Daikin RXQ09ASBU9 Oterra 9K BTU 0.75 Ton Ductless Mini Split Heat Pump Condenser, R-32, 115V

Product's Documents

Below are documents related to this product, you can read online or download:
User Manual Installation Instruction
RXQ09ASBU9 photo

User Manual

This is the main product document for model RXQ09ASBU9. Additionally, the document applies to other Daikin models: RXQ09ASBU9, 208/230V

The file format is pdf, 137 pages, you can download this manual here .

background
Servi ce
Manual
SiUS042501E
[Applied Models]
Inverter Pair : Heat Pump
Inverter Pair
Wall Mounted Type FTXQ-A Series
background
SiUS042501E
i Table of Contents
Introduction .................................................................................... 1
1. Safety Cautions.......................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers.............................2
1.2 Warnings and Cautions Regarding Safety of Users.................................7
2. Icons Used ............................................................................................10
3. Revision History ....................................................................................11
Part 1 General Information .......................................................... 12
1. Applicable Models .................................................................................13
2. Functions...............................................................................................14
Part 2 Specifications.................................................................... 15
1. Specifications ........................................................................................16
Part 3 Printed Circuit Board Connector Wiring Diagram............. 17
1. Indoor Unit.............................................................................................18
2. Outdoor Unit..........................................................................................20
Part 4 Functions and Control .......................................................21
1. Common Functions ...............................................................................22
1.1 Temperature Control ..............................................................................22
1.2 Frequency Principle................................................................................22
1.3 Airflow Direction Control.........................................................................24
1.4 COMFORT AIRFLOW Operation ...........................................................25
1.5 Fan Speed Control for Indoor Unit .........................................................26
1.6 Program Dry Operation ..........................................................................27
1.7 Automatic Cooling/Heating Change-over ...............................................28
1.8 Thermostat Control.................................................................................29
1.9 NIGHT SET Mode ..................................................................................30
1.10 ECONO Operation ................................................................................30
1.11 POWERFUL Operation ..........................................................................31
1.12 Brightness Setting of Indoor Unit Display...............................................32
1.13 Wireless LAN Connection (Optional)......................................................33
1.14 Other Functions......................................................................................37
2. Thermistor Functions ............................................................................38
3. Control Specification .............................................................................39
3.1 Mode Hierarchy ......................................................................................39
3.2 Frequency Control..................................................................................39
3.3 Controls at Mode Changing/Start-up......................................................41
3.4 Discharge Pipe Temperature Control.....................................................43
3.5 Input Current Control..............................................................................44
3.6 High Pressure Protection Control...........................................................45
3.7 Freeze-up Protection Control .................................................................46
3.8 Heating Peak-cut Control .......................................................................46
3.9 Outdoor Fan Control...............................................................................47
3.10 Liquid Compression Protection Function................................................47
3.11 Defrost Control .......................................................................................48
3.12 Electronic Expansion Valve Control .......................................................49
background
SiUS042501E
Table of Contents ii
3.13 Malfunctions ...........................................................................................51
Part 5 Remote Controller ............................................................. 52
1. Applicable Remote Controller ...............................................................53
2. ARC480A83 ..........................................................................................54
3. BRC073A6 ............................................................................................56
4. BRC944B2 ............................................................................................60
Part 6 Service Diagnosis .............................................................. 61
1. General Problem Symptoms and Check Items .....................................63
2. Troubleshooting with LED .....................................................................64
2.1 Indoor Unit..............................................................................................64
2.2 Outdoor Unit ...........................................................................................64
3. Service Diagnosis .................................................................................65
3.1 ARC480 Series.......................................................................................65
3.2 BRC073A6 .............................................................................................68
4. Troubleshooting ....................................................................................70
4.1 Error Codes and Description ..................................................................70
4.2 Indoor Unit PCB Abnormality .................................................................71
4.3 Freeze-up Protection Control/Heating Peak-cut Control ........................72
4.4 Indoor Fan Motor (DC Motor) or Related Abnormality ...........................73
4.5 Indoor Heat Exchanger Thermistor or Related Abnormality...................75
4.6 Room Temperature Sensor Abnormality/Humidity Sensor
Abnormality ............................................................................................76
4.7 Low-voltage Detection or Over-voltage Detection..................................77
4.8 Signal Transmission Error (Between Indoor Unit and Outdoor Unit)......79
4.9 Unspecified Voltage (Between Indoor Unit and Outdoor Unit) ...............81
4.10 Outdoor Unit PCB Abnormality...............................................................82
4.11 OL Activation (Compressor Overload) or HPS Activation (High
Pressure Switch) ....................................................................................83
4.12 Compressor Lock ...................................................................................86
4.13 DC Fan Lock ..........................................................................................87
4.14 Input Overcurrent Detection ...................................................................88
4.15 Electronic Expansion Valve Coil Abnormality.........................................89
4.16 Four Way Valve Abnormality..................................................................90
4.17 Discharge Pipe Temperature Control.....................................................92
4.18 High Pressure Control in Cooling ...........................................................93
4.19 System Shutdown due to Temperature Abnormality in the
Compressor............................................................................................95
4.20 Compressor Sensor System Abnormality ..............................................96
4.21 Position Sensor Abnormality ..................................................................97
4.22 Thermistor or Related Abnormality (Outdoor Unit).................................99
4.23 Electrical Box Temperature Rise..........................................................101
4.24 Radiation Fin Temperature Rise ..........................................................102
4.25 Output Overcurrent Detection ..............................................................103
4.26 Signal Transmission Error on Outdoor Unit PCB .................................105
5. Check ..................................................................................................106
5.1 Thermistor Resistance Check ..............................................................106
5.2 Indoor Fan Motor Connector Check .....................................................106
5.3 Power Supply Waveform Check...........................................................107
background
SiUS042501E
iii Table of Contents
5.4 Electronic Expansion Valve Check.......................................................107
5.5 Four Way Valve Performance Check ...................................................108
5.6 Inverter Unit Refrigerant System Check...............................................108
5.7 Inverter Analyzer Check .......................................................................109
5.8 Outdoor Fan Motor Check....................................................................111
5.9 Installation Condition Check.................................................................111
5.10 Discharge Pressure Check...................................................................112
5.11 Outdoor Fan System Check .................................................................112
5.12 Main Circuit Short Check......................................................................113
5.13 Power Module Check ...........................................................................114
Part 7 Trial Operation and Field Settings .................................. 115
1. Pump Down Operation........................................................................116
2. Forced Cooling Operation ...................................................................117
3. Trial Operation ....................................................................................118
4. Field Settings ......................................................................................120
4.1 When 2 Units are Installed in 1 Room..................................................120
4.2 Temperature Display Switch ................................................................123
4.3 Service Mode of Wireless Remote Controller ......................................124
5. Silicone Grease on Power Transistor/Diode Bridge............................126
Part 8 Appendix .......................................................................... 127
1. Piping Diagrams..................................................................................128
1.1 Indoor Unit............................................................................................128
1.2 Outdoor Unit .........................................................................................129
2. Wiring Diagrams..................................................................................130
2.1 Indoor Unit............................................................................................130
2.2 Outdoor Unit .........................................................................................131
3. Operation Limit....................................................................................132
background
SiUS042501E
Introduction 1
1. Safety Cautions.......................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers.............................2
1.2 Warnings and Cautions Regarding Safety of Users.................................7
2. Icons Used ............................................................................................10
3. Revision History ....................................................................................11
Introduction
background
Safety Cautions SiUS042501E
2 Introduction
1. Safety Cautions
Be sure to read the following safety cautions before conducting repair work.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer.
Caution Items The caution items are classified into Warning and Caution. The Warning items are
especially important since death or serious injury can result if they are not followed closely. The
Caution items can also lead to serious accidents under some conditions if they are not
followed. Therefore, be sure to observe all the safety caution items described below.
Pictograms This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown in the illustration or near the symbol.
1.1 Warnings and Cautions Regarding Safety of Workers
This manual is for the
person in charge of
maintenance and
inspection.
This appliance is
filled with R-32.
Refrigerant
Safety
Group A2L
Warning
Do not store equipment in a room with fire sources (e.g., naked
flames, gas appliances, electric heaters).
Be sure to disconnect the power cable from the socket before
disassembling equipment for repair.
Working on equipment that is connected to the power supply may cause
an electrical shock.
If it is necessary to supply power to the equipment to conduct the repair or
inspect the circuits, do not touch any electrically charged sections of the
equipment.
If refrigerant gas is discharged during repair work, do not touch the
discharged refrigerant gas.
Refrigerant gas may cause frostbite.
When disconnecting the suction or discharge pipe of the
compressor at the welded section, evacuate the refrigerant gas
completely at a well-ventilated place first.
If there is gas remaining inside the compressor, the refrigerant gas or
refrigerating machine oil discharges when the pipe is disconnected, and it
may cause injury.
If refrigerant gas leaks during repair work, ventilate the area.
Refrigerant gas may generate toxic gases when it contacts flames.
Be sure to discharge the capacitor completely before conducting
repair work.
The step-up capacitor supplies high-voltage electricity to the electrical
components of the outdoor unit.
A charged capacitor may cause an electrical shock.
background
SiUS042501E Safety Cautions
Introduction 3
Do not turn the air conditioner on or off by plugging in or
unplugging the power cable.
Plugging in or unplugging the power cable to operate the equipment may
cause an electrical shock or fire.
Be sure to wear a safety helmet, gloves, and a safety belt when
working in a high place (more than 2 m (6.5 ft)).
Insufficient safety measures may cause a fall.
In case of R-32 / R-410A refrigerant models, be sure to use pipes,
flare nuts and tools intended for the exclusive use with the R-32 /
R-410A refrigerant.
The use of materials for R-22 refrigerant models may cause a serious
accident, such as a damage of refrigerant cycle or equipment failure.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-410A / R-22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
Caution
Do not repair electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Do not clean the air conditioner with water.
Washing the unit with water may cause an electrical shock.
Be sure to provide an earth / grounding when repairing the
equipment in a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable
when cleaning the equipment.
The internal fan rotates at a high speed, and may cause injury.
Be sure to conduct repair work with appropriate tools.
The use of inappropriate tools may cause injury.
Be sure to check that the refrigerating cycle section has cooled
down enough before conducting repair work.
Working on the unit when the refrigerating cycle section is hot may cause
burns.
Conduct welding work in a well-ventilated place.
Using the welder in an enclosed room may cause oxygen deficiency.
Warning
background
Safety Cautions SiUS042501E
4 Introduction
Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are
necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating
system, provisions under Work procedure to No ignition sources below shall be
completed prior to conducting work on the system.
Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a
flammable gas or vapor being present while the work is being performed.
General work area
All maintenance staff and others working in the local area shall be instructed on the nature of
work being carried out. Work in confined spaces shall be avoided.
Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work,
to ensure the technician is aware of potentially toxic or flammable atmospheres.
Ensure that the leak detection equipment being used is suitable for use with all applicable
refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
Presence of fire extinguisher
If any hot work is to be conducted on the refrigerating equipment or any associated parts,
appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or
CO
2
fire extinguisher adjacent to the charging area.
No ignition sources
No person carrying out work in relation to a refrigerating system which involves exposing
any pipe work shall use any sources of ignition in such a manner that it may lead to the risk
of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept
sufficiently far away from the site of installation, repairing, removing and disposal, during
which refrigerant can possibly be released to the surrounding space. Prior to work taking
place, the area around the equipment is to be surveyed to make sure that there are no
flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the
system or conducting any hot work. A degree of ventilation shall continue during the period
that the work is carried out. The ventilation should safely disperse any released refrigerant
and preferably expel it externally into the atmosphere.
Checks to the refrigerating equipment
Where electrical components are being changed, they shall be fit for the purpose and to the
correct specification.
At all times the manufacturer’s maintenance and service guidelines shall be followed. If in
doubt, consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
The actual refrigerant charge is in accordance with the room size within which the
refrigerant containing parts are installed;
The ventilation machinery and outlets are operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for
the presence of refrigerant;
Marking to the equipment continues to be visible and legible. Markings and signs that are
illegible shall be corrected;
Refrigerating pipe or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components, unless
the components are constructed of materials which are inherently resistant to being
corroded or are suitably protected against being so corroded.
background
SiUS042501E Safety Cautions
Introduction 5
Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures. If a fault exists that could compromise safety, then no
electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault
cannot be corrected immediately but it is necessary to continue operation, an adequate
temporary solution shall be used. This shall be reported to the owner of the equipment so all
parties are advised.
Initial safety checks shall include:
that capacitors are discharged: this shall be done in a safe manner to avoid possibility of
sparking;
that no live electrical components and wiring are exposed while charging, recovering or
purging the system;
that there is continuity of earth bonding.
Repairs to sealed components
Sealed electrical components shall be replaced.
Repair to intrinsically safe components
Intrinsically safe components must be replaced.
Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration,
sharp edges or any other adverse environmental effects. The check shall also take into
account the effects of aging or continual vibration from sources such as compressors or
fans.
Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall
not be used.
The following leak detection methods are deemed acceptable for all refrigerant systems.
Electronic leak detectors may be used to detect refrigerant leaks but, in the case of
flammable refrigerants, the sensitivity may not be adequate, or may need re-calibration.
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant
used. Leak detection equipment shall be set at a percentage of the LFL (lower flammability
limit) of the refrigerant and shall be calibrated to the refrigerant employed, and the
appropriate percentage of gas (25% maximum) is confirmed.
Leak detection fluids are also suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant
and corrode the copper pipe-work.
Note: Examples of leak detection fluids are
bubble method,
fluorescent method agents.
If a leak is suspected, all naked flames shall be removed/extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the system
remote from the leak. Removal of refrigerant shall be according to the following clause,
Removal and evacuation.
Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose –
conventional procedures shall be used. However, for flammable refrigerants it is important
that best practice be followed, since flammability is a consideration. The following procedure
shall be adhered to:
safely remove refrigerant following local and national regulations;
evacuate;
purge the circuit with inert gas (optional for A2L);
evacuate (optional for A2L);
background
Safety Cautions SiUS042501E
6 Introduction
continuously flush or purge with inert gas when using flame to open circuit;
open the circuit.
The refrigerant charge shall be recovered into the correct recovery cylinders if venting is not
allowed by local and national codes. For appliances containing flammable refrigerants, the
system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable
refrigerants. This process might need to be repeated several times. Compressed air or
oxygen shall not be used for purging refrigerant systems.
For appliances containing flammable refrigerants, refrigerants purging shall be achieved by
breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the
working pressure is achieved, then venting to atmosphere, and finally pulling down to a
vacuum (optional for A2L). This process shall be repeated until no refrigerant is within the
system (optional for A2L). When the final oxygen-free nitrogen charge is used, the system
shall be vented down to atmospheric pressure to enable work to take place.
The outlet for the vacuum pump shall not be close to any potential ignition sources, and
ventilation shall be available.
Charging procedures
In addition to conventional charging procedures, the following requirements shall be
followed.
Ensure that contamination of different refrigerants does not occur when using charging
equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant
contained in them.
Cylinders shall be kept in an appropriate position according to the instructions.
Ensure that the refrigerating system is earthed prior to charging the system with
refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigerating system.
Prior to recharging the system, it shall be pressure-tested with the appropriate purging
gas.
The system shall be leak-tested on completion of charging but prior to commissioning.
A follow up leak test shall be carried out prior to leaving the site.
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar
with the equipment and all its detail. It is recommended good practice that all refrigerants are
recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be
taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that
electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure, ensure that:
mechanical handling equipment is available, if required, for handling refrigerant
cylinders;
all personal protective equipment is available and being used correctly;
the recovery process is supervised at all times by a competent person;
recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from
various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with instructions.
h) Do not overfill cylinders (no more than 80% volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that
the cylinders and the equipment are removed from site promptly and all isolation valves on
the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigerating system unless it has
been cleaned and checked.
background
SiUS042501E Safety Cautions
Introduction 7
Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of
refrigerant. The label shall be dated and signed. For appliances containing flammable
refrigerants, ensure that there are labels on the equipment stating the equipment contains
flammable refrigerant.
Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery
cylinders are employed. Ensure that the correct number of cylinders for holding the total
system charge is available. All cylinders to be used are designated for the recovered
refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of
refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off
valves in good working order. Empty recovery cylinders are evacuated and, if possible,
cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning
the equipment that is at hand and shall be suitable for the recovery of the flammable
refrigerant. If in doubt, the manufacturer should be consulted. In addition, a set of calibrated
weighing scales shall be available and in good working order. Hoses shall be complete with
leak-free disconnect couplings and in good condition.
The recovered refrigerant shall be processed according to local legislation in the correct
recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in
recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated
to an acceptable level to make certain that flammable refrigerant does not remain within the
lubricant. The compressor body shall not be heated by an open flame or other ignition
sources to accelerate this process. When oil is drained from a system, it shall be carried out
safely.
1.2 Warnings and Cautions Regarding Safety of Users
Warning
Do not store the equipment in a room with fire sources (e.g., naked
flames, gas appliances, electric heaters).
Be sure to use parts listed in the service parts list of the applicable
model and appropriate tools to conduct repair work. Never attempt
to modify the equipment.
The use of inappropriate parts or tools may cause an electrical shock,
excessive heat generation or fire.
If the power cable and lead wires are scratched or have deteriorated,
be sure to replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the
same power outlet with other electrical appliances, since it may
cause an electrical shock, excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and
follow the local technical standards related to the electrical
equipment, the internal wiring regulations, and the instruction
manual for installation when conducting electrical work.
Insufficient power circuit capacity and improper electrical work may cause
an electrical shock or fire.
background
Safety Cautions SiUS042501E
8 Introduction
Be sure to use the specified cable for wiring between the indoor and
outdoor units.
Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections may cause excessive heat generation or fire.
When wiring between the indoor and outdoor units, make sure that
the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may
cause an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cables may cause an electrical shock or fire.
Placing heavy items on the power cable, or heating or pulling the power
cable may damage it.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-410A / R-22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and
repair it before charging the refrigerant. After charging the
refrigerant, make sure that there is no leak.
If the leaking point cannot be located and the repair work must be
stopped, be sure to pump-down, and close the service valve, to prevent
refrigerant gas from leaking into the room. Refrigerant gas itself is
harmless, but it may generate toxic gases when it contacts flames, such
as those from fan type and other heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation
site has sufficient strength to withstand the weight of the
equipment.
If the installation site does not have sufficient strength or the installation
work is not conducted securely, the equipment may fall and cause injury.
Check to make sure that the power cable plug is not dirty or loose,
then insert the plug into a power outlet securely.
If the plug is dusty or has a loose connection, it may cause an electrical
shock or fire.
When replacing the coin battery in the remote controller, be sure to
dispose of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases
depending on the conditions of the installation site, to prevent
electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If combustible gas leaks and remains around the unit, it may cause a fire.
Check to see if parts and wires are mounted and connected
properly, and if connections at the soldered or crimped terminals
are secure.
Improper installation and connections may cause excessive heat
generation, fire or an electrical shock.
Warning
background
SiUS042501E Safety Cautions
Introduction 9
If the installation platform or frame has corroded, replace it.
A corroded installation platform or frame may cause the unit to fall,
resulting in injury.
Check the earth / grounding, and repair it if the equipment is not
properly earthed / grounded.
Improper earth / grounding may cause an electrical shock.
Be sure to measure insulation resistance after the repair, and make
sure that the resistance is 1 M or higher.
Faulty insulation may cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause water to enter the room and wet the furniture
and floor.
Do not tilt the unit when removing it.
The water inside the unit may spill and wet the furniture and floor.
Caution
background
Icons Used SiUS042501E
10 Introduction
2. Icons Used
The following icons are used to attract the attention of the reader to specific information.
Icon Type of
Information
Description
Warning
Warning Warning is used when there is danger of personal injury.
Caution
Caution Caution is used when there is danger that the reader,
through incorrect manipulation, may damage equipment,
lose data, get an unexpected result or have to restart (part
of) a procedure.
Note
Note Note provides information that is not indispensable, but
may nevertheless be valuable to the reader, such as tips
and tricks.
Reference
Reference Reference guides the reader to other places in this binder
or in this manual, where he/she will find additional
information on a specific topic.
background
SiUS042501E Revision History
Introduction 11
3. Revision History
Month/Year Version Revised contents
05 / 2025 SiUS042501E First edition
background
SiUS042501E
12 Part 1 General Information
1. Applicable Models .................................................................................13
2. Functions...............................................................................................14
Part 1
General Information
background
SiUS042501E Applicable Models
Part 1 General Information 13
1. Applicable Models
Indoor Unit Outdoor Unit
FTXQ09ASBU9
FTXQ12ASBU9
RXQ09ASBU9
RXQ12ASBU9
background
Functions SiUS042501E
14 Part 1 General Information
2. Functions
Category Functions FTXQ
Basic Function Inverter (with inverter power control)
Operation limit Refer to page 132
PAM control
Standby electricity saving
Compressor Swing compressor
Reluctance DC motor
Comfortable
Airflow
Power-airflow flap (horizontal blade)
Wide-angle louvers (vertical blades)
Auto-swing (up and down)
COMFORT AIRFLOW operation
Comfort Control Auto fan speed
Switchable fan speed
Indoor unit quiet operation
Hot-start function
Automatic defrosting
Operation Automatic cooling/heating change-over
Program dry operation
Fan only
Lifestyle
Convenience
POWERFUL operation (inverter)
ECONO operation
Indoor unit ON/OFF switch
Signal receiving sign
Remote controller with back light
Health and
Cleanliness
Mold proof air filter
Titanium apatite deodorizing filter Option
Wipe-clean flat panel
Removable drain pan
Timer Count up-down ON/OFF timer
NIGHT SET mode
Worry Free
(Reliability &
Durability)
Auto-restart (after power failure)
Self-diagnosis (Remote controller, LED)
Flexibility Chargeless 49.2 ft. (15 m)
Either side drain (left or right)
Remote Control Remote control adaptor (normal open pulse contact) Option
Remote control adaptor (normal open contact) Option
DIII-NET compatible (adaptor) Option
Wireless LAN connection Option
Remote
Controller
Wireless
Wired Option
°F/°C changeover remote controller temperature display
(factory setting: °F)
—
: Available
: Not available
background
SiUS042501E
Part 2 Specifications 15
1. Specifications ........................................................................................16
Part 2
Specifications
background
Specifications SiUS042501E
16 Part 2 Specifications
1. Specifications
Model Indoor Unit FTXQ09ASBU9 FTXQ12ASBU9
Outdoor Unit RXQ09ASBU9 RXQ12ASBU9
Cooling Heating Cooling Heating
Power Supply 1, 60 Hz, 115 V 1, 60 Hz, 115 V
Capacity Rated (Min. ~ Max.) Btu/h 9,000 (2,800 ~ 10,500) 10,900 (3,800 ~ 12,000) 12,000 (3,600 ~ 12,800) 13,500 (3,800 ~ 14,600)
Running Current (Rated) A 7.67 9.20 10.23 10.29
Power Consumption (Rated) W 750 908 1,000 1,015
Power Factor (Rated) % 85.0 85.8 85.0 85.8
SEER2 / HSPF2 20.0 9.0 20.0 9.0
EER2 (Rated) Btu/h·W 12.0 — 12.0 —
COP2@5°F (Rated) W/W — 1.9 — 2.1
Piping Connections Liquid in. (mm) 1/4 (6.4) 1/4 (6.4)
Gas in. (mm) 3/8 (9.5) 3/8 (9.5)
Drain in. (mm) 5/8 (16) 5/8 (16)
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length ft (m) 65-5/8 (20) 65-5/8 (20)
Max. Interunit Height Difference ft (m) 49-1/4 (15) 49-1/4 (15)
Chargeless ft (m) 49-1/4 (15) 49-1/4 (15)
Amount of Additional Charge of
Refrigerant
Oz/ft (g/m) 0.22 (20) 0.22 (20)
Indoor Unit FTXQ09ASBU9 FTXQ12ASBU9
Front Panel Color White (N9.5) White (N9.5)
Airflow Rate H / M / L / SL cfm 424 / 307 / 261 / 134 413 / 328 / 247 / 212 413 / 311 / 244 / 124 434 / 321 / 244 / 208
m³/min 12.0 / 8.7 / 7.4 / 3.8 11.7 / 9.3 / 7.0 / 6.0 11.7 / 8.8 / 6.9 / 3.5 12.3 / 9.1 / 6.9 / 5.9
Fan Type Cross Flow Fan Cross Flow Fan
Drive Input A 0.36 0.42
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward
Air Filter Removable, Washable, Mold Proof Removable, Washable, Mold Proof
Running Current (Rated) A 0.25 0.23 0.27 0.31
Power Consumption (Rated) W 27 25 29 32
Power Factor (Rated) % 93.0 93.9 91.9 90.4
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) in. (mm) 11-1/4 × 30-5/16 × 8-3/4 (286 × 770 × 223) 11-1/4 × 30-5/16 × 8-3/4 (286 × 770 × 223)
Packaged Dimensions (H × W × D) in. (mm) 12-13/16 × 33-1/8 × 14-9/16 (325 × 842 × 370) 12-13/16 × 33-1/8 × 14-9/16 (325 × 842 × 370)
Weight (Mass) lbs (kg) 18 (8) 19 (9)
Gross Weight (Gross Mass) lbs (kg) 24 (11) 25 (12)
Sound Pressure
Level
H / M / L / SL
dB(A) 43 / 35 / 30 / 21 41 / 36 / 28 / 25 46 / 38 / 31 / 21 45 / 37 / 30 / 25
Outdoor Unit RXQ09ASBU9 RXQ12ASBU9
Casing Color Ivory White Ivory White
Heat Exchanger Fin / Spec. Tube Waffle Fin / 7 Hi-XSL Tube Waffle Fin / 7 Hi-XSL Tube
Compressor Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 1Y091BKBX1A 1Y091BKBX1A
Refrigerant Oil Type FW68DA FW68DA
Charge oz (L) 12.68 (0.375) 12.68 (0.375)
Refrigerant Type R-32 R-32
Charge lbs (kg) 1.15 (0.52) 1.65 (0.75)
Airflow Rate m³/min
(cfm)
34.9 (1,233) 32.6 (1,151) 32.4 (1,144) 32.4 (1,144)
Fan Type Propeller Propeller
Drive Input A 0.37 0.42
Running Current (Rated) A 7.42 8.97 9.96 9.98
Power Consumption (Rated) W 723 883 971 983
Power Factor (Rated) % 84.7 85.6 84.8 85.6
Dimensions (H × W × D) in. (mm) 21-15/16 × 26-9/16 × 11-3/16 (557 × 675 × 284) 21-15/16 × 26-9/16 × 11-3/16 (557 × 675 × 284)
Packaged Dimensions (H × W × D) in. (mm) 24-7/16 × 31-1/4 × 14-1/8 (620 × 794 × 359) 24-7/16 × 31-1/4 × 14-1/8 (620 × 794 × 359)
Weight (Mass) lbs (kg) 59 (27) 64 (29)
Gross Weight (Gross Mass) lbs (kg) 64 (29) 70 (32)
Sound Pressure Level dB(A) 48 49 50 52
Conditions Based
on
Indoor 80.0°FDB (26.7°CDB) /
67.0°FWB (19.4°CWB)
70.0°FDB (21.1°CDB) /
60.0°FWB (15.6°CWB)
80.0°FDB (26.7°CDB) /
67.0°FWB (19.4°CWB)
70.0°FDB (21.1°CDB) /
60.0°FWB (15.6°CWB)
Outdoor 95.0°FDB (35°CDB) /
75°FWB (23.9°CWB)
47°FDB (8.33°CDB) /
43.0°FWB (6.11°CWB)
95.0°FDB (35°CDB) /
75°FWB (23.9°CWB)
47°FDB (8.33°CDB) /
43.0°FWB (6.11°CWB)
Piping Length 25 ft (7.5 m) 25 ft (7.5 m)
Drawing No. 3D154610 3D154610
Note SL: The quiet fan level of the airflow setting SL: The quiet fan level of the airflow setting
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
background
SiUS042501E
Part 3 Printed Circuit Board Connector Wiring Diagram 17
1. Indoor Unit.............................................................................................18
2. Outdoor Unit..........................................................................................20
Part 3
Printed Circuit Board
Connector Wiring Diagram
background
Indoor Unit SiUS042501E
18 Part 3 Printed Circuit Board Connector Wiring Diagram
1. Indoor Unit
Control PCB
(A1P)
1) S1 Connector for terminal strip
2) S6 Connector for swing motor (horizontal blade)
3) S91 Connector for humidity sensor PCB (A4P)
4) S200 Connector for DC fan motor
5) S403 Connector for optional wireless LAN connection
6) S430 Connector for optional adaptor
7) S501 Connector for indoor heat exchanger thermistor (R1T)
8) S800 Connector for display/signal receiver PCB (A2P)
9) FG Connector for terminal strip (frame ground)
10) FU1 Fuse (3.15 A, 250 V)
11) V2 Varistor
FU1
S1
V2
S91
S6
FGS200
S800 S430
S403S501
2P721387-21
background
SiUS042501E Indoor Unit
Part 3 Printed Circuit Board Connector Wiring Diagram 19
Display/Signal
Receiver PCB
(A2P)
Humidity sensor
PCB (A4P)
1) S27 Connector for control PCB (A1P)
2) SW1 Indoor unit ON/OFF switch
(Forced cooling operation ON/OFF switch)
Refer to page 117 for details of forced cooling operation.
3) LED1 LED for operation (green)
4) LED2 LED for timer (orange)
5) LED3 LED for optional wireless LAN connection (orange)
3P719708-1
SW1 LED1LED2LED3
S27
1) CON1 Connector for control PCB (A1P)
3E860031-1
CON1
background
Outdoor Unit SiUS042501E
20 Part 3 Printed Circuit Board Connector Wiring Diagram
2. Outdoor Unit
Main PCB (A1P)
1) E Faston tab for grounding
2) L, N, S Faston tab for terminal strip
3) X20A Connector for electronic expansion valve coil
4) X30A Connector for compressor
5) X40A Connector for overload protector and high pressure switch
6) X70A Connector for DC fan motor
7) X80A Connector for four way valve coil
8) X90A Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
9) HR1, HR2 Wire harness for reactor
10) F2U Fuse (3.15 A, 250 V)
11) F3U Fuse (30 A, 250 V)
12) LED LED for service monitor (green)
2P773842-11
X80A
L N S E
X70A
F3U
HR1
HR2
X90A
X30A
F2U
X20A
X40A
LED
background
SiUS042501E
Part 4 Functions and Control 21
1. Common Functions ...............................................................................22
1.1 Temperature Control ..............................................................................22
1.2 Frequency Principle................................................................................22
1.3 Airflow Direction Control.........................................................................24
1.4 COMFORT AIRFLOW Operation ...........................................................25
1.5 Fan Speed Control for Indoor Unit .........................................................26
1.6 Program Dry Operation ..........................................................................27
1.7 Automatic Cooling/Heating Change-over ...............................................28
1.8 Thermostat Control.................................................................................29
1.9 NIGHT SET Mode ..................................................................................30
1.10 ECONO Operation ................................................................................30
1.11 POWERFUL Operation ..........................................................................31
1.12 Brightness Setting of Indoor Unit Display...............................................32
1.13 Wireless LAN Connection (Optional)......................................................33
1.14 Other Functions......................................................................................37
2. Thermistor Functions ............................................................................38
3. Control Specification .............................................................................39
3.1 Mode Hierarchy ......................................................................................39
3.2 Frequency Control..................................................................................39
3.3 Controls at Mode Changing/Start-up......................................................41
3.4 Discharge Pipe Temperature Control.....................................................43
3.5 Input Current Control..............................................................................44
3.6 High Pressure Protection Control...........................................................45
3.7 Freeze-up Protection Control .................................................................46
3.8 Heating Peak-cut Control .......................................................................46
3.9 Outdoor Fan Control...............................................................................47
3.10 Liquid Compression Protection Function................................................47
3.11 Defrost Control .......................................................................................48
3.12 Electronic Expansion Valve Control .......................................................49
3.13 Malfunctions ...........................................................................................51
Part 4
Functions and Control
background
Common Functions SiUS042501E
22 Part 4 Functions and Control
1. Common Functions
1.1 Temperature Control
Definitions of
Temperatures
The definitions of temperatures are classified as following.
Room temperature: temperature of living space of the room
Set temperature: temperature set by remote controller
Room thermistor temperature: temperature detected by room temperature thermistor
Target temperature: temperature determined by microcomputer
Temperature
Control
The temperature of the room is detected by the room temperature thermistor. However, there is
a difference between the temperature detected by room temperature thermistor and the
temperature of living space of the room, depending on the type of the indoor unit or installation
condition. In practice, the temperature control is done by the target temperature appropriately
adjusted for the indoor unit and the temperature detected by room temperature thermistor.
1.2 Frequency Principle
Control
Parameters
The frequency of the compressor is controlled by the following 2 parameters:
The load condition of the operating indoor unit
The difference between the room thermistor temperature and the target temperature
The target frequency is adapted by additional parameters in the following cases:
Frequency restrictions
Initial settings
Forced cooling operation
Inverter Principle To regulate the capacity, a frequency control is needed. The inverter makes it possible to
control the rotation speed of the compressor. The followings explain the inverter principle:
Phase 1
The supplied AC power source is converted into the DC power source for the present.
Phase 2
The DC power source is reconverted into the three phase AC power source with variable
frequency.
When the frequency increases, the rotation speed of the compressor increases resulting in
an increase of refrigerant circulation. This leads to a larger amount of heat exchange per
unit.
When the frequency decreases, the rotation speed of the compressor decreases resulting in
a decrease of refrigerant circulation. This leads to a smaller amount of heat exchange per
unit.
Target temperature
Set temperature
Room temperature
Room thermistor temperature
(R12321)
background
SiUS042501E Common Functions
Part 4 Functions and Control 23
The following drawing shows a schematic view of the inverter principle:
Inverter Features The inverter provides the following features:
The regulating capacity can be changed according to the changes in the outdoor
temperature and cooling/heating load.
Quick heating and quick cooling
The rotation speed of the compressor is increased when starting the heating (cooling).
This enables to reach the set temperature quickly.
Even during extreme cold weather, high capacity is achieved. It is maintained even when the
outdoor temperature is 2C (35.6°F).
Comfortable air conditioning
A fine adjustment is integrated to keep the room temperature constant.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the
room temperature at low power.
Frequency Limits The following functions regulate maximum frequency:
Low frequency
Four way valve operation compensation. Refer to page 41.
High frequency
Compressor protection function. Refer to page 42.
Discharge pipe temperature control. Refer to page 43.
Input current control. Refer to page 44.
Freeze-up protection control. Refer to page 46.
Heating peak-cut control. Refer to page 46.
Defrost control. Refer to page 48.
Forced Cooling
Operation
Refer to page 117 for details.
Refrigerant circulation rate (high)
high f
low f
freq=variable
Refrigerant circulation rate (low)
high speed
low speed
(R2812)
Amount of heat
exchanged air (large)
freq=
constant
50 Hz
50 Hz
60 Hz
60 Hz
capacity=
variable
Amount of heat
exchanged air (small)
AC
power
DC
power
Amount of heat exchanged air
(large)
Amount of heat exchanged air
(small)
background
Common Functions SiUS042501E
24 Part 4 Functions and Control
1.3 Airflow Direction Control
Power-Airflow
(Dual) Flap(s)
The large flap sends a large volume of air downward to the floor and provides an optimum
control in cooling, dry and heating operation.
Cooling/Dry
During cooling or dry operation, the flap retracts into the indoor unit. Then, cool air can be blown
far and distributed all over the room.
Heating
During heating operation, the large flap directs airflow downward to spread the warm air to the
entire room.
Wide-Angle
Louvers
The louvers, made of elastic synthetic resin, provide a wide range of airflow that guarantees
comfortable air distribution.
Auto-Swing The following tables explain the auto-swing process for cooling, dry, heating and fan:
Flap (up and down)
Cooling/Dry Heating Fan
R4004115
5°
45°
(R21049)
15°
65°
(R21050)
0°
65°
background
SiUS042501E Common Functions
Part 4 Functions and Control 25
1.4 COMFORT AIRFLOW Operation
Outline The flow of air will be in the upward direction while in COOL/DRY operation and in the
downward direction while in HEAT operation, which will provide a comfortable wind that will not
come in direct contact with people.
Operation
To start the operation:
Press Comfort button.
The icon appears on the LCD of the remote controller.
To stop the operation:
Press Comfort button again.
The icon disappears from the LCD of the remote controller. The flaps will return to the
memorized position before the start of COMFORT AIRFLOW operation
POWERFUL operation and COMFORT AIRFLOW operation cannot be used at the same
time.
When in AUTO operation, the flap direction differs based on the operation mode (COOL or
HEAT) as shown in the table above.
If the upward and downward airflow direction is selected, the COMFORT AIRFLOW function
will be canceled. Priority is given to the function of whichever button is pressed last.
COOL / DRY operation HEAT operation FAN operation
Flaps direction Goes up Goes down
Not available
Airflow rate AUTO
Comfort
button
background
Common Functions SiUS042501E
26 Part 4 Functions and Control
1.5 Fan Speed Control for Indoor Unit
Outline Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.
The airflow rate can be automatically controlled depending on the difference between the room
thermistor temperature and the target temperature.
Automatic Fan
Speed Control
In automatic fan speed operation, the step SL is not available.
R4003512
= The airflow rate is automatically controlled within this range when FAN setting button is
set to automatic
.
Cooling
The following drawing explains the principle of fan speed control for cooling.
R4004133
The upper limit is at M tap in 30 minutes from the operation start.
Heating
In heating operation, the fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room thermistor temperature and the target
temperature.
The fan stops during defrost operation.
HeatingCoolingStep
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
+2.5°C (+4.5°F)
+1.5°C (+2.7°F)
+0.5°C (+0.9°F)
MH*
M
ML
L
+3°C (+5.4°F)
+2.5°C (+4.5°F)
+1.5°C (+2.7°F)
Fan speed
Room thermistor temperature – target temperature
background
SiUS042501E Common Functions
Part 4 Functions and Control 27
1.6 Program Dry Operation
Outline Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and FAN setting buttons are inoperable.
Details The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two
zones. Then, the unit operates in an appropriate capacity for each zone to maintain the
temperature and humidity at a comfortable level.
R4004134
Thermostat turns on also when the room temperature is in the zone B for 10 minutes.
Room thermistor
temperature at start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24°C or more
(75.2°F or more)
Room thermistor
temperature at start-up
X – 1.0°C
(X – 1.8°F)
X – 0.25°C
(X – 0.5°F)
18 ~ 23.5°C
(64.4 ~ 74.3°F)
X – 0.75°C
(X – 1.4°F)
X – 0.25°C
(X – 0.5°F)
17.5°C or less
(63.5°F or less)
18°C
(64.4°F)
X – 0.75°C
(X – 1.4°F)
X – 0.25°C = 17.75°C
(X – 0.5°F = 63.9°F)
Zone A = Thermostat OFF
Target temperature X
Zone B
Room temperature Room temperature
Zone C = Thermostat ON
Y = X – 1.0°C (1.8°F)
Z = X – 0.25°C (0.5°F)
X – 0.5°C (0.9°F)
background
Common Functions SiUS042501E
28 Part 4 Functions and Control
1.7 Automatic Cooling/Heating Change-over
Outline When the automatic operation is selected with the remote controller, the microcomputer
automatically determines the operation mode as cooling or heating according to the room
temperature and the set temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Details Ts: set temperature (set by remote controller)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
1. The set temperature (Ts) determines the target temperature (Tt).
(Ts = 18 ~ 30°C (64.4 ~ 86°F))
2. The target temperature (Tt) is calculated as;
Tt = Ts + C
where C is the correction value.
C = 0°C (0°F)
3. Thermostat ON/OFF point and operation mode switching point are as follows.
(1) Heating Cooling switching point:
Tr Tt + 3.0°C (+ 5.4°F)
(2) Cooling Heating switching point:
Tr < Tt – 2.5°C (– 4.5°F)
(3) Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating
operation.
4. During initial operation
Tr Ts : Cooling operation
Tr < Ts : Heating operation
R4004135
Ex: When the target temperature is 25°C (77°F)
Cooling → 24°C (75.2°F): Thermostat OFF → 22.5°C (72.5°F): Switch to heating
Heating → 26°C (78.8°F): Thermostat OFF → 28°C (82.4°F): Switch to cooling
Target temperature + 3.0°C (+5.4°F)
Heating Operation
Target temperature – 2.5°C (–4.5°F)
Cooling Operation
Target temperature – 1.0°C (–1.8°F)
= Thermostat OFF
Target temperature + 1.0°C (+1.8°F)
= Thermostat OFF
background
SiUS042501E Common Functions
Part 4 Functions and Control 29
1.8 Thermostat Control
Outline Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Details Thermostat OFF Conditions
The temperature difference is in the zone A.
Thermostat ON Conditions
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
Cooling/Dry
R4004136
Heating
R4004137
Refer to Temperature Control on page 22 for details.
Cooling Dry Heating
10 minutes 7.5 minutes 180 seconds
Zone BZone B
Zone AZone A
OFFOFF
ONON
Zone CZone C
Room thermistor temperature – target temperature
–0.5°C (–0.9°F)
–0.25°C (–0.5°F)
–1.0°C (–1.8°F)
Zone B
Zone B
Zone A
Zone A
OFF
OFF
ON
ON
Zone C
Zone C
1.0°C (1.8°F)
0.5°C (0.9°F)
0.25°C (0.5°F)
0.75°C (1.4°F)
1.0°C (1.8°F)
Room thermistor temperature – target temperature
background
Common Functions SiUS042501E
30 Part 4 Functions and Control
1.9 NIGHT SET Mode
Outline When the OFF TIMER is set, NIGHT SET mode is automatically activated. NIGHT SET mode
keeps the airflow rate setting.
Details NIGHT SET mode continues operation at the target temperature for the first one hour, then
automatically raises the target temperature slightly in the case of cooling, or lowers the target
temperature slightly in the case of heating. This prevents excessive cooling in summer and
excessive heating in winter to ensure comfortable sleeping conditions, and also conserves
electricity.
Cooling
Heating
1.10 ECONO Operation
Outline ECONO operation reduces the maximum operating current and the power consumption.
This operation is particularly convenient for energy-saving. It is also a major bonus when
breaker capacity does not allow the use of multiple electrical devices and air conditioners.
It can be easily activated by pressing ECONO button on the wireless remote controller.
Details When this function is activated, the maximum capacity also decreases.
The remote controller can send the ECONO command when the unit is in cooling, heating,
dry, or automatic operation. This function can only be set when the unit is running. Pressing
ECONO button on the remote controller cancels the function.
This function and POWERFUL operation cannot be used at the same time. The latest
command has the priority.
(R23917)
Target temperature
+0.5°C (+0.9°F)
temperature shift
Operation stops
at the set hour
0.5°C (0.9°F)
1 hour
TIMER operation
NIGHT SET Mode ON
Target temperature
–2°C (–3.6°F)
temperature shift
1 hour
2°C (3.6°F)
(R23918)
TIMER operation
NIGHT SET Mode ON
ECONO operation
(R22012)
Normal operation
Maximum during normal operation
Maximum during ECONO operation
Time
Power
consumption
and current
background
SiUS042501E Common Functions
Part 4 Functions and Control 31
1.11 POWERFUL Operation
Outline In order to exploit the cooling and heating capacity to full extent, the air conditioner can be
operated by increasing the indoor fan rotating speed and the compressor frequency.
Details When POWERFUL button is pressed, the fan speed and target temperature are converted to
the following states for 20 minutes.
A = 40 ~ 80 rpm (depending on the model)
Ex: POWERFUL operation in cooling
POWERFUL operation cannot be used together with ECONO, COMFORT AIRFLOW
operation.
Operation mode Fan speed Target temperature
COOL H tap + A rpm 18°C (64.4°F)
DRY Dry rotating speed + A rpm Lowered by 2.5°C (4.5°F)
HEAT H tap + A rpm 31°C (87.8°F)
FAN H tap + A rpm —
AUTO Same as cooling/heating in
POWERFUL operation
The target temperature is kept
unchanged.
(R24589)
Target temp.
Fan
A rpm
H tap
Set tap
20 minutes
Lower limit of cooling
temperature
Remote controller registers
20 minutes independently.
POWERFUL
ON
POWERFUL
OFF
Ending conditions:
1. Lapse of 20 minutes
2. System operation OFF
3. POWERFUL operation OFF
18°C (64.4°F)
background
Common Functions SiUS042501E
32 Part 4 Functions and Control
1.12 Brightness Setting of Indoor Unit Display
Outline The brightness of the indoor unit display can be adjusted as desired. Also, the display can be
turned OFF.
Details 1. Press and hold FAN button for 5 seconds.
2. Press TEMP ▲ button to select menu number 1.
LED appears and 1 blinks.
R4004121
3. Press FAN button to confirm the select setting.
4. Press TEMP ▲ or TEMP ▼ button to change the setting as follows:
R4004122
5. Press FAN button again. Brightness will be set to the chosen value.
6. Press and hold FAN button for 5 seconds to return to the default screen.
The display automatically returns to the default screen after 60 seconds. To return to the default
screen sooner, press CANCEL button twice.
H: Bright L: Dark of: OFF
background
SiUS042501E Common Functions
Part 4 Functions and Control 33
1.13 Wireless LAN Connection (Optional)
Operation
Wireless LAN connection adapter
The Wireless LAN connection adapter function requires the Daikin One Home for connecting to the air conditioner and controlling
it via your smartphone or tablet over your network.
Attention
•
Wireless LAN sends and receives data using radio waves so there is a risk of transmitted data being subject to eavesdropping and illegal access.
When using wireless LAN, manage the SSID/KEY of the wireless LAN connection adapter, the SSID/KEY of the wireless router, and the app login
information so that they will not be known to others, and ensure that you have an adequate understanding of the risks involved.
In the case that the product is accessed and operated illegally, turn off the wireless LAN connection adapter function.
• Do not use this product near a microwave oven. (This can affect wireless LAN communications.)
• This product cannot be directly connected to the communication line of a telecommunications carrier (internet service provider,
etc.). When connecting to the internet, be sure to connect via a device such as a router.
When the wireless LAN connection adapter function is turned on, the right side of the air conditioner may become slightly warm, but this is not
an abnormality.
WARNING
•
This product may cause electromagnetic interference.
•
This product may cause faulty behavior of the equipment.
• The user is responsible for providing the following items before using this product:
Smartphone or tablet PC
Internet line and communicating device (Modem/router or similar device)
Wireless LAN access point
Application name: [Daikin One Home] (free)
For details on the installation method for the Daikin One Home.
Wireless LAN connection adapter lamp (Orange)
• The Wireless LAN connection adapter lamp lights when connecting to a router (Wireless LAN
access point).
• For Wireless LAN connection adapter operation.
Display
WARNING
When operating an air conditioner from outside the home, it is not possible to check the air conditioner or the surroundings of the air
conditioner, or the state of the people in the room. Therefore, make sure to adequately check for safety before use.
In some cases, there is a risk of death, severe injury, or property damage.
Check the following in advance (while at home)
• Timer settings or reservations that other users may have made. (There is a risk of causing harm to the health of people, animals, or plants in
the home if operation starts and stops unexpectedly)
•
staining of household items)
Check the following before/while operating a unit from outside the home
• If you know that there is someone at home, inform the person when turning the air conditioner on or off from outside the home. (If someone at
home is standing on something such as a stool, the air conditioner turning on or off unexpectedly could surprise them and cause them to fall or
topple over. Additionally, a sudden change in the indoor/outdoor temperature could harm the health of people at home)
· The air conditioner can be turned off and temperature adjustment can be made using a remote controller in the home.
· Do not use the function if the only people at home are persons who are unable to make adjustments to temperature or other settings
themselves, such as young children, disabled persons, or elderly persons.
• Regularly check the settings and operating status of the air conditioner. (Sudden changes in indoor/outdoor temperature pose a health hazard.
There is a risk of harm to animals and plants)
If an error occurs during operation, immediately turn off the air conditioner and contact your dealer.
background
Common Functions SiUS042501E
34 Part 4 Functions and Control
Wireless LAN connection
Web site:
https://go.daikincomfort.com/wifi
F
or instructions on how to connect your unit to wireless LAN and to your Daikin One Home application, please see the website above.
Contains FCC ID: VPYLB1YA
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation.
FCC CAUTION
This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter.
Contains IC: 772C-LB1YA
This device complies with Industry Canada’s applicable licence-exempt RSSs.
Operation is subject to the following two conditions:
(1) This device may not cause interference; and
(2) This device must accept any interference, including interference that may cause undesired operation of the device.
This equipment complies with IC radiation exposure limits set forth for an uncontrolled environment and meets RSS-102 of the IC radio frequency (RF)
Exposure rules. This equipment should be installed and operated keeping the radiator at least 7-7/8 inches (20cm) or more away from person’s body.
The FCC responsible party is Daikin Comfort Technologies Manufacturing, L.P., and may be contacted by calling (713)-861-2500, or at 19001
Kermier Rd., Waller, TX 77484.
(https://www.northamerica-daikin.com)
radiator.
And this intentional radiator has an industry Canada ID: IC 772C-LB1YA.
The manufacturer of the intentional radiator (model no. Type1YA) is Murata Manufacturing co., Ltd (www.murata.com).
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment and meets the FCC radio frequency (RF) Exposure
Guidelines. This equipment should be installed and operated keeping the radiator at least 7-7/8 inches (20cm) or more away from person’s body.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
background
SiUS042501E Common Functions
Part 4 Functions and Control 35
Application software installation
For Android Phones
1) Open [Google Play].
2) Search using the application name:
[Daikin One Home].
3) Follow the directions on the screen to install.
For iOS Phones
1) Open the [App Store].
2) Search using the application name:
[Daikin One Home].
3) Follow the directions on the screen to install.
Attention
• The actual application screen layout and content may differ from what is shown. The layout and content of the application screen is subject to
change without notice.
Connect the air conditioner to your home network.
1.
While operation is stopped, press and hold the button for 5 seconds.
2.
Press or and select menu number .
• “ ” appears on the LCD.
• “
” blinks.
3.
Press to connect to the access point.
The wireless LAN
connection adapter
lamp blinks quickly.
Display
4.
Press to return to the default screen.
No more settings need to be carried out from the remote controller.
5.
Open Daikin One Home App and follow the instructions to set up the wireless LAN.
6.
When the wireless LAN connection adapter lamp switches from blinking to lit, the
connection is complete.
NOTE
• While “SP” is displayed, the options that can be selected using and are 1, 3, A, and OFF.
• Perform wireless LAN connection one indoor unit at a time.
• If you are unable to establish a network connection, refer the troubleshooting provided by the Daikin One Home App.
• When the lamp blinks slowly, the connection is not ready. Perform the connection procedure while it blinks quickly.
background
Common Functions SiUS042501E
36 Part 4 Functions and Control
1.
While operation is stopped, press and hold the button for 5 seconds.
2. Press
• “ ” appears on the LCD.
• “
” blinks.
Check the indoor unit LED.
Wireless LAN connection adapter lamp Status
Blinking for 1 second Connection is not ready
Blinking for 3 seconds
Please initialize the wireless LAN connection adapter
Does not blink or light
Communication is abnormal
There is a possibility of equipment failure
Please request repair
To turn off the wireless connection
To use the remote controller
1.
While operation is stopped, press and hold the button for 5 seconds.
2. Press or and select menu .
• “ ” appears on the LCD.
• “
” blinks, and communication is OFF.
3.
Press
• The wireless LAN connection adapter lamp turn off.
4. Press to return to the default screen.
To reset the connection setting to the factory default
•
If you want to reset the connection settings, it is possible to initialize the wireless LAN connection adapter to its
factory default state. If initialized, data including the network settings and power consumption history will be erased.
• When discarding or transferring to another user, initialize the connection adapter to erase the internal data.
To reset
1.
While operation is stopped, press and hold the button for 5 seconds.
2. Press or and select menu .
• “ ” appears on the LCD.
• “
” blinks.
3.
Press
• The wireless LAN connection adapter lamp blinks for 1 second.
4. Press to return to the default screen.
background
SiUS042501E Common Functions
Part 4 Functions and Control 37
1.14 Other Functions
1.14.1 Hot-Start Function
In order to prevent the cold air blast that normally occurs when heating operation is started, the
temperature of the indoor heat exchanger is detected, and the airflow is either stopped or
significantly weakened resulting in comfortable heating.
The cold air blast is prevented using similar control when defrost control starts or when the
thermostat is turned ON.
1.14.2 Signal Receiving Sign
When the indoor unit receives a signal from the remote controller, the unit emits a signal
receiving sound.
1.14.3 Indoor Unit ON/OFF Switch
ON/OFF switch is provided on the display of the unit.
Press ON/OFF switch once to start operation. Press once again to stop it.
ON/OFF switch is useful when the remote controller is missing or the battery has run out.
R4004227
1.14.4 Auto-restart Function
If a power failure (even a momentary one) occurs during the operation, the system restarts
automatically in the same conditions as before when the power supply is restored to the
conditions prior to the power failure.
It takes 3 minutes to restart the operation because 3-minute standby function is activated.
Operation mode Temperature setting Airflow rate
AUTO 25°C (77°F) Automatic
ON/OFF switch
background
Thermistor Functions SiUS042501E
38 Part 4 Functions and Control
2. Thermistor Functions
(1) Discharge
Pipe Thermistor
The discharge pipe thermistor is used for controlling discharge pipe temperature. If the
discharge pipe temperature (used in place of the inner temperature of the compressor) rises
abnormally, the operating frequency becomes lower or the operation halts.
The discharge pipe thermistor is used for detecting disconnection of the discharge pipe
thermistor.
(2) Outdoor Heat
Exchanger
Thermistor
The outdoor heat exchanger thermistor is used for controlling the target discharge pipe
temperature. The system sets the target discharge pipe temperature according to the
outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve
opening so that the target discharge pipe temperature can be obtained.
In cooling operation, the outdoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature drops
below the outdoor heat exchanger temperature by more than a certain value, the discharge
pipe thermistor is judged as disconnected.
In cooling operation, the outdoor heat exchanger thermistor is used for high pressure
protection.
(3) Outdoor
Temperature
Thermistor
The outdoor temperature thermistor detects the outdoor air temperature and is used for
refrigerant shortage detection, input current control, outdoor fan control, liquid compression
protection function, and so on.
(4) Indoor Heat
Exchanger
Thermistor
The indoor heat exchanger thermistor is used for controlling the target discharge pipe
temperature. The system sets the target discharge pipe temperature according to the
outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve
opening so that the target discharge pipe temperature can be obtained.
In cooling operation, the indoor heat exchanger thermistor is used for freeze-up protection
control. If the indoor heat exchanger temperature drops abnormally, the operating frequency
becomes lower or the operation halts.
In heating operation, the indoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature drops
below the indoor heat exchanger temperature by more than a certain value, the discharge
pipe thermistor is judged as disconnected.
(5) Room
Temperature
Thermistor
The room temperature thermistor detects the room air temperature and is used for
controlling the room air temperature.
Four way valve
Compressor
(R23851)
Expansion valve
(2) Outdoor Heat
Exchanger
Thermistor
(3) Outdoor
Temperature
Thermistor
(5) Room
Temperature
Thermistor
(1) Discharge Pipe
Thermistor
(4) Indoor Heat
Exchanger
Thermistor
background
SiUS042501E Control Specification
Part 4 Functions and Control 39
3. Control Specification
3.1 Mode Hierarchy
Outline The air conditioner control has normal operation mode, forced operation mode, and power
transistor test mode for installation and servicing.
Details
Unless specified otherwise, dry operation command is regarded as cooling operation.
3.2 Frequency Control
Outline The compressor frequency is determined according to the difference between the room
thermistor temperature and the target temperature.
Detail 1. Determine command frequency
Command frequency is determined in the following order of priority.
(1) Limiting defrosts control time
(2) Forced cooling
(3) Indoor frequency command
Air conditioner control mode
Forced operation mode
Forced cooling operation (for pump down operation)
Power transistor test mode
Normal operation mode
Fan
Cooling (includes drying)
Heating
Heating
Defrosting
Stop (indoor unit: OFF)
Preheating control
Discharging from capacitor
Stop
(R22375)
Command frequency
Limit frequency
Skip control
Upper limit function
Compressor protection function
Lower limit function
Four way valve operation compensation, etc.
Target frequency
(R18023)
When the shift of the frequency is less than zero (ΔF<0) by PI control,
the target frequency is used as the command frequency.
Dropping function
Input current control, etc.
Upper limit frequency
FMAX
Lower limit frequency
FMIN
Initial frequency
PI control
Defrost control
background
Control Specification SiUS042501E
40 Part 4 Functions and Control
2. Determine upper limit frequency
The minimum value is set as an upper limit frequency among the frequency upper limits of
the following functions:
Compressor protection, input current, discharge pipe temperature, heating peak-cut,
freeze-up protection, defrost control.
3. Determine lower limit frequency
The maximum value is set as the lower limit frequency among the frequency lower limits of
the following functions:
Four way valve operation compensation, draft prevention, pressure difference upkeep.
4. Determine prohibited frequency
There is a certain prohibited frequency such as power supply frequency.
Initial Frequency When starting the compressor, the frequency is initialized according to the D value of the
indoor unit.
D signal: Indoor frequency command
The difference between the room thermistor temperature and the target temperature is taken as
the D value and is used for frequency command.
OFF = Thermostat OFF
PI Control 1. P control
The D value is calculated in each sampling time (20 seconds), and the frequency is
adjusted according to its difference from the frequency previously calculated.
2. I control
If the operating frequency does not change for more than a certain fixed time, the frequency
is adjusted according to the D value.
When D value is low, the frequency is lowered.
When D value is high, the frequency is increased.
3. Frequency control when other controls are functioning
When frequency is dropping;
Frequency control is carried out only when the frequency drops.
For controlling lower limit;
Frequency control is carried out only when the frequency rises.
4. Upper and lower limit of frequency by PI control
The frequency upper and lower limits are set according to the command of the indoor unit.
When the indoor or quiet outdoor unit operation command comes from the indoor unit, the
upper limit frequency is lower than the usual setting.
Temperature
difference
D
signal
Temperature
difference
D
signal
Temperature
difference
D
signal
–1.0°C (–1.8°F) OFF 0°C (0°F) 4 2.0°C (3.6°F) 8
–0.75°C (–1.3°F) 1 0.5°C (0.9°F) 5 2.5°C (4.5°F) 9
–0.5°C (–0.9°F) 2 1.0°C (1.8°F) 6 3.0°C (5.4°F) 10
–0.25°C (–0.4°F) 3 1.5°C (2.7°F) 7 3.5°C (6.3°F) 11
background
SiUS042501E Control Specification
Part 4 Functions and Control 41
3.3 Controls at Mode Changing/Start-up
3.3.1 Preheating Control
Outline The inverter operation in open phase starts with the conditions of the outdoor temperature, the
discharge pipe temperature, the radiation fin temperature and the preheating command from
the indoor unit.
Details ON condition
Discharge pipe temperature < A
Outdoor temperature < B
Radiation fin temperature < 85°C (185°F)
OFF condition
Discharge pipe temperature > C
Outdoor temperature > D
Radiation fin temperature ≥ 90°C (194°F)
3.3.2 Four Way Valve Switching
Outline The four way valve coil is energized/not energized depending on the operation mode.
(Heating: ON, Cooling/Dry/Defrost: OFF)
In order to eliminate the switching sound as the four way valve coil switches from ON to OFF
when the heating is stopped, the OFF delay switch of the four way valve is carried out.
Details OFF delay switch of four way valve
The four way valve coil is energized for 160* seconds after the operation is stopped.
*10 seconds in heating operation when the outdoor temperature is lower than -9 °C (15.8°F)
3.3.3 Four Way Valve Operation Compensation
Outline At the beginning of operation as the four way valve is switched, the pressure difference to
activate the four way valve is acquired when the output frequency is higher than a certain fixed
frequency, for a certain fixed time.
Details Starting Conditions
1. When the compressor starts and the four way valve switches from OFF to ON
2. When the four way valve switches from ON to OFF during operation
3. When the compressor starts after resetting
4. When the compressor starts after the fault of four way valve switching
The lower limit of frequency keeps A Hz for B seconds for any of the conditions above.
When the outdoor temperature is above C in heating, the frequency decreases depending on
the outdoor temperature.
3.3.4 3-Minute Standby
Turning on the compressor is prohibited for 3 minutes after turning off.
The function is not used when defrosting.
ABCD
(°C) (°F) (°C) (°F) (°C) (°F) (°C) (°F)
2.5 36.5 0 32 4 39.2 2 35.6
Cooling Heating
A (Hz) 40 54
B (seconds) 60
C (°C) 10
(°F) 50
background
Control Specification SiUS042501E
42 Part 4 Functions and Control
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
The function is not used when defrosting.
09 class 12 class
A (Hz) 34 40
B (Hz) 46 54
C (Hz) 54 72
D (Hz) 72 90
E (Hz) 90 112
F (seconds) 180 180
G (seconds) 240 420
H (seconds) 180 180
J (seconds) 180 120
K (seconds) 300 400
(sec.)
Time
(R23251)
(Hz)
Frequency
C
D
E
B
FGHJK
A
background
SiUS042501E Control Specification
Part 4 Functions and Control 43
3.4 Discharge Pipe Temperature Control
Outline The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to
keep the discharge pipe temperature from rising further.
Details
Zone Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of frequency decreases.
Keep zone The upper limit of frequency is kept.
Up zone The upper limit of frequency increases.
Reset zone The upper limit of frequency is canceled.
(°C) (°F)
A 118 244.4
B 105 221.0
C 100 212.0
D 95 203.0
E 90 194.0
(R25005)
Discharge pipe
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
E
A
B
C
D
background
Control Specification SiUS042501E
44 Part 4 Functions and Control
3.5 Input Current Control
Outline The microcomputer calculates the input current while the compressor is running, and sets the
frequency upper limit based on the input current.
In case of heat pump models, this control is the upper limit control of the frequency and takes
priority over the lower limit control of four way valve operation compensation.
Details
Frequency control in each zone
Stop zone
After the input current remains in the stop zone for 2.5 seconds, the compressor is stopped.
Dropping zone
The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
After this, the output frequency is lowered by 2 Hz every second until it reaches the keep
zone.
Keep zone
The present maximum frequency goes on.
Reset zone
Limit of the frequency is canceled.
Limitation of current dropping and stop value according to the outdoor temperature
The current drops when outdoor temperature becomes higher than a certain level
(depending on the model).
Cooling Heating
A (A) 14.5
B (A) 13.2
C (A) 12.2
Compressor Stop
Input current
Dropping zone
Stop zone
Keep zone
Reset zone
(R23249)
A
(A)
B
C
background
SiUS042501E Control Specification
Part 4 Functions and Control 45
3.6 High Pressure Protection Control
Outline In order to prevent abnormal high pressures in the system and hence avoiding activation of the
high pressure safety device the below control function will be activated.
Details
Indoor heat exchanger
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
Pressure
4.15 MPa (602 psi)
High Pressure
Protection
Control
Heating
Peak- cut
control
Condensing
temperature
HPS ≥ 4.15 MPa (602 psi)
Compressor on
Compressor stop
(E3 indication)
Abnormal stop
(E3 indication)
Normal operation
background
Control Specification SiUS042501E
46 Part 4 Functions and Control
3.7 Freeze-up Protection Control
Outline During cooling operation, the signal sent from the indoor unit determines the frequency upper
limit and prevents freezing of the indoor heat exchanger. The signals from the indoor unit are
divided into zones.
Details The operating frequency limitation is judged with the indoor heat exchanger temperature.
R4003644
3.8 Heating Peak-cut Control
Details
During heating operation, the indoor heat exchanger temperature determines the frequency
upper limit to prevent abnormal high pressure.
The operating frequency limitation is judged with the indoor heat exchanger temperature.
: The valves might drop when the outdoor temperature is low to protect the compressor.
Reset zone
Up zone
Keep zone
Dropping zone
Stop zone
13°C (55.4°F)
7°C (44.6°F)
3°C (37.4°F)
0°C (32.0°F)
5°C (41.0°F)
(Reference)
Indoor heat exchanger
temperature (R2T)
Zone
Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of frequency decreases.
Keep zone The upper limit of frequency is kept.
Up zone The upper limit of frequency increases.
Reset zone The upper limit of frequency is canceled.
(°C) (°F)
A 59 138.2
B 55 131.0
C 52 125.6
D 50 122.0
E 45 113.0
Indoor heat exchanger
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
(R23928)
D
C
B
A
E
background
SiUS042501E Control Specification
Part 4 Functions and Control 47
3.9 Outdoor Fan Control
1. Fan ON control to cool down the electrical box
The outdoor fan is turned ON when the electrical box temperature is high while the
compressor is OFF.
2. Fan OFF control during defrosting
The outdoor fan is turned OFF while defrosting.
3. Fan OFF delay when stopped
The outdoor fan is turned OFF 60 ~ 70 seconds after the compressor stops.
4. Fan speed control for pressure difference upkeep
The rotation speed of the outdoor fan is controlled for keeping the pressure difference during
cooling operation with low outdoor temperature.
When the pressure difference is low, the rotation speed of the outdoor fan is reduced.
When the pressure difference is high, the rotation speed of the outdoor fan is controlled
as well as normal operation.
5. Fan speed control during forced operation
The outdoor fan is controlled as well as normal operation during forced operation.
6. Fan speed control during POWERFUL operation
The rotation speed of the outdoor fan is increased during POWERFUL operation.
7. Fan speed control during indoor unit quiet operation
The rotation speed of the outdoor fan is reduced by the command of the indoor unit quiet
operation.
8. Fan ON/OFF control when operation (cooling, heating, dry) starts/stops
The outdoor fan is turned ON when the operation starts. The outdoor fan is turned OFF
when the operation stops.
3.10 Liquid Compression Protection Function
Outline The compressor stops according to the outdoor temperature for protection.
Details Operation stops depending on the outdoor temperature.
The compressor turns off under the conditions that the system is in cooling operation and the
outdoor temperature is below 0°C (32°F).
background
Control Specification SiUS042501E
48 Part 4 Functions and Control
3.11 Defrost Control
Outline Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than a certain value to finish defrosting.
Details Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than A minutes (depending on the duration of the previous defrost control) of
accumulated time have passed since the start of the operation, or ending the previous
defrosting.
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature (B).
A (minute) 20 ~ 25
B (°C) 2 ~ 12
(°F) 35.6 ~ 53.6
C (Hz) 58
D (Hz) 74
E (seconds) 40
F (seconds) 60
G (seconds) 690
H (seconds) 50
J (seconds) 8
K (pulse) 410
L (pulse) 350
M (pulse) 400
Frequency
Compressor
Four way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0 Hz 0 Hz
C Hz
D Hz
J sec.
PI control
8 sec.
H sec.
(R21661)
E sec.
F sec.
G sec.
L pulse zone
Electronic
expansion valve
opening
Normal
control
K pulse
zone
M pulse
zone
Starting
control
background
SiUS042501E Control Specification
Part 4 Functions and Control 49
3.12 Electronic Expansion Valve Control
Outline The following items are included in the electronic expansion valve control.
Electronic expansion valve is fully closed
1. Electronic expansion valve is fully closed when turning on the power.
2. Pressure equalizing control
Open Control
1. Electronic expansion valve control when starting operation
2. Electronic expansion valve control when the frequency changes
3. Electronic expansion valve control for defrosting
4. Electronic expansion valve control when the discharge pipe temperature is abnormally high
5. Electronic expansion valve control when the discharge pipe thermistor is disconnected
Feedback Control
Target discharge pipe temperature control
Details The followings are the examples of electronic expansion valve control for each operation mode.
R4003560
3.12.1 Initialization as Power Supply On
The electronic expansion valve is initialized (fully closed) when the power is turned on. Then,
the valve opening position is set and the pressure is equalized.
3.12.2 Pressure Equalizing Control
When the compressor is stopped, the pressure equalizing control is activated. The electronic
expansion valve opens, and develops the pressure equalization.
: Available
: Not available
Control
Status
Starting operation control
Control when the frequency changes
Target discharge pipe temperature control
Discharge pipe thermistor disconnection control
High discharge pipe temperature control
Defrost control (heating only)
Pressure equalizing control
Opening limit control
Power on ; Compressor stop
Operation start
Frequency change under starting control
During target discharge pipe temperature control
Frequency change under target discharge pipe
temperature control
Discharge pipe thermistor disconnection
Frequency change under discharge pipe thermistor
disconnection control
During defrost control
background
Control Specification SiUS042501E
50 Part 4 Functions and Control
3.12.3 Opening Limit Control
The maximum and minimum opening of the electronic expansion valve are limited.
The electronic expansion valve is fully closed when cooling operation stops, and is opened at a
fixed degree during defrosting.
3.12.4 Starting Operation Control
The electronic expansion valve opening is controlled when the operation starts, thus preventing
superheating or liquid compression.
3.12.5 Control when the Frequency Changes
When the target discharge pipe temperature control is active, if the target frequency changes to
a specified value in a certain time period, the target discharge pipe temperature control is
canceled and the target opening of the electronic expansion valve is changed according to the
frequency shift.
3.12.6 High Discharge Pipe Temperature Control
When the compressor is operating, if the discharge pipe temperature exceeds a certain value,
the electronic expansion valve opens and the refrigerant runs to the low pressure side.
This procedure lowers the discharge pipe temperature.
3.12.7 Discharge Pipe Thermistor Disconnection Control
Outline The disconnection of the discharge pipe thermistor is detected by comparing the discharge pipe
temperature with the condensation temperature. If the discharge pipe thermistor is
disconnected, the electronic expansion valve opens according to the outdoor temperature and
the operation frequency, operates for a specified time, and then stops.
After 3 minutes, the operation restarts and checks if the discharge pipe thermistor is
disconnected. If the discharge pipe thermistor is disconnected, the system stops after operating
for a specified time.
If the disconnection is detected repeatedly, the system is shut down. When the compressor runs
for 60 minutes without any error, the error counter is reset.
Details Determining thermistor disconnection
When the starting control finishes, the detection timer for disconnection of the discharge pipe
thermistor (A seconds) starts. When the timer is over, the following adjustment is made.
1. When the operation mode is cooling
When the following condition is fulfilled, the discharge pipe thermistor disconnection is
ascertained.
Discharge pipe temperature +6°C (+10.8°F) < outdoor heat exchanger temperature
2. When the operation mode is heating
When the following condition is fulfilled, the discharge pipe thermistor disconnection is
ascertained.
Discharge pipe temperature +6°C (+10.8°F) < indoor heat exchanger temperature
When the thermistor is disconnected
When the disconnection is ascertained, the compressor continues operation for 9 minutes and
then stops.
If the compressor stops repeatedly, the system is shut down.
Maximum opening (pulse) 470
Minimum opening (pulse) 60
A (seconds)
Other than below 720
Heating
(When outdoor temperature is below –15°C (5°F))
1200
background
SiUS042501E Control Specification
Part 4 Functions and Control 51
3.12.8 Target Discharge Pipe Temperature Control
The target discharge pipe temperature is obtained from the indoor and outdoor heat exchanger
temperature, and the electronic expansion valve opening is adjusted so that the actual
discharge pipe temperature becomes close to the target discharge pipe temperature. (Indirect
SH (superheating) control using the discharge pipe temperature)
The electronic expansion valve opening and the target discharge pipe temperature are adjusted
every A seconds. The opening degree of the electronic expansion valve is adjusted by the
following.
Target discharge pipe temperature
Actual discharge pipe temperature
Previous discharge pipe temperature
The time depends on the opening of the electronic expansion valve.
3.13 Malfunctions
3.13.1 Sensor Malfunction Detection
Sensor malfunction can be detected in the following thermistor:
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Outdoor temperature thermistor
3.13.2 Detection of Overcurrent and Overload
Outline An excessive output current is detected and the OL temperature is observed to protect the
compressor.
Details If the OL (compressor body) temperature exceeds 125°C (257°F), the system shuts down
the compressor.
If the inverter current exceeds 14.5 A, the system shuts down the compressor.
The upper limit of the current decreases when the outdoor temperature exceeds a certain
level.
A (seconds) 10 ~ 30
SC
(Subcooling)
SH
(Superheating)
The target discharge pipe
temperature is set as to become
the target SH.
The inclination does not change
depending on the operating condition.
(R23014)
background
SiUS042501E
52 Part 5 Remote Controller
1. Applicable Remote Controller ...............................................................53
2. ARC480A83 ..........................................................................................54
3. BRC073A6 ............................................................................................56
4. BRC944B2 ............................................................................................60
Part 5
Remote Controller
background
SiUS042501E Applicable Remote Controller
Part 5 Remote Controller 53
1. Applicable Remote Controller
Refer to the operation manual of applicable model for details. You can download operation
manuals from Daikin Business Portal:
Daikin Business Portal Document Search Item Category Installation/Operation Manual
(URL: https://global1d.daikin.com/business_portal/login/
)
Model Name Wireless R/C Reference Page Wired R/C Reference Page
FTXQ09ASBU9
ARC480A83 54
BRC073A6
BRC944B2
56
60
FTXQ12ASBU9
background
ARC480A83 SiUS042501E
54 Part 5 Remote Controller
2. ARC480A83
R5000453
Signal transmitter
Receiver
• To use the remote controller, aim the
transmitter at the indoor unit. If there
is anything blocking the signals
between the unit and the remote
controller, such as a curtain, the unit
may not operate.
• The maximum transmission distance
is about 23 ft. (7 m).
OFF button
• Press this button once to stop the
operation.
Display (LCD)
• Displays the current settings.
(In this illustration, each section is
shown with all its displays on for the
purpose of explanation.)
• Selects an appropriate operation
mode (COOL or HEAT) automatically
based on the indoor temperature and
starts the operation.
AUTO button
• Starts the COOL, DRY, HEAT or
FAN ONLY operation.
Direct operation buttons
background
SiUS042501E ARC480A83
Part 5 Remote Controller 55
R5000494
Refer to the following pages for details.
Airflow rate 1-5 (Low to High)
TIMER CANCEL button
• Cancels the timer setting.
• Adjusts the airflow direction.
• When you press SWING
button, the flap moves up and
down. The flap stops when you
press SWING button again.
SWING
4
buttons
OFF TIMER button
(NIGHT SET mode)
•
Adjusts the OFF TIMER
setting.
•
The timer can be set
1 ~ 12 hours.
ECONO
3
button
• Starts ECONO operation.
COMFORT button
1
• Starts COMFORT AIRFLOW
operation.
ON TIMER button
•
Adjusts the ON TIMER setting.
• The time can be set
1 ~ 12 hours.
FAN setting button
• Selects the airflow rate setting
every time you press this button.
• In indoor unit quiet operation,
operation sound becomes weak.
(The airflow rate also decreases.)
• In DRY operation, the airflow rate
setting is not available.
• Changes the temperature
setting.
TEMPERATURE
adjustment buttons
: AUTO
: DRY
: COOL
: HEAT
: FAN
18 ~ 30 °C
(64 ~ 86 °F)
Not available
18 ~ 32 °C
(64 ~ 90 °F)
10 ~ 30 °C
(50 ~ 86 °F)
Not available
AUTO
Indoor unit quiet
• Starts POWERFUL operation.
• Wireless LAN connection.
POWERFUL
2
button
and Wireless LAN
3
(optional) button
(push 5 seconds)
1 COMFORT AIRFLOW operation P.25
2 POWERFUL operation P.31
3 Wireless LAN connection (optional) P.33
4 ECONO operation P.30
5 Auto-swing P.24
background
BRC073A6 SiUS042501E
56 Part 5 Remote Controller
3. BRC073A6
2. Fan Speed/Airflow
Direction button
3. Menu/Enter button
8. ON/OFF button
10. Cancel button
9. Operation lamp
11. LCD (with backlight)
4. Up button
5. Down button
6. Right button
7. Left button
1. Operation Mode
Selector button
background
SiUS042501E BRC073A6
Part 5 Remote Controller 57
• Press this button to select the operation
mode of your preference.
• Available modes may vary with the
connected model.
1. Operation Mode Selector button
• Used to change the fan speed and airflow
direction.
• Available fan speeds and airflow directions
may vary with the connected model.
2. Fan Speed/Airflow Direction
button
• This button is enabled by default.
• Used to display the Main Menu or enter
the selected item.
3. Menu/Enter button
• Used to raise the set temperature.
• The next item on the upper side will be
highlighted.
(Keep pressing the button to cycle through
the values or items).
• Used to change the selected item.
4. Up button
• Used to lower the set temperature.
• The next item on the lower side will be
highlighted.
(Keep pressing the button to cycle through
the values or items).
• Used to change the selected item.
5. Down button
• Used to highlight the next items on the
right-hand side.
• The display contents are changed to the
next screen.
• Used to highlight the next items on the
left-hand side.
• The display contents are changed to the
previous screen.
• This lamp lights up during operation.
• This lamp is not lit when the unit operation
is OFF.
• This lamp blink if an error or mode conflict
occurs.
• This button is enabled by default.
• Used to return to the previous screen.
• Press to start or stop the air conditioner.
6. Right button
7. Left button
8. ON/OFF button
9. Operation lamp (Green)
10. Cancel button
• The backlight will be lit for approximately
30
seconds when one of the buttons is
pressed.
• The actions linked to the buttons, except
for the ON/OFF button, are not carried out
when the backlight is not lit.
11. LCD (with backlight)
background
BRC073A6 SiUS042501E
58 Part 5 Remote Controller
Liquid Crystal Display
• There are four display methods for the liquid crystal display (LCD) available. The
Standard display, which is used by default, and the Detailed display. There is also the
possibility to use only Icon or Icon and Text mode (see the Installation manual).
• To change the active display method, select the desired display method in the Display
Method screen.
• The displayed contents on the screen may vary with the operation mode of the
connected models. (E.g.: The following display will appear when the air conditioner is
in heating operation).
Standard display
Detailed display
The clock and Detailed selection items appear on the Detailed
display in addition to the items appearing on the Standard display.
With icons With icons and text (default)
82°F
5
7
4
6
8
3
2
1
82
°F
Heat
Error: Push Menu button
5
7
4
6
8
3
2
1
Set to
With icons With icons and text
10
9
4
Mon
68
82
F
F
5
:
58
P
10
9
Mon
5
:
58
P
3
4
11
Error: Push Menu button
Heat
2
Set to Room
82
F
F
68
background
SiUS042501E BRC073A6
Part 5 Remote Controller 59
1. Operation mode
2. Fan Speed
3. Airflow direction
4. Set/Setback temperature display
Indicates the current operation mode.
Indicates the fan speed that is set for the
air conditioner.
The fan speed will not be displayed if the
air conditioner does not have the fan speed
control function.
Displayed only when the air conditioner is
in operation.
Indicates the airflow direction that is set for
the air conditioner.
The possible directions depend on the
indoor unit.
When the unit is turned ON, the
temperature that is set for the air
conditioner is displayed.
When the unit is turned OFF and Setback
is disabled, the temperature that is set for
the air conditioner is displayed.
When the unit is turned OFF and Setback
is enabled, the temperature that is set for
the setback function is displayed in smaller
digits.
•
•
•
•
•
•
•
•
•
Operation Mode
Cool Heat Auto (Heat)
Fan Dry Auto (Cool)
5. Error “ ”
Indicates a unit error.
•
9. Clock (12/24 hours real time clock)
Indicates that the clock is set.
If the clock is not set, “ -- : -- ” will be
displayed.
•
•
10. Detailed selection
Displayed when the detailed display mode
is selected.
No detailed items are selected by default.
•
•
6. Timer enabled “ ”
Indicates that the schedule timer or the
OFF timer is enabled.
•
7. Under Centralised control “ ”
Indicates that the air conditioner is under
the management of central control
equipment (optional accessories) and the
operation of the system through the remote
controller is prohibited.
•
8. Setback “ ”
The setback icon flashes when the unit is
turned on under the setback control.
•
Indicates that the clock needs to be set
again.
The schedule timer function will not work
unless the clock is set again.
•
•
11. Timer problem “ ”
background
BRC944B2 SiUS042501E
60 Part 5 Remote Controller
4. BRC944B2
R5000214
This remote controller cannot be used together with a standard wireless remote controller.
Otherwise, what appears on this remote controller's display may fail to correspond to actual
operating conditions.
background
SiUS042501E
Part 6 Service Diagnosis 61
1. General Problem Symptoms and Check Items .....................................63
2. Troubleshooting with LED .....................................................................64
2.1 Indoor Unit..............................................................................................64
2.2 Outdoor Unit ...........................................................................................64
3. Service Diagnosis .................................................................................65
3.1 ARC480 Series.......................................................................................65
3.2 BRC073A6 .............................................................................................68
4. Troubleshooting ....................................................................................70
4.1 Error Codes and Description ..................................................................70
4.2 Indoor Unit PCB Abnormality .................................................................71
4.3 Freeze-up Protection Control/Heating Peak-cut Control ........................72
4.4 Indoor Fan Motor (DC Motor) or Related Abnormality ...........................73
4.5 Indoor Heat Exchanger Thermistor or Related Abnormality...................75
4.6 Room Temperature Sensor Abnormality/Humidity Sensor
Abnormality ............................................................................................76
4.7 Low-voltage Detection or Over-voltage Detection..................................77
4.8 Signal Transmission Error (Between Indoor Unit and Outdoor Unit)......79
4.9 Unspecified Voltage (Between Indoor Unit and Outdoor Unit) ...............81
4.10 Outdoor Unit PCB Abnormality...............................................................82
4.11 OL Activation (Compressor Overload) or HPS Activation (High
Pressure Switch) ....................................................................................83
4.12 Compressor Lock ...................................................................................86
4.13 DC Fan Lock ..........................................................................................87
4.14 Input Overcurrent Detection ...................................................................88
4.15 Electronic Expansion Valve Coil Abnormality.........................................89
4.16 Four Way Valve Abnormality..................................................................90
4.17 Discharge Pipe Temperature Control.....................................................92
4.18 High Pressure Control in Cooling ...........................................................93
4.19 System Shutdown due to Temperature Abnormality in the
Compressor............................................................................................95
4.20 Compressor Sensor System Abnormality ..............................................96
4.21 Position Sensor Abnormality ..................................................................97
4.22 Thermistor or Related Abnormality (Outdoor Unit).................................99
4.23 Electrical Box Temperature Rise..........................................................101
4.24 Radiation Fin Temperature Rise ..........................................................102
4.25 Output Overcurrent Detection ..............................................................103
4.26 Signal Transmission Error on Outdoor Unit PCB .................................105
5. Check ..................................................................................................106
5.1 Thermistor Resistance Check ..............................................................106
5.2 Indoor Fan Motor Connector Check .....................................................106
5.3 Power Supply Waveform Check...........................................................107
5.4 Electronic Expansion Valve Check.......................................................107
Part 6
Service Diagnosis
background
SiUS042501E
62 Part 6 Service Diagnosis
5.5 Four Way Valve Performance Check ...................................................108
5.6 Inverter Unit Refrigerant System Check...............................................108
5.7 Inverter Analyzer Check .......................................................................109
5.8 Outdoor Fan Motor Check....................................................................111
5.9 Installation Condition Check.................................................................111
5.10 Discharge Pressure Check...................................................................112
5.11 Outdoor Fan System Check .................................................................112
5.12 Main Circuit Short Check......................................................................113
5.13 Power Module Check ...........................................................................114
background
SiUS042501E General Problem Symptoms and Check Items
Part 6 Service Diagnosis 63
1. General Problem Symptoms and Check Items
Symptom Check Item Measures
Reference
Page
The unit does not
operate.
Check the power supply. Check if the rated voltage is supplied. —
Check the type of the indoor unit. Check if the indoor unit type is compatible with the
outdoor unit.
—
Check the outdoor temperature. Heating/cooling operations are not available when
the outdoor temperature is out of the operation
limit. Check the reference page for the operation
limit.
132
Diagnose with remote controller
indication.
—70
Check the remote controller
addresses.
Check if address settings for the remote controller
and indoor unit are correct.
63
Operation sometimes
stops.
Check the power supply. A power failure of 2 to 10 cycles stops air
conditioner operation. (Operation lamp OFF)
—
Check the outdoor temperature. Heating/cooling operations are not available when
the outdoor temperature is out of the operation
limit. Check the reference page for the operation
limit.
132
Diagnose with remote controller
indication.
—70
The unit operates but
does not cool, or does
not heat.
Check for wiring and piping errors in
the connection between the indoor
unit and outdoor unit.
——
Check for thermistor detection errors. Check if the thermistor is mounted securely. —
Check for faulty operation of the
electronic expansion valve.
Set the unit to cooling operation, and check the
temperature of the liquid pipe to see if the
electronic expansion valve works.
—
Diagnose with remote controller
indication.
—70
Diagnose by service port pressure
and operating current.
Check for refrigerant shortage.
—
Large operating noise
and vibrations
Check the resistance between the
terminals of the power module.
—114
Check the power module. — —
Check the installation condition. Check if the required spaces for installation
(specified in the installation manual) are provided.
—
background
Troubleshooting with LED SiUS042501E
64 Part 6 Service Diagnosis
2. Troubleshooting with LED
2.1 Indoor Unit
Operation Lamp The operation lamp blinks when any of the following errors is detected.
1. When a protection device of the indoor or outdoor unit is activated, or when the thermistor
malfunctions.
2. When a signal transmission error occurs between the indoor and outdoor units.
In either case, conduct the diagnostic procedure described in the following pages.
R6001275
2.2 Outdoor Unit
The outdoor unit has one green LED on the PCB. When the microcomputer works in order, the
LED blinks. However, the LED turns OFF while the standby electricity saving function is
activated and the power supply to the outdoor unit is OFF.
Refer to page 20 for the location of LED.
Operation lamp
(green)
background
SiUS042501E Service Diagnosis
Part 6 Service Diagnosis 65
3. Service Diagnosis
3.1 ARC480 Series
3.1.1 Method 1
1. When TIMER CANCEL button is held down for 5 seconds, 00 is displayed on the
temperature display screen.
2. Press TIMER CANCEL button repeatedly until a long beep sounds.
R6001152
1. A short beep or two consecutive beeps indicate non-corresponding codes.
2. To return to the normal mode, hold TIMER CANCEL button down for 5 seconds. When the
remote controller is left untouched for 60 seconds, it also returns to the normal mode.
3. Not all the error codes are displayed. When you cannot find the error code, try method 2.
Refer to page 66.
The code indication changes in the sequence shown below.
ARC480A83
TIMER CANCEL button
< ARC480 Series >
No. Code No. Code No. Code
1 00 16 A3 31 UF
2 A5 17 H8 32 UH
3 E7 18 H9 33 P4
4 F3 19 C9 34 H7
5 F6 20 CC 35 U2
6 L3 21 C4 36 EA
7 L4 22 C5 37 AH
8 L5 23 J3 38 E9
9 U4 24 J6 39 FA
10 E6 25 J8 40 E8
11 H6 26 E5 41 CH
12 H0 27 A1 42 J9
13 A6 28 E1 43 E3
14 U0 29 UA 44 H3
15 C7 30 U3 45 F8
background
Service Diagnosis SiUS042501E
66 Part 6 Service Diagnosis
3.1.2 Method 2
1. Press the center of TEMP button and OFF button at the same time.
R6001161
SC is displayed on the LCD.
R6001158
2. Select SC (service check) with TEMP ▲ or TEMP ▼ button.
3. Press FAN button to enter the service check mode.
R6001162
00 is displayed and the left-side number blinks.
R6001159
4. Press TEMP ▲ or TEMP ▼ button and change the number until you hear the two
consecutive beeps or the long beep.
R6001163
5. Diagnose by the sound.
Beep: The left-side number does not correspond with the error code.
Two consecutive beeps: The left-side number corresponds with the error code but the
right-side number does not.
Long beep: Both the left-side and right-side numbers correspond with the error code.
The numbers indicated when you hear the long beep are the error code.
Refer to Error codes and description on page 70.
background
SiUS042501E Service Diagnosis
Part 6 Service Diagnosis 67
6. Press FAN button.
R6001162
The right-side number blinks.
R6001160
7. Press TEMP ▲ or TEMP ▼ button and change the number until you hear the long beep.
R6001163
8. Diagnose by the sound.
Beep: The left-side number does not correspond with the error code.
Two consecutive beeps: The left-side number corresponds with the error code but the
right-side number does not.
Long beep: Both the left-side and right-side numbers correspond with the error code.
9. Determine the error code.
The numbers indicated when you hear the long beep are the error code.
Refer to Error codes and description on page 70.
10.Press FAN button for 5 seconds to exit from the service check mode.
When the remote controller is left untouched for 60 seconds, it returns to the normal mode
also.
R6001162
background
Service Diagnosis SiUS042501E
68 Part 6 Service Diagnosis
3.2 BRC073A6
Relations
Between Modes
On power-up, the message “Checking the connection. Please standby.” will be displayed on
the remote controller screen temporarily and then the basic screen will be displayed. To access
a mode from the basic screen, refer to the figure below.
When any of the operation buttons are pressed, the backlight will come on and remain lit for
about 30 seconds. Be sure to press a button while the backlight is on.
R6001167
Basic screen
Main Menu screen
Service Settings screen** Maintenance Menu screen
Main Menu
• Airflow Direction
• Energy Saving Options
• Schedule
• Maintenance Information
• Current Settings
• Clock & Calendar
• Language
Press Cancel
button once.
Press
Menu/OK
button once.
Basic Screen
• Operation mode changeover
• Fan speed control
• Menu display
• Confirmation of each setting
• On
• Off
• Cancel
• Operation lamp
Press Cancel button
for 4 seconds or more.
Press Cancel
button once.
Press Cancel button
for 4 seconds or more.
Press Cancel
button once.
Maintenance Menu
• Error Display
Service Settings
• Test Operation
• Maintenance Contact
• Field Settings
• Error History
# The items shown on the remote controller are different depending on the connected indoor unit.
** Not displayed in multi-split system.
SettingReturn
Airflow Direction
Energy Saving Options
Schedule
Maintenance Information
Configuration
Current Settings
1/2Main Menu
82
°F
Cool
Set to
Test Operation
Maintenance Contact
Field Settings
Error History
Service Settings
SettingReturn
Error Display
Maintenance Menu
SettingReturn
background
SiUS042501E Service Diagnosis
Part 6 Service Diagnosis 69
Service
Diagnosis
The following message is displayed on the screen when an error occurs during operation.
Check the error code and take the corrective action specified for the particular model.
Screen
Operation lamp
Menu/OK button
1
82
°F
Cool
Set to
Error: Push Menu button
82
°F
• If an error occurs, the error message or error icon
and the operation lamp will blink.
• To display the error code and contact information,
the Menu/Enter button needs to be enabled.
• Press the Menu/Enter button.
Operation
lamp
2
Contact Info
012
–
345
–
6789
Indoor Model
––––––––––
Outdoor Model
––––––––––
Error Code:
Return
• The error code blinks and the contact address will
appear.
• Notify your Daikin dealer of the Error code and
Model name.
Operation Method
background
Troubleshooting SiUS042501E
70 Part 6 Service Diagnosis
4. Troubleshooting
4.1 Error Codes and Description
: Displayed only when system down occurs for method 1.
Error
Codes
Description
Reference
Page
System 00 Normal —
U0 Refrigerant shortage —
U2 Low-voltage detection or over-voltage detection 77
U4 Signal transmission error
(between indoor unit and outdoor unit)
79
UA Unspecified voltage
(between indoor unit and outdoor unit)
81
Indoor
Unit
A1 Indoor unit PCB abnormality 71
A5 Freeze-up protection control/heating peak-cut control 72
A6 Indoor fan motor (DC motor) or related abnormality 73
C4 Indoor heat exchanger thermistor or related abnormality 75
C9 Room temperature thermistor or related abnormality 76
CC Humidity sensor abnormality 76
Outdoor
Unit
E1 Outdoor unit PCB abnormality 82
E5 OL activation (compressor overload) or HPS activation (high
pressure switch)
83
E6 Compressor lock 86
E7 DC fan lock 87
E8 Input overcurrent detection 88
E9 Electronic expansion valve abnormality 89
EA Four way valve abnormality 90
F3 Discharge pipe temperature control 92
F6 High pressure control in cooling 93
F8 System shutdown due to temperature abnormality in the
compressor
95
H0 Compressor system sensor abnormality 96
H6 Position sensor abnormality 97
H9 Outdoor temperature thermistor or related abnormality 99
J3 Discharge pipe thermistor or related abnormality 99
J6 Outdoor heat exchanger thermistor or related abnormality 99
L3 Electrical box temperature rise 101
L4 Radiation fin temperature rise 102
L5 Output overcurrent detection 103
P4 Radiation fin thermistor or related abnormality 99
U7 Signal transmission error on outdoor unit PCB 105
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 71
4.2 Indoor Unit PCB Abnormality
Error Code A1
Method of Error
Detection
The system checks if the circuit works properly within the microcomputer of the indoor unit.
Error Decision
Conditions
The system cannot set the internal settings.
Supposed
Causes
Wrong models interconnected
Defective indoor unit PCB
Disconnection of connector
Reduction of power supply voltage
Troubleshooting
Wire Harness (Connector): Terminal strip ~ Control PCB (S1)
Correct the connection.
OK?
Check the power supply
voltage.
Start operation.
Voltage as rated?
Error repeats?
Check the power supply
voltage.
Start operation.
Voltage as rated?
Error repeats?
Error repeats?
Combination of the
indoor and outdoor unit
matched?
Check the connection of
connectors. ★
YES
NO
NO
YES
NO
NO
YES
(R23407)
Caution
* To secure the connection,
disconnect the connectors once
and then reconnect.
YES
NO
YES
NO
YES
NO
YES
Match the compatible
models.
Correct the power
supply.
Replace the indoor unit
PCB (control PCB).
Completed.
Completed.
Correct the power
supply.
Replace the indoor unit
PCB (control PCB).
Completed.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting SiUS042501E
72 Part 6 Service Diagnosis
4.3 Freeze-up Protection Control/Heating Peak-cut Control
Error Code A5
Method of Error
Detection
Freeze-up protection control
During cooling operation, the freeze-up protection control (operation halt) is activated
according to the temperature detected by the indoor heat exchanger thermistor.
Heating peak-cut control
During heating operation, the temperature detected by the indoor heat exchanger thermistor
is used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
Error Decision
Conditions
Freeze-up protection control
During cooling operation, the indoor heat exchanger temperature is below 0°C (32°F).
Heating peak-cut control
During heating operation, the indoor heat exchanger temperature is above 59 ~ 60°C (138.2
~ 140°F).
Supposed
Causes
Short-circuited air
Clogged air filter of the indoor unit
Dust accumulation on the indoor heat exchanger
Defective indoor heat exchanger thermistor
Defective indoor unit PCB
Troubleshooting
R6001296
Check No.01 Refer to P.106
NO
NO
NO
Check No. 01
Check the indoor heat exchanger
thermistor.
YES
YES
YES
YES
NO
Caution
Provide sufficient air passage.
Clean the air filter.
Clean the indoor heat
exchanger.
Replace the indoor unit PCB
(control PCB).
Replace the indoor heat
exchanger thermistor.
As
described in the
thermistor characteristic
chart?
Check the air filter.
Check the dust accumulation on
the indoor heat exchanger.
Dirty?
Dirty?
Check the air passage.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is there any air short circuit?
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 73
4.4 Indoor Fan Motor (DC Motor) or Related Abnormality
Error Code A6
Method of Error
Detection
The rotation speed detected by the Hall IC during fan motor operation determines abnormal fan
motor operation.
Error Decision
Conditions
The detected rotation speed does not reach the demanded rotation speed of the target tap, and
is less than 50% of the maximum fan motor rotation speed.
Supposed
Causes
Remarkable decrease in power supply voltage
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective capacitor of the fan motor
Defective indoor unit PCB
Troubleshooting
Caution
OK?
NO
YES
YES
NO
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the connector for
connection.
Note: The motor may break when the
motor connector is disconnected
with the power supply on.
(Turn off the power supply before
connecting the connector also.)
∗ To secure the connection,
once disconnect the connector
and then reconnect it.
Foreign matters in or
around the fan?
Rotate the fan by hand.
Correct the connection.
Remove the foreign matters.
Turn off the power supply.
(Unplug the power cable or turn
the breaker off.)
A Go to the next page
(R23939)
background
Troubleshooting SiUS042501E
74 Part 6 Service Diagnosis
Rubber cushion
Check No.03 Refer to P.106
R6000581
Check No. 03
Check No. 03
Check No. 03
NO
YES
YES
YES
NO
NO
YES
NO
Is the rotation pulse
generated?
Turn the power on again.
Check the fan motor for
breakdown or short circuit.
Check the motor control voltage.
Check the indoor unit PCB for
rotation pulse.
Fan rotates smoothly?
Resistance OK?
Is the motor control
voltage 15 VDC
generated?
Replace the indoor fan motor.
Replace the indoor unit PCB
(control PCB).
Replace the indoor fan motor.
Replace the indoor unit PCB
(control PCB).
YES
NO
NO
Abnormal
sound occurs?
Is the rubber cushion
properly fitted?
YES
Correct the position of
rubber cushion or replace
the rubber cushion.
Replace the bearing rubber
cushion.
A Continued from the
previous page
(R24945)
Rubber
cushion
Bearing
rubber
cushion
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 75
4.5 Indoor Heat Exchanger Thermistor or Related
Abnormality
Error Code C4
Method of Error
Detection
The temperatures detected by the thermistors determine thermistor errors.
Error Decision
Conditions
The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or less
with the power on.
Supposed
Causes
Disconnection of connector
Defective thermistor(s)
Defective indoor unit PCB
Troubleshooting
C4 : Indoor heat exchanger thermistor
Check No.01 Refer to P.106
YES
(R21870)
NO
Check No. 01
Check the thermistor resistance
value.
YES
NO
Caution
Correct the connection.
Replace the defective
thermistor(s).
Replace the indoor unit PCB
(control PCB).
Normal?
Normal?
Check the connection of
connectors.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting SiUS042501E
76 Part 6 Service Diagnosis
4.6 Room Temperature Sensor Abnormality/Humidity
Sensor Abnormality
Error Code C9, CC
Method of Error
Detection
Sensor abnormality is detected by input value.
Error Decision
Conditions
The input from the humidity sensor is 4.96 V and more or 0.04 V and less.
Supposed
Causes
Disconnection of connector
Defective humidity sensor
Defective indoor unit PCB
Troubleshooting
R6000515
C9 : Room temperature sensor
CC : Humidity sensor
Correct the connection.
Replace the control PCB.
Completed.
Normal?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the connection of
connectors.
NO
YES
* Connect the connector again for
ensuring the connection.
Replace the humidity sensor
PCB.
Error code displayed?
YES
NO
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 77
4.7 Low-voltage Detection or Over-voltage Detection
Error Code U2
Method of Error
Detection
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Error Decision
Conditions
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below 50 V (depending on the
model).
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Over-voltage detection:
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer
(over 400 V).
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes
Power supply voltage out of specification
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Disconnection of compressor harness
Short circuit inside the fan motor winding
Noise
Momentary drop of voltage
Momentary power failure
Defective outdoor unit PCB
background
Troubleshooting SiUS042501E
78 Part 6 Service Diagnosis
Troubleshooting
Correct the power supply.
Replace the outdoor
unit PCB (main PCB).
Check for such factors for a
long term.
(R22445)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NO
YES
YES
YES
YES
Reconnect the harness.
Check the power supply voltage.
Check the connection of the
compressor harness.
(Precaution before turning on the power again)
Make sure the power has been off for at
least 30 seconds.
Disturbance factors
Noise
Power supply distortion
Turn on
the power. System
restarted? (Repeat a few
times.)
Loose or disconnected?
NO
NO
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Does the
outdoor fan rotate
smoothly?
Is the
voltage fluctuation
within ±10% from the
rated value?
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 79
4.8 Signal Transmission Error (Between Indoor Unit and
Outdoor Unit)
Error Code U4
Method of Error
Detection
The signal transmission data received from the outdoor unit is checked whether it is normal.
Error Decision
Conditions
The data sent from the outdoor unit cannot be received normally, or the content of the data is
abnormal.
Supposed
Causes
Power supply voltage not as specified
Reduction of power supply voltage
Wiring error
Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
Defective outdoor unit PCB
Short circuit inside the fan motor winding
Defective indoor unit PCB
Disturbed power supply waveform
Disconnected connectors or broken harness of overload protector and high pressure switch
Overload protector or high pressure switch activated
background
Troubleshooting SiUS042501E
80 Part 6 Service Diagnosis
Troubleshooting
R6001297
Check No.11 Refer to P.107
Check No.11
Check the power supply
waveform.
Check the voltage of the
connection wires on the indoor
terminal board between No. 1
and No. 3, and between No. 2
and No. 3.
YES
Blink
Replace the indoor unit PCB
(control PCB).
Locate the cause of the
disturbance of the power
supply waveform, and correct
it.
NO
Continuously ON or OFF
NO
YES
YES
NO
Caution
Correct the indoor unit -
outdoor unit connection wires.
Go to E5 troubleshooting.
Replace the outdoor unit PCB
(main PCB).
Replace the connection wires
between the indoor unit and
outdoor unit.
Properly insulated?
Is there any disturbance?
Is there any wiring error?
Check the indoor unit - outdoor
unit connection wires.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Before you check the LED, cancel
the standby electricity saving
function by starting fan operation
with the remote controller.
Wait at least for 7 sec. after turning
on the power.
NO
YES
Check the power supply voltage.
Correct the power supply.
YES
NO
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Rotate the
outdoor fan by hand.
Does the outdoor fan rotate
smoothly?
Is the
voltage fluctuation
within ±10% from the
rated value?
Is LED blinking?
Check the LED on the outdoor
unit PCB.
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 81
4.9 Unspecified Voltage (Between Indoor Unit and Outdoor
Unit)
Error Code UA
Method of Error
Detection
The supply power is detected for its requirements (pair type is different from multi type) by the
indoor/outdoor transmission signal.
Error Decision
Conditions
The pair type and multi type are interconnected.
Supposed
Causes
Wrong models interconnected
Wrong wiring of connecting wires
Wrong indoor unit PCB or outdoor unit PCB mounted
Defective indoor unit PCB
Defective outdoor unit PCB
Troubleshooting
R6001298
Caution
NO
YES
YES
NO
Match the compatible models.
Correct the connection.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the combination of the
indoor and outdoor unit.
OK?
Are the
connecting wires connected
properly?
Check the code numbers
(2P012345, for example) of the
indoor and outdoor unit PCB
with the service parts list.
If not matched, change for the
correct PCB.
background
Troubleshooting SiUS042501E
82 Part 6 Service Diagnosis
4.10 Outdoor Unit PCB Abnormality
Error Code E1
Method of Error
Detection
The system checks if the microprocessor is working in order.
The system checks if the zero-cross signal comes in properly.
Error Decision
Conditions
The microprocessor program runs out of control.
The zero-cross signal is not detected.
Supposed
Causes
Defective outdoor unit PCB
Defective electronic expansion valve driver
Noise
Momentary drop of voltage
Momentary power failure
Troubleshooting
R6001299
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Continuously ON, OFF
Blink
YES
NO
Replace the outdoor unit
PCB (main PCB).
Ground the system.
Zero-cross signal
abnormality.
Replace the outdoor unit
PCB (main PCB).
Turn on the power again.
Is LED blinking?
Grounded?
Check if the outdoor unit is
grounded.
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 83
4.11 OL Activation (Compressor Overload) or HPS Activation
(High Pressure Switch)
Error Code E5
Method of Error
Detection
A compressor overload is detected through compressor OL.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of discharge pipe thermistor
Disconnection of indoor or outdoor heat exchanger thermistor
Defective discharge pipe thermistor
Defective indoor or outdoor heat exchanger thermistor
Disconnection of connector X40A
Disconnection of 2 terminals of OL (Q1M)
Disconnection of 2 terminals of HPS (S1PH)
Defective OL (Q1M)
Defective HPS (S1PH)
Broken OL and HPS harness
Defective electronic expansion valve or coil
Defective four way valve or coil
Defective outdoor unit PCB
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
background
Troubleshooting SiUS042501E
84 Part 6 Service Diagnosis
Troubleshooting
R6001300
OL (Q1M) activating temperature: 120 ~ 130°C (248 ~ 266°F)
OL (Q1M) recovery temperature: 110°C (230°F)
High pressure switch (S1PH) activating pressure: 602 psi (4.15 MPa)
High pressure switch (S1PH) recovery pressure: 464 psi (3.2 MPa)
Check No.01 Refer to P.106
Caution
YES
NO
OK
NG
NG
OK
NG
OK
Refrigerant shortage
Refrigerant overfill
Water mixed
Stop valve
Disconnect the connector X40A
from the PCB.
Disconnect the 2 terminals of
the OL (Q1M).
Disconnect the 2 terminals of
the HPS (S1PH).
Resistance
f
Resistance
f
Resistance
f
Nearly 0 :
Nearly 0 :
Nearly 0 :
Insert the thermistor in
position.
Discharge pipe thermistor
Indoor heat exchanger thermistor
Outdoor heat exchanger thermistor
Discharge pipe thermistor
Indoor heat exchanger thermistor
Outdoor heat exchanger thermistor
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
Replace the four way valve
or the coil.
Replace the outdoor unit
PCB (main PCB).
Thermistor
disconnected?
NG
OK
Replace the defective
thermistor(s).
Check No. 01
Check the thermistor
resistance value
Check No. 13
Check the four way valve.
Check No. 14
Check the refrigerant line.
Check No. 12
Check the electronic
expansion valve.
Replace the OL
(Q1M).
Replace the harness.
YES
NO
Connect the connector
X40A
properly.
Is the connector X40A
properly connected?
Check the
resistance between the 2
terminals on connector
X40A
Check the
resistance between the
2 terminals of the OL
(Q1M).
Replace the HPS (S1PH).
Check the
resistance between the 2
terminals of the of the
HPS (S1PH).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 85
Check No.12 Refer to P.107
Check No.13 Refer to P.108
Check No.14 Refer to P.108
background
Troubleshooting SiUS042501E
86 Part 6 Service Diagnosis
4.12 Compressor Lock
Error Code E6
Method of Error
Detection
A compressor lock is detected by the current waveform generated when applying
high-frequency voltage to the motor.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Closed stop valve
Compressor locked
Disconnection of compressor harness
Defective electronic expansion valve
Troubleshooting
R6001301
Check No.12 Refer to P.107
Check No.15 Refer to P.109
Turn off the power. Disconnect the
harnesses U, V, and W.
Caution
NO
YES
YES
NO
NO
YES
NO
YES
Check No.15
Check with the inverter analyzer.
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Open the stop valve.
* Inverter analyzer:
RSUK0917C
Replace the compressor.
Replace the compressor.
Check the electronic
expansion valve coil.
Go to Check No. 12.
Stop valve
closed?
Emergency stop
without compressor running?
System shut
down after errors repeated
several times?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Any outdoor unit LED off?
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 87
4.13 DC Fan Lock
Error Code E7
Method of Error
Detection
An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC.
Error Decision
Conditions
The fan does not start in 15 ~ 30 seconds even when the fan motor is running.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Disconnection of the fan motor
Foreign matter stuck in the fan
Defective fan motor
Defective outdoor unit PCB
Troubleshooting
Check No.16 Refer to P.111
Caution
YES
YES
NO
YES
NO
NO
YES
NO
NO
Turn on the power.
Rotate the fan.
YES
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB (main PCB).
Turn off the power and
reconnect the connector.
Remove the foreign
matters.
Replace the outdoor fan
motor.
Replace the fuse.
Replace the outdoor unit
PCB (main PCB).
Fan motor
connector disconnected?
Foreign matters
in or around the fan?
Replace the outdoor fan
motor.
Fan rotates
smoothly?
Pulse signal
generated?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the fuse (#) for the
fan motor blown?
# F2U
background
Troubleshooting SiUS042501E
88 Part 6 Service Diagnosis
4.14 Input Overcurrent Detection
Error Code E8
Method of Error
Detection
An input overcurrent is detected by checking the input current value with the compressor
running.
Error Decision
Conditions
The current exceeds about 14.5 A for 2.5 seconds with the compressor running.
The upper limit of the current decreases when the outdoor temperature exceeds a certain level.
Supposed
Causes
Outdoor temperature is out of operation range.
Defective compressor
Defective power module
Defective outdoor unit PCB
Short circuit
Troubleshooting
Check No.15 Refer to P.109
Check No.17 Refer to P.111
Check No.18 Refer to P.112
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
* An input overcurrent may result from wrong internal wiring. If the system is interrupted by an input
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
(R21863)
NO
YES
YES
NO
Start operation and measure the
input current.
Check No. 18
Check the discharge pressure.
Check No. 17
Check the installation condition.
Check No.15
Check with the inverter analyzer.
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Replace the outdoor unit
PCB (main PCB).
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Any LED off?
Input current
flowing above its stop level?
* Inverter analyzer:
RSUK0917C
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 89
4.15 Electronic Expansion Valve Coil Abnormality
Error Code E9
Method of Error
Detection
Detect errors based on check of continuity of the electronic expansion valve.
Error Decision
Conditions
High input voltage from electronic expansion valve to the microcomputer due to overcurrent.
Low input voltage from electronic expansion valve to the microcomputer due to
disconnected connectors.
Supposed
Causes
Defective electronic expansion coil
Broken harness of electronic expansion coil
Defective connection of electronic expansion coil connector
Defective outdoor unit main PCB
Troubleshooting
R6001235
Check No.12 Refer to P.107
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
NO
YES
YES
Restart operation.
Turn OFF the power supply once
and turn ON again.
Check the connection of
connectors.
NO
The cause can be external
factors other than malfunction.
Investigate the cause of noise.
Replace the electronic
expansion valve.
Replace the outdoor unit
PCB (PDLQ PCB).
Normal?
The cause can be external
factors other than malfunction.
Investigate the cause of noise.
E9 error again?
E9 error again?
Check No. 12
Is the coil resistance of
the electronic expansion
valve normal?
NO
YES
Correct the connection.
background
Troubleshooting SiUS042501E
90 Part 6 Service Diagnosis
4.16 Four Way Valve Abnormality
Error Code EA
Method of Error
Detection
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
function within their normal ranges in each operation mode.
Error Decision
Conditions
The following condition continues over C seconds after operating for 5 minutes.
Cooling/Dry
A – B < –5°C (A – B < –9°F)
Heating
B – A < –5°C (B – A < –9°F)
A: Room thermistor temperature
B: Indoor heat exchanger temperature
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor(s)
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Outdoor temperature
C
(seconds)
–15°C (5°F) or higher 300
Lower than –15°C (5°F) 600
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 91
Troubleshooting
R6001164
Check No.01 Refer to P.106
Check No.13 Refer to P.108
Check No.14 Refer to P.108
NG
OK
NO
OK
NG
OK
YES
NG
Correct the four way valve
coil.
Reconnect the harness.
YES
YES
YES
NO
NO
Replace the outdoor
unit PCB (main PCB).
Replace the defective
thermistor(s).
Refer to the refrigerant line
check procedure.
Replace the four way valve
(defective or dust-clogged).
Reconnect the
thermistor(s).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Refrigerant shortage
Water mixed
Stop valve
Four way valve
coil disconnected (loose)?
Harness
disconnected?
Any thermistor
disconnected?
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.
Check No. 13
Check the four way valve
switching output.
Check the continuity of the four way
valve coil and harness.
Replace the four way
valve coil.
NO
Resistance
between harnesses
about 556 ~ 614 :?
Disconnect the harness from the
connector.
background
Troubleshooting SiUS042501E
92 Part 6 Service Diagnosis
4.17 Discharge Pipe Temperature Control
Error Code F3
Method of Error
Detection
An error is determined with the temperature detected by the discharge pipe thermistor.
Error Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above A, the compressor
stops.
The error is cleared when the discharge pipe temperature has dropped below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
If the frequency drops, the temperature is lowered in compensation.
Supposed
Causes
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Troubleshooting
Check No.01 Refer to P.106
Check No.12 Refer to P.107
Check No.14 Refer to P.108
AB
°C °F °C °F
118 244.4 90 194.0
(R20417)
Caution
NG
OK
OK
OK
NG
NG
∗ Discharge pipe thermistor
∗ Outdoor heat exchanger thermistor
∗ Outdoor temperature thermistor
∗ Refrigerant shortage
∗ Four way valve
∗ Water mixed
∗ Stop valve
Check No. 12
Check the electronic
expansion valve.
Replace the defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 93
4.18 High Pressure Control in Cooling
Error Code F6
Method of Error
Detection
High-pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if
the temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Error Decision
Conditions
The temperature sensed by the outdoor heat exchanger thermistor rises above 59°C
(138.2°F).
The error is cleared when the temperature drops below 52°C (125.6°F).
Supposed
Causes
Installation space not large enough
Dirty outdoor heat exchanger
Defective outdoor fan motor
Defective stop valve
Defective electronic expansion valve or coil
Defective outdoor heat exchanger thermistor
Defective outdoor unit PCB
Troubleshooting
Check No.01 Refer to P.106
Check No.12 Refer to P.107
Check No.17 Refer to P.111
(R20418)
Caution
Replace the outdoor fan
motor.
Reconnect the connector or
fan motor lead wires.
Replace the stop valve.
Replace the outdoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit
PCB (main PCB).
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Check the installation space.
NG
OK
OK
NG
NG
OK
OK
OK
NG
NG
Check No. 19
Check the outdoor fan.
Check No. 18
Check the discharge
pressure.
Check No. 12
Check the electronic
expansion valve.
Check No. 01
Check the outdoor heat
exchanger thermistor.
Check No. 17
Check the installation
condition.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting SiUS042501E
94 Part 6 Service Diagnosis
Check No.18 Refer to P.112
Check No.19 Refer to P.112
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 95
4.19 System Shutdown due to Temperature Abnormality in
the Compressor
Error Code F8
Method of Error
Detection
Operation is halted when the temperature detected by the discharge pipe thermistor exceeds
the determined limit.
Error Decision
Conditions
Temperature exceeds the detection threshold of 127.5°C (261.5°F) during forced cooling
operation.
Supposed
Causes
Abnormal operation due to air intrusion
Defective discharge pipe thermistor
Troubleshooting
Check No.01 Refer to P.106
YES
(R23655)
NO
OK
NG
Caution
Replace the outdoor unit. #
Replace both the discharge pipe
thermistor and the outdoor unit
PCB (main PCB).
Replace the outdoor unit.
#
Abnormal
deformation of piping in the
outdoor unit
Check No. 01
Check the discharge pipe
thermistor
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
#
Replace the unit as directed in the installation manual, making sure that air does not intrude
into the refrigerant piping.
background
Troubleshooting SiUS042501E
96 Part 6 Service Diagnosis
4.20 Compressor Sensor System Abnormality
Error Code H0
Method of Error
Detection
The system checks the DC current before the compressor starts.
Error Decision
Conditions
The voltage converted from the DC current before compressor start-up is out of the range
0.5 ~ 4.5 V.
The DC voltage before compressor start-up is below 50 V.
Supposed
Causes
Broken or disconnected harness
Defective outdoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
(R24613)
YES
Turn off the power. Then, turn on
the power to restart the system.
YES
NO
Replace the harness.
Replace the outdoor unit
PCB (main PCB).
Is the harness broken?
Restart
operation and error displayed
again?
Check the (relay) harness for the
compressor.
Not a malfunction.
Keep observing.
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 97
4.21 Position Sensor Abnormality
Error Code H6
Method of Error
Detection
A compressor start-up failure is detected by checking the compressor running condition through
the position detection circuit.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Power supply voltage out of specification
Disconnection of the compressor harness
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage outside the specified range
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Turn off the power.
Check the power supply voltage.
Correct the power supply.
(R24909)
NO
YES
A Go to the next page
Check No. 20
Check the short circuit of the diode
bridge.
Replace the outdoor unit
PCB (main PCB).
Normal?
NO
YES
Check No. 18
Check the discharge pressure.
Replace the stop valve.
OK?
Is the voltage
fluctuation within
±10% from the rated
value?
background
Troubleshooting SiUS042501E
98 Part 6 Service Diagnosis
R6001304
Check No.15 Refer to P.109
Check No.18 Refer to P.112
Check No.20 Refer to P.113
Check the connection.
NO
NO
NO
YES
YES
YES
Check No.15
Check with the inverter analyzer.
Turn off the power. Disconnect the
harnesses U, V, and W.
Turn on the power. Check the
electrolytic capacitor voltage.
Electrical
components or
compressor harnesses
connected as
specified?
Replace the outdoor unit
PCB (main PCB).
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Replace the compressor.
Reconnect the electrical
components or compressor
harnesses as specified.
Inverter analyzer:
RSUK0917C
Within 320±50 VDC?
Any LED OFF?
A Continued from the
previous page
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 99
4.22 Thermistor or Related Abnormality (Outdoor Unit)
Error Code H9, J3, J6, P4
Method of Error
Detection
This fault is identified based on the thermistor input voltage to the microcomputer.
A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision
Conditions
The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or
less with the power on.
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Supposed
Causes
Disconnection of the connector for the thermistor
Defective thermistor(s)
Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger
thermistor in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
Troubleshooting In case of P4
Replace the outdoor unit PCB (main PCB).
P4 : Radiation fin thermistor
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting SiUS042501E
100 Part 6 Service Diagnosis
Troubleshooting In case of H9, J3, J6
H9 : Outdoor temperature thermistor
J3 : Discharge pipe thermistor
J6 : Outdoor heat exchanger thermistor
Check No.01 Refer to P.106
(R20406)
Caution
NO
YES
YES
NO
NO
YES
Turn on the power again.
Normal?
Reconnect the connectors
or thermistors.
J3 error: the discharge
pipe temperature is
lower than the heat
exchanger temperature.
Replace the defective
thermistor(s) of the following
thermistors.
∗ Outdoor temperature
thermistor
∗ Discharge pipe thermistor
∗ Outdoor heat exchanger
thermistor
Cooling: Outdoor heat
exchanger
temperature
Heating: Indoor heat
exchanger
temperature
Replace the indoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
Error displayed
again on remote
controller?
Indoor heat
exchanger thermistor
functioning?
Check No. 01
Check the thermistor resistance
value.
Check No. 01
Check the indoor heat exchanger
thermistor resistance value in the
heating operation.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 101
4.23 Electrical Box Temperature Rise
Error Code L3
Method of Error
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Error Decision
Conditions
With the compressor off, the radiation fin temperature is above A.
The error is cleared when the radiation fin temperature drops below B.
To cool the electrical components, the outdoor fan starts when the radiation fin temperature
rises above C and stops when the radiation fin temperature drops below B.
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Troubleshooting
Check No.17 Refer to P.111
Check No.19 Refer to P.112
ABC
(°C) (°F) (°C) (°F) (°C) (°F)
82 179.6 65 149 70 158
Caution
WARNING
To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above C and stops when the radiation
fin temperature drops below B.
(R22998)
YES
NO
YES
NG
NO
OK
NO
YES
Turn off the power. Then, turn on
the power to restart the system.
Check the radiation fin
temperature.
Radiation fin dirty?
Check No. 19
Check the outdoor fan.
Error again or
outdoor fan activated?
Replace the outdoor unit
PCB (main PCB).
Clean up the radiation fin.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor fan
motor.
Correct the connectors
and fan motor lead wire.
Replace the outdoor unit
PCB (main PCB).
Above A?
Check the installation
condition.
Go to Check No. 17.
background
Troubleshooting SiUS042501E
102 Part 6 Service Diagnosis
4.24 Radiation Fin Temperature Rise
Error Code L4
Method of Error
Detection
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
compressor on.
Error Decision
Conditions
If the radiation fin temperature with the compressor on is above A.
The error is cleared when the radiation fin temperature drops below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Silicone grease not applied properly on the radiation fin after replacing the outdoor unit PCB
Troubleshooting
Refer to Silicone Grease on Power Transistor/Diode Bridge on page 126 for details.
Check No.17 Refer to P.111
Check No.19 Refer to P.112
AB
(°C) (°F) (°C) (°F)
89 192.2 80 176.0
Caution
Turn off the power. Then, turn on
the power to restart the system.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(R23953)
NO
NG
OK
NO
YES
Check the radiation fin
temperature.
NO
YES
YES
Above A?
Check No. 19
Check the outdoor fan.
Error displayed
again?
Has the PCB
been replaced?
Check if silicone grease is
applied properly on the
radiation fin. If not, apply
the silicone grease.
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor fan
motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB (main PCB).
YES
NO
Radiation fin
dirty?
Clean up the radiation fin.
Check the installation
condition.
Go to Check No. 17.
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 103
4.25 Output Overcurrent Detection
Error Code L5
Method of Error
Detection
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Error Decision
Conditions
A position signal error occurs while the compressor is running.
A rotation speed error occurs while the compressor is running.
An output overcurrent signal is fed from the output overcurrent detection circuit to the
microcomputer.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Poor installation condition
Closed stop valve
Defective power module
Wrong internal wiring
Abnormal power supply voltage
Defective outdoor unit PCB
Power supply voltage out of specification
Defective compressor
Troubleshooting
(R24911)
Caution
NO
YES
NO
YES
* An output overcurrent may result from wrong internal wiring. If the system is interrupted by an output
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
Check No. 17
Check No.15
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power. Then, turn on
the power to restart the system.
See if the same error occurs.
Monitor the power supply voltage,
discharge and suction pressures,
and other factors for a long term.
Possible causes
* Momentary drop of power supply
voltage
* Compressor overload
* Short circuit
Check the installation condition.
Check with the inverter analyzer.
Not a malfunction.
Keep observing.
Check the connectors and
other components.
Fully open the stop valve.
Error again?
Stop valve fully open?
* Inverter analyzer:
RSUK0917C
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A Go to the next page
background
Troubleshooting SiUS042501E
104 Part 6 Service Diagnosis
Check No.15 Refer to P.109
Check No.17 Refer to P.111
Check No.18 Refer to P.112
Check No.22 Refer to P.114
(R24912)
NO
YES
NO
YES
NO
YES
YES
NO
Check No. 22
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Check the power supply voltage.
Check the power module.
Correct the power supply.
Replace the compressor.
Correct the power supply
or replace the outdoor unit
PCB (main PCB).
Replace the outdoor unit
PCB (main PCB).
Any LED off?
Normal?
Short circuit
or wire breakage
between compressor's coil
phases?
Check the discharge
pressure.
Go to Check No. 18.
A Continued from the
previous page
Is the voltage
fluctuation within
±10% from the rated
value?
background
SiUS042501E Troubleshooting
Part 6 Service Diagnosis 105
4.26 Signal Transmission Error on Outdoor Unit PCB
Error Code U7
Method of Error
Detection
Communication error between microcomputer mounted on the main PCB and power module.
Error Decision
Conditions
The abnormality is determined when the data sent from the power module cannot be
received for 9 seconds.
The error counter is reset when the data from the power module can be successfully
received.
Supposed
Causes
Defective outdoor unit PCB
Troubleshooting
(R21808)
Caution
YES
NO
Turn off the power. Then, turn on
the power to restart the system.
Error again?
The cause can be an
external factor other than
the malfunction.
Observe the operating
condition in long term.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor unit
PCB (main PCB).
background
Check SiUS042501E
106 Part 6 Service Diagnosis
5. Check
5.1 Thermistor Resistance Check
Check No.01 Measure the resistance of each thermistor using multimeter.
The resistance values are defined by below table.
If the measured resistance value does not match the listed value, the thermistor must be
replaced.
Disconnect the connector of thermistor ASSY from the PCB to measure the resistance
between the pins using multimeter.
To check the thermistor soldered on a PCB, disconnect the PCB from other PCB/parts, and
measure the resistance between the both ends of soldered thermistor.
R6001195
When replacing the defective thermistor(s), replace the thermistor as ASSY.
5.2 Indoor Fan Motor Connector Check
Check No.03 Check the connection of connector.
1. Check the connector for connection.
2. Turn the power off.
3. Check if each resistance at the phases U - V and V - W is 20.9 - 23.2 .
R6001148
Multimeter
Resistance range
Thermistor ASSY Soldered thermistor
Multimeter
R(25°C / 77°F) = 20 k:, B = 3950 K
Thermistor
temperature
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
R(25°C / 77°F) = 20 k:
B = 3950 K
Resistance (k:)
197.8
148.2
112.1
85.60
65.93
51.14
39.99
31.52
25.02
20.00
16.10
13.04
10.62
8.707
7.17650
–4
5
14
23
32
41
50
59
68
77
86
95
104
113
122
°C °F
(˚C)
(k:)
–15
0
15 30
45
150
100
50
(˚F)
5 32 59 86 113
3
2
1
Phase U
Phase W
Phase V
S200
background
SiUS042501E Check
Part 6 Service Diagnosis 107
5.3 Power Supply Waveform Check
Check No.11 Measure the power supply waveform between No. 1 and No. 2 on the terminal strip, and check
the waveform disturbance.
Check if the power supply waveform is a sine wave (Fig.1).
Check if there is waveform disturbance near the zero-cross (sections circled in Fig.2).
5.4 Electronic Expansion Valve Check
Check No.12 Conduct the following to check the electronic expansion valve (EV).
1. Check if the EV connector is correctly connected to the PCB.
2. Turn the power off and on again, and check if the EV generates a latching sound.
3. If the EV does not generate a latching sound in step 2, disconnect the connector and check
the continuity using a multimeter.
4. Check the continuity between the pins 5 - 1, 5 - 2, 5 - 3, 5 - 4. If there is no continuity
between the pins, the EV coil is faulty.
5. If the continuity is confirmed in step 3, the outdoor unit PCB (main PCB) is faulty.
R6001188
[Fig.1] [Fig.2]
(R1736)
(R1444)
Harness 5P
5P Connector
Check
X20A
5 - 1
5 - 2
5 - 3
5 - 4
1 2 3 4 5
background
Check SiUS042501E
108 Part 6 Service Diagnosis
5.5 Four Way Valve Performance Check
Check No.13
R6001279
5.6 Inverter Unit Refrigerant System Check
Check No.14
R6000874
Start heating operation.
NO
YES
YES
Four way valve
coil resistance at
556 ~ 614 :?
NO
Turn off the power and turn it on
again.
Replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Replace the four way valve
coil.
Replace the four way valve.
NO
YES
X80A
voltage at 0 VDC with
compressor on?
X80A
voltage at
120 ~ 380 VDC for 3 sec.
after compressor starts, and
then at about 10
VDC? (Fig. 1)
Disconnect the four way valve coil
from the connector and check the
continuity.
(Fig. 1)
Voltage at X80A
120 ~ 380 VDC
10 VDC
Time
Compressor
ON
3 sec.
< Caution on resetting the power supply >
Be sure to wait for 30 sec. or more after turning off the power.
Four way valve coil
Cooling / Dry : No continuity
Heating : Continuity
Refrigerant system check
Is the discharge pipe
thermistor disconnected from
the holder?
Check for refrigerant leakage.
See the service diagnosis on
refrigerant shortage (U0).
YES
NO
Reconnect the thermistor.
Replace the refrigerant.
background
SiUS042501E Check
Part 6 Service Diagnosis 109
5.7 Inverter Analyzer Check
Check No.15 Characteristics
Inverter analyzer: RSUK0917C
If an abnormal stop occurs due to compressor startup failure or overcurrent output when using
an inverter unit, it is difficult to judge whether the stop is caused by the compressor failure or
some other failure (main PCB, power module, etc.). The inverter analyzer makes it possible to
judge the cause of trouble easily and securely. Connect an inverter analyzer as a
quasi-compressor instead of compressor and check the output of the inverter.
Operation Method
Step 1
Be sure to turn the power off.
Step 2
Install an inverter analyzer instead of a compressor.
Note:
Make sure the charged voltage of the built-in smoothing electrolytic capacitor drops to 10 VDC
or below before carrying out the service work.
Reference:
If the terminals of the compressor are not FASTON terminals (difficult to remove the wire on the
terminals), it is possible to connect wires available on site to the outdoor unit from output side of
PCB. Do not connect them to the compressor at the same time, otherwise it may result in
incorrect detection.
Step 3
Activate the power transistor test
Power transistor test operation can be activated only once after turning on the power supply.
If reactivation of the power supply transistor operation is needed, turn the power supply off and
then on again.
(
R22731
)
(1) Remove the terminals from
the compressor.
(2) Connect the terminals to the
terminals of the inverter
analyzer.
Compressor
Inverter analyzer
Be careful not to let the terminals (U,V,W)
touch each other. Otherwise, high voltage
is applied.
Compressor
background
Check SiUS042501E
110 Part 6 Service Diagnosis
1. Turn the power on.
2. Press the center of TEMP button and OFF button on the remote controller at the same time.
3. Select T with TEMP or TEMP button.
4. Press FAN button.
5. Press FAN ONLY button to start the power transistor test operation.
R6000683
Diagnose method (Diagnose according to 6 LEDs lighting status.)
1. If all the LEDs are lit uniformly, the compressor is defective.
Replace the compressor.
2. If the LEDs are not lit uniformly, check the power module.
Refer to Check No.22.
3. If NG in Check No.22, replace the power module.
(Replace the main PCB. The power module (IPM801) is united with the main PCB.)
If OK in Check No.22, check if there is any solder cracking on the PCB.
4. If any solder cracking is found, replace the PCB or repair the soldered section.
If there is no solder cracking, replace the PCB.
1. When the output frequency is low, the LEDs blink slowly. As the output frequency increases,
the LEDs blink quicker. (The LEDs look like they are lit.)
2. On completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals.
Otherwise, the terminals may be burned due to loosening.
2, 3
5
4
2
(R15292)
Direction of crimp
FASTON terminal
This size is shortened
by the crimp.
background
SiUS042501E Check
Part 6 Service Diagnosis 111
5.8 Outdoor Fan Motor Check
Check No.16 Outdoor fan motor
Check if the sinusoidal voltage is generated between pins 1 - 3 and 3 - 5 when the fan motor is
manually rotated once.
R6001180
5.9 Installation Condition Check
Check No.17
5
3
1 Phase U
Phase V
Phase W
X70A
PCB
Installation condition check
OK
Check the allowable
dimensions of the air
suction and
discharge area.
Is the airflow blocked by
obstacles or winds
blowing in the opposite
direction?
(R19394)
NG
YES
YES
NO
Is the discharged air
short-circuited?
NO
NO
YES
Is the outdoor heat
exchanger very dirty?
Change the installation
location or direction.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Change the installation
location or direction.
Check the outdoor temperature.
(The outdoor temperature
should be within the operation
range.)
background
Check SiUS042501E
112 Part 6 Service Diagnosis
5.10 Discharge Pressure Check
Check No.18
5.11 Outdoor Fan System Check
Check No.19 DC motor
(R21121)
YES
YES
YES
NO
NO
NO
NO
YES
Is the air filter or
indoor/outdoor heat
exchanger dirty?
Is the
connection pipe deformed?
Is the stop valve
open?
High?
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean the dirty air filter or
indoor/outdoor heat exchanger.
Replace the compressor.
Discharge pressure check
(R21195)
YES
NO
NO
YES
Outdoor fan system is functioning.
Check the outdoor fan system.
Reconnect the connector.
Is
the outdoor fan
running?
Fan motor lead
wire connector
disconnected?
Go to Check No. 16.
background
SiUS042501E Check
Part 6 Service Diagnosis 113
5.12 Main Circuit Short Check
Check No.20 Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is about
0 V before checking
Measure the resistance between the pins of the DB1 referring to the table below.
If the resistance is or less than 1 k, short circuit occurs on the main circuit.
R6001280
Positive terminal (+) of
digital multimeter
~ (2, 3) + (4) ~ (2, 3) – (1)
Negative terminal (–) of
digital multimeter
+ (4) ~ (2, 3) – (1) ~ (2, 3)
Resistance is OK. several k ~
several M

several k ~
several M
Resistance is NG. 0 or 0 0 0 or
Multimeter
–
+
123
4
–~~+
background
Check SiUS042501E
114 Part 6 Service Diagnosis
5.13 Power Module Check
Check No.22 Check to make sure that the voltage between (+) and (–) of the power module is about 0 V
before checking.
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Follow the procedure below to measure resistance between the terminals of the power
module and the terminals of the compressor with a multimeter. Evaluate the measurement
results referring to the following table.
R6001303
UVW can also be measured at X30A connector pins if multimeter can reach the connector pins.
Positive terminal (+) of
digital multimeter
Power module
(+)
UVW
Power module
(–)
UVW
Negative terminal (–) of
digital multimeter
UVW
Power module
(+)
UVW
Power module
(–)
Resistance is OK. several k ~ several M
Resistance is NG. 0 or
+: 27 pinU: 26 pinV: 25 pinW: 24 pin–: 23 or 22 or 21 pin
background
SiUS042501E
Part 7 Trial Operation and Field Settings 115
1. Pump Down Operation........................................................................116
2. Forced Cooling Operation ...................................................................117
3. Trial Operation ....................................................................................118
4. Field Settings ......................................................................................120
4.1 When 2 Units are Installed in 1 Room..................................................120
4.2 Temperature Display Switch ................................................................123
4.3 Service Mode of Wireless Remote Controller ......................................124
5. Silicone Grease on Power Transistor/Diode Bridge............................126
Part 7
Trial Operation and
Field Settings
background
Pump Down Operation SiUS042501E
116 Part 7 Trial Operation and Field Settings
1. Pump Down Operation
Outline In order to protect the environment, be sure to conduct pump down operation when relocating or
disposing of the unit.
Details 1. Remove the valve caps from the liquid stop valve and the gas stop valve.
2. Carry out forced cooling operation.
3. After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4. After 2 to 3 minutes, close the gas stop valve and stop the forced cooling operation.
5. Attach the valve cap once procedures are complete.
Refer to Forced Cooling Operation on page 117 for details.
Gas stop valve
Valve cap
Close
Liquid stop valve
Service port
(R13628)
Hexagonal
wrench
background
SiUS042501E Forced Cooling Operation
Part 7 Trial Operation and Field Settings 117
2. Forced Cooling Operation
Outline The forced cooling operation is allowed when both the following conditions are met.
1. The outdoor unit is not abnormal and not in the 3-minute standby mode.
2. The outdoor unit is not operating.
Protection functions have priority over all other functions during forced cooling operation.
Details With indoor unit ON/OFF switch
Press indoor unit ON/OFF switch for at least 5 seconds. The operation will start.
Forced cooling operation will stop automatically after about 15 minutes.
To stop the operation, press indoor unit ON/OFF switch.
R4004227
ON/OFF switch
background
Trial Operation SiUS042501E
118 Part 7 Trial Operation and Field Settings
3. Trial Operation
Outline Trial operation should be carried out in either cooling or heating operation.
1. Measure the supply voltage and make sure that it is within the specified range.
2. In cooling operation, select the lowest programmable temperature; in heating operation,
select the highest programmable temperature.
3. Carry out the trial operation in accordance with the operation manual to ensure that all
functions and parts, such as louvers movement, are working properly.
For protection, the system disables restart operation for 3 minutes after the system has
been turned off.
4. After trial operation is complete, set the temperature to a normal level (26 ~ 28°C (78 ~ 82°F)
in cooling, 20 ~ 24°C (68 ~ 75°F) in heating).
Procedure When operating the air conditioner in COOL operation in winter, or HEAT operation in summer,
set it to the trial operation mode using the following method.
1. Press the center of TEMP button and OFF button on the remote controller at the same time.
2. Select T (trial operation) with Temp , or button.
3. Press FAN button to enter the trial operation mode.
4. Press COOL or HEAT button to start trial operation.
5. Trial operation terminates in about 30 minutes and switches into normal mode.
To quit trial operation, press OFF button.
R7000277
The air conditioner draws a small amount of power in its standby mode. If the system is not
to be used for some time after installation, shut off the circuit breaker to eliminate
unnecessary power consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system will restore
the original operation mode when the circuit breaker is opened again.
1, 5
1, 2
4
4
3
background
SiUS042501E Trial Operation
Part 7 Trial Operation and Field Settings 119
Test Items
Test items Symptoms
Indoor and outdoor units are installed securely. Fall, vibration, noise
No refrigerant gas leaks. Incomplete cooling/heating
function
Refrigerant gas and liquid pipes and indoor drain hose
extension are thermally insulated.
Water leakage
Draining line is properly installed. Water leakage
System is properly grounded. Electrical leakage
Only specified wires are used for all wiring, and all wires are
connected correctly.
No operation or burn damage
Indoor or outdoor unit's air inlet or air outlet are
unobstructed.
Incomplete cooling/heating
function
Stop valves are opened. Incomplete cooling/heating
function
Indoor units properly receive remote control commands. No operation
Explain to the user that when using a smartphone for
operation, it is necessary to prepare a repeater, or similar
device, if the signal from the wireless LAN router is weak
near the air conditioner.
Air conditioner not responding to
smartphone
background
Field Settings SiUS042501E
120 Part 7 Trial Operation and Field Settings
4. Field Settings
4.1 When 2 Units are Installed in 1 Room
Outline When 2 indoor units are installed in one room, the 2 wireless remote controllers can be set for
different addresses. Change the address setting of one of the 2 units.
Procedure 1. Remove the battery cover of the remote controller.
2. Cut the address jumper.
3. Press the center of TEMP button and OFF button on the remote controller at the same time.
4. Press TEMP ▲ or TEMP ▼ button to select A (address setting).
5. Press FAN button to enter the address setting mode.
Then, the indoor unit OPERATION lamp will blink for about 1 minute.
6. Press the indoor unit ON/OFF switch while the OPERATION lamp is blinking.
7. Press FAN button on the remote controller for 5 seconds to return to the previous display.
If setting could not be carried out completely while the OPERATION lamp was blinking, carry
out the setting process once again from the beginning.
Replace the remote controller if you cut a jumper unintentionally
.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
R7000030
R7000447
R7000448
Address
EXIST
Jumper
CUT
1
2
Jumper
4
3, 4
3
5, 7
Indoor unit
ON/OFF switch
OPERATION
lamp
background
SiUS042501E Field Settings
Part 7 Trial Operation and Field Settings 121
Procedure BRC073A6 Wired Remote Controller
<Basic screen>
6-1 Press and hold the Cancel
button for 4 seconds or longer.
The Service Settings menu is
displayed.
6-1
82°F
Cool
Set to
<Service Settings>
6-2 Select Field Settings and press
the Menu/Enter button.
6-2
Test Operation
Maintenance Contact
Field Settings
Error History
Service Settings
SettingReturn
<Field settings>
6-3 Highlight the "Mode No.", and
select the desired "Mode No." by
using the (Up/Down) buttons.
6-3
Field Settings
Mode
1b
SettingReturn
● The current settings are displayed.
● CODE NO. " -- " means that there is no function
available.
6-4 Highlight the SECOND CODE.
of the FIRST CODE NO. to be
changed and select the desired
SECOND CODE NO. by using the
(Up/Down) buttons. Multiple
identical mode number settings
are available.
Press the Menu/Enter
button.
6-5 Press the Menu/Enter button. The
6-6 Select Yes and press the Menu/
Enter button. The settings are
saved and the Field settings
screen returns.
6-5
6-6
NoYes
Field Settings
Save the settings?
SettingReturn
<Field Settings>
FIRST CODE (SW) NO.
SECOND CODE NO.
background
Field Settings SiUS042501E
122 Part 7 Trial Operation and Field Settings
6-7 After all changes are completed,
press the Cancel button twice.
6-8 The backlight goes out and
"Checking the connection. Please
stand by" is displayed during
initialization. After the initialization,
the Basic screen returns.
Mode
No.
First
Code
No.
Description of the setting
Second code No.
01 02 03 04
1b
8 Daylight Saving Time Disable Enable* — —
11 (Private use) NA* NA — —
13 Basic screen display Icon+Text* Icon — —
15 (Private use) NA* NA — —
1c
0 (Private use) NA NA* — —
2 (Private use) NA NA* — —
4 (Private use) NA NA* — —
5 (Private use) NA* — — —
6 (Private use) NA* — — —
14 (Private use) NA* NA — —
1e
1 (Private use) NA NA* — —
2 Setback function Do not use Heat only Cool only Cool and Heat*
5 (Private use) NA NA* — —
6 (Private use) NA NA* — —
8 (Private use) NA* — — —
9 (Private use) NA NA* — —
a (Private use) NA* — — —
* Factory default setting
background
SiUS042501E Field Settings
Part 7 Trial Operation and Field Settings 123
4.2 Temperature Display Switch
ARC480 Series You can select Fahrenheit or Celsius for temperature display.
Press TEMP ▲ button and ON TIMER buttons simultaneously for 5 seconds to change the
unit of temperature display.
BRC073A6 You can select Fahrenheit or Celsius for temperature display.
Display the Configuration menu.
Press the ▲ or ▼ buttons to select "Celsius / Fahrenheit" and press the Menu/Enter
button.
Press the ▲ or ▼ buttons to select Celsius or Fahrenheit.
Press the Menu/Enter button to confirm the settings and to return to the Basic Screen.
(R14477)
Display
Celsius / Fahrenheit
Contrast Adjustment
Configuration
SettingReturn
Fahrenheit
Celsius / Fahrenheit
Celsius / Fahrenheit
SettingReturn
background
Field Settings SiUS042501E
124 Part 7 Trial Operation and Field Settings
4.3 Service Mode of Wireless Remote Controller
The remote controller mode is hierarchized by special conditions and operation content.
Refer below for the main hierarchy of the menu.
R5000463
Normal mode
Service mode
Normal mode is operated by the end user.
Simplified service diagnosis on normal mode
The code indication changes every time the TIMER CANCEL button is
pressed.
Service Check mode
In service check mode, the left-side number and the right-side
number can be identified individually.
Address setting mode
This mode sets the address corresponding to the jumper position.
Trial operation mode
Press for
5 seconds
Press for
5 seconds
Press for 5 seconds
Pressing the center of the temperature adjustment
button has the same function as pressing both
buttons simultaneously.
Proceed to
1
background
SiUS042501E Field Settings
Part 7 Trial Operation and Field Settings 125
R5000462
Overview of Settings
After replacing the indoor unit PCB, all the values are returned to the factory settings.
Use the remote controller to change the settings again.
When only the remote controller is replaced, the values stored in the PCB remain the same.
There is no hassle to the end user.
1
Field settings mode
Room temperature adjustment settings may be applied.
When changing the settings, make sure the button was correctly pressed by listening for
the beep sound. (The beep can be heard even if the button is pressed within a setting
which is unavailable. In this case, the setting will be invalid.)
Press the buttons to change the setting items and the setting values.
•
Confirm/Send
Setting items
Setting values
Setting items Setting options
Factory
Setting
Contents
4
Dry keep 0: OFF
1: ON
0
Stops the airflow of indoor unit when the thermostat is
OFF to prevent increase of room humidity.
0: When thermostat is OFF, the fan rotor will still be
OPERATING, hence there is airflow.
1: When thermostat is OFF, the fan rotor will be
STOPPED, hence there is no airflow.
6
Room temperature
adjustment (cooling)
0: Low 2 (–2°C)
1: Low 1 (–1°C)
2: Standard (0°C)
3: High 1 (+1°C)
4: High 2 (+2°C)
2
Adjustment of indoor temperature thermistor in cooling
operation.
Used for adjustment of room temperature control.
7
Room temperature
adjustment (heating)
0: Low 2 (–2°C)
1: Low 1 (–1°C)
2: Standard (0°C)
3: High 1 (+1°C)
4: High 2 (+2°C)
2
Adjustment of indoor temperature thermistor in heating
operation.
Used for adjustment of room temperature control.
10
Auto-restart 0: OFF
1: ON
1
This setting decides the operation of the unit when the
power supply resumed after a power supply shutdown
(i.e. power failure).
0: When the power supply resumes, the unit remains in
stopped operation.
1: When the power supply resumes, the unit resumes
the operation before the shutdown of power supply.
12
Warmer airflow setting 0: OFF
1: ON
0
This setting makes the discharge airflow temperature
warmer.
background
Silicone Grease on Power Transistor/Diode Bridge SiUS042501E
126 Part 7 Trial Operation and Field Settings
5. Silicone Grease on Power Transistor/Diode
Bridge
Outline Apply the specified silicone grease to the heat generation part of a power transistor/diode bridge
when you replace an outdoor unit PCB. The silicone grease encourages the heat dissipation of
a power transistor/diode bridge.
Details 1. Wipe off the old silicone grease completely.
2. Apply the silicone grease evenly. See the illustrations below for examples of application.
3. Tighten the screws of the power transistor/diode bridge.
4. Make sure that the heat generation parts are firmly contacted to the radiation fin.
Note: Smoke emission may be caused by bad heat radiation when the silicone grease is not
appropriately applied.
OK: Evenly applied
NG: Not evenly applied
NG: Foreign matter is stuck.
(R22541)
Power transistor
(or diode bridge)
Silicone grease
Radiation
fin
PCB
(R21866)
Foreign matter
(R21867)
background
SiUS042501E
Part 8 Appendix 127
1. Piping Diagrams..................................................................................128
1.1 Indoor Unit............................................................................................128
1.2 Outdoor Unit .........................................................................................129
2. Wiring Diagrams..................................................................................130
2.1 Indoor Unit............................................................................................130
2.2 Outdoor Unit .........................................................................................131
3. Operation Limit....................................................................................132
Part 8
Appendix
background
Piping Diagrams SiUS042501E
128 Part 8 Appendix
1. Piping Diagrams
1.1 Indoor Unit
FTXQ09ASBU9 FTXQ12ASBU9
4D152532 4D150950
background
SiUS042501E Piping Diagrams
Part 8 Appendix 129
1.2 Outdoor Unit
RXQ09ASBU9
RXQ12ASBU9
3D153768
3D150194
background
Wiring Diagrams SiUS042501E
130 Part 8 Appendix
2. Wiring Diagrams
2.1 Indoor Unit
FTXQ09/12ASBU9
A1P: Control PCB
A2P: Display/signal receiver PCB
A3P: Optional wireless LAN connection PCB
A4P: Humidity sensor PCB
Refer to page 18 for Printed Circuit Board Connector Wiring Diagram.
3D152536
background
SiUS042501E Wiring Diagrams
Part 8 Appendix 131
2.2 Outdoor Unit
RXQ09/12ASBU9
A1P: Main PCB
Refer to page 20 for Printed Circuit Board Connector Wiring Diagram.
3D153370
background
Operation Limit SiUS042501E
132 Part 8 Appendix
3. Operation Limit
FTXQ09/12ASBU9
3D154240
background
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
©
All rights reserved
Daikin products are manufactured for export to numerous countries throughout the world. Prior to
purchase, please confirm with your local authorized importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.
Specifications, designs and other content appearing in this brochure are current as of May 2025 but subject to change without notice.
SiUS042501E
05/2025 AK.K

Specifications