfamiliarwithallprecautionsrequired;
and that has complied with all the requirements of the authority
havingjurisdiction.”
Ifyouarenotqualied(asdenedbyANSIabove)andlicensedor
certiedasrequiredbytheauthorityhavingjurisdictiontoperforma
giventaskdonotattempttoperformanyoftheproceduresdescribed
in this manual. If you do not understand the instructions given in
this manual do not attempttoperformany procedures outlined in
thismanual.
PREPARING FOR THE INSTALLATION
1. ReadtheGeneralSafetyInformationsection,page4ofthis
manual first and then the entire manual carefully. If you
don’tfollowthesafetyrules,thewaterheaterwillnotoperate
pr o p er l y.I t c oul d c auseD E AT H,S E R I OU S B O DI LYIN J U RY
AND/ORPROPERTYDAMAGE.
This manual contains instructions for the installation,
oper a t ion,andm a int e nanc eo fthe gas - f ir e dwa terh e ate r. It
alsocontainswarningsthroughoutthemanualthatyoumust
readandbeawareof.Allwarningsandallinstructionsare
essentialtotheproperoperationofthewaterheaterandyour
safety.Sincewecannotputeverythingonthefirstfewpages,
READ THE ENTIRE MANUAL BEFORE ATTEMPTING TO
INSTALL OR OPERATE THE WATER HEATER.
2.The installation must conform with these instructions and
thelocalcodeauthorityhavingjurisdiction.Intheabsence
oflocalcodes,theinstallationmustcomplywiththecurrent
editions of the National Fuel Gas Code, ANSI Z223.1/
NFPA54orCAN /CSA - B149.1theNaturalGasandPropane
Installation Code. All documents are available from the
CanadianStandardsAssociation,8501EastPleasantValley
Road, Cleveland, OH 44131. NFPA documents are also
available from the National Fire Protection Association, 1
BatterymarchPark,Quincy,MA02269.
3.If after reading this manual you have any questions or do
notunderstandanyportionoftheinstructions,callthelocal
gasutilityorthemanufacturerwhosenameappearsonthe
ratingplate.
4.Carefully plan the place where you are going to put the
water heater. Correct combustion, vent action, and vent
pipeinstallationareveryimportantinpreventingdeathfrom
possiblecarbonmonoxidepoisoningandfires,seeFigures
3 and 7.
Examinethelocationtoensurethewaterheaterc omplieswith
theFacttoConsiderAboutTheLocationsectioninthismanual.
5.For
background
6
ROUGH IN DIMENSIONS
INSTALLATION CONSIDERATIONS
FIGURE 1.
K
HOT WATER
OUTLET
DRAIN
VA LV E
HOT
COLD
TOP VIEW
L
GAS INLET
INSTALL IN ACCORDANCE WITH LOCAL CODES
DRAIN VALVE
K
COLD WATER
INLET
OUTER DOOR
(BURNER ASSEMBL Y BEHIND)
DRAFT HOOD
F
H
J
B
D
A
E
M
background
7
THERMOMETERS (Not Supplied)
Thermometersshouldbeobtainedandeldinstalled.
Thermometersareinstalledinthesystemasameansofdetecting
thetemperatureoftheoutletwatersupply.
ThisWaterHeaterhasbeendesigncertifiedascomplyingwith
ANSIZ21.10.3-CSA4.3currenteditionforwaterheatersandis
consideredsuitablefor:
Water (Potable) Heating and Space Heating: All models are
consideredsuitableforwater(potable)heatingandspaceheating.
HOTTERWATERCANSCALD:
Waterheatersareintendedtoproducehotwater.Waterheatedtoa
temperaturewhichwillsatisfyspaceheating,clotheswashing,dish
washing,andothersanitizingneedscanscaldandpermanentlyinjure
youuponcontact.Somepeoplearemorelikelytobepermanently
injuredbyhotwaterthanothers.Theseincludetheelderly,children,
theinrm,orphysically/mentallyhandicapped.Ifanyone
background
8
usedinthesameroomorareacontainingagaswaterheaterorother
openameorsparkproducingappliance.NOTE:Flammablevaporsmay
bedrawnbyaircurrentsfromotherareasofthestructuretotheappliance.
Also, the water heater must be located and/or protected so it is not
subjecttophysicaldamagebyamovingvehicle.
Thiswaterheatermustnotbeinstalleddirectlyoncarpeting.Carpeting
mustbeprotectedbymetalorwoodpanelbeneaththewaterheater
extendingbeyondthefullwidthanddepthofthewaterheaterbyatleast
3”(76.2mm)inanydirection,orifthewaterheaterisinstalledinan
alcoveorcloset,theentireoormustbecoveredbythepanel.Failure
toheedthiswarningmayresultinarehazard.
HIGH ALTITUDE
Waterheaterscoveredinthismanualhavebeentestedandapproved
for installation at elevations up to 7,700 feet (2,347 m) above sea
level.Forinstallationabove7,700feet(2,347m),thewaterheater’s
Btuinputshouldbereducedattherateof4percentforeach1,000
feet(305m)abovesealevelwhichrequiresreplacementoftheburner
oriceinaccordancewiththeNationalFuelGasCodeANSIZ223.1/
NFPA 54 or the Natural Gas and Propane Installation Code CAN/
CSAB149.1.Contactyourlocalgassupplierforfurtherinformation.
Failuretoreplacethestandardoricewiththeproperhighaltitude
orice when installed
background
9
INSULATION BLANKETS
Do not obstruct water heater air intake
with insulating blanket.
Gas and carbon monoxide detectors
are available.
Install water heater in accordance with
the instruction manual.
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
Breathing Hazard - Carbon Monoxide Gas
background
10
GAS SUPPLY SYSTEMS
Low pressure building gas supply systems are dened as those
systemsthatcannotunderanycircumstancesexceed14”W.C.
(1/2PSIGauge).Thesesystemsdonotrequirepressureregulation.
Measurementsshouldbetakentoinsurethatgaspressuresarestable
andfallwithintherequirementsstatedonthewaterheaterratingplate.
readings should be taken with all gas burning equipment off (static
pressure)andwithallgasburningequipmentrunningatmaximumrate
(dynamicpressure).Thegassupplypressuremustbestablewithin1.5”
W.C. from static todynamicpressuretoprovide good performance.
Pressuredropsthatexceed1.5”W.C.maycauseroughstarting,noisy
combustionornuisanceoutages.Increasesorspikesinstaticpressure
duringoffcyclesmaycausefailuretoigniteorinseverecasesdamage
toappliancegasvalves.Ifyourlowpressuresystemdoesnotmeet
theserequirements,theinstallerisresponsibleforthecorrections.
HighPressurebuildingsupplysystemsusepressuresthatexceed
14” W.C. (1/2 PSI Gauge). These systems must use eld supplied
regulatorsto lower the gaspressure to less than 14” W.C. (1/2 PSI
Gauge).Appliancesrequiregasregulatorsthatareproperlysizedforthe
waterheaterinputanddelivertheratingplatespeciedpressures.Gas
supplysystemswherepressureexceeds5PSIoftenrequiremultiple
regulatorstoachievedesiredpressures.Systemsinexcessof5PSI
building pressure should be designed by gas delivery professionals
forbestperformance.Waterheatersconnectedtogassupplysystems
thatexceed14”W.C.(1/2PSIGauge)atanytimemustbeequipped
withagassupplyregulator.
GAS PRESSURE REQUIREMENTS
BL-100naturalgasmodelrequiresaminimumgassupplypressureof
5”w.c.(1.25kPa);BL-80naturalgasmodelrequiresaminimumgas
supplypressureof6”w.c.(1.49kPa).Theminimumsupplypressure
is measured while gas is owing (dynamic pressure). The supply
pressure(dynamic)shouldneverfallbelowthespeciedminimum
supplypressure.Thesupplypressureshouldbemeasuredwithallgas
redappliancesconnectedtothecommonmainringatfullcapacity.If
thesupplypressuredropsmorethan1.5”W.C.(0.37kPa)asgasbegins
toowtothewaterheaterthenthesupplygassystemincludingthe
gaslineand/orthegasregulatormayberestrictedorundersized.See
SupplyGasregulatorsectionandGasPipingsectionofthismanual.
Thegasvalveonallmodelshasamaximumgassupplypressurelimit
of14” W.C.
valve
background
11
WATER PIPING
WATER (POTABLE) HEATING AND SPACE HEATING
Thiswaterheatershallnotbeconnectedtoanyheatingsystems
orcomponent(s)usedwithanon-potablewaterheatingappliance.
Allpipingcomponentsconnectedtothis unit for space heating
applicationsshallbesuitableforusewithpotablewater.
Toxicchemicals,suchasthoseusedforboilertreatmentshallnot
beintroducedintothissystem.
Whenthesystemrequireswaterforspaceheatingattemperatures
higherthanrequiredfordomesticwaterpurposes,amixingvalve
mustbeinstalled.PleaserefertoFigure6forsuggestedpiping
arrangement.
Thesewaterheaterscannotbeusedinspaceheatingapplications
only.
CLOSED WATER SYSTEMS
Water supply systems may, because of code requirements or
such conditions as high line pressure, among others, have
installed devices such as pressure reducing valves, check
valves,andbackflowpreventers.Devicessuchasthesecause
thewatersystemtobeaclosedsystem.
THERMAL EXPANSION
Aswaterisheated,itexpands(thermalexpansion).Inaclosed
systemthevolumeof waterwillgrowwhenit isheated.Asthe
volumeofwatergrowstherewillbeacorrespondingincreasein
water pressure due to thermal expansion. Thermal expansion
cancauseprematuretankfailure(leakage).Thistypeoffailure
is not covered under the limited warranty. Thermal expansion
canalso cause intermittent Temperature-Pressure ReliefValve
operation: water discharged from the valve due to excessive
pressurebuildup.Thisconditionisnotcoveredunderthelimited
warranty.TheTemperature-PressureReliefValveisnotintended
fortheconstantreliefofthermalexpansion.
A properly sized thermal expansion tank must be installed on
all closed systems to control the harmful effects of thermal
expansion.Contactalocalplumbingservicetechniciantohave
athermalexpansiontankinstalled.
FIGURE 7.
NOTE: To protect against untimely corrosion of hot and cold
waterttings, itisstronglyrecommended thatdi-electricunions
orcouplingsbeinstalledonthiswaterheaterwhenconnectedto
copperpipe.
Figure7showsthetypicalattachmentofthewaterpipingtothe
water heater.
background
12
NOTE: In addition to the factory installed Temperature-Pressure
Relief Valve on the water heater, each remote storage tank that
maybeinstalledandpipedtoawaterheatingappliancemustalso
have its own properly sized, rated and approved Temperature-
PressureReliefValveinstalled.Callthetollfreetechnicalsupport
phonenumberlistedonthebackcoverofthismanualfortechnical
assistanceinsizingaTemperature-PressureReliefValveforremote
storagetanks.
For safe operation of the water heater, the Temperature-Pressure
ReliefValvemustnotberemovedfromitsdesignatedopeningnor
plugged.TheTemperature-PressureReliefValvemustbeinstalled
directlyintothettingofthewaterheaterdesignedforthereliefvalve.
Installdischargepipingsothatanydischargewillexitthepipewithin
6inches(15.2cm)aboveanadequateoordrain,orexternaltothe
building.Incoldclimatesitisrecommendedthatitbeterminatedat
anadequatedraininsidethebuilding.Becertainthatnocontactis
madewithanyliveelectricalpart.Thedischargeopeningmustnot
beblockedorreducedinsizeunderanycircumstances.Excessive
length,over30feet(9.14m),oruseofmorethanfourelbowscan
causerestrictionandreducethedischargecapacityofthevalve.
No valve or other obstruction is to be placed between the
Temperature-PressureReliefValve andthetank. Donotconnect
dischargepipingdirectlytothedrainunlessa6”(15.2cm)airgapis
provided.Topreventbodilyinjury,hazardtolife,orpropertydamage,
the relief valve must be allowed to discharge water in adequate
quantitiesshouldcircumstancesdemand.Ifthedischargepipeis
notconnectedto a drain or other suitable means, thewaterow
maycausepropertydamage.
Water Damage Hazard
Temperature-Pressure Relief Valve discharge
pipe must terminate at adequate drain.
CAUTION
T&P Valve Discharge Pipe Requirements:
Shallnotbesmallerinsizethantheoutletpipesizeofthevalve,
orhaveanyreducingcouplingsorotherrestrictions.
Shallnotbepluggedorblocked.
Shallnotbeexposedtofreezingtemperatures.
Shallbeofmateriallistedforhotwaterdistribution.
Shallbeinstalledsoastoallowcompletedrainageofboththe
Temperature-PressureReliefValveandthedischargepipe.
Mustterminateamaximumofsixinchesaboveaoordrain
orexternaltobuilding.Incoldclimates,itisrecommended
thatdischargepipebeterminatedatanadequatedraininside
building.
Shallnothaveanyvalveorotherobstructionbetweenthe
reliefvalveandthedrain.
background
13
amountofcombustionaircanresultinareorexplosionandcauseproperty
damage,seriousbodilyinjuryordeath.
UNCONFINED SPACE
An Unconfined Space is one whose volumeis not lessthan 50
cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the
totalinputratingofallappliancesinstalledinthespace.Rooms
communicating directly with the space, in which the appliances
are installed, through openings not furnished with doors, are
consideredapartoftheunconfinedspace.
Makeupairrequirementsfortheoperationofexhaustfans,kitchen
ventilation systems, clothes dryers and fireplaces shall also be
considered in determining the adequacy of a space to provide
combustion,ventilationanddilutionair.
UNUSUALLY TIGHT CONSTRUCTION
Inunconfinedspacesinbuildings,infiltrationmaybeadequateto
provideairforcombustion,ventilationanddilutionoffluegases.
However,inbuildingsofunusuallytightconstruction(forexample,
weatherstripping,heavilyinsulated,caulked,vaporbarrier,etc.)
additionalair must be provided using the methods described in
theConfinedSpacesectionthatfollows.
CONFINED SPACE
AConnedSpaceisonewhosevolumeislessthan50cubicfeetper
1,000Btu/hr(4.8cubicmetersperkW)ofthetotalinputratingofall
appliancesinstalledinthespace.
Openingsmustbeinstalledtoprovidefreshairforcombustion,ventilation
and dilution in conned spaces. The required size for the openings is
dependentonthemethodusedtoprovidefreshairtotheconnedspace
andthetotalBtu/hrinputratingofallappliancesinstalledinthespace.
DIRECT VENT APPLIANCES
Appliances installed in a Direct Vent conguration that derive all
air for combustion from the outdoor atmosphere through sealed
intakeair piping are not factored inthe total appliance input Btu/hr
calculationsusedtodeterminethesizeofopeningsprovidingfresh
airintoconnedspaces.
EXHAUST FANS
Whereexhaustfansareinstalled,additionalairshallbeprovided
toreplacetheexhaustedair.Whenanexhaustfanisinstalledin
thesamespacewithawaterheater,sufficientopeningstoprovide
freshairmustbeprovidedthataccommodatetherequirements
for all appliancesintheroomandthe exhaustfan. Undersized
openingswillcauseairtobedrawnintotheroomthroughthewater
heatersventsystemcausingpoorcombustion.Sooting,serious
damagetothewaterheaterandtheriskoffireorexplosionmay
result.Itcanalsocreateariskofasphyxiation.
LOUVERS AND GRILLES
Thefreeareasofthefreshairopeningsintheinstructionsthatfollowdonot
takeintoaccountthepresenceoflouvers,grillesorscreensintheopenings.
Therequiredsizeofopeningsforcombustion,ventilationanddilution
airshallbebasedonthe“netfreearea”ofeachopening.Wherethe
freeareathroughadesignoflouverorgrilleorscreenisknown,itshall
beusedincalculatingthesizeofopeningrequiredtoprovidethefree
areaspecied.Wherethelouverandgrilledesignandfreeareaarenot
known,itshallbeassumedthatwoodlouverswillhave25%freearea
andmetallouversandgrilleswillhave75%freearea.Nonmotorized
louversandgrillesshallbexedintheopenposition.
FRESH AIR OPENINGS FOR CONFINED SPACES
The following instructions shall be used to calculate the size,
number and placement of openings providing fresh air for
combustion, ventilation and dilution in confined spaces. The
illustrationsshowninthissectionofthemanualareareference
for the openings that provide fresh air into confined spaces
only.Do not refer to these illustrations for the purpose of vent
installation. See Venting Installation on page 14 for complete
ventinginstallationinstructions.
OUTDOOR AIR THROUGH TWO OPENINGS
background
14
OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS
FIGURE 10.
Theconnedspaceshallbeprovidedwithtwopermanenthorizontal
ducts, one commencing within 12 inches (300 mm) of the top and
one commencing within 12 inches (300 mm) of the bottom of the
enclosure.Thehorizontalductsshallcommunicatedirectlywiththe
outdoors.SeeFigure10.
Eachductopeningshallhaveaminimumfreeareaof1squareinch
per2,000Btu/hr(1100mm2perkW)oftheaggregateinputratingof
allappliancesinstalledintheenclosure.
Whenductsareused,theyshallbeofthesamecrosssectionalarea
asthefreeareaoftheopeningstowhichtheyconnect.Theminimum
dimensionofrectangularairductsshallbenotlessthan3inches.
OUTDOOR AIR THROUGH TWO VERTICAL DUCTS
The illustrations shown in this section of the manual are a
reference for the openings that provide fresh air into conned
spacesonly.
DO NOT refer to these illustrations for the purpose of vent
installation. See Venting Installation on page 14 for complete
ventinginstallationinstructions.
FIGURE 11.
The conned space shall be provided with two permanent vertical
ducts, one commencing within 12 inches (300 mm) of the top and
one commencing within 12 inches (300 mm) of the bottom of the
enclosure. The vertical ducts shall communicate directly with the
outdoors.SeeFigure11.
Eachductopeningshallhaveaminimumfreeareaof1squareinch
per4,000Btu/hr(550mm2perkW)oftheaggregateinputratingof
allappliancesinstalledintheenclosure.
Whenductsareused,theyshallbeofthesamecrosssectionalarea
asthefreeareaoftheopeningstowhichtheyconnect.Theminimum
dimensionofrectangularairductsshallbenotlessthan3inches.
AIR FROM OTHER INDOOR SPACES
FIGURE 12.
Theconnedspaceshallbeprovidedwithtwopermanentopenings,
one commencing within 12 inches (300 mm) of the top and one
commencingwithin12inches(300mm)ofthebottomoftheenclosure.
SeeFigure12.
Eachopeningshallcommunicatedirectlywithanadditionalroom(s)
ofsufcientvolumesothatthecombinedvolumeofallspacesmeets
thecriteriaforanUnconnedSpace.
Eachopeningshallhaveaminimumfreeareaof1squareinchper
1,000Btu/hr(2200mm2perkW)oftheaggregateinputratingofall
appliancesinstalledintheenclosure.Eachopeningshallnotbeless
than100squareinches(645cm2).
VENTING
background
15
If the water heater is being installed as a replacement for an
existingheaterinpre-existingventing,athoroughinspectionof
existingventingsystemmustbeperformedpriortoanyinstallation
work.
VENT DAMPERS - Any vent damper, whether it is operated
thermallyorother wisemustberemovedifitsuseinhibitsproper
draftingofthewaterheater.
Thermally OperatedVent Dampers:thisgas-firedwater heater
has a thermal efficiency at or above 80% which may produce
a relatively low flue gas temperature. Such temperatures may
not be high enough to properly open thermally operated vent
dampers.Thiswouldcausespillageofthefluegasesandmay
cause carbon monoxide poisoning. Vent dampers must bear
evidenceofcertificationascomplyingwiththecurrenteditionof
th eA m er i c a n N a t io n a l S t an d a r d A N S I Z 21. 6 6C G A 6 .14(c o ve r i ng
electrically and mechanically actuated vent dampers). Before
installation of any vent damper,consultthe local gas utilityfor
furtherinformation.
Toinsurep r o p erve ntin goft h i s g a s - f i r e dwat e rheater, t h ec o r r e c t
ventpipediametermustbeutilized.Anyadditionsordeletions
ofothergasappliancesonacommonventwiththiswaterheater
mayadverselyaffecttheoperationofthewaterheater.Consult
yourgassupplierifanysuchchangesareplanned.
Forproperventingincertaininstallations,alargerdiametervent
pipemaybenecessary.Consultyourgassuppliertoaidyouin
determiningtheproperventingforyourwaterheaterfromthevent
tablesinthecurrenteditionoftheNationalFuelF󵐡l
background
16
GAS PIPING
Contact your local gas service company to ensure that adequate
gasservice is available and to review applicable installation codes
foryourarea.
SizethemaingaslineinaccordancewithTable3.Theguresshown
areforstraightlengthsofpipeat0.5in.W.C.pressuredrop,whichis
considerednormalforlowpressuresystems.Note:Fittingssuchas
elbows,teesandline regulatorswilladdtothepipepressure drop.
AlsorefertothecurrenteditionsoftheNationalFuelGasCode(NFPA
54)orNaturalGasandPropaneInstallationCode(CAN/CSAB149.1).
Makesuregassuppliedissametypelistedonmodelratingplate.The
inletgaspressuremustnotexceed14inchwatercolumn(2.6kPa)
fornaturalandpropane(L.P.)gas.Theminimuminletgaspressure
shownonratingplateisthatwhichwillpermitringatratedinput.
Ifthegascontrolvalveissubjectedtopressuresexceeding1/2pound
persquareinch(3.5kPa),thedamagetothegascontrolvalvecould
resultinareorexplosionfromleakinggas.
Ifthemaingaslineshut-offservingallgasappliancesisused,also
turn“off”thegasat each appliance. Leave allgas appliances shut
“off”untilthewaterheaterinstallationiscomplete.
Agaslineofsufcientsizemustberuntothewaterheater.Consult
thecurrenteditionofNationalFuelGasCodeANSIZ223.1/NFPA54
ortheNaturalGasandPropaneInstallationCodeCAN/CSAB149.1
andyourgassupplierconcerningpipesize.
Theremustbe:
• A readily accessible manual shut off valve in the gas supply line
servingthewaterheater,and
• Asedimenttrapaheadofthegascontrolvalvetohelppreventdirt
andforeignmaterialsfromenteringthegascontrolvalve.
• Aexiblegasconnectororagroundjointunionbetweentheshut
offvalveandcontrolvalvetopermitservicingoftheunit.
Besuretocheckallthegaspipingforleaksbeforelightingthewater
heater.Useasoapywatersolution,notamatchoropename.Rinse
offsoapysolutionandwipedry.
The minimum inlet gas pressure shown on the rating plate is that
whichwillpermitringattheratedinput.
TABLE 3. GAS SUPPLY LINE SIZES (IN INCHES)*
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET PER HOUR
background
17
SEDIMENT TRAPS
Asedimenttrapshallbeinstalledasclosetotheinletofthewater
heateraspracticalatthetimeof water heater installation.The
sediment trap shall be either atee fitting with a capped nipple
inthe bottom outlet orother device recognized as an effective
sediment trap. If a tee fitting is used, it shall be installed in
conformance with one of the methods of installation shown in
theFigures15and16.
Contaminantsinthegaslinesmaycauseimproperoperationof
thegascontrolvalvethatmayre sultinf ireorexplo si on.Before
attachingthegaslinebesurethatallgaspipeiscleanonthe
in s i de.Tot rapa ny dir torf o r eignmate r i ali ntheg ass upplylin e,
asedimenttrapmustbeincorporatedinthepiping.Thesediment
trapmustbereadilyaccessible.Installinaccordancewiththe
“GasPiping”section.RefertothecurrenteditionoftheNational
FuelGasCode,ANSIZ223.1/NFPA54ortheNaturalGasand
PropaneInstallationCodeCAN/CSAB149.1.
background
18
FLAMMABLE
WARNING:
If you do not follow these instructions exactly, a
fire or explosion may result causing property damage, personal
injury or loss of life.
BEFORE LIGHTING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES
A.
C.
D.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
LIGHTING INSTRUCTIONS
TOP KNOB
FIGURE 'A'
"OFF" POSITION
OFF
ON
PILOT
background
19
START UP CONDITIONS
DRAFT HOOD OPERATION
Check draft hood operation by performing a worst case
depressurization of the building. With all doors and windows
closed, and with all air handling equipment and exhaust fans
operating such as furnaces, clothes dryers, range hoods and
bathroomfans,amatchameshouldstillbedrawnintothedraft
hoodofthewaterheaterwithitsburnerring.Iftheameisnot
drawn toward the draft hood, shut off water heater and make
necessaryairsupplychangestocorrect.
CONDENSATION
Whenever the water heater is filled with cold water, some
condensatewillformwhiletheburnerison.Awaterheatermay
Shortrepeatedheatingcyclescausedbysmallhotwaterusescan
cause temperatures at the point of use to exceed the thermostat
settingby up to 30°F(16.7°C). If you experiencethis type of use
you should consider using lower temperature settings to reduce
scaldhazards.
Any water heater’s intended purpose is to heat water. Hot water
isneededforcleansing,cleaning,andsanitizing(bodies,dishes,
clothing). Untempered hot water can present a scald hazard.
Dependingonthetimeelement,andthepeopleinvolved(adults,
children, elderly, inrm, etc.) scalding may occur at different
temperatures.
HOTTERWATERCANSCALD:Waterheatersareintendedtoproduce
hot water. Waterheated to a temperature which will satisfy space
heating,clothes washing,dishwashing,andothersanitizingneeds
canscaldandpermanently injure you upon contact. Somepeople
aremorelikelytobepermanentlyinjured byhotwaterthanothers.
Theseincludetheelderly,children,theinrm,orphysically/mentally
handicapped.Ifanyoneusinghotwaterinyourhometsintooneof
thesegroupsorifthereisalocalcodeorstatelawrequiringacertain
temperaturewateratthehotwatertap,thenyoumusttakespecial
precautions. In addition to using the lowest possible temperature
settingthatsatisesyourhotwaterneeds,ameanssuchasamixing
valve should be used at the hot water taps used by these people or
atthewaterheater.Mixingvalvesareavailableatplumbingsupplyor
hardwarestores,seeFigure6.Followmanufacturer’sinstructionsfor
installationofthevalves.Beforechangingthefactorysettingonthe
thermostat,readthe“TemperatureRegulation”sectioninthismanual,
seeFigures17and18.
TEMPERATURE REGULATION
FOR YOUR INFORMATION
appeartobeleakingwheninfactthewateriscondensation.This
usuallyhappenswhen:
a.Anewwaterheaterislledwithcoldwaterforthersttime.
b.Bur n i n ggaspr o d u c e s w a t e r vap o r i n w a t e r h e a t e r s,pa r t i c u l a r l y
highefciencymodelswhereuetemperaturesarelower.
c.Largeamountsofhotwaterareusedinashorttimeandthe
rellwaterinthetankisverycold.
Moisturefromtheproductsofcombustioncondenseonthecooler
tank surfaces and form drops of water which may fall onto the
burnerorotherhotsurfacestoproducea“sizzling”or“frying”noise.
Excessive condensation can cause pilot outage due to water
runningdownthefluetubeontothemainburnerandputtingout
the pilot.
Neverallowsmallchildrentouseahotwatertap,ortodrawtheethe=p󷒡󻾡󽾣”
background
20
CHECKING GAS INPUT
Withthisheaterinoperation,determinewhetheritisreceivingthe
fullratedinput of gas.This may be donebytimingthegasmeter
andmeasuringgaspressurewithagaugeormanometer.Whenthe
heaterisoperatingatfullcapacity(fullgasinput)itshouldconsume
approximately1cubicfootofgasinthetimeshowninTable5.
TABLE 5. INPUT CHECK TIME REQUIRED
TO CONSUME 1 CU. FT. OF GAS
Model Type of Gas
BTU Per
Cu. Ft.
Approx. Time Required To
Consume 1 Cu. Ft. of Gas
BL-80
BL-100
Natural 1050 50.3sec.
Use this formula to “clock” the meter. Be sure that other gas
consumingappliancesarenotoperatingduringthisinterval.
3,600XH=Btu/Hr
T
T=Timeinsecondsneededtoburnonecubicfootofgas.
H=HeatingvalueofgasinBtu’spercubicfootofgas.
Btu/Hr=Actualheaterinputrate.
Example:
T=50.3seconds/ft
3
H=1,050Btu/ft
3
(naturalgas)
Btu/Hr=?
3,600X1,050=75,100Btu/Hr(22.0kW)
50.3
Comparetheactual input ratetothatgiven on the heater’srating
plate.Intheexample,theBL-100’sfullinputrateshouldbe75,100
Btu/Hrfornaturalgas.
Because of the suddenness and amount of water, condensation
watermaybediagnosedasa“tankleak”.Afterthewaterinthetank
warmsup(a0󾺠M
background
21
PERIODIC MAINTENANCE
VENTING SYSTEM INSPECTION
Atleastonceayearavisualinspectionshouldbemadeoftheventing
system.Youshouldlookfor:
1. Obstructions which could cause improper venting. The
combustionandventilationairowmustnotbeobstructed.
2. Damage or deterioration which could cause improper venting
orleakageofcombustionproducts.
3. Rustedakesaroundtopofwaterheater.
Be sure the vent piping is properly connected to prevent escape
ofdangerousuegaseswhichcouldcausedeadlyasphyxiation.
Obstructions and deteriorated vent systems may present serious
health risk or asphyxiation.
Chemical vapor corrosion of the ue and vent system may occur
if air for combustion contains certain chemical vapors. Spray can
propellants, cleaning solvents, refrigerator and air conditioner
refrigerants,swimmingpoolchemicals,calciumandsodiumchloride,
waxes,bleachandprocesschemicalsaretypicalcompoundswhich
arepotentiallycorrosive.
Ifafterinspectionofventsystemyoufoundsootingordeterioration,
somethingiswrong.Callthelocalgasutilitytocorrectproblemand
cleanorreplacetheueandventingbeforeresumingoperationof
water heater.
BURNER INSPECTION
Flood damage to a water heater may not be readily visible or
immediatelydetectable.However,overa period oftimeaooded
water heater will create dangerous conditions which can cause
DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
Contactaqualiedinstallerorservicetechniciantoreplaceaooded
waterheater.Donotattempttorepairtheunit!Itmustbereplaced!
Atleastonceayearavisualinspectionshouldbemadeofthemain
burnerandpilotburner,seeFigure19.Inspectburneramesthrough
viewport.Flamesshouldbeverysmallwithabluehazeandsmall
amountsofyellowororangeattheedges.Afterseveralminutesof
operationtheburnerscreenmayglowred.
You should ]
background
22
WhencheckingtheTemperature-PressureReliefValveoperation,
makesurethat(1)nooneisinfrontoforaroundtheoutletofthe
Temperature-PressureReliefValvedischargeline,and(2)thatthe
waterdischargewillnotcauseanypropertydamage,asthewater
maybeextremelyhot.Usecarewhenoperatingvalveasthevalve
maybehot.
Tocheckthereliefvalve,lifttheleverattheendofvalveseveraltimes,
seeFigure21.Thevalveshouldseatproperlyandoperatefreely.
Ifaftermanuallyoperatingthevalve,itfailstocompletelyresetand
continuesto release water,immediately close thecoldwaterinlet
to the water heaterand drain thewater heater, see DrainingAnd
Flushingonpage24.ReplacetheTemperature-PressureReliefValve
with a properly rated/sized new one, see Temperature-Pressure
ReliefValveonpage11forinstructionsonreplacement.
DISCHARGE PIPE
TEMPERATURE-PRESSURE
RELIEF VALVE
FIGURE 21.
IftheTemperature-PressureReliefValveonthewaterheaterweeps
ordischargesperiodically,thismaybeduetothermalexpansion.
NOTE:Excessivewaterpressureisthemostcommoncauseof
Temperature-Pressure Relief Valve leakage. Excessive water
systempressure is most oftencaused by “thermal expansion”
ina“closedsystem.”SeeClosedWaterSystemsandThermal
Expansiononpage11.TheTemperature-PressureReliefValve
isnotintendedfortheconstantreliefofthermalexpansion.
Temperature-Pressure Relief Valve leakage due to pressure
build up in a closed system that does not have a thermal
expansion tank installed is not covered under the limited
warranty. Thermal expansion tanks must be installed on all
closedwatersystems.
DO NOT PLUG THE TEMPERATURE-PRESSURE RELIEF
VALVE OPENING. THIS CAN CAUSE PROPERTY DAMAGE,
SERIOUS INJURY OR DEATH.
Explosion Hazard
Temperature-Pressure Relief Valve
must comply with ANSI Z21.22-
CSA 4.4 and ASME code.
Properly sized temperature-
pressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.
RECOMMENDED PROCEDURE FOR PERIODIC
REMOVAL OF LIME DEPOSITS FROM TANK TYPE
COMMERCIAL WATER HEATERS
Theamountofcalciumcarbonate(lime)releasedfromwateris
indirectproportiontowatertemperatureandusage,seechart.
Thehigherthewatertemperatureorwaterusage,themorelime
depositsaredroppedoutofthewater.Thisisthelimescalewhich
formsinpipes,heatersandoncookingutensils.
INSTALLEDINSUITABLEAREA:Toinsuresufficientventilation
and combustion air supply, proper clearances from the water
heater must be maintained. See Facts to ConsiderAboutThe
Location section. Combustible materials such as clothing,
cleaningmaterials,orflammableliquids,etc.must
background
23
Limeaccumulationnotonly reduces the life of the equipment but
alsoreducesefciencyoftheheaterandincreasesfuelconsumption.
The usage of water softening equipment greatly reduces the
hardness of the water. However, this equipment does not always
removeallofthehardness(lime).Forthisreasonitisrecommended
thataregularschedulefordelimingbemaintained.
Thetimebetweencleaningwillvaryfromweekstomonthsdepending
uponwaterconditionsandusage.
Thedepthoflimebuildupshouldbemeasuredperiodically.Heaters
equipped with cleanouts will have about 2” of lime buildup when
theleveloflimehasreachedthebottomofthecleanoutopening.A
schedulefordelimingshouldthenbesetup,basedontheamount
oftimeitwouldtakefora1”buildupoflime.Itisrecommendedthat
thewaterheaterinitiallybeinspectedafter6months.
Example1:
Initial inspection after 6 months shows 1/2” of lime accumulation.
Therefore,theheatershouldbedelimedonceayear.
Example2:
Initialinspectionafter6monthsshows2”oflimeaccumulation.
Therefore,theheatershouldbedelimedevery3months.
FIGURE 22.
DELIMING SOLVENTS
UN•LIME is recommended for deliming. UN•LIME is a patented
foodgradeacidwhichissafetohandleanddoesnotcreatethe
harmfulfumeswhichareassociatedwithotherproducts.
UN•LIMEmaybeobtainedfromyourdealer,distributororwater
heatermanufacturer.OrderPartNumber9005416105,1gallon,
packed 4 gallons per case or Part Number 9005417105, 5
galloncontainer.
NOTE:Un•LimeisnotavailableforuseinCanada.
Hydrochloric base acids are not recommended for use on glass
lined tanks.
Observehandlinginstructionsonlabelofproductbeingused.
TANK CLEANOUT PROCEDURE
Thefollowingpracticeswillensurelongerlifeandenabletheunitto
operateatitsdesignedefciency:
1. Onceamonththeheatershouldbeushed.Openthedrainvalve
andallowtwogallonsofwatertodrainfromtheheater.Inletwater
valveshouldremainopentomaintainpressureintank.
2. Acleanoutopeningisprovidedforperiodiccleaningofthetank.
Gasmustbeshutoffandheaterdrainedbeforeopeningcleanout.
Tocleanheaterthroughcleanoutopening,proceedasfollows:
1. Drain heater.
background
24
4. Putcapwithmaleadapterbackonthecontainerandslide3/4”
hoseover endofmaleadapter andfastenin placeusinghose
clampprovided.
DELIME USING FLO-JUG METHOD
5. Slidethehoseclampoverendofhoseandslidehoseoverthe
male adapter in the water heater drain opening and secure in
placeusinghoseclamp.
6. Liftcontainertothe“Pour”Positionbeingcarefultokeepthevent
in the handle above the liquid level and pour the UN•LIME into
the heater.
7. Lowercontainer,youmayhavetoplacethecontaineronitsempty
cartontopreventtheUN•LIMEfromowingbackintothecontainer.
8. LetUN•LIMEremainintheheaterfor5minutesandthenlower
thecontainertothe“Drain”Position.
9. Deliming activity is indicated by foaming on the surface of the
UN•LIME.Ifthereisdelimingactivity,repeatsteps6thru8.
Normally,lime removal will be completed within onehour. Severe
build-upoflimemaytakelongerthananhourtocompletedescaling.
Note:TocheckUN•LIMEforcontinueduse,placesomescaleorwhite
chalkinaglasswithasmallamountofUN•LIME.Ifthematerialis
vigorouslydissolvedbythe UN•LIME, it canbereused;ifnot,the
UN•LIMEshouldbereplaced.
Ifthetemperature-pressurereliefvalveontheapplianceweepsor
dischargesperiodically,thismaybeduetothermalexpansion.You
mayhaveacheckvalveinstalledinthewaterlineorawatermeter
with a check valve. Consult your local water supplier or service
technicianfor further information. Do not plug the temperature-
pressurereliefvalve.
DRAINING AND FLUSHING
It is recommended that the water heater storage tank be
drained and ushed every 6 months to reduce sediment
buildup.Thewaterheatershouldbedrainedifbeingshutdown
during freezing temperatures. See Installation Considerations
inthismanualforthelocationofthewaterheatercomponents
describedbelow.
background
background
26
TROUBLESHOOTING GUIDELINES
Theseguidelinesshouldbeutilizedbyaqualiedserviceagent.
Problem Cause Solution
background
27
WATER PIPING DIAGRAMS
October 2009 | Printed in U.S.A. | © A. O. Smith For Technical Information and Automated Fax Service, call 800-527-1953 or visit www.hotwater.com. AOSCG61130 | PAGE 1 of 1
A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heaters operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
SINGLE FLUE - (1 UNIT)
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
FULL PORT BALL VALV
E
TEMPERATURE GAGE
WATER FLOW SWITCH
CHECK VALVE
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
background
28
October 2009 | Printed in U.S.A. | © A. O. Smith For Technical Information and Automated Fax Service, call 800-527-1953 or visit ww w.hotwater.com. AOSCG61140 | PAGE 1 of 1
A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater ’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
SINGLE FLUE - (1 UNIT) WITH VERTICAL STORAGE TANK
background
29
October 2009 | Printed in U.S.A. | © A. O. Smith For Technical Information and Automated Fax Service, call 800-527-1953 or visit ww w.hotwater.com. AOSCG61150 | PAGE 1 of 1
A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater ’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
SINGLE FLUE - (1 UNIT) WITH HORIZONTAL STORAGE TANK
background
30
October 2009 | Printed in U.S.A. | © A. O. Smith For Technical Information and Automated Fax Service, call 800-527-1953 or visit www.hotwater.com. AOSCG61160 | PAGE 1 of 1
A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
SINGLE FLUE - (1 UNIT) WITH MIXING VALVE TWO TEMPERATURE
background
31
October 2009 | Printed in U.S.A. | © A. O. Smith For Technical Information and Automated Fax Service, call 800-527-1953 or visit ww w.hotwater.com. AOSCG61170 | PAGE 1 of 1
A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater ’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
SINGLE FLUE - (2 UNITS)
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
FULL PORT BALL VALV
E
TEMPERATURE GAGE
WATER FLOW SWITCH
CHECK VALVE
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
background
32
SINGLE FLUE
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
FULL PORT BALL VALV
TEMPERATURE GAGE
WATER FLOW SWITCH
CHECK VALVE
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
background
33
NOTES
background
34
NOTES
background
35
LIMITED WARRANTY
EFFECTIVE
For 3 Years, in t he event of a tank leak, we will repair or, at our
discret ion, replace t he defe cti ve wat er heat er.
For 1 Year, in t he e vent o f part f ailure, we will repair or, at our
discret ion, replac e t he def ecti ve part .
We warrant this product against def ects in materials or
workmans hip as described in t his document i f installed wit hin
the United Sta tes or Canada and prov ided t he product remains
at its original plac e o f installat ion.
Warranty co v erage begins the date of installation O R the dat e of
background
36
500 Tennessee Waltz Pkwy., Ashland City, TN 37015
TechnicalSupport:800-527-1953•Parts:800-433-2545
www.hotwater.com
Copyright©2014A.O.SmithCorporation,Allrightsreserved.

Specifications

AO Smith BL-80 100 Questions and Answers