Service Instructions
GOODMAN® BRAND GRVM97/GDVM97 & AMANA® BRAND ARVM97/ADVM97
97% MODULATING GAS FURNACES WITH VARIABLE-SPEED ECM MOTOR
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
®
Pride and workmanship go into every product to provide
our customers with quality products. It is possible,
however, that during its lifetime a product may require
service. Products should be serviced only by a qualied
service technician who is familiar with the safety
procedures required in the repair and who is equipped with
the proper tools, parts, testing instruments and the
appropriate service manual. REVIEW ALL SERVICE
INFORMATION IN THE APPROPRIATE SERVICE
MANUAL BEFORE BEGINNING REPAIRS.
ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL,
ADJUST, SERVICE, MAINTENANCE OR REPAIR
(HEREINAFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN
THIS MANUAL SHOULD SERVICE THE EQUIPMENT.
THIS EQUIPMENT IS NOT INTENDED FOR USE BY
PERSONS (INCLUDING CHILDREN) WITH REDUCED
PHYSICAL, SENSORY OR MENTAL CAPABILITIES, OR LACK
OF EXPERIENCE AND KNOWLEDGE, UNLESS THEY HAVE
BEEN GIVEN SUPERVISION OR INSTRUCTION CONCERNING
USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR
THEIR SAFETY.
CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT
THEY DO NOT PLAY WITH THE EQUIPMENT.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR
ANY INJURY OR PROPERTY DAMAGE ARISING FROM
IMPROPER SUPERVISION, SERVICE OR SERVICE
PROCEDURES. IF YOU SERVICE THIS UNIT, YOU ASSUME
RESPONSIBILITY FOR ANY INJURY OR PROPERTY
DAMAGE WHICH MAY RESULT. IN ADDITION, IN
JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES
TO SERVICE THE EQUIPMENT SPECIFIED IN THIS
MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE
THE EQUIPMENT. IMPROPER SUPERVISION, INSTALLATION,
ADJUSTMENT, SERVICING, MAINTENANCE OR REPAIR OF
THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR
ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR
THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT
PROPER SUPERVISION OR TRAINING MAY RESULT IN
PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
WARNING
WARNING
DO NOT BYPASS SAFETY DEVICES
TABLE OF CONTENTS
Important Information .................................................................... 2
Product Identicatication ............................................................... 3
System Operation .......................................................................... 4
R-32 Information .......................................................................... 15
Scheduled Maintenance .............................................................. 20
Servicing ...................................................................................... 22
Checking Voltage......................................................................... 23
Checking Wiring .......................................................................... 23
Checking Thermostat, Wiring ...................................................... 23
Checking Transformer and Control Circuit .................................. 24
Checking Duct Static ................................................................... 27
Checking Temperature Rise ........................................................ 27
Checking Primary Limit Control ................................................... 28
Checking Auxiliary Limit Control .................................................. 29
Checking Flame Rollout Control .................................................. 29
Inducer Draft Blower Motor.......................................................... 30
Checking Modulating Gas Valve .................................................. 30
Checking Main Burners ............................................................... 31
Checking Orices ........................................................................ 31
Checking Gas Pressure............................................................... 31
Checking Hot Surface.................................................................. 33
Checking For Flashback .............................................................. 34
Checking Pressure Control.......................................................... 34
High Altitude Application (USA) ................................................... 34
Checking For Delayed Ignition .................................................... 35
Checking Integrated Ignition Control Boards ............................... 35
Checking Flame Sensor .............................................................. 36
Troubleshooting ........................................................................... 40
Wiring Diagram ............................................................................ 53
WARNING
THIS FURNACE MAY BE PAIRED WITH A COOLING UNIT THAT
USES R-32 REFRIGERANT. IF THE REFRIGERATION UNIT PAIRED
WITH THIS FURNACE DOES NOT USE R-32, THE R-32 FUNCTION
IN THE FURNACE CONTROL BOARD NEEDS TO BE TURNED OFF.
PLEASE SEE THE ELECTRICAL AND THE R-32 SECTIONS FOR
MORE DETAILS.
REFRIGERANT SYSTEMS OTHER THAN 410A OR R32 MAY RE-
QUIRE AN ADDITIONAL MITIGATION CONTROL BOARD. REFER
TO THE INSTALLATION MANUAL OF THE INDOOR EVAPORATOR
COIL TO DETERMINE INSTALLATION REQUIREMENTS FOR THAT
SUPPLIER’S REFRIGERANT DETECTION SYSTEM.

2
RECOGNIZE SAFETY SYMBOLS, WORDS AND
LABELS
IMPORTANT INFORMATION
OUTSIDE THE U.S., call 1-713-861-2500.
(Not a technical assistance line for dealers.) Your telephone company will bill you for the call.
WARNING
HIGH VOLTAGE
DISCONNECT ALL POWER BEFORE SERVICING
OR INSTALLING THIS UNIT. MULTIPLE POWER
SOURCES MAY BE PRESENT. FAILURE TO DO SO
MAY CAUSE PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
WARNING
THIS UNIT SHOULD NOT BE CONNECTED TO, OR USED IN
CONJUNCTION WITH, ANY DEVICES THAT ARE NOT DESIGN
CERTIFIED FOR USE WITH THIS UNIT OR HAVE NOT BEEN
TESTED AND APPROVED BY THE MANUFACTURER. SERIOUS
PROPERTY DAMAGE OR PERSONAL INJURY, REDUCED UNIT
PERFORMANCE AND/OR HAZARDOUS CONDITIONS MAY RESULT
FROM THE USE OF DEVICES THAT HAVE NOT BEEN APPROVED
OR CERTIFIED BY THE MANUFACTURER.
WARNING
TO PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL
INJURY, OR DEATH. DO NOT STORE COMBUSTIBLE MATERIALS
OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR
VAPORS IN THE VICINITY OF THIS APPLIANCE.
B10259-216
CO can cause serious illness including permanent brain
damage or death.
Advertencia especial para la instalación de calentadores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
B10259-216
El monóxido de carbono puede causar enfermedades severas
como daño cerebral permanente ó muerte.
Las emisiones de monóxido de carbono pueden circular a través
del aparato cuando se opera en cualquier modo.
B10259-216
RISQUE D'EMPOISONNEMENT AU
MONOXYDE DE CARBONE
Cette ventilation est nécessaire pour éviter le danger d'intoxication
au CO pouvant survenir si un appareil produisant du monoxyde
de carbone continue de fonctionner au sein de la zone confinée.

PRODUCT IDENTIFICATION
3
To locate an authorized servicer, please consult your tele-
phone book or the dealer from whom you purchased this
product. For further assistance, please contact:
CONSUMER INFORMATION LINE
AMANA
®
BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at: hac.consumer.a[email protected]
fax us at: (731) 856-1821
(Not a technical assistance line for dealers.)
CONSUMER INFORMATION LINE
GOODMAN
®
BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at:
fax us at: (731) 856-1821
(Not a technical assistance line for dealers.)
Outside the U.S., call 1-713-861-2500.
(Not a technical assistance line for dealers.) Your tele-
phone company will bill you for the call.
A R V M 97 060 3 B N A A
12345,67,8,9 10 11 12 13 14
Brand
G - Goodman
A - Amana
Configuration
M - Upflow/Horizontal R410A
C - Downflow/Horizontal R410A
R- Upflow/ Horizontal R32
D - Downflow/Horizontal R32
MOTOR
V - Variable-Speed ECM / Communicating
9 - Multi-Speed ECM (9 taps) / Non-Communicating
Gas Valve
T - Two Stage
M - Modulating
AFUE
80 - 80% AFUE
92 - 92% AFUE
96 - 96% AFUE
97 - 97% AFUE
MBTU/h
030 - 30,000 BTU/h 080 - 80,000 BTU/h
040 - 40,000 BTU/h 100 - 100,000 BTU/h
060 - 60,000 BTU/h 120 - 120,000 BTU/h
D - 24.5"
Maximum CFM
3 - 1200 CFM
4 - 1600 CFM
5 - 2000 CFM
C - 21"
NOx
N - Natural Gas ≥ 40 NG/J NOx
N - Low NOx (90%+) ≤ 40 NG/J NOx
X - Low NOx (80%) ≤ 40 NG/J NOx
U - Ultra Low NOx ≤ 14 NG/J NOx
Cabinet Width
A - 14"
B - 17.5"
B - 1st Revision
Minor Revision
A - Initial Release
B - 1st Revision
Major Revision
A - Initial Release
NOMENCLATURE

SYSTEM OPERATION
4
Control System – General Information
The furnace contains internal logic to control equipment stag-
ing. An adjustable target runtime is available (range from 1 to
240 minutes) and set through the appropriate system menu.
The system will constantly be adjusting staging in an eort
to satisfy the thermostat call for cooling (Y only) or heating
(W Only) as close to the set target runtime as possible. See
information below for setting options.
Comfort Setting Menu (CFS): There are 6 options
available in the Comfort Setting Menu which impacts both
the System Target Runtime and Dual Fuel Operation. Dual
Fuel operation adjustments only apply if a communicating
heat pump is installed Comfort Setting Options 1 – 5 have
set values for the System Target Runtime and option
6 enables additional menus to customize all comfort
settings. See list below for the System Target Run times
associated with the rst 5 Comfort Settings. These rst
5 options are setup to help satisfy the thermostat slower
or faster based on the selection where option 1, with a
10 minute Target Runtime, is attempting to satisfy much
faster than option 5, with a 30 minute Target Runtime.
System Target Runtime:
Comfort Setting Option 1) 10 Minute System Target
Runtime
Comfort Setting Option 2) 15 Minute System Target
Runtime
Comfort Setting Option 3) 20 Minute System Target
Runtime
Comfort Setting Option 4) 25 Minute System Target
Runtime
Comfort Setting Option 5) 30 Minute System Target
Runtime
Dual Fuel Adjustment: This system will automatically
determine if the heat pump is capable of satisfying the
thermostat in the selected System Target Runtime. If the
heat pump is unable to satisfy in the selected time, dual
fuel settings will determine how many attempts should
be given to the heat pump before temporarily locking it
out and using the furnace. These dual fuel settings also
determine at what time the system should remove the
temporary heat pump lockout and run the heat pump again.
There are four adjustable items associated with Dual Fuel
control. In the same way as the System Target Time, each
of these items have defaulted values for Comfort Settings
1 – 5. Only when Comfort Setting 6 is selected will each
item be available for full adjustment.
1. Stage Up Percent (7 segment menu SUP): This is
a value that determines how far past the target
runtime the system should continue running the
heat pump before transitioning to the furnace. For
example, assume this menu was set to 20% with
a target runtime of 20 minutes. If the thermostat
did not remove the heating call after 20 minutes,
the system would allow for an additional 20%
heat pump run (20% of the 20 minute target is an
additional 4 minutes). In this case, the system
would transition to gas heat after 24 minutes if
the thermostat call was still present. Each time
this occurs, the system records this as a strike
against the heat pump (the strike is important
when looking at the Over Target Threshold)
2. Over Target Threshold (7 segment menu Ott): If
the heat pump has consecutively transitioned to
gas heat for the selected Over Target Threshold
amount of times, meaning for this many
consecutive cycles it has been unable to satisfy
the target time by itself, then the heat pump will
be temporarily locked out and the furnace will
become the primary heat source.
3. Stage Down Percent (7 segment menu SdP): This
only applies when the heat pump is in a temporary
lockout condition. In this case, the system will
be trying to determine when the best time is to
remove the lockout and run the heat pump again.
To determine the best time to remove the heat
pump lockout the system looks at how easily the
furnace is able to satisfy the thermostat using
Low Stage Gas Heat Only. Assume this setting
is 15% and the target time is 20 minutes. If Low
Stage Gas Heat can satisfy the thermostat in less
than 17 minutes (20 minutes - 15% = 17 minutes)
then the algorithm records a strike against the
gas furnace. (this strike is important when looking
at the Under Target Threshold).
4. Under Target Threshold (7 segment menu Utt): If
the furnace is able to satisfy the thermostat using
Low Stage Gas Heat Only for the selected number
of consecutive cycles the heat pump lockout will be
temporarily removed. The heat pump will then be used
during the next cycle. If the heat pump can satisfy the
thermostat in less than the System Target Runtime
the temporary heat pump hold will be completely
removed and the heat pump will become the primary
heat source again. If it fails to do so, the strike count
against the furnace will be reset and the furnace will
remain the temporary primary heat source until the
Under Target Threshold is reached again.

SYSTEM OPERATION
5
The system will automatically make adjustments in an attempt
to satisfy the thermostat as close to this target runtime as pos-
sible. After a power cycle or mode change (cooling to heating
or heating to cooling) the system will run full capacity for the
selected mode during the rst thermostat call. Based on the
selected target runtime and how long the initial cycle takes
to satisfy the thermostat, the control algorithm will adjust the
system stage times for a 2 stage unit or the capacity demand
percentage for an inverter / modulating unit for the next cycle.
NOTE: actual run times may change depending on variations
of load throughout the day.
The following table shows the default values for all
Comfort Setting Options (1 – 5)
Comfort
Setti ng
Opti on
Target
Ti me
(Minutes)
Stage Up
Percentage
(%)
Stage Down
Percentage
(%)
Over Target
Threshhold
(Strike Count)
Under Target
Threshhold
(Strike Count)
1 10 20 20 2 10
2 15 20 20 4 8
3 20 20 20 6 6
4 25 20 20 8 4
5 30 20 20 10 2
The following table shows the ranges for each of item
when the adjustable Comfort Setting Option 6 is selected.
The table shows the minimum value, the maximum value
and the defaulted value. All items can be adjusted up or
down by increments of 1 which provides full exibility
for all items. Note: it is critical that these numbers be set
properly. If Comfort Setting option 3 is desired but a target
time of 60 is preferred, select Comfort Setting Option 6
to enable all the adjustable menus, set the Target Time
to 60 and make sure the other menus are set to match
that of Comfort Setting Option 3.
Menu Minimum Value Maximum Value Default Value
Target Time (t9t) 1 minute 240 minutes 60 minutes
Stage Up Percent (SUP) 0% 100% 20%
Stage Down Percent (SdP) 0% 100% 20%
Over Target Threshold (Ott) 1 strike 254 strikes 20 strikes
Under Target Threshold (Utt) 1 strike 254 strikes 20 strikes
CIRCULATOR BLOWER SPEED
The Airow quantity is displayed as a number on the three
7 segment displays, rounded to the nearest 100 CFM.
The display alternates airow amount and the system
operating status.
Each furnace has a “Maximum CFM” it is capable of
providing. All fan operations (Constant CFM, Cooling
Airow Proles, Low and High Stage gas heat airow,
outdoor Air Conditioner / Heat Pump Airow, etc.) are
based o of multipliers which are percentages of this
maximum CFM. Max CFM is as follows:
3 Ton Models 1400 CFM
4 Ton Models 1760 CFM
5 Ton Models 2200 CFM
Setup Furnace Airow: Adjust the Gas Heating Airow
menu (gAF) setting to the desired percentage of
maximum airow. In most cases the default gas heat
airow will provide a temperature rise near the middle of
the acceptable range. High Stage CFM can be calculated
by the following equation: CFM = Max CFM * Selected
Heating Airow Percentage.
For Communicating Outdoor Units: Main airflow
adjustment is not required. The Outdoor unit will
determine the appropriate amount of indoor airow to
request. Airow Trims can be made if desired.
For Non-Communicating outdoor units, determine the
proper airow (based o tonnage of) the outdoor unit.
Most cooling systems are designed to work with airow
between 350 and 450 CFM per ton. 400 CFM/TON is
the industry standard. Once desired airow has been
determined, see Tonnage / Airow table to identify the
Tonnage Selection that is closest to the desired airow.
This table is based on 400 CFM per ton where Airow =
(400 CFM) x (Selected Tonnage).
Example: if 1520 CFM is the desired airow the Tonnage
Selection that matches this is 3.8
Enter the Tonnage (ton) menu either by using the on
board push buttons or phone application and select
the Tonnage Selection you identied. Note: Trim is also
available if additional adjustment is required.
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
1 400
2.3 920 3.6 1440 4.9 1960
1.1 440 2.4 960 3.7 1480 5 2000
1.2 480 2.5 1000 3.8 1520 5.1 2040
1.3 520 2.6 1040 3.9 1560 5.2 2080
1.4 560 2.7 1080 4 1600 5.3 2120
1.5
600 2.8 1120 4.1 1640 5.4 2160
1.6 640 2.9 1160
4.2 1680
5.5 2200
1.7 680 3 1200 4.3 1720 5.6 2240
1.8 720 3.1 1240 4.4 1760 5.7 2280
1.9 760 3.2 1280 4.5 1800 5.8
2320
2 800 3.3 1320 4.6
1840 5.9 2360
2.1 840 3.4 1360 4.7 1880 6 2400
2.2 880 3.5 1400 4.8 1920
COOLING AIRFLOW RAMPING PROFILES
The multi-circulator blower also oers several custom ON/
OFF ramping proles. These proles may be used to enhance
cooling performance and increase comfort level. The ramping
proles are selected using the Cooling Airow Prole menu
(if push buttons are used, use the CAP menu to select the
desired prole). Refer to the bullet points below for a descrip-
tion of each ramping prole.

SYSTEM OPERATION
6
OFF
100% CFM 100% CFM
1 min
OFF
Figure 50
• provides only an OFF delay of one (1) minute at 100% of the cooling demand Profile A(1)
Figure 1
50% CFM
1/2 min
100% CFM
100% CFM
1 min
OFF
OFF
Figure 51
• ramps up to full cooling demand airflow by first stepping up to 50% of the full
demand for 30 seconds. The motor then ramps to 100% of the required airflow. A one (1)
minute OFF delay at 100% of the cooling airflow is provided.
Profile B(2)
Figure 2
100% CFM
OFF
OFF
• ramps up to 85% of the full cooling demand airflow and operates there for
approximately 7 1/2 minutes. The motor then steps up to the full demand airflow. Profile C
also has a one (1) minute 100% OFF delay.
Profile C(3)
Figure 52
Figure 3
OFF
OFF
• ramps up to 50% of the demand for 1/2 minute, then ramps to 85% of the full
cooling demand airflow and operates there for approximately 7 1/2 minutes. The motor
then steps up to the full demand airflow. Profile D has a 1/2 minute at 50% airflow OFF delay.
Profile D(4 or 5)
Figure 53
Figure 4
In general lower heating speeds will: reduce electrical con-
sumption, lower operating sound levels of the blower, and
increase the outlet air temperature delivered to the home if heat
mode is running. If cooling mode is running the same airow
adjustment will decrease the outlet air temperature delivered to
the home. The speeds available allow the blower performance
to be optimized for the particular homeowner’s needs.
LOW VOLTAGE WIRING - GENERAL INFORMA-
TION
The Furnace functions with any thermostat that can be con-
gured to provide 24VAC on Y for cooling calls and 24VAC
on W for Heating calls. Based on these simple inputs, internal
algorithms will decide how to control two stages of furnace
heat in addition to any single or multi stage outdoor heating
/ cooling operation (the algorithms will handle dual fuel multi-
stage systems as well). The thermostat must be setup to
provide only a Y call when cooling is required and only a W
call when heating is required. This is generally accomplished
by selecting single stage heat / single stage cool mode during
setup (if setup is required). Do not set thermostat to heat pump
operation as system will not operate properly.
NOTE: The only exception is if a single stage non-commu-
nicating Heat Pump is connected to the furnace. Refer to
Non-Communicating Single Stage Heat Pump diagram for
details.
Thermostat connections to the control board are R, C, G,
W, Y & Dehum. Provided the thermostat does not require a
common wire as few as two thermostat wires may be used
for heat only (R and W) or cool only (R and Y) systems. A
minimum three thermostat wires may be used for heating
and cooling systems (R, W and Y). Refer to thermostat wiring
diagrams below for your system conguration.
Low voltage connections can be made through either the right
or left side panel of the furnace. Thermostat wiring entrance
holes are located in the blower compartment.
Heating CFM
MODEL & TEMP RISE RANGE (MID RISE)
CFM RISE CFM RISE CFM RISE CFM RISE
RECOMMENDED CFM FOR 100% FIRING RATE
& EXPECTED TEMPERATURE RISE
1080
50
1400 51 1430 50 1800 50
LOWEST RECOMMENDED CFM FOR 100%
FIRING RATE & EXPECTED TEMPERATURE
RISE
830
65
1100 65 1100 65 1380 65
MODEL & TEMP RISE RANGE (MID RISE)
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
RECOMMENDED CFM FOR 100% FIRING RATE
& EXPECTED TEMPERATURE RISE
1370 40 1400 51 1760 41 1780 50 1950 55
LOWEST RECOMMENDED CFM FOR 100%
FIRING RATE & EXPECTED TEMPERATURE
RISE
990 55 1200 60 1320 55 1380 65 1670 65
*RVM970603BNA*
25-55 (40)
*RVM970803BNA*
30-60 (45)
*RVM970804CNA*
25-55 (40)
*RVM971005CNA*
35-65 (50)
*RVM971205DNA*
35-65 (50)
*DVM970603BNA*
35-65 (50)
*DVM970803BNA*
35-65 (50)
*DVM970804CNA*
35-65 (50)
*DVM971005CNA*
35-65 (50)

SYSTEM OPERATION
7
CONDENSATE SWITCH
COMMUNICATING
OUTDOOR UNIT
THERMOSTAT
MAIN CONTROL BOARD
For gas heat only operations (no outdoor unit installed) the
thermostat must be setup to provide a single stage W call
when heating is required. See Gas Heat Only wiring diagram
for wiring instructions.
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
Y
24 VAC
Thermostat
1
2
C
GAS HEAT ONLY
LOW VOLTAGE WIRING - COMMUNICATING
OUTDOOR UNIT
Internal logic will control staging of all multi stage equipment (2
stage AC/HP units and Inverter AC/HP units). The thermostat
is only required to provide a single stage heat / cool call and
fan or dehumidication call during operation.
Two wires are required between the indoor unit and outdoor
unit on the 1 and 2 terminals. It is recommended to install a
separate transformer with all 2 stage outdoor units to reduce
the power draw on the indoor transformer.
4 wires (R,C for power and 1, 2 for communications) can be
used for AC applications. See wiring images for details.
Do not connect R & C between the indoor unit and the outdoor
unit if there is already a transformer installed in the outdoor
unit providing 24VAC to the outdoor control. In this case, just
use 1 and 2 terminals for communications.
R
C
G
Y
Optional
Optional
Optional if
feature
supported by
thermostat
INDOOR
BOARD TERMINAL
CONNECTIONS
OUTDOOR
BOARD TERMINAL
CONNECTIONS
OUTDOOR
TRANSFORMER
1
2
C
R
C
G
Y
1
2
C
COMMUNICATING TWO STAGE AIR
CONDITIONER OR HEAT PUMP
1
2
C
R
C
G
Y
Optional
Optional
Optional if
feature
supported by
thermostat
INDOOR
BOARD TERMINAL
CONNECTIONS
OUTDOOR
BOARD TERMINAL
CONNECTIONS
1
2
C
R
C
G
Y
24 VA C
Thermostat
COMMUNICATING INVERTER
AIR CONDITIONER OR HEAT PUMP
LOW VOLTAGE WIRING - NON-COMMUNICATING
OUTDOOR UNIT

SYSTEM OPERATION
8
When using the furnace with a single stage non-communi-
cating air conditioner or heat pump use the wiring methods
shown. When using a single stage air conditioner, the thermo-
stat must be setup for single stage heating and single stage
cooling mode. When using a single stage heat pump, the
thermostat must be setup for dual fuel operation where the
reversing valve is energized in cooling mode (See Non-Com-
municating Single Stage Heat Pump wiring diagram). In both
cases airow must be selected using the tonnage menu where
Airow = (400 CFM) x (Selected Tonnage). Tonnage values
range from 1 to 6 in 0.1 increments.
NOTE: Airow will not go above the system Max CFM. If the
tonnage value selected generates an airow value above the
Max CFM, the system will cap this value and not provide any
more airow than the Max CFM.
NOTE: When installing a non-communicating outdoor unit
without using the Cool Cloud HVAC App, airow adjustments
must be made using the control push buttons. The initial ver-
sion of the phone application will not be capable of making
this setting change with this equipment conguration.
R
C
G
Y
Optional
Optional
INDOOR
BOARD TERMINAL
CONNECTIONS
R
C
G
Y
24 VA C
Thermostat
1
2
C
Heat Pump
Optional
R
C
Y
This is the only
case where setting the
thermostat to heat pump
mode is acceptable.
NON-COMMUNICATING SINGLE STAGE HEAT
PUMP
R
C
G
Y
Optional
Optional
Optional if
feature
supported by
thermostat
INDOOR
BOARD TERMINAL
CONNECTIONS
1
2
C
R
C
G
Y
C
Y
Remote
Condensing Unit
(Single-Stage Cooling)
24 VA C
Thermostat
Non-Communicating Single Stage A/C
Dehumidification
The control board is equipped with a 24 volt dehum input in
the thermostat wiring connector to be used with a thermostat
or dehumidistat. Dehumidication mode allows the air han-
dler’s circulator blower to operate at a slightly lower speed
(85% of calculated speed) during a combined thermostat
call for cooling and thermostat call for dehumidication or
dehumidistat call for dehumidication. This lower blower
speed enhances dehumidication of the conditioned air as it
passes through the AC coil. If using the dehum input with a
thermostat, congure the thermostat to energize this terminal
when dehumidication is desired. If using an external dehu-
midistat, connect it between the R and Dehum terminals. The
dehumidistat must operate on 24 VAC and utilize a switch
which closes on humidity rise. Refer to the low voltage wiring
diagrams for additional wiring details.
Dehumidistat (close on humidity rise)
R
C
G
Y
Dehumidistat
(close on humidity rise)

SYSTEM OPERATION
9
Key Mitigations:
1. Full featured TS (dehum & overcool)
2. Connect G and dehum wire correctly
3. Dehumidistat
Dehumidification Control Options
1) Install Dehum wire
and DO NOT install G
Wire
2) Install Dehumidistat
in living space or
return duct
Is there a setting in the
thermostat to enable
Dehum without fan? (G)
Yes
No
During a call for Dehum,
does the thermostat
provide 24V to Dehum, Y,
and G?
Yes
No
Choose that setting
Wire the system and test
functionality
Yes
No
Wire the system and
test functionality
Dehumidification Control Options
Dry Environment
Yes
No
Install any 24VAC
thermostat on the
market - Use Y, W, G
signals
Thermostat has a Dehum or
Configurable terminal with
Dehum option
Yes
No
Does your thermostat have a
whole house Dehumidifier
setting?
Install Dehumidistat in
living space or return
duct
If the Dehumidistat
opens on a rise on
humidity, then you
will set Dehum logic
to Low via Coolcloud
app or push buttons
If the Dehumidistat
closes on a rise in
humidity, then you
will set Dehum logic
to High via Coolcloud
app or push buttons
Thermostat only sends Dehum + G on a
call for Dehum
A Dehumidistat needs to be installed in
the living space or return duct
If the Dehumidistat opens
on a rise on humidity,
then you will set Dehum
logic to Low via Coolcloud
app or push buttons
If the Dehumidistat closes on
a rise in humidity, then you will
set Dehum logic to High via
Coolcloud app or push buttons

SYSTEM OPERATION
10
FOSSIL FUEL APPLICATIONS
This furnace can be used in conjunction with a heat pump in
a fossil fuel application. A fossil fuel application refers to a
combined gas furnace and heat pump installation which uses
an outdoor temperature sensor to determine when to run the
heat pump or gas furnace.
For non-communicating single stage heat pump installations
a fossil fuel kit can be used. Follow the wiring guidelines in the
fossil fuel kit installation instructions. All furnace connections
must be made to the furnace integrated control module and
the “FURNACE” terminal strip on the fossil fuel control board.
For Fossil Fuel systems the heat pump is given priority
when a compressor balance point lockout condition
is not present. Transitions from primary heat pump
heating to backup gas heating will result in full capacity
operation during the rst thermostat call. The furnace
PCB algorithms will then continuously adjust the stage
times or the percent capacity after the initial call in an
attempt to satisfy the thermostat at the target runtime.
Automatic Fossil Fuel Adjustment: If both compressor
balance point and backup heat balance point lockouts are
not present, the furnace algorithms will determine if the
heat pump is capable of satisfying the thermostat in the
selected target runtime. If the heat pump is not capable
of this it will be locked out until the furnace can satisfy
the thermostat, under the target runtime, while running
completely in low stage. At that point, an attempt will
be given to the heat pump and a decision made to keep
using gas heat or to transition back to the heat pump.
115 VOLT LINE CONNECTION OF ELECTRONIC AIR
CLEANER
HIGH VOLTAGE !
TO AVOID PERSONAL INJURY OR DEATH DUE TO
ELECTRICAL SHOCK, DISCONNECT ELECTRICAL POWER
BEFORE SERVICING OR CHANGING ANY ELECTRICAL
WIRING.
WARNING
The accessory load specications are as follows:
EAC 1.0 Amp maximum at 120 VAC
The furnace integrated control module is equipped with
a line voltage accessory terminal for controlling power
to an optional eld supplied electronic air cleaner or any
device required to operate in parallel with a circulating
fan demand.
To connect an electronic air cleaner using the line voltage
EAC terminal:
• Turn OFF power to the furnace before installing any
accessories.
• Follow the air cleaner manufacturers’ instructions for
locating, mounting, grounding, and controlling ac-
cessories. Utilize ¼”quick connect terminals to make
accessory wiring connections to the furnace integrated
control module.
• Connect the hot terminal utilized for accessory opera-
tion to the EAC terminal and the neutral side of power
to NEUTRAL bus on the integrated furnace control or
the neutral connection in the furnace junction box.
• All eld wiring must conform to applicable codes.
• Connections should be made as shown.
• If it is necessary for the installer to supply additional line
voltage wiring to the inside of the furnace, the wiring
must conform to all local codes, and have a minimum
temperature rating of 105°C.
• All line voltage wire splices must be made inside the
furnace junction box.
Low Voltage Ventilation
The Venlaon connecons provide dry contact for eld venlator
wiring connecons. These connecons are normally open and
energize during the R-32 fault/alarm condion. VT IN and VT OUT
connecons are provided on the control board and are shown in
the image below.
Low Voltage A2L Alarm
The A2L alarm connecon provides 24VAC for eld alarm wiring
connecons. These connecons are normally open and energize
during the R-32 fault/alarm condion. An A2L Alarm connecon
is provided on the control board and is shown in the image below.
Field Installed Accessories
Addional accessories that do not have dedicated terminals on the
furnace control board may require an addional daughter board
to be installed. Please refer to service manual on your product for
more informaon.
NOTE: This furnace is equipped with a control board that is capable
of monitoring for R-32 refrigerant leaks in the indoor refrigeraon
unit. Please verify that the R-32 sensor wire is plugged in to the
furnace control board before startup, if applicable. If furnace is
not paired with a R-32 refrigeraon system, the default sengs in
the furnace control board will need to be changed. Please see the
R-32 secon for addional informaon.
ACCESSORIES
Optional Field installed Supply Air & Return
Air Temperature Sensors
Optional Supply Air Sensor 0130F00933 & Return Air
Sensor 0130F00934 are available for purchase from your
distributor.

11
SYSTEM OPERATION
R-32 SENSOR
24 VOLT A2L ALARM
(OPTIONAL))
24 VOLT VENTILATION
(OPTIONAL)
CONNECTION LOCATION
FOR RA SENSOR
CONNECTION LOCATION
FOR SA SENSOR
24 VOLT HUM.
Accessory Control (Ventilators)
If an external humidier, dehumidier or ventilator is
installed, it may require airow from the HVAC system to
function accordingly.
1. Make sure the installed 24VAC thermostat is capable of
controlling the accessory or accessories.
2. Connect the appropriate accessory control wires to the
accessory devices from the thermostat (see thermostat
manual for connecon and setup instrucons).
3. If the thermostat is capable of providing a connuous fan
call (G signal) during accessory operation: Make sure
to connect the thermostat G terminal to the G terminal
on the indoor unit. Setup thermostat to ensure G signal is
energized during accessory operaon.
Figure 5
4. Select the appropriate fan only airow for the accessory
using the indoor unit push buon menus or the CoolCloud
HVAC phone applicaon.
5. Using the thermostat, independently test each accessory
in addion to independently tesng connuous fan mode.
AUXILIARY ALARM SWITCH:
The control is equipped with a 24VAC Aux Alarm to be
used for a condensate switch install (designated by
“Condensate” on the control). These contacts could also
be used with compatible CO
2
sensors or Fire Alarms. By
default, an AUX switch is normally closed and opens when
the water level in the evaporator coil base pan reaches an
undesirable level. The control will respond by turning o the
outdoor condensing unit and display EEd. If the AUX switch
is detected closed for 30 seconds, normal operation resumes
and error messages are no longer displayed.
CoolCloudHVAC Phone Application – General Information
Examples of Cool Cloud HVAC Phone Application
Screens
NOTE: Actual screen may look dierent based on the
device being used.

12
SYSTEM OPERATION
The Bluetooth
®
word mark and logos are registered
trademarks owned by Bluetooth SIG, Inc., and any use of
such marks are under license.
This furnace is Bluetooth
®
ready and functions with
a custom phone application designed to improve the
setup / diagnostic experience of the installing contractor.
Users can see specic model information, review active
diagnostic error codes, observe system status during
operation, make system menu adjustments such as
the target runtime, add site visit notes and run system
testing of all operational modes (heat / cool / fan) directly
from the phone. The phone application is also capable of
directly updating the furnace software anytime updates
are available (the application will automatically notify
the user if updates are available). Software update time
could take approximately 15 minutes to complete. The
phone must remain within Bluetooth range for only the
download step of an update. The user will be notied once
the download is completed and installation begins. At
this time the phone can be removed from the Bluetooth
range if necessary (NOTE: if the phone is out of range, the
user will not know when the installation has completed
or what the existing status of the installation is).
Download the CoolCloud Phone Application and create
an account to get started. A Wi-Fi / Cellular connection
will be required for account setup.
Connecting Phone Application to Furnace
When in close proximity to the furnace, the phone
application will detect the Bluetooth Network being
broadcasted by the system. Once the Bluetooth network
is selected by the user, due to security reasons, the user
will be prompted for a 3 digit access code before system
information can be displayed. The 3 digit code will be
displayed on the three seven segment displays of the
furnace control board. A sight glass is located close to
the control board that can be used to see these digits.
The user must enter the access code into the phone
application when prompted to do so in order to gain
access to system information. 3 failed entry attempts will
result in a new code being displayed on the control. If
all 3 digits are not visible from the sight glass, the user
has two options to connect.
Option 1) Perform thermostat task as instructed by the
phone application to gain access. The following steps
will explain what this task involves.
Step 1, ensure the thermostat is in an idle state (no cool,
heat or fan calls). To do this, set the thermostat fan
mode to Auto (not ON) and then remove any active heat
/ cool calls. This task needs to be completed within 5
minutes of the process beginning.
Step 2, provide any 24VAC call to the control from the ther-
mostat (cooling, heating or fan will work). This task must
occur within 8 minutes after the Step 1 is complete.
Step 3, remove the call that was provided during Step 2.
This task must be completed within 1 minute after the
call is provided during Step 2.
If the phone remains within Bluetooth range during the
three steps, the user will be notied when each step has
been completed and informed about what to do next. If
the user is not within Bluetooth range during this process
the phone application will still provide instruction
about what tasks to complete. After all 3 steps have
successfully been completed, the user will have access
to system information once in range.
Option 2) Remove the furnace door, ensure the control
has power and then read the 3 digits. The code will
temporarily remain active after a power cycle so the
door can put back on before making the connection if
desirable. NOTE: power will be cycled to the control
board with this option. If it is not desirable to cycle power
to the unit for diagnostic purposes Option 1 may be a
better method to connect.
At power-up, the furnace control will display the unit
address (a two digit number) on the 2
nd
and 3
rd
characters
of the three seven segment displays. After the furnace
control has completed its’ internal start-up routine, the
furnace control will display the Status Menu.
The control board will display “Id L” while in idle (stand-
by) mode waiting for a call from the thermostat. The
furnace control is now ready to receive inputs from the
room thermostat.
The furnace control board will detect any compatible
communicating outdoor unit connected to it. Items that
appear in the main menu will vary accordingly. Example,
you will not see heat pump specic menus unless a
compatible heat pump is detected by the furnace control.

13
SYSTEM OPERATION
Push Buttons
LEFT
CENTER
RIGHT
Three push-buttons on the control board may be used to
navigate menus and select options. The three buttons are
labeled Left, Center and Right. The center button is used
to enter into the option menu and make the selection, the
left and right buttons are used to browse the main menu
and option menus. When the center button is pressed in
the main menu, the furnace control will go to the option
menu and display the default or previously-selected
option. Pressing the left or right button will display
the next available option. When the next adjustable or
selectable option is displayed, the furnace control will
ash the option with ½ second ON and ½ second OFF
indicating the option has not yet been selected.
To select an option; press and release the center button
to stop the current option from ashing. When the option
has stopped ashing, press the center button again to
select that option.
While navigating through options; if no switches are
pressed during a 30 second time period, the display will
time-out and return to the Status Menu. Simultaneously
pressing & releasing any two switches will also return the
furnace control back to the Status Menu. If the previously
displayed option was not selected and a timeout occurs,
the displayed option will not be stored in control memory
as a selected option.
The Status Menu includes the following items;
• The operation mode
• Blower CFM (if blower is running)
• Humidication/Dehumidication mode (if active)
• Ventilator operation (if active)
• Any active fault codes
Menu items will appear in rotation as follows:
• Each item is ON for 2 seconds
• OFF for 1 second
• Then to the next item
Example of Menu Navigation & Option Change
This is an example for how to use the push buttons to make
a change to the constant fan speed.
1. When looking at the Furnace Control, the three 7
Segment displays (located just above the push but-
tons) will be displaying system status. System status
includes the current modes of operation, airow and
any active error codes.
LEFT CENTER
RIGHT
Press then Release
2. Press and release the Right Button (This will cycle
through the menus in one direction). Pressing the
Left Button would cycle through the menus in the
opposite direction.
3. Continue pressing and releasing the Right Button
until you see FSd which is the menu for Constant
Fan Multiplier.
LEFT CENTER RIGHT
Press then Release
4. Press and release the Center Button. The center
button is used to enter menus and make selections
within menus.
5. What will be displayed is the currently selected fan
only percentage. For this example the assumption
is that this currently selected fan only percentage is
25% and changing this to 45% is the objective.
6. Press and Release the Right button. The screen will
change to 35 and start ashing. The ashing indicates
the displayed option has not been selected yet.
7. Press and Release the Right button again. The 7
segment displays will continue ashing but will now
display 45.

SYSTEM OPERATION
14
LEFT CENTER RIGHT
Press then Release
1. Press and Release the Center Button again. The
45 being displayed will stop ashing. To then
complete the selection process and make 45 the
ocial fan only setting Press and Release the
Center Button for the last time. This nal step will
jump the user back to the main menu list and FSd
will be displayed again.
2. The constant fan multiplier has now been
changed from 25 to 45
Airow Display
When the blower is running the CFM will be displayed in
Status Menu. The rst 7 segment character will display
“A”. The second & third characters will display the actual
CFM divided by 100. The actual CFM will display rounded
up or down to the nearest 100 CFM as follows;
· 550 to 649 CFM display as “A06”
· 1150 to 1249 CFM display as “A12”
Alarm Display
If an active alarm is present, the alarm code shall be
reported in Status Menu starting with “E” and following
with the appropriate two digit alarm code.
Clearing Faults
While in the Last 10 Faults option menu, push & hold the
center button for 5 seconds. This will clear all non-active
alarm(s) in the Last 10 Faults menu. The display will ash
three times to conrm faults have been cleared.
Learn Menu
Using this option resets the communicating network
which will cause the furnace to discover what devices
are present on ClimateTalk™ network. This menu will
not appear when the furnace control is connected to a
Non-Comm OD unit.
Code Release Number Menu
This is a reference only menu to display the rmware
release revision numbers for each micro-controller.
Constant Fan Speed Menu
This menu allows for adjustment of the multiplier for
constant fan operation in 10% increments. Each furnace
has a “Maximum CFM” determined by motor HP. All
fan operations are based o of multipliers which are
percentages of this number. Max CFM is shown below.
The default constant fan multiplier is 30%.
Model Max CFM
3 Ton Models 1400
4 Ton Models 1760
5 Ton Models 2200
NOTE:*RVM970803 max CFM is
1650
Gas Heat Airow Multiplier Menu
The menu is used to change the gas heat airow multiplier
for gas heat operation. In most cases the default gas heat
airow will provide a temperature rise near the middle
of the acceptable range. The multiplier will be expressed
by the 2
nd
& 3
rd
characters of the display as a percentage
of max CFM.
Gas Heat Fan O Delay Menu
The default setting is 90 seconds. The available
adjustment range is from 30 to 180 seconds in 30 second
increments.
Gas Heat Fan On Delay Menu
The default setting is 30 seconds. The available
adjustment range is from 5 to 30 seconds in 5 second
increments.
Gas Heat Trim Factor Option Menu
Gas Heat airow may be trimmed from -10% to +10% in
2% increments.
Gas Heat Stage Multiplier Menu (CFM)
This menu allows adjustment of the low fire CFM
multiplier. The default CFM for low re is 50% of high re.
Gas Pressure Test Menu
This menu allows 100% ring rate be locked in to check
gas valve pressure.

SYSTEM OPERATION
15
R-32 Information
R-32 Function
This furnace is equipped with a control board that is capa-
ble of shutting o the gas heat and turning on the blower
fan in case of an R-32 refrigerant leak in the indoor cooling
unit. If the cooling unit that is paired with this furnace does
not utilize R-32 as the refrigerant, the R-32 functionalities in
the furnace control board will need to be turned o for the
furnace to run properly.
R-32 function on the control board is ON by default. The
R-32 function can be disabled through the furnace control
by entering the A2L Function Enabled menu and selecting
“no”. If A2L function is disabled, the furnace control will
ignore all A2L functions. If A2L function is enabled, the con-
trol will monitor the R-32 sensor information.
To enter the A2L Function Enabled menu, press the left or
right button until LED displays “A2E”. Press the center
button and the LED will display the selected option (yes or
no). Press the left or right button to select one of the two
options and press the center button to conrm the option.
R-32 Sensor Wire Routing
IMPORTANT NOTE: WIRING ROUTING MUST NOT IN-
TERFERE WITH CIRCULATOR BLOWER OPERATION,
FILTER REMOVAL OR ROUTINE MAINTENANCE. WIRE
SHOULD NOT BE ROUTED NEAR HOT SURFACES AND
SHOULD BE PROTECTED FROM SHARP EDGES. EXTRA
PRECAUTION SHOULD BE TAKEN TO AVOID ROUTING
NEAR THE OUTLET FLUE PIPE.
The R-32 Sensor wire coming from the indoor refrigeration
unit will need to be routed into the furnace and connected to
the connection point on the furnace control board. This wire
should be routed alongside the thermostat wires through the
low voltage openings in the left or right side of the furnace
blower compartment. Please see the electrical section for the
location of the R-32 Sensor connection on the control board.
Furnace Start Up
During furnace start up, the furnace control will identify the
connected R-32 sensor and will start monitoring the sensor
communication. A green LED located next to the sensor con-
nection will indicate if there is communication between the fur-
nace control and the R-32 sensor. The LED will be ON during
the duration of the startup and then will either start blinking
or turn OFF. The blinking LED signies that communication
with the R-32 sensor is present. The LED OFF signies that
there is no signal with the sensor.
If there are no alarms or faults, the furnace will go into regular
run mode after a warm up period. The furnace control monitors
the R-32 sensor once per second.
R-32 Refrigerant Leak
If the R-32 sensor on the indoor cooling unit detects a spec-
ied concentration of R-32 refrigerant, the furnace will enter
Mitigation Mode to dilute the refrigerant concentrations in case
of a leak. In Mitigation Mode, the furnace will do the following:
1) Display the A2L Refrigerant Leakage error code (EA0)
2) Shut down the gas operation
3) Energize the optional ventilation and alarm outputs.
4) Run the fan at max CFM airow
Once the R-32 sensor stops detecting a leak, the fan will
continue to run for 5 minutes. After the 5 minutes, if there
are no other alarms or faults, the control will de-energize the
optional ventilation and alarm outputs and then go back to
the original operating mode per the thermostat.
A2L Verication
The A2L Function Verication menu allows the installer to
verify if the R-32 function operates properly. This menu
simulates the refrigerant leak process and is only able to be
used when there are no active alarms or faults. To verify the
R-32 functions, enter the A2L Function Verication menu and
select “YES”. To enter the A2L Function Verication menu,
press the left or right button until LED displays “A2u”. Press
the center button and the LED will display the selected option
(yes or no). Press the left of right button to select one of the
two options and press the center button to conrm the option.
Once “YES” is selected, the furnace will do the following:
1) Display the A2L Refrigerant Leakage code (EA0)
2) Shut down the gas operation
3) Energize the optional ventilation and alarm outputs.
4) Run the fan at max CFM airow
The control will exit the verication function if:
1) The 5 minute timeout expires or
2) An alarm or fault is detected or
3) The user turns OFF the A2L Function Verification.
NORMAL SEQUENCE OF OPERATION
POWER UP
The normal power up sequence is as follows:
• 115 VAC power applied to furnace.
• Integrated control module performs internal checks.
• Integrated control module monitors safety circuits con-
tinuously.
• Furnace awaits call from thermostat. 7-segment LED’s
display LDL while awaiting call from thermostat.
HEATING MODE
NOTE: Upon power up, the gas valve stepper motor
may activate to change position. During this event, a
slight clicking sound from the stepper motor may be

SYSTEM OPERATION
16
heard. This clicking sound is inherent to the stepper
motor calibration and does not indicate a problem.
The normal operational sequence in heating mode is as
follows:
• W thermostat contact closes, initiating a call for heat.
• Integrated control module performs safety circuit
checks.
• Induced draft blower is energized on high speed for a
15-second prepurge.
• Induced draft blower steps to low speed following pre-
purge. Low stage pressure switch contacts are closed.
Igniter warm up begins upon Inducer draft blower step
to low speed and presence of closed low stage pressure
switch contacts.
• Gas valve opens at end of igniter warm up period,
delivering gas to burners and establishing ame.
• Low stage gas ow on Modulating product is 50% ow
rate.
• Integrated control module monitors ame presence.
Gas valve will remain open only if ame is detected.
• Based on the furnace internal control algorithms the gas
valve and induced draft blower will modulate to provide
the correct gas input needed. After a power cycle, the
rst gas heat call will result in high stage operation.
• Circulator blower is energized on heat speed following
the selected blower on delay and will begin to ramp
up. Electronic air cleaner terminal is energized with
circulator blower.
• Furnace is now operating on the specied stage deter-
mined by the internal control algorithm.
• Furnace runs, integrated control module monitors safety
circuits continuously.
• The W terminal thermostat contacts open, which ends
the call for heat.
• The gas valve closes, extinguishing the ame.
• Induced draft blower is de-energized following a 15
second post purge.
• Circulator blower continues running for the selected
heat o delay period.
• Circulator blower and electronic air cleaner terminal
are de-energized.
• Circulator blower shuts o after the heat o delay period
expires.
• Furnace awaits next call from thermostat.
OPERATIONAL CHECKS
The burner ames should be inspected with the burner
compartment door installed. Flames should be stable, quiet,
soft, and blue (dust may cause orange tips but they must not
be yellow). Flames should extend directly outward from the
burners without curling, oating, or lifting o. Flames must
not impinge on the sides of the heat exchanger ring tubes.
SAFETY CIRCUIT DESCRIPTION
A number of safety circuits are employed to ensure safe and
proper furnace operation. These circuits serve to control any
potential safety hazards and serve as inputs in the monitoring
and diagnosis of abnormal function. These circuits are contin-
uously monitored during furnace operation by the integrated
control module.
INTEGRATED CONTROL MODULE
The integrated control module is an electronic device which,
if a potential safety concern is detected, will take the neces-
sary precautions and provide diagnostic information through
an LED.
PRIMARY LIMIT
The primary limit control is located on the partition panel and
monitors heat exchanger compartment temperatures. It is
a normally-closed (electrically), automatic reset, tempera-
ture-activated sensor. The limit guards against overheating
as a result of insucient conditioned air passing over the
heat exchanger.
AUXILIARY LIMIT
The auxiliary limit controls are located on or near the circula-
tor blower and monitors blower compartment temperatures.
They are a normally-closed (electrically), manual-reset sen-
sors. These limits guard against overheating as a result of
insucient conditioned air passing over the heat exchanger.
ROLLOUT LIMIT
The rollout limit controls are mounted on the burner/manifold
assembly and monitor the burner ame. They are normal-
ly-closed (electrically), manual-reset sensors. These limits
guard against burner ames not being properly drawn into
the heat exchanger.
PRESSURE SWITCHES
The pressure switches are normally-open (closed during
operation) negative air pressure-activated switches. They
monitor the airow (combustion air and ue products) through
the heat exchanger via pressure taps located on the induced
draft blower and the coil front cover. These switches guard
against insucient airow (combustion air and ue products)
through the heat exchanger and/or blocked condensate drain
conditions.
FLAME SENSOR
The ame sensor is a probe mounted to the burner/manifold
assembly which uses the principle of ame rectication to
determine the presence or absence of ame.
Burner Flame

SYSTEM OPERATION
17
TROUBLESHOOTING
Electrostatic Discharge (ESD) Precautions
NOTE: Discharge body’s static electricity before
touching unit. An electrostatic discharge can adversely
aect electrical components.
Use the following precautions during furnace instal-
lation and servicing to protect the integrated control
module from damage. By putting the furnace, the con-
trol, and the person at the same electrostatic potential,
these steps will help avoid exposing the integrated
control module to electrostatic discharge. This pro-
cedure is applicable to both installed and uninstalled
(ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the
integrated control module or any wire connected to the
control prior to discharging your body’s electrostatic
charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the fur-
nace away from the control. Any tools held in a person’s
hand during grounding will be discharged.
3. Service integrated control module or connecting wiring
following the discharge process in step 2. Use caution
not to recharge your body with static electricity; (i.e., do
not move or shue your feet, do not touch ungrounded
objects, etc.). If you come in contact with an ungrounded
object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new
control from its container. Follow steps 1 through 3 if
installing the control on a furnace. Return any old or new
controls to their containers before touching any unground-
ed object.
DIAGNOSTIC CHART
HIGH VOLTAGE !
T
O
AVOID
PERSONAL
INJURY
OR
DEATH
DUE
TO
ELECTRICAL
SHOCK
,
DISCONNECT
ELECTRICAL
POWER
BEFORE
PERFORMING
ANY
SERVICE
OR
MAINTENANCE
.
WARNING
Refer to the Troubleshooting Chart in the back of this
manual for assistance in determining the source of unit
operational problems. The 7-segment LED displays
will display an error code that may contain a letter and
number. The error code may be used to assist in trou-
bleshooting the unit.
RESETTING FROM LOCKOUT
Furnace lockout results when a furnace is unable to
achieve ignition after three attempts during a single call
for heat. It is characterized by a non-functioning furnace
and an code displayed on the 7-segment display. If
the furnace is in “lockout”, it will (or can be) reset in any
of the following ways.
1. Automatic reset. The integrated control module will
automatically reset itself and attempt to resume normal
operations following a one hour lockout period.
2. Manual power interruption. Interrupt 115 volt power to
the furnace.
3. Manual thermostat cycle. Lower the thermostat so that
there is no longer a call for heat for 1 -20 seconds then
reset to previous setting.
NOTE: If the condition which originally caused the lock-
out still exists, the control will return to lockout. Refer
to the Troubleshooting Chart for aid in determining the
cause.
MAINTENANCE
ANNUAL INSPECTION
TO AVOID ELECTRICAL SHOCK, INJURY OR DEATH,
DISCONNECT
ELECTRICAL POWER BEFORE PERFORMING ANY
MAINTENANCE. IF YOU MUST HANDLE THE IGNITER,
HANDLE WITH CARE. TOUCHING THE IGNITER ELEMENT
WITH BARE FINGERS, ROUGH HANDLING OR VIBRATION
COULD DAMAGE THE IGNITER RESULTING IN PREMATURE
FAILURE. ONLY A QUALIFIED SERVICER SHOULD EVER
HANDLE THE IGNITER.
WARNING
The furnace should be inspected by a qualied install-
er, or service agency at least once per year. This check
should be performed at the beginning of the heating
season. This will ensure that all furnace components
are in proper working order and that the heating system
functions appropriately. Pay particular attention to the
following items. Repair or service as necessary.
• Flue pipe system. Check for blockage and/or leakage.
Check the outside termination and the connections at
and internal to the furnace.
• Heat exchanger. Check for corrosion and/or buildup
within the heat exchanger passageways.
• Burners. Check for proper ignition, burner ame, and
ame sense.
• Drainage system. Check for blockage and/or leakage.
Check hose connections at and internal to furnace.
• Wiring. Check electrical connections for tightness and/
or corrosion. Check wires for damage.
• Filters.
• R-32 Sensor Wire. Check R-32 sensor wire connecon for
ghtness and check wire for damage.

SYSTEM OPERATION
18
FILTERS
FILTER MAINTENANCE
Improper lter maintenance is the most common cause
of inadequate heating or cooling performance. Filters
should be cleaned (permanent) or replaced (disposable)
every two months or as required. When replacing a lter,
it must be replaced with a lter of the same type and size.
FILTER REMOVAL
Depending on the installation, diering lter arrange-
ments can be applied. Filters can be installed in either the
central return register or a side panel external lter rack
(upow only). A media air lter or electronic air cleaner
can be used as an alternate lter. Follow the lter sizes
given in the Recommended Minimum Filter size table to
ensure proper unit performance.
To remove lters from an external lter rack in an upright
upow installation, follow the directions provided with
external lter rack kit.
Horizontal Unit Filter Removal
Filters in horizontal installations are located in the cen-
tral return register or the ductwork near the furnace.
To remove:
1. Turn OFF electrical power to furnace.
2. Remove filter(s) from the central return register or
ductwork.
3. Replace lter(s) by reversing the procedure for removal.
4. Turn ON electrical power to furnace.
Media Air Filter or Electronic Air Cleaner Removal
r Cleaner oval
Follow the manufacturer’s directions for service.
BURNERS
Visually inspect the burner ames periodically during the
heating season. Turn on the furnace at the thermostat and
allow several minutes for ames to stabilize, since any
dislodged dust will alter the ames normal appearance.
Flames should be stable, quiet, soft, and blue (dust may
cause orange tips but they must not be yellow). They
should extend directly outward from the burners without
curling, oating, or lifting o. Flames must not impinge
on the sides of the heat exchanger ring tubes.
INDUCED DRAFT AND CIRCULATOR BLOWERS
T
O
ENSURE
PROPER
UNIT
PERFORMANCE
,
ADHERE
TO
THE
FILTER
SIZES
GIVEN
IN
THE
RECOMMENDED
M
INIMUM
F
ILTER
S
IZE
T
ABLE
OR
S
PECIFICATION
S
HEET
APPLICABLE
TO
YOUR
MODEL
.
CAUTION
The bearings in the induced draft blower and circula-
tor blower motors are permanently lubricated by the
manufacturer. No further lubrication is required. Check
motor windings for accumulation of dust which may
cause overheating. Clean as necessary.
CONDENSATE TRAP AND DRAIN SYSTEM (QUALIFIED
SERVICER ONLY)
Annually inspect the drain tubes, drain trap, and eld-sup-
plied drain line for proper condensate drainage. Check
drain system for hose connection tightness, blockage,
and leaks. Clean or repair as necessary.
FLAME SENSOR (QUALIFIED SERVICER ONLY)
Under some conditions, the fuel or air supply can cre-
ate a nearly invisible coating on the ame sensor. This
coating acts as an insulator causing a drop in the ame
sense signal. If the ame sense signal drops too low the
furnace will not sense ame and will lock out. The ame
sensor should be carefully cleaned by a qualied servicer
using emery cloth or steel wool. Following cleaning, the
ame sense signal should be as indicated in the Speci-
cations Sheet.
BURNERS
WARNING
HIGH
VOLTAGE
E
LECTRICAL COMPONENTS ARE CONTAINED IN BOTH
COMPARTMENTS.
T
O AVOID ELECTRICAL SHOCK, INJURY OR
DEATH, DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS
OR ATTEMPT ANY ADJUSTMENT.
C
ONTACT A QUALIFIED
SERVICE AGENT AT ONCE IF AN ABNORMAL FLAME
APPEARANCE SHOULD DEVELOP.
Periodically during the heating season make a visual check
of the burner ames. Turn the furnace on at the thermostat.
Wait a few minutes since any dislodged dust will alter the
normal ame appearance. Flames should be stable, quiet,
soft and blue with slightly orange tips. They should not be
yellow. They should extend directly outward from the burner
ports without curling downward, oating or lifting o the ports.
Check the
Burner Flames for:
1. Stable, soft and blue.
2. Not curling, floating
or lifting off.
Burner Flame

SYSTEM OPERATION
19
Proper equipment promotes faster, more ecient service and
accurate repairs resulting in fewer call backs.
HEATING PERFORMANCE TEST
Before attempting to diagnose an operating fault, run a heating
performance test and apply the results to the Service Problem
Analysis Guide.
To conduct a heating performance test, the BTU input to the
furnace must be calculated.
After the heating cycle has been in operation for at least fteen
minutes and with all other gas appliances turned o, the gas
meter should be clocked.
To nd the BTU input, multiply the number of cubic feet of
gas consumed per hour by the heating value of the gas being
used. (The caloric value of the gas being used is found by
contacting your local utility.)
FLUE PASSAGES (QUALIFIED SERVICER ONLY)
The heat exchanger ue passageways should be in-
spected at the beginning of each heating season.
Before Leaving an Installation
• Cycle the furnace with the thermostat at least three times.
Verify cooling and fan only operation.
• Review the Owner’s Manual with the homeowner and
discuss proper furnace operation and maintenance.
• Leave literature packet near furnace.
Repair and Replacement Parts
• When ordering any of the listed functional parts, be sure
to provide the furnace model, manufacturing, and serial
numbers with the order.
• Although only functional parts are shown in the parts
list, all sheet metal parts, doors, etc. may be ordered by
description.
• Parts are available from your distributor.
Functional Parts List-
Gas Valve Blower Motor
Gas Manifold Blower Wheel
Natural Gas Orice Blower Mounting Bracket
Propane Gas Orice Blower Cuto
Igniter Blower Housing
Flame Sensor Heat Exchanger with
Rollout Limit Switch Recuperator Coil
Primary Limit Switch Coil Front Cover
Auxiliary Limit Switch Integrated Control Module
Pressure Switch Transformer
Induced Draft Blower Bluetooth Module
Door Switch

SCHEDULED MAINTENANCE
20
CLOCKING A GAS METER
1. Turn o all gas appliances in the home.
2. Turn on the furnace. Ensure the furnace is operating at 100% ring rate on 2 stage and modulating furnace product.
3. Once heating cycle is at a steady state (typically 15 minutes of operation), use a stopwatch to time how long it takes
the smallest unit of measure dial on the gas meter to make a full revolution. In Table 1, one cubic foot is selected. The
smallest unit of measure will vary depending on the gas meter.
CUBIC
FEET
1
1
One
In this example
we are using the
one cubic foot
dial on the gas
meter
4. Using Table 2 below, nd the number of seconds it took for the dial to make a full revolution. To the right of that number of
seconds and below the Size of Test Dial (selected in step 3 and shown in Table 1) will be the Cubic Feet per Hour (CFH).
1/4
cu/ft
1/2
cu/ft
1
cu/ft
2
cu/ft
5
cu/ft
1/4
cu/ft
1/2
cu/ft
1
cu/ft
2
cu/ft
5
cu/ft
10 90 180 360 720 1800 36 25 50 100 200 500
11 82 164 327 655 1636 37 -- -- 97 195 486
12 75 150 300 600 1500 38 23 47 95 189 474
13 69 138 277 555 1385 39 -- -- 92 185 462
14 64 129 257 514 1286 40 22 45 90 180 450
15 60 120 240 480 1200 41 -- -- -- 176 439
16 56 113 225 450 1125 42 21 43 86 172 429
17 53 106 212 424 1059 43 -- -- -- 167 419
18 50 100 200 400 1000 44 -- 41 82 164 409
19 47 95 189 379 947 45 20 40 80 160 400
20 45 90 180 360 900 46 -- -- 78 157 391
21 43 86 171 343 857 47 19 38 76 153 383
22 41 82 164 327 818 48 -- -- 75 150 375
23 39 78 157 313 783 49 -- -- -- 147 367
24 37 75 150 300 750 50 18 36 72 144 360
25 36 72 144 288 720 51 -- -- -- 141 355
26 34 69 138 277 692 52 -- -- 69 138 346
27 33 67 133 265 667 53 17 34 -- 136 340
28 32 64 129 257 643 54 -- -- 67 133 333
29 31 62 124 248 621 55 -- -- -- 131 327
30 30 60 120 240 600 56 16 32 64 129 321
31 -- -- 116 232 581 57 -- -- -- 126 316
32 28 56 113 225 563 58 -- 31 62 124 310
33 -- -- 109 218 545 59 -- -- -- 122 305
34 26 53 106 212 529 60 15 30 60 120 300
35 -- -- 103 206 514
GAS RATE -- CUBIC FEET PER HOUR
Seconds fo
r
One
Revolution
Size of Test Dial
Seconds fo
r
One
Revolution
Size of Test Dial
Locate 40 seconds for one
revolu�on in the chart below
Then locate the 1 cu � dial column and select the
corresponding CFH from the 40 seconds for one revolu�on row
*

SCHEDULED MAINTENANCE
21
5. Use this formula to verify the Cubic Feet per Hour (CFH) input determined in step 4 is correct:
(3600 x Gas Meter Dial Size) / Time (seconds) = Cubic Feet per Hour (CFH)
3600 is used as there are 60 seconds in
a minute and 60 minutes in an hour.
60x60=3600
6. Check with your local utility for actual BTU content (caloric value) of natural gas in the area (the average is 1025
BTU’s).
7. Use this formula to calculate the BTU/HR input (See BTU/HR Calculation Example):
Cubic Feet per Hour (CFH) x BTU content of your natural gas = BTU/HR input
8.
BTU/HR Calculation Example:
The unit being tested takes 40 seconds for the 1 cubic foot dial to make one complete revolution. Using the chart, this
translates to 90 cubic feet per hour. Based upon the assumption that one cubic foot of natural gas has 1,025 BTU’s (Check
with your local utility for actual BTU content), the calculated input is 92,250 BTU’s per hour.
Furnace Nameplate Input in this example: 90,000 BTU/HR
Calculated Gas Input in this example: 92,250 BTU/HR
This example is within the 5% tolerance input and does not need adjustment.
CAUTION
Always connect a manometer to the outlet tap at the
gas valve before adjusng the pressure regulator. In
no case should the final manifold pressure vary more
than plus or minus .2 inches water column from 3
inches water column for natural gas.
A properly operating unit must have the BTU per hour input and CFM of air, within the limits shown to prevent short cycling
of the equipment. As the external static pressure goes up, the temperature rise will also increase. Consult the proper tables
for temperature rise limitation.
pressure regulator.
To adjust the pressure regulator on the gas valve, turn downward (clockwise) to increase
pressure and input, and upward (counterclockwise) to decrease pressure and input. A properly operating unit must
have the BTU per hour input and CFM of air, within the limits shown to prevent short cycling of the equipment. As the
external static pressure goes up, the temperature rise will also increase. Consult the proper tables for temperature
rise limitation.

22
SERVICING
Some of the electronic boards being used today, with ame
rectication, will not function properly and/or at all without
polarization of incoming power. Some also require phasing
between the primary and secondary sides of step-down
transformers.
.
.
GND
GND
THIS IS L1 OR THE
HOT POWER LEG
THIS IS THE COMMON
OR NEUTRAL LEG
INCOMING POWER
CHECKING FOR PHASING - PRIMARY TO SECONDARY OF UNMARKED TRANSFORMERS*
TRANSFORMER
.
SECONDARY
PRIMARY
.
GND
C
R
LINE VOLTAGE
L1 (HOT)
LINE VOLTAGE
(NEUTRAL)
METER READS
24 VOLTS
METER READS
120 VOLTS
.
GND
C
R
N
L1
.
GND
C
R
N
L1
READS 96 VOLTS - IN PHASE
READS 144 VOLTS - OUT OF PHASE
.
If meter reads approximately 96 volts - the primary to secondary are in phase - if reads approximately 144 volts out of phase
- reverse low voltage wires.
C
R
GND
NEUTRAL
L1
PHASING SYMBOL
24 V
120 V
These then should be wired to the furnace accordingly.
Some transformers will display phasing symbols as shown
in the illustration to the left to assist in determining proper
transformer phasing.

SERVICING
23
CHECKING VOLTAGE
WARNING
HIGH
VOLTAGE
D
ISCONNECT
ALL
POWER BEFORE SERVICING OR
CHANGING ANY ELECTRICAL WIRING.
M
ULTIPLE POWER
SOURCES MAY BE PRESENT.
F
AILURE TO DO SO MAY CAUSE
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1. Remove the burner door.
2. Remove cover from the Junction Box and gain access to
incoming power lines.
With Power ON:
L
INE VOLTAGE NOW PRESENT
WARNING
3. Using a voltmeter, measure the voltage across the hot
and neutral connections.
NOTE: To energize the furnace, the Door Interlock Switch
must be engaged at this point.
4. No reading - indicates open wiring, open fuse, no pow-
er, or faulty Door Interlock Switch from unit to fused
disconnect service. Repair as needed.
5. With ample voltage at line voltage connectors, energize
the furnace blower motor by jumpering terminals R to
G on the integrated ignition control.
6. With the blower motor in operation, the voltage should
be 115 volts ± 10 percent.
7. If the reading falls below the minimum voltage, check
the line wire size. Long runs of undersized wire can
cause low voltage. If wire size is adequate, notify the
local power company of the condition.
8. After completing check and/or repair, replace Junction
Box cover and reinstall the service panel doors.
9. Turn on electrical power and verify proper unit operation.
CHECKING WIRING
D
ISCONNECT
ALL
POWER BEFORE SERVICING.
WARNING
1. Check wiring visually for signs of overheating, damaged
insulation and loose connections.
2. Use an ohmmeter to check continuity of any suspected
open wires.
3. If any wires must be replaced, replace with AWM, 105°C.
2/64 inch thick insulation of the same gauge or its
equivalent.
CHECKING THERMOSTAT, WIRING
THERMOSTAT AND WIRING
D
ISCONNECT
ALL
POWER BEFORE SERVICING.
WARNING
1. Remove the blower compartment door to gain access to
the thermostat low voltage wires located at the furnace
integrated control module terminals.
2. Remove the thermostat low voltage wires at the furnace
control panel terminal board.
3. Jumper terminals R to W on the integrated ignition control.
With Power On (and Door Interlock Switch closed):
L
INE VOLTAGE NOW PRESENT
WARNING
4. Induced Draft Motor must run and pull in pressure
switch.
5. If the hot surface igniter heats and at the end of the
igniter warm-up period the gas valve opens and the
burners ignite, the trouble is in the thermostat or wiring.
6. With power o, check the continuity of the thermostat
and wiring. Repair or replace as necessary.
If checking the furnace in the air conditioning mode, pro-
ceed as follows.
7. With power o, Jumper terminals R to Y to G.
8. Turn on the power.
9. If the furnace blower motor starts and the condensing
unit runs, then the trouble is in the thermostat or wiring.
Repair or replace as necessary.
10. After completing check and/or repair of wiring and
check and/or replacement of thermostat, reinstall
blower compartment door.
11. Turn on electrical power and verify proper unit operation.

24
SERVICING
CHECKING TRANSFORMER AND CONTROL CIRCUIT
A step-down transformer 120 volt primary to 24 volt secondary,
40 VA (Heating and Cooling Models) supplies ample capacity
of power for either operation.
WARNING
HIGH
VOLTAGE
D
ISCONNECT
ALL
POWER BEFORE SERVICING OR
CHANGING ANY ELECTRICAL WIRING.
M
ULTIPLE POWER
SOURCES MAY BE PRESENT.
F
AILURE TO DO SO MAY CAUSE
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1. Remove blower compartment door to gain access to the
thermostat low voltage wires located at the furnace inte-
grated control module.
2. Remove the thermostat low voltage wires at the furnace
integrated control module terminals.
With Power On (and Door Interlock Switch closed):
L
INE VOLTAGE NOW PRESENT
WARNING
3. Use a voltmeter, check voltage across terminals R and
C. Must read 24 VAC.
4. No voltage indicates faulty transformer, open fuse, bad
wiring, bad splice, or open door interlock switch.
5. Check transformer primary voltage at incoming line
voltage connections, fuse, splices, and blower door in-
terlock switch.
6. If line voltage is available to the primary side of trans-
former and not at secondary side, the transformer is
inoperative. Replace.
7. After completing check and/or replacement of trans-
former and check and/or repair of control circuit, rein-
stall blower compartment door.
8. Turn on electrical power and verify proper unit operation.
4-Wire ECM Motors
Description
These models utilize an Nidec US motors, 4-wire variable
speed ECM blower motor. The ECM blower motor provides
constant CFM.
The motor is a serially communicating variable speed mo-
tor. Only four wires are required to control the motor: +Vdc,
Common, Receive, and Transmit.
The +Vdc and Common wires provide power to the motor's
low voltage control circuits. Typical supply voltage is 9-15
volts DC.
ECM Control Connections
ECM control connections are made through the integrated
ignition control. No other control connections are needed.
Checking ECM Motors
ECM motors connect directly to the AC Line Voltage. DO NOT
insert contactors in series with the ECM Motor AC Line. The
control is powered continuously to insure reliable start-up.
The connector plug is polarized, verify and reverify correct
connector orientation before applying power. DO NOT force
plug into motor and make sure power is o before inserting
power connector. DO NOT apply voltage to terminals 1 or 2.
General Checks/Considerations
1. Check power supply to the furnace. Ensure power supply
is within the range specied on rating plate.
2. Check motor power harness. Ensure wires are continuous
and make good contact when seated in the connectors.
Repair or replace as needed.
3. Check motor control harness. Ensure wires are continuous
and make good contact when seated in the connectors.
Repair or replace as needed.
4. Check thermostat and thermostat wiring. Ensure thermo-
stat is providing proper cooling/heating/continuous fan
demands. Repair or replace as needed.
5. Check blower wheel. Conrm wheel is properly seated on
motor shaft. Set screw must be on shaft at and torqued
to 165 in-lbs minimum. Conrm wheel has no broken or
loose blades. Repair or replace as needed.
6. Ensure motor and wheel turn freely. Check for interference
between wheel and housing or wheel and motor. Repair
or replace as needed.

SERVICING
25
7. Check housing for cracks and/or corrosion. Repair or
replace as needed.
8. Check motor mounting bracket. Ensure mounting bracket
is tightly secured to the housing. Ensure bracket is not
cracked or broken.
ULTRACHECK-EZ
TM
DIAGNOSTIC TOOL
The UltraCheck-EZ
TM
diagnostic tool is the preferred method
(part # UTT-01) to diagnose the ECM motor.
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
To use the diagnostic tool, perform the following steps:
1. Disconnect power to the furnace.
2. Disconnect the 4-circuit control harness from the motor.
3. Plug the 4-circuit connector from the diagnostic tool into
the motor control connector.
4. Connect one alligator clip from the diagnostic tool to a
ground source.
5. Connect the other alligator clip to a 24VAC source.
NOTE: The alligator clips are NOT polarized.
NOTE: The UltraCheck-EZ
TM
diagnostic tool is equipped
with a non-replaceable fuse. Connecting the tool to a source
other than 24VAC could damage the tool and cause the fuse
to open. Doing so will render the diagnostic tool inoperable.
6. Turn on power to the furnace.
WARNING
Line Voltage now present.
7. Depress the orange power button on the diagnostic tool
to send a run signal to the motor. Allow up to 5 seconds
for the motor to start.
NOTE: If the orange power button does not illuminate when
depressed, the tool either has an open fuse or is not properly
connected to a 24VAC source.
8. The green LED on the diagnostic tool will blink indicating
communications between the tool and motor. See table
below for indications of tool indicators and motor actions.
Replace or repair as needed.
Power
Button
Green
LED
Motor
Action
Indication(s)
OFF OFF
Not
Rotating
Confirm 24VAC to
UltraCheck-EZ
TM
tool.
If 24VAC is confirmed,
diagnostic tool is
inoperable.
ON Blinking
Rotating
Motor and control/end
bell are functioning
properly.
ON OFF
Rotating
Replace motor
control/end bell.
ON Blinking
Not
Rotating
Check motor (see
Motor Check s below).
ON OFF
Not
Rotating
Replace motor
control/end bell; verify
motor (see Motor
Check s below).
9. Depress the orange power button to turn o motor.
10. Disconnect power. Disconnect diagnostic tool.
11. Reconnect the 4-wire harness from control board to motor.
ELECTRICAL CHECKS - HIGH VOLTAGE POWER
CIRCUITS
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Disconnect power to the furnace.
2. Disconnect the 5-circuit power connector to the ECM motor.
3. Turn on power to the furnace.
WARNING
Line Voltage now present.
4. Measure voltage between pins 4 and 5 on the 5-circuit
connector. Measured voltage should be the same as the
supply voltage to the furnace.

26
SERVICING
5
4
3
2
1
Lines 1 and 2 will be connected
for 120VAC Power Connector
applications only
Gnd
AC Line Neutral Connection
AC Line Hot Connection
}
POWER CONNECTOR
"Motor Half“
(Viewed from Plug End)
5. Measure voltage between pins 4 and 3. Voltage should
be approximately zero.
6. Measure voltage between pins 5 and 3. Voltage should be
the same as the supply voltage to the furnace.
7. If no voltage is present, check supply voltage to the furnace.
8. Disconnect power to the furnace. Reconnect the 5-circuit
power harness disconnected in step 2.
ELECTRICAL CHECKS - LOW VOLTAGE CONTROL
CIRCUITS
1. Turn on power to the furnace.
WARNING
Line Voltage now present.
2. Check voltage between pins 1 and 4 on the 4-wire motor
control harness between the motor and control board.
Voltage should be between 3 and 15 VDC.
3. If no voltage is present, check control board.
MOTOR CONTROL/END BELL CHECKS
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Disconnect power to the furnace.
NOTE: Motor contains capacitors that can hold a charge for
several minutes after disconnecting power. Wait 5 minutes
after removing power to allow capacitors to discharge.
2. Disconnect the motor control harness and motor power
harness.
3. Remove the blower assembly from the furnace.
4. Remove the (3) screws securing the control/end bell to
the motor. Separate the control/end bell. Disconnect the
3-circuit harness from the control/end bell to remove the
control/end bell from the motor.
5. Inspect the NTC thermistor inside the control/end bell
(see gure below). Replace control/end bell if thermistor
is cracked or broken.
6. Inspect the large capacitors inside the control/end bell (see
gure below). Replace the control/end bell if any of the
capacitors are bulging or swollen.

SERVICING
27
7. Locate the 3-circuit connector in the control/end bell. Using
an ohmmeter, check the resistance between each terminal
in the connector. If the resistance is 100kΩ or greater, the
control/end bell is functioning properly. Replace the control/
end bell if the resistance is lower than 100kΩ.
8. Reassemble motor and control/end bell in reverse of
disassembly. Replace blower assembly into the furnace.
MOTOR CHECKS
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
1. Disconnect power to the furnace.
NOTE: Motor contains capacitors that can hold a charge for
several minutes after disconnecting power. Wait 5 minutes
after removing power to allow capacitors to discharge.
2. Disassemble motor as described in steps 2 through 4
above.
3. Locate the 3-circuit harness from the motor. Using an
ohmmeter, measure the resistance between each motor
phase winding. The resistance levels should be equal.
Replace the motor if the resistance levels are unequal,
open circuited or short circuited.
4. Measure the resistance between each motor phase winding
and the motor shell. Replace the motor if any phase winding
is short circuited to the motor shell.
5. Reassemble motor and control/end bell in reverse of
disassembly. Replace blower assembly into the furnace.
CHECKING DUCT STATIC
The maximum and minimum allowable external static pres-
sures are found in the specication section. These tables also
show the amount of air being delivered at a given static by a
given motor speed or pulley adjustment.
The furnace motor cannot deliver proper air quantities (CFM)
against statics other than those listed.
Too great of an external static pressure will result in insu-
cient air that can cause excessive temperature rise, resulting
in limit tripping, etc. Whereas not enough static may result in
motor overloading.
To determine proper air movement, proceed as follows:
1. With clean lters in the furnace, use a manometer to
measure the static pressure of the return duct at the inlet
of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct. (Positive
Pressure)
3. Add the two (2) readings together for total external static
pressure.
NOTE: Both readings may be taken simultaneously and read
directly on the manometer if so desired. If an air conditioner
coil or Electronic Air Cleaner is used in conjunction with the
furnace, the readings must also include theses components,
as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the minimum or
maximum allowable statics, check for closed dampers, reg-
isters, undersized and/or oversized poorly laid out duct work.
.
Checking Static Pressure
CHECKING TEMPERATURE RISE
The more air (CFM) being delivered through a given furnace,
the less the rise will be; so the less air (CFM) being delivered,
the greater the rise. The temperature rise should be adjusted
in accordance to a given furnace specications and its exter-
nal static pressure. An incorrect temperature rise may result
in condensing in or overheating of the heat exchanger. An
airow and temperature rise table is provided in the blower
performance specication section. Determine and adjust
temperature rise as follows:

28
SERVICING
1. Operate furnace with burners ring for approximately ten
minutes. Check BTU input to furnace - do not exceed
input rating stamped on rating plate. Ensure all registers
are open and all duct dampers are in their nal (fully or
partially open) position.
2. Place thermometers in the return and supply ducts as
close to the furnace as possible. Thermometers must not
be inuenced by radiant heat by being able to “see” the
heat exchanger.
SUPPLY
AIR
RETURN
AIR
Temperature Rise Measurement
3. Subtract the return air temperature from the supply air
temperature to determine the air temperature rise. Allow
adequate time for thermometer readings to stabilize.
4. Adjust temperature rise by adjusting the circulator blower
speed. Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise.
Refer to Circulator Blower Speed section in the Product
Design section of this manual for speed changing details.
Temperature rise is related to the BTUH output of the
furnace and the amount of air (CFM) circulated over the
heat exchanger. Measure motor current draw to determine
that the motor is not overloaded during adjustments.
CHECKING PRIMARY LIMIT CONTROL
Primary limit controls are nonadjustable, automatic reset,
bi-metal type limit control. Refer to the following drawing for
the location of the primary limit.
*
*
*
* *
*
*
2
PRIMARY LIMIT
CONTROL
Primary Limit Control Location
(90% Upow Furnace Shown, Counterow Similar)
The following drawing illustrates the style of limit switches
used on the 90% furnaces.
ENCLOSED DISK
FRONT VIEW SIDE VIEW
Primary Limit Control Style
(90% Furnaces)
WARNING
HIGH
VOLTAGE
D
ISCONNECT
ALL
POWER BEFORE SERVICING OR
CHANGING ANY ELECTRICAL WIRING.
M
ULTIPLE POWER
SOURCES MAY BE PRESENT.
F
AILURE TO DO SO MAY CAUSE
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1. Remove burner compartment door to gain access to
the primary limit.
2. Remove low voltage wires at limit control terminals.
3. With an ohmmeter, test between these two terminals
as shown in the following drawing. The ohmmeter
should read continuous unless heat exchanger tem-
perature is above limit control setting. If not as above,
replace the control.

SERVICING
29
COLOR
IDENTIFYING
TAB
Testing Primary Limit Control
(90% Furnaces)
4. After completing check and/or replacement of primary
limit control, reinstall burner compartment door.
5. Turn on electrical power and verify proper unit operation.
To aid in identifying these controls, refer to the Primary Limit
Charts in furnace Technical Manual for part number, tempera-
ture setting and color(s) code.
CHECKING AUXILIARY LIMIT CONTROL
The auxiliary limit control is designed to prevent furnace
operation in case of main blower failure in horizontal or coun-
terow installations. It may also open if the power supply is
interrupted while the furnace is ring.
The auxiliary limit control is suitable for both horizontal right
and horizontal left installations. Regardless of airow direc-
tion, it does not need to be relocated. The (2) two auxiliary
limits are located on the blower housing (one on each side),
as shown in the following illustration.
LIMIT
AUXILIARY LIMIT
CONTROL
AUXILIARY LIMIT
CONTROL
BLOWER HOUSING
Auxiliary Limit Control Location
(Select 90% / 95% Furnaces)
MANUAL OR AUTOMATIC RESET AUXILIARY
LIMITS LOCATED IN BLOWER SIDE
WARNING
HIGH
VOLTAGE
D
ISCONNECT
ALL
POWER BEFORE SERVICING OR
INSTALLING THIS UNIT.
M
ULTIPLE POWER SOURCES MAY
BE PRESENT.
F
AILURE TO DO SO MAY CAUSE PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
1. Remove the wires from the auxiliary limit control terminals.
2. Using an ohmmeter, test for continuity across the two
terminals (only test when the auxiliary limit is at room
temperature).
RED
RESET
BUTTON
COLOR
IDENTIFYING
Testing Auxiliary Limit Control
WARNING
T
O AVOID POSSIBLE FIRE, ONLY RESET THE AUXILIARY LIMIT CONTROL
ONCE.
I
F IT SHOULD OPEN A SECOND TIME, A QUALIFIED SERVICER
MUST DETERMINE WHY THE AUXILIARY LIMIT OPENED BEFORE
RESETTING AGAIN.
CHECKING FLAME ROLLOUT CONTROL
A temperature activated manual reset control is mounted to
the manifold assembly on 90% furnaces, as shown in the
following illustration.

30
SERVICING
*
*
*
* *
*
*
2
FLAME
ROLLOUT
SWITCHES
Flame Rollout Switch Location
(90% Upow Furnace Shown, Counterow Similar)
The control is designed to open should a ame roll out occur.
An over ring condition or ame impingement on the heat
shield may also cause the control to open. If the rollout control
opens, the air circulation blower will run continuously.
L
INE VOLTAGE NOW PRESENT
WARNING
1. Remove the burner compartment door to gain access to
the rollout switch(es) mounted to burner bracket.
2. Reset the manual rollout switch.
3. Remove wires from rollout switch.
4. Using an ohmmeter, check for continuity across the switch.
5. If the switch will not close after manually resetting, it must
be replaced.
If a roll out switch has tripped, it is important to nd out why.
Possible causes could be ame impingement, orice plate
out of position, burners with excessive cross-over slot dimen-
sion, over-ring, improper orices, improper gas pressure,
air leaking from around the heat exchanger into the burner
compartment, air leaking through the heat exchanger itself.
6. After check and/or replacement of rollout switch, reinstall
burner compartment door and verify proper unit operation.
INDUCED DRAFT BLOWER MOTOR
WARNING
HIGH
VOLTAGE
D
ISCONNECT
ALL
POWER BEFORE SERVICING OR
INSTALLING THIS UNIT.
M
ULTIPLE POWER SOURCES MAY
BE PRESENT.
F
AILURE TO DO SO MAY CAUSE PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
1. Remove burner compartment door to gain access to
the induced draft blower motor.
2. Disconnect the motor wire leads from its connection
point at the induced draft motor.
3. Using a ohmmeter, test for continuity between each of
the motor leads.
4. Touch one probe of the ohmmeter to the motor frame
(ground) and the other probe in turn to each lead.
If the windings do not test continuous or a reading is
obtained to ground, replace the motor.
5. If the windings have a continuity reading, reconnect
wires. Turn power on to the furnace and turn the
thermostat on in the heating mode. Check voltage for
115V at the induced draft motor terminals during the tri-
al for ignition. If you have 115V and the motor does not
run, replace the induced draft motor.
6. After completing check and/or replacement of induced
draft motor, reinstall burner compartment door.
7. Turn on electrical power and verify proper unit opera-
tion.
CHECKING MODULATING GAS VALVE
The gas valve on ComfortBridge™ Modulating Furnace uses
a 24VAC electrically stepped valve by White Rodgers. The
furnace will re at 100% ring rate for the rst heating cycle.
Based on the furnace internal control algorithms the gas
valve and induced draft blower will modulate to provide the
correct gas input needed. The valve provides control of the
main burner gas ow, pressure regulation, and 100 percent
safety shut o.
NOTE: Upon power up, the gas valve stepper motor may
activate to change position. This actually is a calibration pro-
cess for the modulating gas valve. During this event a slight
clicking sound from the stepper motor may be heard. This
clicking sound is inherent to the stepper motor and does not
indicate a problem.
The front cover pressure switch is wired in series with Pin 5
on the gas valve (24 volt hot) so if you are not getting voltage
to the valve ensure the front cover pressure switch is closed.
Recommend voltage checks on the gas valve:
PIN 5 - TH - MAIN VALVE 24 VAC
PIN 4 - TR - GROUND
PIN 3 - TX - COMMUNICATION TO IFC 3.3 VDC
PIN 2 - RX - COMMUNICATION TO STEPPER 5.0 VDC
PIN 1 - TH - BOARD 24 VAC

SERVICING
31
WARNING
D
ISCONNECT
ALL
POWER BEFORE SERVICING
CHECKING MAIN BURNERS
The main burners are used to provide complete combustion
of various fuels in a limited space, and transfer this heat of
the burning process to the heat exchanger.
Proper ignition, combustion, and extinction are primarily due
to burner design, orice sizing, gas pressure, primary and
secondary air, vent and proper seating of burners.
BURNERS
Burners have been redesigned for 34.5" chassis furnaces.
Overall length and width dimensions remain the same as 40"
model burners. The burners used 34.5" models have burner
head insert with larger diameter center hole and a larger
number of surrounding holes.
34.5 Burners
WARNING
D
ISC
ONNECT
ALL
G
AS AND
E
LECTRICAL
P
OWER
S
UPPLY.
In checking main burners, look for signs of rust, oversized and
undersized carry over ports restricted with foreign material,
etc., burner cross-over slots should not be altered in size.
CHECKING ORIFICES
*RVM97/*DVM97 model furnaces have factory installed #45
natural gas orices.
The only time resizing is required is when a reduction in ring
rate is required for an increase in altitude or a furnace is being
converted for use with L.P. gas.
Orices should be treated with care in order to prevent dam-
age. They should be removed and installed with a box-end
wrench in order to prevent distortion. In no instance should
an orice be peened over and re-drilled. This will change
the angle or deection of the vacuum eect or entraining
of primary air, which will make it dicult to adjust the ame
properly. This same problem can occur if an orice spud of a
dierent length is substituted.
WARNING
D
ISCONNECT
ALL
G
AS AND
E
LECTRICAL
P
OWER
S
UPPLY.
1. Check orice visually for distortion and/or burrs.
2. Check orice size by the number stamped on the orice.
A
GAS
STREAM
B
The length of Dimension "A" determines the angle of Gas
Stream "B".
DENT OR
BURR
GAS
STREAM
B
A dent or burr will cause a severe deection of the gas stream.
CHECKING GAS PRESSURE
GAS SUPPLY PRESSURE MEASUREMENT
T
O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE
INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT
RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES
OPERATING.
CAUTION
Gas inlet and manifold pressures should be checked and
adjusted in accordance to the type of fuel being consumed.
The line pressure supplied to the gas valve must be within
the range specied below. The supply pressure can be mea-
sured at the gas valve inlet pressure tap or at a hose tting
installed in the gas piping drip leg. The supply pressure must
be measured with the burners operating. To measure the gas
supply pressure, use the following procedure.

32
SERVICING
WARNING
D
ISCONNECT ELECTRICAL POWER AND SHUT OFF GAS SUPPLY.
1. After turning o gas to furnace at the manual gas shuto
valve external to the furnace, remove burner compartment
door to gain access to the gas valve.
2. Connect a calibrated manometer (or appropriate gas pres-
sure gauge) at either the gas valve inlet pressure tap or
the gas piping drip leg as shown in the following gures.
NOTE: At either location, a hose tting must be installed prior
to making the hose connection.
.
Measuring Inlet Gas Pressure
(Alternate Method)
3. Turn ON the gas and electrical power supply and operate
the furnace and all other gas consuming appliances on
the same gas supply line.
4. Measure furnace gas supply pressure with burners ring.
Supply pressure must be within the range specied in the
following table.
Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c.
Propane Gas Minimum: 11.0" w.c. Maximum: 13.0" w.c.
INLET GAS SUPPLY PRESSURE
If supply pressure diers from above, make necessary ad-
justments to pressure regulator, gas piping size, etc., and/or
consult with local gas utility.
WARNING
HIG
H
VOLTAGE
D
ISCONNECT
ALL
ELECTRICAL POWER AND SHUT OFF GAS
SUPPLY BEFORE SERVICING OR INSTALLING THIS UNIT.
M
ULTIPLE POWER SOURCES MAY BE PRESENT.
F
AILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
5. Disconnect manometer after turning o gas at manual
shuto valve. Reinstall plug before turning on gas to fur-
nace.
6. Turn OFF any unnecessary gas appliances started in step 3.
7. Turn on gas to furnace and check for leaks. If leaks are
found, repair and then reinstall burner compartment door.
8. Turn on electrical power and verify proper unit operation.
WARNING
HIGH
VOLTAGE
D
ISCONNECT
ALL
ELECTRICAL POWER AND SHUT OFF GAS
SUPPLY BEFORE SERVICING OR INSTALLING THIS UNIT.
M
ULTIPLE POWER SOURCES MAY BE PRESENT.
F
AILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Gas Manifold Pressure Measurement and Adjustment
Natural Gas Adjustments
WARNING
HIG
H
VOLTA
GE
DISCONNECT ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY
BEFORE SERVICING OR INSTALLING.
NOTE: Follow this procedure to test the gas valve pressure
at 100% ring rate.
Only small variations in gas pressure should be made by
adjusting the gas valve pressure regulator. The manifold
pressure must be measured with the burners operating. To
measure and adjust the manifold pressure, use the following
procedure.
1. After turning o gas to furnace at the manual gas shuto
valve external to the furnace, remove burner compartment
door to gain access to the gas valve.
2. Connect a calibrated manometer (or appropriate gas
pressure gauge) at the gas valve outlet pressure tap.
L
INE VOLTAGE NOW PRESENT
WARNING
3. Turn ON the gas and electrical power supply and operate
the furnace.
4. White-Rodgers 36J27 Valves:
a. Remove 1/8” N.P.T. plug using 5/16” Allen wrench &
connect proper adapter for manometer connection.
b. Attach a hose and manometer to the outlet pressure
tap.
c. Turn ON the gas supply.
d. Turn on power and close thermostat “R” and “W1”

SERVICING
33
WARNING
HIGH VOLTAGE
D
ISCONNECT ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY
BEFORE SERVICING OR INSTALLING.
Gas Type Gas Input Nominal Range
50% .9" w.c.
100% 3.5" w.c.
50% 2.5" w.c.
100% 10.0" w.c.
Propane
.6"w.c. - 3.8"w.c.
2.2"w.c. - 10.3"w.c.
Manifold Gas Pressure
Natural
CHECKING HOT SURFACE IGNITER
120V Silicon Nitride Igniter - Amana® Brand and Good-
man® Brand A/GRVM97 and A/GDVM97 furnaces use a
120V silicon nitride igniter for ignition. The normal operating
temperature is approximately 2156°F - 2678°F.
D
ISCONNECT
ALL
POWER BEFORE SERVICING.
WARNING
1. Remove burner compartment door to gain access to the
igniter.
2. Igniter cool - approximately 70 - 77°F.
3. Disconnect the igniter from the Ignition Control.
4. Using an ohmmeter measure the resistance of the igniter:
120 Volt Silicon Nitride: 120V Nitride Igniter should read
between 37 to 68 ohms.
5. Reconnect igniter.
L
INE VOLTAGE NOW PRESENT
WARNING
6. Place unit in heating cycle, measure current draw of igniter
during preheat cycle.
The steady state current at 120V is 0.37 to 0.68 amps.
7. After checking and/or replacing of hot surface igniter,
reinstall burner compartment door and verify proper unit
operation.
contacts to provide a call for low stage heat.
e. Measure the gas manifold pressure with burners ring.
Adjust manifold pressure.
f. Use the modulation adjustment screw on the gas valve
and turn clockwise one click using a pocket screwdriver
to increase gas ow. Allow the gas ow to adjust ap-
proximately 15 seconds before moving the adjustment
screw again. Turn the modulation adjustment screw
counterclockwise with a pocket screwdriver to decrease
gas ow if this adjustment is needed. Allow the gas ow
to adjust approximately 15 seconds before moving the
adjustment screw again. These changes should only be
done to ne tune the gas ow.
g. Turn o all electrical power and gas supply to the system.
h. Remove the manometer hose and adapter from gas
valve.
i. Install 1/8” N.P.T. plug using 5/16” Allen wrench.
j. Turn on electrical and gas supply to the furnace.
Measuring Manifold Gas Pressure
(36J27 Valve)
WARNING
HIGH
VOLTAGE
D
ISCONNECT
ALL
ELECTRICAL POWER AND SHUT OFF GAS SUPPLY
BEFORE SERVICING OR INSTALLING.
WARNING
HIGH
VOLTAGE
D
ISCONNECT
ALL
ELECTRICAL POWER AND SHUT OFF GAS
SUPPLY BEFORE SERVICING OR INSTALLING THIS UNIT.
M
ULTIPLE POWER SOURCES MAY BE PRESENT.
F
AILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

34
SERVICING
CHECKING FOR FLASHBACK
Flashback will also cause burning in the burner venturi, but is
caused by the burning speed being greater than the gas-air
ow velocity coming from a burner port.
Flashback may occur at the moment of ignition, after a burner
heats up or when the burner turns o. The latter is known as
extinction pop.
Since the end results of ashback and delayed ignition can
be the same (burning in the burner venturi) a denite attempt
should be made to determine which has occurred.
If ashback should occur, check for the following:
1. Improper gas pressure - adjust to proper pressure
2. Check burner for proper alignment and/or replace burner.
3. Improper orice size - check orice for obstruction.
CHECKING PRESSURE CONTROL
The pressure control is a safety device to prevent the com-
bustion cycle from occurring with inadequate venting caused
by a restricted or blocked vent pipe. In addition to the high re
and low re pressure switches, A/GRVM97 and A/GDVM97
model furnaces have a "front cover pressure switch" wired
in series with the gas valve. This pressure switch keeps the
gas valve from opening in the event of condensate backing
up in the secondary heat exchanger. This could occur from
improperly connected drains or a plugged drain tube.
WARNING
HIGH
VOLTAGE
D
ISCONNECT
ALL
POWER BEFORE SERVICING OR
INSTALLING THIS UNIT.
M
ULTIPLE POWER SOURCES MAY
BE PRESENT.
F
AILURE TO DO SO MAY CAUSE PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
1. Remove burner compartment door to gain access to
pressure switch(es).
2. Remove wires from the pressure switch(es) electrical
terminals.
3. Remove the pressure control hose from the control and
interconnect with an manometer as shown in the following
gure.
4. With an ohm meter connected across the pressure switch
terminals and with the inducer running, the switch should
close and the ohm meter should show a complete circuit
across the pressure switch. If the switch is not closed,
compare the negative pressure to the closing point speci-
ed for the particular switch. Either the switch is defective
or the inducer/venting system is inadequate.
OPEN TO
ATMOSPHERE
INCLINED MANOMETER
HOSE TO INDUCED
DRAFT BLOWER TAP
1/4" TEE
INDUCED DRAFT BLOWER
PRESSURE SWITCH
PRESSURE SWITCH
HOSE
INDUCED
DRAFT
BLOWER
*
*
*
* *
*
*
M
1
2
3P
C
ON
O
F
F
COIL COVER
PRESSURE SWITCH
Blower Pressure Switch
Negative Pressure Measurement
(90% Upow Furnace Shown, Counterow Similar)
HIGH ALTITUDE APPLICATION (USA)
When furnaces are installed at high altitude, the appropriate
High Altitude Orice or Pressure Switch Kit must be applied.
This is required due to the natural reduction in the density of
both the gas fuel and combustion air as altitude increases.
The High Altitude Orice Kit will provide the proper design
certied input rate within the specied altitude range.
High Altitude Orice or Pressure Switch Kits are purchased
according to the installation altitude and usage of either natu-
ral or propane gas. Refer to the Technical Manual or product
Specication Sheet for a tabular listing of appropriate altitude
ranges and corresponding manufacturer's high altitude (Nat-
ural or Propane Gas) orice or pressure switch kits.
Do not derate the furnace by adjusting the manifold pressure
to a lower pressure than specied on the furnace rating plate.
The combination of the lower air density and a lower manifold
pressure will prohibit the burner orice from drawing the prop-
er amount of air into the burner. This may cause incomplete
combustion, ashback, and possible yellow tipping.
In some areas the gas supplier may articially derate the gas
in an eort to compensate for the eects of altitude. If the
gas is articially derated the appropriate orice size must be
determined based on the BTU/ft
3
content of the derated gas
and the altitude. Refer to the National Fuel Gas Code, NFPA
54/ANSI Z223.1, and information provided by the gas supplier
to determine the proper orice size.

SERVICING
35
CHECKING FOR DELAYED IGNITION
Delayed ignition is a delay in lighting a combustible mixture
of gas and air which has accumulated in the combustion
chamber.
When the mixture does ignite, it may explode and/or rollout
causing burning in the burner venturi.
If delayed ignition should occur, the following should be
checked. Furnace design makes this extremely unlikely un-
less safety controls have been by-passed or tampered with.
Never by-pass or alter furnace controls.
1. Improper gas pressure - adjust to proper pressure
2. Improper burner positioning - burners should be in locating
slots, level front to rear and left to right.
3. Carry over (lighter tube or cross lighter) obstructed - clean.
4. Main burner orice(s) deformed, or out of alignment to
burner - replace.
CHECKING INTEGRATED IGNITION CONTROL
BOARDS
NOTE: Failure to earth ground the furnace, reversing the
neutral and hot wire connection to the line (polarity), or a
high resistance connection in the neutral line may cause the
control to lockout due to failure to sense ame.
TO AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO THE UNIT
MUST BE PROPERLY POLARIZED AND GROUNDED.
DISCONNECT POWER
BEFORE PERFORMING SERVICE LISTED BELOW.
WARNING
The ground wire must run from the furnace all the way back
to the electrical panel. Proper grounding can be conrmed by
disconnecting the electrical power and measuring resistance
between the neutral (white) connection and the burner closest
to the ame sensor. Resistance should be less than 2 ohms.
The ignition control is a combination electronic and electro-
mechanical device and is not eld repairable. Complete unit
must be replaced.
L
INE VOLTAGE NOW PRESENT
WARNING
These tests must be completed within a given time frame due
to the operation of the ignition control. The trial for ignition
period is 4 seconds.
The ignition control is capable of diagnosing many furnace
failures to help in troubleshooting. The control utilizes a dual,
7-segment LED display to indicate diagnostic codes.
When the control is powered up normally the light will be on
continuously. The display will indicate "ON" when powered
and in standby mode. This can be used to test for 120 volts
and 24 volts to the control since both must be present for
the light to be on. If this step fails, check for 120 volts to the
control and check the transformer and its associated wiring.
If this step is successful give the control a call for heat and
wait ve (5) seconds or until the furnace goes into lockout. If
the control detects a failure it will now be shown on the diag-
nostic indicator light/display. Refer to the Abnormal Operation
section in the Sequence of Operation section of this manual
for more detail on failure codes.
1. Check for 120 volts from Line 1 (Hot) to Line 2 (Neutral)
at the ignition control. No voltage, check the door switch
connections and wire harness for continuity.
2. With the thermostat calling for heat, check for 24 volts
from W1 to C terminal on the ignition control. No voltage.
Check transformer, room thermostat, and wiring.
If you have 24 volts coming o the transformer but receive
approximately 13 volts on the terminal board between (C)
and (R), check for blown fuse.
3. Check for 120 volts to the induced draft blower (low-stage)
by measuring voltage between Pin 3 and Pin 4 (on the
5-pin connector) located on circuit board. No voltage,
check for loose connection in the 5-pin connector or re-
place ignition control.
Check for 120 volts to the induced draft blower (high-
stage) by measuring voltage between Pin 2 and Pin 4 (on
the 5-pin connector) located on circuit board. No voltage,
check for loose connection in the 5-pin connector, no call
for high stage heat or replace ignition control.
4. If voltage is present in Steps 1 through 3 and the induced
draft blower is operating, check for 120 volts to the igniter
during the preheat cycle. Measure voltage between Pin
1 and Pin 5 (on the 5-pin connector) located on ignition
control. No voltage, check low stage and high stage pres-
sure switches or replace the ignition control board.
5. After the igniter warm-up time, begin checking for 24 volts
to the gas valve. Voltage will be present for seven seconds
only if proof of ame has been established.
6. If proof of ame was established voltage will be provided
to the air circulation blower following the heat on delay
period.
a. BEFORE replacing the ECM motor assembly or the
end bell, rst check the motor with a Goodman #UTT-
01 UltraCheck-EZ
TM
diagnostic tool. If the motor runs
with the diagnostic tool, the motor is good. To check
the end bell, see the previous variable speed testing
section of this manual before replacing the end bell.
b. The two-stage variable speed furnaces should have
120 Volts at the motor at all times, even without a
call for cooling or heating. These motors receive their
operational signals through the 4-pin wiring harness,
connected between the motor and integrated control
board.

36
SERVICING
CHECKING FLAME SENSOR
A ame sensing device is used in conjunction with the ignition
control module to prove combustion. If proof of ame is not
present the control will de-energize the gas valve and "retry"
for ignition or lockout.
WARNING
HIGH
VOLTAGE
D
ISCONNECT
ALL
POWER BEFORE SERVICING OR
INSTALLING THIS UNIT.
M
ULTIPLE POWER SOURCES MAY
BE PRESENT.
F
AILURE TO DO SO MAY CAUSE PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
1. Disconnect the ame sensor wire from the sensor.
2. Connect a micro-amp meter in series with this wire and
the sensor terminal.
3. Be sure the positive side of the meter is to the ame sen-
sor wire and the negative side of the meter is to sensor
terminal.
L
INE VOLTAGE NOW PRESENT
WARNING
4. Place the unit into a heating cycle.
5. As soon as ame is established a micro-amp reading
should be evident once proof of ame (micro-amp reading)
is established, the hot surface igniter will be de-energized.
6. The Integrated Ignition controls will have 1 to 8 mi-
cro-amps. If the micro-amp reading is less than the
minimum specified, check for high resistance wiring
connections, sensor to burner gap, dirty ame sensor, or
poor grounding.
7. If absolutely no reading, check for continuity on all com-
ponents and if good - replace ignition control module.
NOTE: Contaminated fuel or combustion air can create a
nearly invisible coating on the ame sensor. This coating
works as an insulator causing a loss in the ame sense sig-
nal. If this situation occurs the ame sensor must be cleaned
with steel wool.

37
STATUS CODES
Name 7-Segment Display Cloud / Phone App
Idle
L
Idle
Constant Fan
Constant Fan
Compressor Cooling, Low Stage
Compressor Cooling, Low Stage
Compressor Cooling, High Stage
Compressor Cooling, High Stage
Compressor Heat, Low Stage
Compressor Heat, Low Stage
Compressor Heat, High Stage
Compressor Heat, High Stage
Gas Heat, Low Stage
Gas Heat, Low Stage
Gas Heat, High Stage
Gas Heat, High Stage
Defrost, Low Stage Gas Heat
Defrost, Low Stage Gas Heat
Defrost, High Stage Gas Heat
Defrost, High Stage Gas Heat
Name 7-Segment Display Cloud / Phone App
Idle
L
Idle
Constant Fan
Constant Fan
Compressor Cooling
Compressor Cooling
Compressor Heat
Compressor Heat
Gas Heat, Low Stage
Gas Heat, Low Stage
Gas Heat, High Stage
Gas Heat, High Stage
Defrost, Low Stage Gas Heat
Defrost, Low Stage Gas Heat
Defrost, High Stage Gas Heat
Defrost, High Stage Gas Heat
Name 7-Segment Display Cloud / Phone App
Idle
L
Idle
Constant Fan
Constant Fan
Compressor Cooling, Low Stage
Compressor Cooling, Low Stage
Compressor Cooling, High Stage
Compressor Cooling, High Stage
Compressor Cooling, Single Stage
Compressor Cooling, Single Stage
Compressor Heat, Low Stage
Compressor Heat, Low Stage
Compressor Heat, High Stage
Compressor Heat, High Stage
Compressor Heat, Single Stage
Compressor Heat, Single Stage
Gas Heat, Low Stage
Gas Heat, Low Stage
Gas Heat, High Stage
Gas Heat, High Stage
Defrost, Low Stage Gas Heat
Defrost, Low Stage Gas Heat
Defrost, High Stage Gas Heat
Defrost, High Stage Gas Heat
Name 7-Segment Display Cloud / Phone App
Humidifier
Humidifier
De-Humidifier
De-Humidifier
Ventilator
L
Ventilator
Single-Stage AC, Legacy 2-Stage
Humidifier, De-Humidifier and Ventilator
ClimateTalk Comm Inverter AC/HP
ClimateTalk Comm 2-Stage AC/HP

38
MENU OPTIONS
Name/Cloud/Phone App 7 Segment Display User Modifiable Options Comments
Last 10 Faults
N/A Views the control last 10 history faults.
Learn Menu
Yes or No. Resets communication network.
Code Release No
N/A Views the control firmware revision number and Shared Data number.
Shared Data Revision
N/A Views the control Shared Data revision number and shared data upload.
Reset To Factory Default
Yes or No. Reset the furnace setting to factory defaults.
Constant Fan Speed
Adjustable between 25% to + 100% with 10% ingrements.
Default is 25%.
Select the indoor blower airflow at constant fan mode.
Gas Heating Airflow
Adjustable between Min and Max. Min, Max, Step and
Default are defined in Shared Data.
Select the indoor blower airflow multiplier for gas heat operation.
Gas Heat Off Delay
Adjustable between 30 seconds to 180 seconds with 5
seconds increments. Default is 30 seconds.
Selects the indoor blower heat off delay.
Gas Heat On Delay
Adjustable between 5 seconds to 30 seconds with 30 seconds
increments. Default is 90 seconds.
Selects the indoor blower heat off delay.
Gas Heat Trim Factor
Adjustable between -10% to +10% with 2% increments.
Default is 0%.
Trims the heating airflow by the selected amount.
Gas Heat Stage Multiplier
Adjustable between Min and Max. Min, Max, Step and
Default are defined in Shared Data.
Selects gas heat stage multiplier
Gas Pressure Test
Yes or No. Checks gas valve pressure at 100% firing rate.
Function Enable/Disable
Not implemented in the initial
Backup Heat Balance Points
Adjustable between Min and Max. Min, Max, Step and
Default are defined in Shared Data.
This menu only shows up when a communicating Heat Pump is detected.
Comfort Setting
First 5 option values are defined in Shared Data. The 6th option
shall be hard-coded in the firmware with other 5 settings. The
Provides the 6 comfort setting options for the furnace staging algorithm operation,
only shows up when ClimateTalk or DataAC T-Stat is not connected.
Hum On Enable
1 ~ 16 options and the default option is 15. Provides the 16 humidifier enabling options in different operation modes.
Ventilation On Time
Adjustable between 0 ~ 60 minutes. The default is 0 minute
Off).
Adjusts the ventilation on time and turn it on/off.
DeHum Logic
Hi and Lo. The default is Lo.
Provides the DeHum logic input level for DeHum operation. Only applies
when the legacy 24VAC input is active.
A2L Function Verification
Yes or No. Refer to R-32 Section.
A2L Function Enabled
Yes or No. Enables or disables A2L functions. Refer to R-32 section.
Name/Cloud/Phone App 7 Segment Display User Modifiable Options Comments
Tonnage
Adjustable between 1 to 6 ton with 0.1 increments.
Default is 3 ton.
Only visible when communicating outdoor unit is not detected.
Cool Trim Factor
Adjustable between -10% to +10% with 2% increments.
Default is 0%.
Trims the cooling airflow by the selected amount.
Cool Airflow Profile
A(1), B(2), C(3), D(4 or 5) Select cooling airflow profiles.
Cool On Delay
Adjustable between 5 to 30 seconds with 5 seconds
increments. Default is 5 seconds.
Selects the cooling on delay.
Cool Off Delay
Adjustable between 30 to 120 seconds with 30 seconds
increments. Default is 60 seconds.
Selects the cooling off delay.
Cool Stage Multiplier
Adjustable between 60% to + 100% with 1% increments.
Default is 70%.
Selects stage multiplier for 2-stage OD unit.
Defrost Gas Heat Stage
1 or 2 Selects the gas heat stage for defrost operation.
Compressor Balance Points
Adjustable and defined in Shared Data Provides the compressor balance point options for HP operation.
HP Trim Factor
Adjustable between -10% to +10% with 2% increments.
Default is 0%.
Trims the heating airflow by the selected amount.
HP On Delay
Adjustable between 5 to 30 seconds with 5 seconds
increments. Default is 5 seconds.
Selects the HP heating on delay.
HP Off Delay
Adjustable between 30 to 120 seconds with 30 seconds
increments. Default is 60 seconds.
Selects the HP heating off delay
HP Stage Multiplier
Adjustable between 70% to 100% with 5% increments.
Default is 70%.
Select stage multiplier for 2-stage OD unit.
Name/Cloud/Phone App 7 Segment Display User Modifiable Options Comments
Cool Trim Factor
-10%, -8%,-6%, -4%, -2%, 0%, 2%, 4%, 6%, 8%,10% Trims the cooling airflow by the selected amount.
Cool Airflow Profile
A, B, C, D Select cooling airflow profiles.
Cool On Delay
5, 10, 20, 30 Selects the cooling on delay.
Furnace
Outdoor AC/HP, Single-Stage AC/HP
ClimateTalk Comm Outdoor 2-Stage AC/HP

39
MENU OPTIONS
Push Button Menu Options
Name/Cloud/Phone App
7 Segment Display
User Modifiable Options
Comments
Cool Trim Factor
-10%, -8%,-6%, -4%, -2%, 0%, 2%, 4%, 6%, 8%,10% Trims the cooling airflow by the selected amount.
Cool Airflow Profile
A, B, C, D Select cooling airflow profiles.
Cool On Delay
5, 10, 20, 30 Selects the cooling on delay.
Cool Off Delay
30, 60, 90, 120 Selects the cooling off delay.
Dehumidifcation Enable
ON, OFF Enables the dehum function for OD operation.
Defrost Gas Heat Stage
1 or 2 Selects the gas heat stage for defrost operation.
Compressor Balance Points
Adjustable and defined in Shared Data Selects the compressor balance point options for HP operation.
HP Trim Factor
-10%, -8%,-6%, -4%, -2%, 0%, 2%, 4%, 6%, 8%,10% Trims the heating airflow by the selcted amount
HP On Delay
5, 10, 15 Selects the HP heating on delay.
HP Off Delay
30, 50, 70, 90 Selects the HP heating off delay.
HP Defrost Interval
30, 60, 90, 120 Provides the defrost options for compressor heating operation.
Compressor Delay L
0, 5, 15, 30 Provides the compressor delay options for heating operation.
History Fault and Clear L
Yes or No.
Views the comm outdoor history and clear the outdoor unit
history fault.
Name/Cloud/Phone App
7 Segment Display
User Modifiable Options
Comments
Boost Mode
On or Off Provides the options for inverter boot operation.
Boost Temp
On(Always), 70F, 75F, 80F, 85F, 90F, 95F, 100F, 105F Provides the 9 temperature options for boot operation.
Set Max Current
OFF, 40%, 50%, 60%, 70%, 80%, 90% Selects Max Current options
Vertical Rise
SL (Same Level), OL (Outdoor Lower), IL (Indoor
Lower)
Selects the level of outdoor vas indoor equipment.
System Reset Menu
Yes or No. Reset all outdoor unit settings to factory default.
System Verification Test
On or Off Runs System Verification Test after Installation.
Pump Down
On or Off Enters Pump Down mode.
Charge Mode
On or Off Enters charge mode.
Cool-Trim Factor - High
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15 Trims the cooling airflow by the selected amount.
Cool-Trim Factor - Intermediate
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15 Trims the cooling airflow by the selected amount.
Cool-Trim Factor - Low L
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15 Trims the cooling airflow by the selected amount.
Cool Airflow Profile
A, B, C, D Select cooling airflow profiles.
Cool On Delay
5, 10, 20, 30 Selects the cooling on delay.
Cool Off Delay
30, 60, 90, 120 Selects the cooling off delay.
Dehum Enable
On or Off Enables the dehum function for compressor operation.
Cool Reset Menu L
Yes or No. Resets all cooling settings to factory default.
Cool Max RPS Range
01(58 to 62.5 RPS), 02(63 to 67.5 RPS), 03(68RPS),
04(68.5 to 73 RPS), 05(73.5 to 78 RPS)
Selects the appropriate range for the installed system
configuration.
Cool Max RPS Selection
10 RPS values from inverter
Selects the appropriate compressor RPS for the installed system
configuration.
Defrost Gas Heat Stage
1 or 2 Selects the gas heat stage for defrost operation.
Compressor Balance Points
Adjustable and defined in Shared Data Provides the compressor balance point options for HP operation.
Force Defrost
On or Off
HP Trim Factor - High
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15 Trims the heating airflow by the selected amount.
HP Trim Factor - Intermediate
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15 Trims the heating airflow by the selected amount.
HP Trim Factor - Low L
-15, -12, -9, -6, -3, 0, 3, 6, 9, 12, 15 Trims the heating airflow by the selected amount.
HP On Delay
5, 10, 20, 30 Selects the HP heating on delay.
HP Off Delay
30, 60, 90, 120 Selects the HP heating on delay.
HP Defrost Interval
Maximum amount of compressor runtime before
defrost occurs.
Provides the defrost options for compressor heating operation.
HP Reset Menu
Yes or No. Resets all heating settings to factory default.
HP Max RPS Range
01(58 to 62.5 RPS), 02(63 to 67.5 RPS), 03(68RPS),
04(68.5 to 73 RPS), 05(73.5 to 78 RPS)
Selects the appropriate range for the installed system
configuration.
HP Max RPS Selection
10 RPS values from inverter
Selects the appropriate compressor RPS for the installed system
configuration.
History Fault and Clear L
Yes or No.
Views the comm outdoor history and clear the outdoor unit
history fault.
ClimateTalk Comm Outdoor 2-Stage AC/HP
ClimateTalk Comm Outdoor Inverter AC/HP

TROUBLESHOOTING
40
Internal Control Fault
Lockout Due to Exces s i ve Retri es or Recycl es
Status
Seven Segment Display
Alarm Code Definition Table
Low Stage Pres s ure Swi tch Stuck Cl os ed At
the Beginning of Heating
Low Stage Pres s ure Swi tch Open
Open High Limit Switch
Flame Detected When no Flame Should be
Pres ent
Open Fuse
Low Fl ame Si gnal
Igniter Fault or Improper Grounding
High Stage Pressure Switch Stuck Closed at
Start of Heating Cycle
Hi gh Sta ge Pres s ure Swi tch Open
Revers ed Li ne Pol a ri ty
Internal Gas Valve Error
External Gas Val ve Error
Auxiliary Limit Switch Open
Condensate Switch Open
Grounding Fault
Rollout Switch Open
Redundant Relay Open
Redundant Relay Stuck Closed
Status
Data Not Yet on Network
Invalid Data on Network
Invalid External Shared Data
Invalid Downloaded Firmware
Un-Recognized Data ID
Blower Motor Not Running
Blower Communication Alarm
Blower Motor HP/ID Mismatch
Blower Motor Operating in Power,
Temperature, or Speed Limit
Blower Motor Current Trip or Lost Rotor
Blower Motor Locked Rotor
Over/Under Voltage Trip or Over
Temperature Trip
Incomplete Parameters Sent to Motor
Inadequate Airflow
Network Communication Alarm
E-Module Network Communication Alarm
Bluetooth Module Network Communication
Alarm
A2L Sensor Comm Alarm
A2L Refrigerant Leakage Alarm
A2L Sensor Internal Alarm
A2L Relay Alarm
Seven Segment Display
Alarm Code Definition Table

TROUBLESHOOTING
41
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Normal operation.
Idle • Normal operation. • None • Normal operation.
Furnace fails to operate.
Integrated control module
LED display provides no
signal.
No 115v power to furnace or no
24 volt power to integrated
control module.
Blown fuse or tripped circuit
breaker.
Integrated control module is non-
functional.
• Manual disconnect switch turned
OFF, door switch open or 24 volt wire
improperly connected or loose.
• Furnace electrical supply shared
with other devices.
• Integrated control module is non-
functional.
• Check 115 volt power to furnace and
integrated control module.
• Check for possible shorts in 115 volt
circuit. Repair as necessary.
• Replace non-functional integrated
control module.
• Turn power OFF prior to repair.
• Read precautions in "Electrostatic
Discharge" section of manual.
• Replace control with correct
replacement part.
Furnace fails to operate.
Circulator blower motor not
running when it should be
running.
• Loose wiring connection at
circulator motor power leads or
circulator motor power leads
disconnected.
• Failed circulator blower motor
• Tighten or correct wiring connection.
• Check circulator blower motor.
Replace if necessary.
• Turn power OFF prior to repair.
• Replace circulator motor with
correct replacement part.
Furnace fails to operate.
Integrated control module has
lost communications with
circulator blower motor.
• Loose wiring connection at
circulator motor power leads,
• Failed circulator blower motor.
• Failed integrated control module.
• Tighten or correct wiring connection.
• Check circulator blower motor.
Replace if necessary.
• B28:B32Check integrated control
module. Replace if necessary.
• Turn power OFF prior to repair.
• Replace circulator motor with
correct replacement part.
• Replace integrated control module
with correct replacement part.
Furnace fails to operate.
Circulator blower motor horse
power in shared data set does
not match circulator blower motor
horse power.
• Incorrect circulator blower motor in
furnace.
• Incorrect shared data det in
integrated control module.
• Verify circulator blower if motor
horsepower is the same specified for the
specific model. Replace if necessary.
• Verify shared data set is correct for the
specific model. Re-populate data using
the CoolCloud HVAC App if required.
• Turn power OFF prior to repair.
• Replace circulator motor with
correct replacement part.
• Error code will be cleared once
shared data and motor horsepower
match.
Furnace operates at reduced
performance.
Airflow delivered is less than
expected.
Circulator blower motor is
operating in a power,
temperature or speed limiting
condition.
• Blocked filters.
• Restrictive ductwork.
• Undersized ductwork.
• High ambient temperatures.
• Check filters for blockage. Clean filters
or remove obstruction.
• Check ductwork for blockage. Remove
obstruction. Verify all registers are fully
open.
• Verify ductwork is appropriately sized
for system. Resize/replace ductwork if
necessary.
• See "III. Product Description" and "IV
Location Requirements &
Considerations" for furnace installation
requirements.
• Turn power OFF prior to repair.
Furnace fails to operate.
Circulator blower motor senses a
loss of rotor control.
Circulator blower motor senses
high current.
• Abnormal motor loading, sudden
change in speed or torque, sudden
blockage of furnace air inlet/outlet.
• Check filters, filter grilles, registers,
duct system and furnace air inlet/outlet
for blockages.
• Turn power OFF prior to repair.
Furnace fails to operate.
Circulator blower motor fails to
start 10 consecutive times.
• Obstruction in circulator blower
housing.
• Seized circulator blower motor
bearings.
• Failed circulator blower motor.
• Check circulator blower for
obstructions. Remove and
repair/replace wheel or motor if
necessary.
• Turn power OFF prior to repair.
• Replace motor with correct
replacement part.
• Replace wheel with correct
replacement part.
Furnace fails to operate.
Circulator blower motor shuts
down due to over or under
voltage condition.
Circulator blower motor shuts
down due to over temperature
condition on power module.
• High AC line voltage to furnace.
• Low AC line voltage to furnace.
• High ambient temperatures.
• Check power to furnace. Verify line
voltage to furnace is within the range
specified on the furnace rating plate.
See "III. Product Description" and "IV
Location Requirements &
Considerations" for furnace installation
requirements.
• Turn power OFF prior to repair.
• Replace motor with correct
replacement part.
• Re-populate data using the
CoolCloudHVAC App if required.
Furnace fails to operate.
Circulator blower motor does not
have enough information to
operate properly.
Motor fails to start 40
consecutive times.
• Error with integrated control
module.
• Motor has a rotor condition.
• Check integrated control module.
Verify control is populated with correct
shared data set. See data errors above
for details.
• Check for locked rotor condition.
• Turn power OFF prior to repair.

TROUBLESHOOTING
42
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Furnace operates at reduced
performance or operates on
low stage when high stage is
expected.
Airflow is lower than demanded.
• Blocked filters.
• Restrictive ductwork.
• Undersized ductwork.
• High ambient temperatures.
• Check filters for blockage. Clean filters
or remove obstruction.
• Check ductwork for blockage. Remove
obstruction. Verify all registers are fully
open.
• Verify ductwork is appropriately sized
for system. Resize/replace ductwork if
necessary.
• Turn power OFF prior to repair.
Furnace fails to operate.
Data not yet on network. • No network Data
• Populate shared data set using the
CoolCloudHVAC App.
• Turn power OFF prior to repair.
• Use the CoolCloudHVAC App to
download the shared data set to the
furnace.
• Error code will be cleared once
data is downloaded from the
CoolCloudHVAC App.
Operation different than
expected or no operation.
Invalid shared data.
• Shared data set is invalid. Use the
CoolCloudHVAC App to download
the shared data to the furnace.
• Verify shared data set is correct for the
specific model. Re-populate shared data
set using the CoolCloudHVAC App.
• Turn power OFF prior to repair.
• Error code will be cleared once
data is downloaded from the
CoolCloudHVAC App.
Furnace fails to operate.
Furnace lockout due to excessive
number of ignition "retries" (3
total).
Failure to establish flame.
Loss of flame after
establishment.
• Failure to establish flame. Cause
may be no gas to burners, front cover
pressure switch stuck open, bad
igniter or igniter alignment, improper
orifices, or coated/oxidized or
improperly connected flame sensor.
• Loss of flame after establshment.
Cause may be interrupted gas
supply, lazt burner flames (improper
gas pressure or restriction in flue
and/or combustion air piping), front
cover pressure switch opening, or
improper induced draft blower
performance.
• Locate and correct gas interruption.
• Check front cover pressure switch
operation (hose, wiring, contact
operation). Correct if necessary.
• Replace or realign igniter.
• Check flame sense signal. Clean
sensor if coated and/or oxidized.
• Check flue piping for blockage, proper
length, elbows and termination.
• Verify proper induced draft blower
performance.
• Turn power OFF prior to repair.
• Igniter is fragile, handle with care.
• Clean flame sensor with steel
wool.
• See "Vent/Flue Pipe" section for
piping details.
Furnace fails to operate.
Low-stage pressure switch circuit
closed at start of heating cycle.
• Low stage pressure switch contacts
sticking.
• Short in pressure switch circuit
wiring.
• Replace low stage pressure switch.
• Repair short in wiring.
• Turn power OFF prior to repair.
• Replace pressure switch with
proper replacement part.
Induced draft blower runs
continuously with no further
furnace operation.
Low-stage pressure switch circuit
open.
• Pressure switch hose blocked,
pinched, or connected improperly.
• Blocked flue and/or inlet air pipe,
blocked drain system or weak
induced draft blower.
• Incorrect pressure switch set point
or malfunctioning switch contacts.
• Loose or improperly connected
wiring.
• Inspect pressure switch hose.
Repair/replace if necessary.
• Inspect flue and/or inlet air piping for
blockage, proper length, elbows and
termination. Check drain system.
Correct as necessary.
• Correct pressure switch set point or
contact motion.
• Tighten or correct wiring connections.
• Turn power OFF prior to repair.
• Replace pressure switch with
proper replacement part.
• Replace induced draft blower with
proper replacement part.
Circulator blower runs
continuously with no furnace
operation.
Primary limit circuit open.
• Insufficient conditioned air over the
heat exchanger.
• Blocked filters, restrictive ductwork.
• Inproper circulator blower speed or
failed circulator blower motor.
• Loose or improperly connected
wiring in high limit circuit.
• Check filters and ductwork for
blockage. Clean filters or remove
obstruction.
• Check circulator blower speed and
performance. Correct speed or replace
blower motor if necessary.
• Tighten or correct wiring connections.
• Turn power OFF prior to repair.
• See Specification Sheet applicable
for your model for allowable temp
rise range and proper circulator
speed.
Induced draft blower and
circulator blower run
continuously with no furnace
operation.
Flame sensed with no call for
heat.
• Short to ground in flame sense
circuit.
• Lingering burner flame.
• Slow closing gas valve.
• Correct short at flame sensor or in
flame sensor wiring.
• Check for lingering flame.
• Verify proper operation of gas valve.
• Turn power OFF prior to repair.
No furnace operation.
Open fuse. • Short in low voltage wiring
• Locate and correct short in low voltage
wiring.
• Turn power OFF prior to repair.
• Replace fuse with 3-amp
automotive type.

TROUBLESHOOTING
43
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Normal furnace operation with
weak flame signal.
Flame sense micro amp signal is
low.
• Flame sensor is coated/oxidized.
• Flame sensor incorrectly positioned
in burner flame.
• Lazy burner flame due to improper
gas pressure or combution air.
• Clean flame sensor if coated or
oxidized.
• Inspect flame sensor for proper
alignment.
• Check inlet air piping for blockage,
proper length, elbows and termination.
• Compare current gas pressure to
rating plate and adjust as needed.
• Turn power OFF prior to repair.
• Clean flame sensor with steel
wool.
• See "Vent/Flue Pipe" section for
piping details.
• See rating plate for proper gas
pressure.
Furnace fails to operate.
Problem with igniter circuit.
• Improperly connected igniter.
• Shorted igniter.
• Poor furnace ground.
• Igniter relay fault on integrated
control module.
• Check and correct wiring from
integrated control module to igniter.
• Replace shorted igniter.
• Check and correct furnace ground
wiring.
• Check igniter output from control.
Replace if necessary.
• Turn power OFF prior to repair.
• Replace ingiter with correct
replacement part.
• Replace control with correct
replacement part.
Furnace fails to operate on
high stage. Furnace operates
normally on low stage.
High-stage pressure switch
circuit closed at start of heating
cycle.
• High stage pressure switch contacts
sticking.
• Short in pressure switch circuit
wiring.
• Replace high stage pressure switch.
• Repair short in wiring.
• Turn power OFF prior to repair.
• Replace pressure switch with
proper replacement part.
Furnace fails to operate on
high stage. Furnace operates
normally on low stage.
High-stage pressure switch
circuit open.
• Pressure switch hose blocked,
pinched, or connected improperly.
• Blocked flue and/or inlet air pipe,
blocked drain system or weak
induced draft blower.
• Incorrect pressure switch set point
or malfunctioning switch contacts.
• Loose or improperly connected
wiring.
• Inspect pressure switch hose.
Repair/replace if necessary.
• Inspect flue and/or inlet air piping for
blockage, proper length, elbows and
termination. Check drain system.
Correct as necessary.
• Check induced draft blower
performance. Correct as necessary.
• Correct pressure switch set point or
contact motion.
• Tighten or correct wiring connections.
• Turn power OFF prior to repair.
• Replace pressure switch with
proper replacement part.
• Replace induced draft blower with
proper replacement part.
Furnace fails to operate.
Grounding fault • Poor neutral connection.
• Verify neutral wire connection to
furnace and continuity to ground source.
• Turn power OFF prior to repair.
Furnace fails to operate.
Open rollout switch.
• Gas pressure too high.
• Burners mis-aligned.
• Restricted heat exchanger or
venting.
• Check and correct gas pressure.
• Check and correct burner alignment.
• Check and correct restriction
• Turn power OFF prior to repair.
External return air
temperature reading not
visible on CoolCloud app
Return Air Temperature Sensor
Circuit is Open (External)
NOTE: Allow time as the control may
take up to 90 seconds to detect sensors.
• Verify that the sensor probe is plugged
in all the way
• Verify that the sensor probe connector
is properly crimped.
• Verify that resistance across the
sensor probe is 10kΩ at 77°F.
Resistance is lower at temperatures
higher than 77°F. Resistance is higher
at temperatures lower than 77°F.
• Replace PCB
External return air
temperature reading not
visible on CoolCloud app
Return Air Temperature Sensor
Circuit is Shorted (External)
• Check sensor probe terminals &
conductors for electrical short.
• Check PCB connector for shorts if
sensor short error reported when sensor
probe is not plugged in.
• Replace PCB
Supply air temperature
reading not visible on
CoolCloud app
Supply Air Temperature Sensor
Circuit is Open (External)
NOTE: Allow time as the control may
take up to 90 seconds to detect sensors.
• Verify that the sensor probe is plugged
in all the way
• Verify that the sensor probe connector
is properly crimped.
• Verify that resistance across the
sensor probe is 10kΩ at 77°F.
Resistance is lower at temperatures
higher than 77°F. Resistance is higher
at temperatures lower than 77°F.
• Replace PCB

TROUBLESHOOTING
44
Symptom
LED
Status
Fault Description Possible Causes Corrective Action(s) Notes & Cautions
Supply air temperature
reading not visible on
CoolCloud app
E18
Supply Air Temperature Sensor
Circuit is Shorted (External)
• Check sensor probe terminals &
conductors for electrical short.
• Check PCB connector for shorts if
sensor short error reported when sensor
probe is not plugged in.
• Replace PCB
Onboard return air
temperature reading not
visible on CoolCloud app
E19
Onboard return air temperature
sensor is unplugged
• Power cycle the furnace, the control
may take up to 90 seconds to detect
sensors
• Check PCB for any visible electrical or
mechanical damage to onboard sensor
(R311).
• Replace PCB
Onboard return air
temperature reading not
visible on CoolCloud app
E1A
Onboard return air temperature
sensor is shorted
• Power cycle the furnace, the control
may take up to 90 seconds to detect
sensors
• Check PCB for any visible electrical or
mechanical damage to onboard sensor
(R311).
• Replace PCB
Furnace fails to operate. EEr
Polarity if 115 volt AC is
reversed.
• Polarity of 115 volt AC power to
furnace or integrated control module
is reversed.
• Poor furnace ground.
• Review wiring diagram to correct
polarity.
• Verify proper ground. Correct if
necessary.
• Check and correct wiring.
• Turn power OFF prior to repair.
Furnace fails to operate. EEb
Gas valve is not energized when
it should be.
External gas valve error.
• Miswired gas valve circuit.
• Open gas valve circuit.
• Gas valve relay on integrated
control board stuck open.
• Check wiring in gas valve circuit.
• Replace integrated control board.
• Turn power OFF prior to repair.
Furnace fails to operate. EEC
Gas valve is energized when it
should not be.
Internal gas valve error.
• Miswired gas valve circuit.
• Shorted gas valve wiring.
• Gas valve relay on integrated
control board stuck open.
• Check wiring in gas valve circuit.
• Replace integrated control board.
• Turn power OFF prior to repair.
Furnace fails to operate. EEd
Aux limit switch open (blower
compartment).
• 115 volt power supply was shut off
during heat cycle.
• Insufficient conditioned air over the
heat exchanger. Blocked filters,
restrictive ductwork, improper
circulator blower speed or failed
circulator blower motor.
• Check filters and ductwork for
blockage. Clean filters or remove
obstruction.
• Check circulator blower speed and
performance. Correct speed or replace
blower motor if necessary.
• Tighten or correct wiring connections.
• Turn power OFF prior to repair.
• See Specification Sheet applicable
for your model for allowable temp
rise range and proper circulator
speed.
Furnace fails to operate. EEF
AUX switch (condensate switch)
open.
• High water level in evaporator coil
drain pan or auxiliary drain pan
• Check evaporatpr coil drain pan, trap,
piping and auxiliary drain pan.
• Turn power OFF prior to repair.
Furnace fails to operate. EbF Inducer communicating error.
• Ensure the inducer connector is
properly inserted and the integrated
control module is properly grounded.
• Turn power OFF prior to repair.
Furnace fails to operate. ECF
Gas valve stepper motor
communication error.
• No power to gas valve • Verify voltage to gas valve. • Turn power OFF prior to repair.
Furnace stops heating and
only the fan is operating.
EAF
Furnace has lost communication
with the R-32 sensor and the
furnace is in mitigation mode.
• Verify wire connection to R-32 sensor
is not loose.
• Verify the R-32 sensor wire is not
damaged.
• Replace R-32 sensor if necessary.
• Turn power OFF prior to repair.
• Replace R-32 sensor with proper
replacement part.
Furnace stops heating and
only the fan is operating.
EA0
R-32 sensor has detected a
refrigerant leak and furnace is in
mitigation mode.
• Investigate the indoor coil for a
refrigerant leak.
• Furnace will resume normal operation
once a leak is not detected and the 5
minute delay period is over.
• Turn power OFF prior to repair.
Furnace stops heating and
only the fan is operating.
EA1
R-32 sensor has detected a fault
and furnace is in mitigation
mode.
• Investigate the R-32 sensor.
• Replace the R-32 sensor if necessary.
• Turn power OFF prior to repair.
• Replace R-32 sensor with proper
replacement part.
Furnace stops heating and
only the fan is operating.
EA2
A2L relay in the furnace control
board has detected a fault and
furnace is in mitigation mode.
• Investigate the A2L relay.
• Cycle power to the furnace.
• Replace the integrated control board if
necessary.
• Turn power OFF prior to repair.
• Replace the integrated control
board with proper replacement part.

45
Troubleshooting ComfortBridge - 97% (Mod)
No Heat
Replace gas valve to match gas
type
Does gas valve type match
the gas being used, Check
label on side of gas valve
denoting gas type, either
LP or NAT
No
Replace front cover PS
Correct drainage issue, installed
incorrectly, blocked etc
No
No
Is front cover
pressure
switch
closed
Is furnace holding
condensate internally
above the front cover
PS port
Yes
Yes
Yes
Replace gas valve
Yes
Verify 24v from W to C
Check wiring harness between
board & draft inducer, if wiring
ok, replace board
Replace draft inducer
Replace PS
Replace igniter
Yes
If all check ok replace control
board
Does furnace
triple 7
segment LED
display IDL
Is thermostat calling
for heat and furnace
LED display show
g1 or gH2
No
Check furnace breaker, switch, door
switch, 115 vac at Line H & Line N on
control board, 115 VAC at transformer
primary, 24 VAC at transformer
secondary
No
Check for vent obstruction or
excessive vent length / elbows
Is inducer
motor running
Yes
Does igniter
warm up at all
No
Is low fire
PS closed
No No
Is draft inducer motor
getting 30 VAC min
between all three phases
from control board
Yes
Is negative
pressure
enough to close
low fire PS
No
No
Yes
Yes
Yes
Allow 1 minute for furnace calibration
on power up, inducer will ramp up
and down during this time.
low fire pressure switch is not
staying closed
igniter relay on control board is
faulty, replace board.
Yes
Igniter
resistance 37-68
ohms at room
temperature
No
Does igniter
stay on for 17
second warm
up
Yes
Make tubing corrections as
necessary
Correct gas supply pressure
problem
Yes
No
Does gas valve open
verified by a manifold
pressure range of 1.8-2.5”
wc for nat gas, 5.8-6.8” wc
for LP gas
Is gas supply pressure
verified to furnace. During trial
for ignition supply pressure
must be 5-10”wc for nat gas
and 11-13”wc for LP gas
Yes
No
Verify all pnematic tubing
between gas valve, inducer
and pressure switches is
installed per diagram on
furnace door
No
Yes
Yes
No

46
Troubleshooting ComfortBridge - 97% (Mod)
Yes
Do burners light as
expected
Check gas orfice size, 60k, 80k,
100k BTUH models on NAT
GAS should have #45 silver
orfices, 115k BTUH on NAT
GAS will have brass #43 orfices
.60k, 80k, 100k models on LP
GAS should have #1.25 black
orifices. 115k on LP GAS
should have #55 brass orfices
Yes
Yes
Yes
No
No
No
Do burners stay on
long enough for
the firing rate to go
down
Does blower
motor come on 30
seconds after
igntion
Yes
Does actual temp
rise fall within the
range specified
on furnace rating
plate
Is flame signal
steady and at least
1 microamp
Yes
Check burners for dirt, check for
burner allignment, check
position of orfice plate between
burners and H/E
Check for fault code displayed
on control board. Check that
low firePS and front cover PS
staying closed
Check for fault code displayed
and make corrective action
based on fault code. Use
UTT-01 to diagnose motor
No
Correct condition causing rise
to be out of range
Bring furnace up to highfire by using field test mode, during the call for heat, push
the fault recall button twice within a 5 second period, when ft appears on the
display push & hold fault recall again for 3 seconds. Furnace will go up to 100%
input and manifold pressure should be 3.2-3.8”wc for nat gas, 9.5-10.5 for LP gas.
No
Is manifold
pressure
correct?
Yes
Is gas supply pressure still in
acceptable range to furnace.
During trial for ignition supply
pressure must be 5-10”wc for
nat gas and 11-13”wc for LP
gas
Correct gas supply pressure
problem
Completed
No
Does burner stay
on to satisfy
thermostat
Yes
Check for loose or leaking
pneumatic tubing between
inducer, PS, gas valve, check
for plugged H fitting
Check for fault code displayed
No
Yes
No

47
Troubleshooting Error Codes - (B0 & B1)
Board flashes
B0 & B1
No
Yes
Check wiring
harnesses and wiring
connections.
Correct loose wiring
issue.
Ohm motor for open
or shorted circuit. Is
motor open or
shorted?
Test control voltage at the
control board. Replace
integrated control board if
necessary.
Test ECM motor and controller
with ECM tester. Replace motor
and/or controller if necessary
Replace motor if open or
shorted.
Correct power supply if out of
range. Replace motor if
necessary
Check for primary
voltage to blower motor.
Is the power supply
voltage between 104 &
127 vAC (115vAC +
10%)? (Typically
115-127vAC)
Yes
Check control
voltage between
pins 1 & 4. Voltage
should be between
3-15 vDC (Typically
9-15 vDC)
Yes
No
No
Error Code:
B0 - Circulator blower motor not
running when it should be running.
B1 - Integrated control module has
lost communications with
circulator blower motor.
Applicable Models:
(for Goodman Amana Brand)
*RVS-U, *DVT, *RVT, *DVM,
*RVM
(for Daikin)
DR**SC-U, DD**TC, DR**TC,
DD97MC, DR97MC
Method of Error Detection:
B0 - High voltage to the motor,
no DC voltage to the motor or no
communication to blower motor.
B1 - Bad ground or no
communication to blower motor.
Error Decision Conditions:
Primary voltage to blower motor
out of range.
Missing DC voltage between pins
1 and 4.

48
Troubleshooting Error Code - (B2-B6, B9)
Board flashes
B2,B3,B4,B5,B6, or B9
No
Yes
Does the
furnace have the
correct blower
motor?
Verify shared data set is correct
for specific model. Repopulate
shared data if required
Correct power supply if out of
range
Replace motor if necessary.
Verify correct motor horsepower.
Replace if necessary
Check for blocked
filters, restrictive
ductwork, undersized
ductwork. Does the
furnace have any of
these conditions?
Yes
Is the furnace
operating in a high
ambient condition
outside of the
temperature range
specified?
Yes
No
No
Does the
furnace have
the correct
shared data?
Check primary
voltage to blower
motor. Is the power
supply voltage
between 104 & 127
vAC (115vAC
+10%)?
Address high ambient condition
if necessary.
Check filters, remove
obstructions, verify registers are
fully open and RA grills are not
blocked. Verify duckwork is
appropriately sized. Resize/
replace ductwork if necessary.
No
No
Yes
Yes
Error Code:
B2 - Circulator blower motor HP in
shared data set does not match
circulator blower motor HP.
B3 - Circulator blower motor is
operating in a power, temperature
or speed limiting condition.
B4 - Circulator blower motor
senses a loss of rotor control or
high current.
B5 - Circulator blower motor fails
to start 10 consecutive times.
B6 - Circulator blower motor shuts
down due to over or under voltage
condition, or over temperature
condition.
B9 - Airflow is lower than
demanded.
Applicable Models:
(for Goodman/Amana Brand)
*RVS80-U, *RVS96-U, *DVT,
*RVT, *DVM97, *RVM97
(for Daikin)
DR**SC-U
Method of Error Detection:
Wrong horsepower blower motor,
primary voltage to motor is out of
range, high temperature, high amp
draw blower motor failure.
Error Decision Conditions:
Wrong horsepower blower motor,
primary voltage to motor is out of
range, high temperature, high amp
draw blower motor failure.

49
Troubleshooting Error Codes - (E0 - 90%)
Board flashes
E0
No
Yes
Are burners
firing up?
Check gas valve On/Off switch
is turned to On position and 24V
present at gas valve? Check
wire harness connection on gas
valve.
Check flame sense signal.
Clean flame sensor if coated
and/or oxidized.
Check manifold gas pressure is
remaining constant and not
dropping below required range
Verify 115VAC present at ignitor.
Replace if voltage is present
Is hot surface
ignitor
glowing?
Yes
Is supply gas present
and manifold gas
pressure within
range. (Nat. Gas 3.2"
to 3.8" W.C, LP 9.7" -
10.3" W.C)
Yes
No
No
Error Code:
E0 - Lockout due to an excessive
number of ignition retries (3 total)
Applicable Models:
All 90% models
Method of Error Detection:
Furnace fails to ignite after 3
retires
Error Decision Conditions:
No gas or low gas pressure at
manifold. Bad hot surface ignitor -
not glowing, dirty flame sensor
Are burners
staying lit?
Yes
No
Verify front cover pressure
switch is remaining close.
replace if needed
Is front cover
pressure switch
making?
No
Yes
Check pressure switch hose for
kinks and/or moisure. Drain trap
prime and clear. Check vent
pipe for blockage, proper length,
elbows, and termination. Verify
proper inducer draft blower

50
Troubleshooting Error Codes - (E3)
Board flashes E3
No
Yes
Check for blocked
filters, restrictive
ductwork, undersized
ductwork. Does the
furnace have any of
these conditions?
Correct blower speed to
maintain temperature rise within
the specifications.
Correct any wiring issues
Correct power supply if out of
range
Replace blower motor or
controller as needed.
Check primary voltage
to blower motor. Is the
power supply voltage
between 104 and 127
vAC (115vAC + 10%)?
Is the circulator
blower speed set
to the correct
speed for heating
airflow
No
No
Does the blower motor
have any loose or
improperly connected
wiring in the primary
limit circuit or to the
blower motor from the
control board?
Replace primary limit
Clean filters, remove
obstructions, verify registers are
fully open and RA grills are not
blocked. Verify ductwork is
appropriately sized. Resize/
replace ductwork if necessary.
No
Yes
Yes
Error Code:
E3 - Primary limit circuit is open.
Applicable Models:
All furnace models
Method of Error Detection:
Temperature across primary limit
during heating operation.
Error Decision Conditions:
During heating operation, primary
limit break temperature has
opened the primary limit circuit.
Is the primary
limit stuck open
or shorted?
No
Yes
No
No
Yes
Check the
performace of the
blower motor. Is
the blower motor
operating
properly?
Yes
Check gas inlet
and manifold
pressure. Are both
of these withing
specifications?
Yes
Adjust inlet and/or manifold
pressure to specification.
Perform combustion analysis to
determine other possible issues.

51
Troubleshooting Fault Codes - (E4 & E6)
Board flashes
E4 or E6
No
Does the furnace
have an actual
ground wire from
the furnace to the
breaker panel
ground bar?
Correct short at flame sensor or
in flame sensor wiring.
Check for lingering flame. Verify
proper operation of gas valve.
Yes
Correct furnace wiring - install
ground wire to breaker
Does the furnace
have a lingering
burner flame or a
slow closing gas
valve?
Yes
Check flame
sense micro
amp signal. Is
the micro amp
reading 1 or
lower?
Yes
No
No
Check flame sense
circuit to ground. Does
flame sense circuit
have a short to
ground?
No
Yes
Clean flame sensor with steel
wool (never use sand paper). If
flame sensor rod is pitted or
damaged - replace as needed.
Inspect for proper flame sensor
alignment.
Check gas inlet and manifold
pressures to rating plate and
adjust as needed.
If flame sense micro amp signal
to control board is more than 1
(typical range of 2 to 4), replace
control board as needed.
Error Code:
E4 - Flame sensed with no call for
heat.
E6 - Flame sense micro amp
signal is minimal.
Applicable Models:
All furnace models
Method of Error Detection:
Micro amp signal from flame
sensor.
Error Decision Conditions:
Micro amp reading with no call for
heat.
Low micro amp reading after
furnace ignition.

52
Troubleshooting Error Code - (Eb & EC)
Board flashes
Eb or EC
No
Check gas valve
wiring circuit. Is
wiring to gas valve
correct?
Integrated
control board
stuck closed.
Replace
integrated
control board.
Remove wiring connections
to the gas valve and check
for voltage at these
connections. If voltage is
present, check gas valve for
short to ground or loose
connection. Repair loose
connection or replace gas
valve as needed.
Verify voltage to gas valve is
the same as transformer
voltage. If voltage is not the
same, check for grounding
issue, If voltage is the same,
replace gas valve as needed.
Yes
Correct miswiring to gas
valve.
Yes
Yes
No
No
Is gas valve
shorted?
Yes
With no call for
heat, do you
have voltage to
gas valve?
With a call for heat and
the igniter on, do you
have voltage between
M & Common on the
gas valve?
No
Using the
wiring
diagram,
locate the MV
(MVL) and
Common
wires in the
wiring harness
connection on
the integrated
control board.
With a call for heat
and the igniter on,
do you have
voltage between
these 2 pins?
Integrated control board
stuck closed. Replace
integrated control board.
Replace gas valve as
needed.
Error Code:
Eb - Gas valve is not energized
when it should be. External Gas
Valve Error.
EC - Gas valve is energized when
it should not be. Internal Gas
Valve Error.
Applicable Models:
(for Goodman/Amana Brand)
All furnace models
(for Daikin)
All furnace models, except Daikin
modulating furnaces
Method of Error Detection:
No voltage to gas valve when
voltage should be present.
Voltage to gas valve with no call
for heat.
Error Decision Conditions:
No voltage reading at gas valve
with a call for heat.
Voltage reading at gas valve with
no call for heat.
Remove wires on
gas valve and check
gas valve for
shorted to ground.
No
Yes

WIRING DIAGRAMS
53
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.