Patents Pending
Siemens Industry, Inc.
Norcross, GA 30092 U.S.A.
Assembled in Mexico
HP Ratings
Terminal & Wire Information
Accessories
Description Lug Size Wire Range
12
Wire Tightening Torque
Line / Load Lugs 14 – 2 AWG 14 – 6 AWG 35 lb-in. 14-10 AWG / 40 lb-in. 8 AWG /
45 lb-in. 6 AWG
Neutral Lugs 14 – 4 AWG 14 – 6 AWG 20 lb-in. 14-10 AWG / 25 lb-in. 8 AWG /
35 lb-in. 6 AWG
USE 75°C COPPER WIRE ONLY
Fuse and Short Circuit Information
This switch is suitable for use on a circuit capable of delivering not more than 100,000
amperes, RMS symmetrical, 240 volts maximum when protected by class J, R or T fuses rated
60 amperes maximum.
Danger! Unless Class J, R or T fuses are used to protect this switch, it may present a risk
of re and injury to persons if installed on circuits capable of delivering more than 10,000
amperes, RMS symmetrical.
This switch is suitable for use on a circuit capable of delivering not more than 10,000 amperes,
RMS symmetrical, 240 volts maximum, when protected by Class K fuses, Class H fuses or a
UL Listed Circuit Breaker rated for 10,000 amperes, RMS symmetrical, 240 volts maximum.
This switch is suitable for use on a circuit capable of delivering not more than 10,000 amperes,
250 volts DC maximum, when protected by fuses marked with an interrupting rating of 10,000
amperes, 250 volts DC.
Danger! Unless fuses marked for an interrupting rating of 10,000 amperes at 250 volts DC
are used to protect this switch, this switch may present a risk of re and injury to persons if
installed on circuits capable of delivering more than 10,000 amperes.
Type VBII
240 Volts AC (V ) Maximum
250 Volts AC (V ) Maximum
Cat. No.
Non-Fusible General Duty Safety Switch
60 Amps Maximum
Type
s
Pc. No. R500587T00
Cat. No. LNF222RA
3R Rainproof
240VAC
1Ø
10
Max. HP
240VAC
3
3Ø
15
250VDC
10
Ground Lug Kit: HG61234
Neutral Kit: HN22A
3
Suitable for 3-Phase, 3-Wire, Grounded B-Phase Systems
when neutral kit HN22A is installed.
12
Wire range per NEC wire-bending requirements.
For questions on this device please call 1-800-241-4453.
http://www.usa.siemens.com/powerdistribution
Suitable for use as Service Equipment when used with ground bar kit HG61234 on 3 phase,
3 wire systems or when used with HN22A neutral kit on 1 phase, 3 wire or 3 phase, 4 wire
systems.