DAIKIN ROOM AIR CONDITIONER
INSTALLATION MANUAL
R32 Split Series
Installation manual
Manuel dinstallation
Manual de instalación
Manuel dinstallation
00_CV_3P740831-2E.indd 1 2024/07/17 13:10:56
background
1 ■English
Contents
Safety Considerations .................................... 1
Accessories ..................................................... 3
Precautions for Selecting a Location ........... 3
Precautions on Installation ............................ 4
Outdoor Unit Installation Diagram ................ 4
Installation Space Requirements .................. 5
Selecting a Location for Installation of the
Indoor Units ..................................................... 6
Outdoor Unit Installation ................................ 7
1. Installing the outdoor unit ............................................ 7
2. Drain work (Only for heat pump models) ..................... 7
3. Flaring the pipe end ..................................................... 7
4. Refrigerant piping ........................................................ 8
5. Pressure test and evacuating system .......................... 9
Wiring ............................................................... 10
Facility Setting
(cooling at low outdoor temperature) ........... 12
When attaching the drain pan heater
(Only for heat pump models) ......................... 12
Pump Down Operation ................................... 13
Trial Operation and Testing ............................ 13
1. Trial operation and testing ........................................... 13
2. Test items .................................................................... 13
Safety Considerations
The pictures in this document are for illustrative purposes only.
Refer also to the General Safety Considerations in the
separate booklet.
Read the precautions in this manual
carefully before operating the unit.
Refrigerant
Safety Group
A2L
This appliance is lled with R32.
Read these Safety Considerations for Installation carefully
before installing an air conditioner or heat pump. After completing
the installation, make sure that the unit operates properly during
the startup operation.
Instruct the user on how to operate and maintain the unit.
Inform users that they should store this installation manual with
the operation manual for future reference.
Always use a licensed installer or contractor to install this product.
Improper installation can result in water or refrigerant leakage,
electric shock, re, or explosion.
Meanings of DANGER, WARNING, CAUTION, and NOTE
Symbols:
DANGER
...........
Indicates an imminently hazardous
situation which, if not avoided, will
result in death or serious injury.
WARNING
.........
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
CAUTION
..........
Indicates a potentially hazardous
situation which, if not avoided, may
result in minor or moderate injury.
It may also be used to alert against
unsafe practices.
NOTE
................
Indicates situations that may result
in equipment or property damage
accidents only.
DANGER
• Refrigerant gas is heavier than air and replaces oxygen.
A massive leak can lead to oxygen depletion, especially
in basements, and an asphyxiation hazard could occur
leading to serious injury or death.
•
Do not ground units to water pipes, gas pipes, telephone
wires, or lightning rods as incomplete grounding can cause
a severe shock hazard resulting in severe injury or death.
Additionally, grounding to gas pipes could cause a gas leak
and potential explosion causing severe injury or death.
• If refrigerant gas leaks during installation, ventilate the
area immediately. Refrigerant gas may produce toxic gas
if it comes into contact with re. Exposure to this gas could
cause severe injury or death.
• After completing the installation work, check that the
refrigerant gas does not leak throughout the system.
• Do not install unit in an area where ammable materials
are present due to risk of explosions that can cause
serious injury or death.
• Safely dispose all packing and transportation materials
in accordance with federal/state/local laws or ordinances.
Packing materials such as nails and other metal or
wood parts, including plastic packing materials used for
transportation may cause injury or death by suffocation.
• All possible ignition sources, including cigarette smoking,
should be kept sufciently far away from the site of
installation, repairing, removing and disposal.
WARNING
•
Only qualied personnel licensed or certied in their jurisdiction
must carry out the installation work. Installation must be done in
accordance with this installation manual. Improper installation
may result in water leakage, electric shock, or re.
• Pipe-work including piping material, pipe routing, and
installation shall include protection from physical damage
in operation and service, and be in compliance with
national and local codes and standards, such as ASHRAE
15, ASHRAE 15.2, IAPMO Uniform Mechanical Code, ICC
International Mechanical Code, or CSA B52. All eld joints
shall be accessible for inspection prior to being covered or
enclosed.
• When installing the unit in a small room, take measures
to keep the refrigerant concentration from exceeding
allowable safety limits. Excessive refrigerant leaks, in the
event of an accident in a closed ambient space, can lead
to oxygen deciency.
01_EN_3P740831-2E.indd 1 2024/07/17 13:18:33
background
2■English
• Use only specied accessories and parts for installation
work. Failure to use specied parts may result in water
leakage, electric shock, re, or the unit falling.
• Install the air conditioner or heat pump on a foundation
strong enough that it can withstand the weight of the unit.
A foundation of insufcient strength may result in the unit
falling and causing injury.
• Take into account strong winds, typhoons, or earthquakes
when installing. Improper installation may result in the unit
falling and causing accidents.
• Make sure that a separate power supply circuit is provided
for this unit and that all electrical work is carried out by
qualied personnel licensed or certied in their jurisdiction
according to local, state, and national regulations. An
insufcient power supply capacity or improper electrical
construction may lead to electric shock or re.
•
Make sure that all wiring is secured, that specied wires are
used, and that no external forces act on the terminal connections
or wires. Improper connections or installation may result in re.
•
When wiring, position the wires so that the service lid can be
securely fastened. Improper positioning of the service lid may
result in electric shock, re, or the terminals overheating.
• Before touching electrical parts, turn off the unit.
•
The circuit must be protected with safety devices in
accordance with local and national codes, i.e. a circuit breaker.
• Securely fasten the outdoor unit service lid. If the service
lid is not installed properly, dust or water may enter the
outdoor unit causing re or electric shock.
•
When installing or relocating the system, keep the refrigerant
circuit free from substances other than the specied refrigerant
(R32) such as air. Any presence of air or other foreign substance
in the refrigerant circuit can cause an abnormal pressure rise or
rupture, which may result in equipment damage and even injury.
• Do not change the setting of the protection devices. If the
pressure switch, thermal switch, or other protection device
is shorted and operated forcibly, or parts other than those
specied by Daikin are used, re or explosion may occur.
• Do not use means to accelerate the defrosting process (if
possible) or to clean, other than those recommended by
the manufacturer.
•
The appliance must be stored in a room without continuously
operating ignition sources (for example: open ames, an
operating gas appliance or an operating electric heater).
• Do not pierce or burn.
• Be aware that refrigerants may not contain an odor.
• Comply with national gas regulations.
• The indoor equipment and pipes shall be securely
mounted and guarded such that accidental rupture of
equipment cannot occur from such events as moving
furniture or reconstruction activities.
CAUTION
• Do not touch the switch with wet ngers. Touching a switch
with wet ngers can cause electric shock.
•
Do not allow children to play on or around the unit to prevent injury.
• Wear adequate personal protective equipment (protective
gloves, safety glasses,…) when installing, maintaining or
servicing the system.
• The heat exchanger ns are sharp enough to cut. To avoid
injury, wear gloves or cover the ns while working around
them.
• Do not touch the refrigerant pipes during and immediately
after operation as the refrigerant pipes may be hot or
cold, depending on the condition of the refrigerant owing
through the refrigerant piping, compressor, and other
refrigerant cycle parts. Your hands may suffer burns or
frostbite if you touch the refrigerant pipes. To avoid injury,
give the pipes time to return to normal temperature or, if
you must touch them, be sure to wear proper gloves.
•
Install drain piping to ensure proper drainage. Improper drain
piping may result in water leakage and property damage.
• Insulate piping to prevent condensation.
• Be careful when transporting the product.
• Do not turn off the power immediately after stopping
operation. Always wait for at least 5 minutes before turning
off the power. Otherwise, water leakage may occur.
• Do not use a charging cylinder. Using a charging cylinder
may cause the refrigerant to deteriorate.
•
Refrigerant R32 in the system must be kept clean, dry, and tight.
(a) Clean and Dry -- Foreign materials (including mineral
oils such as SUNISO oil or moisture) should be
prevented from getting into the system.
(b)
Tight -- R32 does not contain any chlorine, does not
destroy the ozone layer, and does not reduce the earth’s
protection again harmful ultraviolet radiation. R32 can
contribute to the greenhouse effect if it is released.
Therefore take proper measures to check for the tightness
of the refrigerant piping installation. Read the chapter
Refrigerant Piping and follow the procedures.
• The outdoor unit is for R32. See the catalog for indoor
models that can be connected. Normal operation is not
possible when connected to non-compatible indoor units.
•
Remote controller (wireless kit) transmitting distance can be
shorter than expected in rooms with electronic uorescent
lamps (inverter or rapid start types). Install the indoor unit
far away from uorescent lamps as much as possible.
•
Indoor units are for indoor installation only. Outdoor units
can be installed either outdoors or indoors.
• Do not install the air conditioner or heat pump in the
following locations:
(a) Where a mineral oil mist or oil spray or vapor is
produced, for example, in a kitchen.
Plastic parts may deteriorate and fall off or result in
water leakage.
(b) Where corrosive gas, such as sulfurous acid gas, is
produced.
Corroding copper pipes or soldered parts may result in
refrigerant leakage.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of
the control system and cause the unit to malfunction.
(d) Where ammable gas may leak, where there is carbon
ber, or ignitable dust suspension in the air, or where
volatile ammables such as thinner or gasoline are
handled. Operating the unit in such conditions can
cause a re.
• Take adequate measures to prevent the outdoor unit
from being used as a shelter by small animals. Small
animals making contact with electrical parts can cause
malfunctions, smoke, or re. Instruct the user to keep the
area around the unit clean.
• Servicing shall be performed only as recommended by the
manufacturer and licensed or certied in their jurisdiction.
NOTE
• The outdoor unit should be positioned where the unit and
power supply wires (breaker panel to outdoor unit) are at
least 10ft (3m) away from any televisions or radios. (The
unit may cause interference with the picture or sound.)
Depending on the radio waves, a distance of 10ft (3m)
may not be sufcient to eliminate the noise.
• Dismantling the unit, treatment of the refrigerant, oil and
additional parts must be done in accordance with the
relevant local, state, and national regulations.
• Only use tools for R32 or R410A, such as a gauge
manifold, charge hose, gas leak detector, reverse ow
check valve, refrigerant charge base, vacuum gauge, or
refrigerant recovery equipment.
• If the conventional refrigerant and refrigerator oil are
mixed in R32, the refrigerant may deteriorate.
• As maximum allowable pressure is 604psi (4.17MPa), the
wall thickness of eld-installed pipes should be selected
in accordance with the relevant local, state, and national
regulations.
RN007(R32)-U
English
01_EN_3P740831-2E.indd 2 2024/07/17 13:18:33
background
3 ■English
Accessories
1
Installation manual
A
This is at the bottom of the packaging.
1
Drain socket*
B
6
1
1
3
Drain cap (1)*
C
Drain cap (2)*
D
Warranty
E
1
General Safety Considerations
G
Refrigerant
charge label
Affix near the
manufacturer’s label.
F
* Only for heat pump models
1
1
2
2
+ =
2
=
1
=
Precautions for Selecting a Location
1) Choose a place solid enough to bear the weight and vibration of the unit, where the operating sound will not be amplied.
2) Choose a location where the air discharged from the unit or the operating sound will not cause a nuisance to the neighbors of
the user.
3) Avoid locations, such as near bedrooms, where the operating sound may cause disturbance.
4) There must be sufcient space to carry the unit into and out of the site.
5) There must be sufcient space for air passage and no obstructions around the air inlet and the air outlet.
6) In coastal areas or other places with a salty atmosphere or one containing sulfate gas, corrosion may shorten the life of the air
conditioner.
7) Since water will ow from the drain of the outdoor unit, do not place anything under the unit which must be kept away from
moisture.
8) A location where ammable gas does not leak. Position at least 6-5/8ft (2m) from propane gas cylinders.
NOTE
Cannot be installed suspended from a ceiling or stacked.
CAUTION
When operating the air conditioner in a low outdoor ambient temperature, be sure to
follow the instructions described below.
• To prevent exposure to wind, install the outdoor unit with its suction side facing the
wall.
• Never install the outdoor unit at a site where the suction side may be exposed
directly to wind.
• To prevent exposure to wind, it is recommended to install a bafe plate on the air
discharge side of the outdoor unit.
• In heavy snow areas, select an installation site where the snow will not affect the unit.
• If there is a likelihood of snow accumulating on the outdoor unit, attach a snow
protection hood.
• In high humidity areas or heavy snow areas, it is recommended to attach a drain pan
heater to prevent ice build-up from the bottom frame.
• Construct a large canopy.
• Construct a pedestal.
Install the unit high enough off
the ground to prevent burying
in snow.
01_EN_3P740831-2E.indd 3 2024/07/17 13:18:33
background
4■English
Precautions on Installation
• Check the strength and level of the installation surface so that the unit does not cause
any operating vibrations or noise after installation.
• Fix the unit in place securely using foundation bolts, as in the gure. (Prepare 4
sets of 5/16 inch (M8) or 3/8 inch (M10) foundation bolts, nuts and washers; all sold
separately.)
• It is best to screw in the foundation bolts until their ends are 3/4 inch (20mm) from the
foundation surface.
3/4”
(20mm)
Outdoor Unit Installation Diagram
Manufacturer’s
label
Refrigerant piping must be protected from
physical damage.
Install a plastic cover or equivalent.
In sites with poor drainage, use
block bases for the outdoor unit.
Adjust foot height until the unit is
level. Otherwise, water leakage or
pooling of water may occur.
Gas pipe
Liquid pipe
Max. allowable piping length
Max. allowable piping height
Additional refrigerant required for refrigerant
pipe exceeding 49-1/4ft (15m) in length.
Refrigerant piping must be kept to a minimum.
*Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
**The suggested shortest pipe length is 10ft (3m), in order to avoid
noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how
the unit is installed and the environment in which it is used.)
O.D. 1/4 inch (6.4mm)
0.22oz/ft (20g/m)
O.D. 1/2 inch (12.7mm) O.D. 5/8 inch (15.9mm)
10ft (3m)
65-5/8ft (20m)
98-1/2ft (30m)
Min. allowable piping length
(Foot bolt-hole centers)
(From unit’s side)
**
*
Allow 11-13/16 (300)
of work space below the
ceiling surface.
9-13/16 (250) from wall
How to remove the stop
valve cover
1) Remove the screw on the
stop valve cover.
2) Slide the stop valve cover
downward to remove it.
1) Insert the upper part of
the stop valve cover into
the outdoor unit.
2) Tighten the screw.
How to attach the stop
valve cover
Stop valve cover
CAUTION
Keep the piping length between
10ft (3m) and 98-1/2ft (30m).
Wrap the insulation pipe with
finishing tape from bottom to top.
Allow space for piping and
electrical servicing.
4-15/16 (125)
If strong wind blows into the air discharge
side from the front and there is a danger
that the fan may be damaged, change the
orientation of the air discharge side of the
outdoor unit or use an air direction
adjustment grille (sold separately).
If there is a danger of the unit falling or overturning,
fix the unit with foundation bolts, or with wire or
other means.
RXF18, RKF18, RXT15, RXT18 RXF24, RKF24, RXT24
unit: inch (mm)
13-5/8 (346)
23-5/8 (600)
(Foot bolt-hole
centers)
Refrigerant charge label
Please ll in with indelible ink,
1
the factory refrigerant charge of the product,
2
the additional refrigerant amount charged in the eld and
1
+
2
the total refrigerant charge
on the refrigerant charge label supplied with the product.
Afx the refrigerant charge label near the manufacturer’s label
after lling it out.
1
1
2
2
+ =
2
=
1
=
45
3
2
1
1 factory refrigerant charge of the
product: see unit manufacturer’s
label
2 additional refrigerant amount
charged in the eld
3 total refrigerant charge
4 outdoor unit
5 refrigerant cylinder and manifold
for charging
English
01_EN_3P740831-2E.indd 4 2024/07/17 13:18:34
background
5 ■English
Installation Space Requirements
•
Position the unit on a horizontal surface. Any tilt in the unit should be 3° or less to the horizontal.
•
Where a wall or other obstacle is in the path of the outdoor unit’s intake or exhaust airow, follow the installation space requirements
below.
• For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.
• Secure as much installation space around the unit as the location allows, as more space will result in more efcient operation.
unit: inch (mm)
Top view
More than 3-15/16 (100)
More than 13-3/4 (350)
More than
1-15/16 (50)
More than
1-15/16 (50)
More than
1-15/16 (50)
Top view
More
than
3-15/16
(100)
More than
13-3/4
(350)
More than
3-15/16 (100)
More than
13-3/4 (350)
Side view
47-1/4
(1200)
or less
Wall facing one side Walls facing two sides
Walls facing three sides
More than
3-15/16 (100)
More than
13-3/4 (350)
When installed as in the figure on the left, it is recommended to either
change the orientation of the outdoor unit outlet side or use the air direction
adjustment grille (sold separately).
01_EN_3P740831-2E.indd 5 2024/07/17 13:18:34
background
6■English
Selecting a Location for Installation of the Indoor Units
• Minimum required oor area (A
min
)
The minimum required oor area of the room where the indoor unit is installed varies depending on the installation
height and refrigerant amount.
Indoor unit installation
height (m)
Refrigerant amount (kg)
h (m)
0.6 1.8 2.0 2.2 2.4 2.6
< 1.84 No restriction
1.9 31.0 6.9 6.2 5.6 5.2 4.8
2.0 34.3 7.3 6.5 5.9 5.4 5.0
2.1 37.8 7.6 6.9 6.2 5.7 5.3
2.2 41.5 8.0 7.2 6.5 6.0 5.5
2.3 45.4 8.4 7.5 6.8 6.3 5.8
2.4 49.4 8.7 7.8 7.1 6.5 6.0
2.5 53.6 9.1 8.2 7.4 6.8 6.3
2.6 58.0 9.4 8.5 7.7 7.1 6.5
2.7 62.6 9.8 8.8 8.0 7.4 6.8
2.8 67.3 10.2 9.2 8.3 7.6 7.0
2.9 72.2 10.5 9.5 8.6 7.9 7.3
3.0 77.2 10.9 9.8 8.9 8.2 7.5
3.1 82.5 11.3 10.1 9.2 8.4 7.8
3.2 87.9 11.6 10.5 9.5 8.7 8.0
3.3 93.4 12.0 10.8 9.8 9.0 8.3
3.4 99.2 12.3 11.1 10.1 9.3 8.5
3.5 105.1 12.7 11.4 10.4 9.5 8.8
3.6 111.2 13.1 11.8 10.7 9.8 9.0
3.7 117.5 13.4 12.1 11.0 10.1 9.3
3.8 123.9 13.8 12.4 11.3 10.3 9.6
3.9 130.5 14.5 12.7 11.6 10.6 9.8
4.0 137.3 15.3 13.1 11.9 10.9 10.1
4.1 144.2 16.0 13.4 12.2 11.2 10.3
4.2 151.4 16.8 13.7 12.5 11.4 10.6
4.3 158.7 17.6 14.3 12.8 11.7 10.8
4.4 166.1 18.5 15.0 13.1 12.0 11.1
20.0
18.0
16.0
14.0
12.0
10.0
8.0
6.0
4.0
2.0
0.0
0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.8 4.2
4.4
Refrigerant amount (kg)
Minimum required floor area (m
2
)
180.0
160.0
140.0
120.0
100.0
80.0
60.0
40.0
20.0
0.0
3.6 4.0
No restrictions
on floor area /
installation
height where the
indoor unit is
installed
h= 0.6 m
h= 2.0 m
h= 2.2 m
h= 1.8 m
Indoor unit installation
height (ft)
Refrigerant amount (lb)
h (ft)
2.0 5.9 6.6 7.2 7.9 8.5
< 4.05 No restriction
4.2 333 74 67 61 56 51
4.4 369 78 70 64 59 54
4.6 407 82 74 67 62 57
4.9 447 86 77 70 64 60
5.1 489 90 81 74 67 62
5.3 532 94 84 77 70 65
5.5 577 98 88 80 73 68
5.7 624 102 91 83 76 70
6.0 673 106 95 86 79 73
6.2 724 109 98 90 82 76
6.4 777 113 102 93 85 78
6.6 831 117 106 96 88 81
6.8 888 121 109 99 91 84
7.1 946 125 113 102 94 87
7.3 1006 129 116 106 97 89
7.5 1068 133 120 109 100 92
7.7 1131 137 123 112 103 95
7.9 1197 141 127 115 106 97
8.2 1264 145 130 118 108 100
8.4 1334 149 134 122 111 103
8.6 1405 156 137 125 114 106
8.8 1478 164 141 128 117 108
9.0 1553 173 144 131 120 111
9.3 1629 181 148 134 123 114
9.5 1708 190 154 138 126 116
9.7 1788 199 161 141 129 119
0
20
40
60
80
100
120
200
Minimum required floor area (ft
2
)
0
400
600
800
1000
1200
1400
1800
Refrigerant amount (lb)
1.7 2.1 2.5 2.9 3.3 3.7 4.1 4.5 4.9 5.3 5.7 6.1 6.5 6.9 7.3 7.7 8.1
9.7
lb = kg* 2.2046
ft
2
= m
2
* 10.764
200
1600
140
160
180
8.5 8.9 9.3
No restrictions
on floor area /
installation
height where the
indoor unit is
installed
h= 2.0 ft
h= 5.9 ft
h= 6.6 ft
h= 7.2 ft
English
01_EN_3P740831-2E.indd 6 2024/07/17 13:18:34
background
7 ■English
Outdoor Unit Installation
1. Installing the outdoor unit
• When installing the outdoor unit, refer to “Precautions for Selecting a Location” on page3 and “Outdoor Unit
Installation Diagram” on page4.
• If drain work is necessary, follow the procedures below.
2. Drain work (Only for heat pump models)
CAUTION
• In cold areas, do not use a drain socket, drain caps (1, 2) and a drain hose with the outdoor unit. (Drain water may freeze,
impairing heating performance.)
• If the drain port is covered by a mounting base or oor
surface, place additional foot bases of at least 1-1/4
inch (30mm) in height under the outdoor unit’s feet.
1) Attach
C
drain cap (1) and
D
drain cap (2).
2) Attach
B
drain socket to the shape of drain hole and
x it by turning.
• When attaching
B
drain socket to the bottom
frame, make sure to connect the drain hose to the
drain socket rst.
Bottom frame
Drain cap
Pinch the bottom
frame in.
Drain cap (1)
Drain cap (2)
D
Drain cap (2)
Air outlet side
B
Drain
socket
C
D
Hose (available commercially, inner dia. 5/8” (16mm))
Drain socket
B
Drain hole
Turn to fix.
Bottom frame
3. Flaring the pipe end
WARNING
• Do not apply mineral oil to the are.
• Prevent mineral oil from getting into the system as this would reduce the service life of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with this unit.
• Never install a dryer to this R32 unit in order to guarantee its service life.
• The drying material may dissolve and damage the system.
• Incomplete aring may result in refrigerant gas leakage.
CAUTION
• Do not reuse joints which have been used once already.
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing
downward, so that the lings do not enter the
pipe.
3) Put the are nut on the pipe.
4) Flare the pipe.
5) Check that the aring has been done correctly.
Check
The flare’s inner
surface must be
flaw-free.
When flaring, do
not over-tighten
and crack.
The pipe end must
be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.
Set exactly at the position shown below.
Flaring
A
Die
A
0-0.020 inch
(0-0.5mm)
Clutch-type
Flare tool for R32 or R410A
0.039-0.059 inch
(1.0-1.5mm)
Clutch-type (Rigid-type)
0.059-0.079 inch
(1.5-2.0mm)
Wing-nut type (Imperial-type)
Conventional flare tool
Cut exactly at
right angles.
Remove burrs.
01_EN_3P740831-2E.indd 7 2024/07/17 13:18:34
background
8■English
4. Refrigerant piping
CAUTION
• Use the are nut xed to the main unit. (This is to prevent the are nut from cracking as a result of deterioration over time.)
• Use a torque wrench when tightening the are nuts to prevent damage to the are nuts and gas leakage.
• Excessive tightening of the are nut can result in the are nut cracking in the long term, leading to gas leakage.
• Align the centers of both ares and tighten the are nuts 3 or 4 turns by hand, then tighten them fully with a spanner and a
torque wrench.
Torque wrench
Piping union
Flare nut
Spanner
Flare nut
Do not apply refrigeration oil, gas leak prevention
agent, etc., to the outer surface of the flare or threads
(flare nut, union).
(May result in cracking of the flare nut or damage to
the threads)
Union
Tightening torque
Piping connection
Flare nut
Gas side Liquid side
1/2 inch (12.7mm) 5/8 inch (15.9mm) 1/4 inch (6.4mm)
36-1/2–44-1/2lbf • ft
(49.5-60.3N • m)
45-5/8–55-5/8lbf • ft
(61.8-75.4N • m)
10-1/2–12-5/8lbf • ft
(14.2-17.2N • m)
Valve cap
Width across ats
11/16 inch (17mm) 7/8 inch (22mm) 1 inch (26mm)
10-1/2–12-5/8lbf • ft
(14.2-17.2N • m)
16-1/4–19-7/8lbf • ft
(22.1-26.9N • m)
23-1/4–28-3/8lbf • ft
(31.5-38.5N • m)
Service port cap
7-7/8–10-7/8lbf • ft
(10.7-14.7N • m)
Cautions on pipe handling
• Protect the open end of the pipe from dust and moisture.
• All pipe bends should be as gentle as possible. Use a pipe bender for bending.
Selection of copper and heat insulation materials
When using commercial copper pipes and ttings, observe the following:
• Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F) (0.035 to 0.045kcal/mh°C)
Be sure to use insulation that is designed for use with HVAC Systems.
• ACR Copper only.
• Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as below.
Gas side
Piping size
O.D. 5/8 inch
(15.9mm)
O.D. 1/4 inch
(6.4mm)
1-15/16 inch (50mm)
or more
1-3/16 inch (30mm)
or more
0.039 inch (1.0mm)
(C1220T-O)
0.031 inch (0.8mm)
(C1220T-O)
I.D. 5/8-13/16 inch
(16-20mm)
I.D. 5/16-13/32 inch
(8-10mm)
13/32 inch
(10mm) Min.
Minimum bend radius Piping thickness Thermal insulation size
Thermal insulation
thickness
Liquid side
O.D. 1/2 inch
(12.7mm)
1-9/16 inch (40mm)
or more
0.031 inch (0.8mm)
(C1220T-O)
I.D. 9/16-5/8 inch
(14-16mm)
• Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
• Using nishing tape, bundle and wrap the indoor unit piping and drain hose together
so that the drain hose is below the other piping.
Gas pipe
Liquid pipe
Gas pipe
insulation
Liquid pipe
insulation
Finishing tape
Drain hose
Wall
If no flare cap is
available, cover
the flare mouth
with tape to keep
dirt and water out.
Be sure to
place a cap.
Rain
English
01_EN_3P740831-2E.indd 8 2024/07/17 13:18:35
background
9 ■English
Outdoor Unit Installation
5. Pressure test and evacuating system
WARNING
• Make sure that air or any matter other than refrigerant (R32) does not get into the refrigeration cycle.
• If refrigerant gas leaks should occur, ventilate the room as soon and as much as possible.
• R32, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• Use tools for R32 or R410A (such as the gauge manifold, charging hose, or vacuum pump adapter).
CAUTION
It is highly recommended that you do not open/close the stop valves when the outdoor temperature is below −5°F (−21°C) as
this may result in refrigerant leakage.
• When piping work is complete, it is necessary to perform a pressure test
and evacuate system with a vacuum pump.
• If using additional refrigerant, purge the air from the refrigerant pipes and
indoor unit using a vacuum pump, then charge additional refrigerant.
• Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench to the
specied tightening torque.
Compound
pressure gauge
Pressure
meter
High-pressure
valve
Low-pressure
valve
Vacuum pump
Service port
Liquid
stop
valve
Valve caps
Gas stop valve
Charging
hoses
Gauge
manifold
1) Pressurize the liquid pipe and gas pipe from the service port of gas stop valve to 604psi (4.17MPa) (do not pressurize
more than 604psi (4.17MPa)) for 1 hour minimum, 24 hours recommended. If there is a pressure drop, check for leaks,
make repairs and perform the pressure test again.
2) Connect the gauge manifold’s charging hose to the gas stop valve’s service port.
3) Fully open the low-pressure valve (Lo) on the gauge manifold and fully close the high-pressure valve (Hi).
(High-pressure valve will require no further operation.)
4) Evacuate system using vacuum pump to below 500 microns for 1 hour minimum.
5) Close the low-pressure valve (Lo) on the gauge manifold and stop vacuum pumping.
(Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing
back.)*
1
6) Remove the valve caps from the liquid stop valve and gas stop valve.
7) To open the liquid stop valve, turn the rod of the valve 90° counter-clockwise using a hexagonal wrench.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from the indoor unit’s are and outdoor unit’s are and valve rods.
After the check is complete, wipe all soapy water off*
2
.
8) Disconnect the charging hoses from the service port for the gas stop valve, then fully open the liquid and gas stop valves.
(Do not attempt to turn the valve rods further than they can go.)
9) Tighten the valve caps and service port caps for the liquid and gas stop valves with a torque wrench to the specied
torques.
Refer to “4. Refrigerant piping” on page8 for details.
*
1
If the compound pressure gauge pointer swings back, the refrigerant may have water content or there may be a loose
pipe joint.
Check all pipe joints and retighten nuts as needed, then repeat steps 3) through 5).
*
2
Under no circumstances shall potential sources of ignition be used in the searching for or detection of
refrigerant leaks.
A halide torch (or any other detector using a naked ame) shall not be used.
Do not use substances containing chlorine and electronic leak detection for gas leak detection.
01_EN_3P740831-2E.indd 9 2024/07/17 13:18:35
background
10■English
Wiring
WARNING
• RISK OF ELECTRIC SHOCK CAUSE INJURY OR DEATH.
System contains oversize protective earthing (grounding) terminal which shall be properly connected.
• Do not ground units to water pipes, gas pipes, telephone wires, or lightning rods as incomplete grounding can cause a
severe shock hazard resulting in severe injury or death.
Additionally, grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death.
• Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electric shock, or re.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or re.
• The circuit must be protected with safety devices in accordance with local and national codes, i.e. a circuit breaker.
• Use an all-pole disconnection type circuit breaker with at least 1/8 inch (3mm) between the contact point gaps.
• When carrying out wiring, take care not to pull at the conduit.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or re.
• Do not turn on the circuit breaker until all work is completed.
CAUTION
Precautions to be taken for power supply wiring
Recommend stranded cable for interunit wiring. Local code always supersedes recommendation.
• For stranded wires, make sure to use the round crimp-style terminal for
connection to the power supply terminal block. Place the round crimp-
style terminals on the wires up to the covered part and secure in place.
Round crimp-style
terminal
Stranded wire
Screw
Flat washer
Screw Screw
Flat washer
Flat washer
Good Wrong
A
Round
crimp-style
terminal
Round crimp-style
terminal
Round crimp-style
terminal
Arrow view A
• If solid core wire must be used, be sure to curl the end of the lead. Improper work may cause heat and re.
Good
Good
Stripping wire at terminal block
Wrong
Wrong
Strip wire end
to this point.
Excessive strip length
may cause electric shock
or current leakage.
English
01_EN_3P740831-2E.indd 10 2024/07/17 13:18:35
background
11 ■English
Wiring
[Method of mounting conduit]
When wiring, remove the top plate and look at the wiring diagram on the back of the top plate.
1) Dismount the service lid by removing the 2 screws.
2) Slide the protection plate up and remove it.
3) Pass wires through the conduit and secure them with a lock nut.
Protection plate
Conduit mounting plate
Wiring diagram
Top plate
Service lid
Screw
1
2
3
1
2
3
Terminal block
Conduit
Lock nut
Conduit
mounting plate
Shape the wires so that there is
no lifting of the protection plate or
other structural parts.
L
1
L
2
[Wiring procedure]
1) Strip the insulation from the wire (3/4 inch (20mm)).
2) Connect the inter-unit wires between the indoor and outdoor units so that the terminal numbers match. Tighten the
terminal screws securely. It is recommended that a slot-head screwdriver be used to tighten the screws.
3) Pull the wire lightly to make sure that it does not disconnect.
4) Pass the wiring through the cutout on the bottom of the protection plate and attach the protection plate.
5) After completing the work, reattach the service lid to its original position.
1
2
3
1 2 3
Follow local codes for wiring
and safety devices between
outdoor unit and power
source.
For the ground wire, use
AWG10, stranded and
insulated wire.
Ground
Firmly fix the wires with
the terminal screws.
Recommend using AWG14, stranded and
insulated wire for connections between indoor and
outdoor units.
Local code always supersedes recommendation.
Outdoor unit
Indoor
unit
Power supply
60Hz 208-230V
RXT15 20A
RXF18/24
RKF18/24 25A
RXT18/24
Firmly fix the wires with
the terminal screws.
L
1
L
2
Ground
This air conditioner must be grounded. For grounding, follow all local, and state electrical codes.
NOTE
Take care to ensure that all wiring between indoor unit and outdoor unit has a consistent connection. Any splices can cause
communication errors.
01_EN_3P740831-2E.indd 11 2024/07/17 13:18:35
background
12■English
Facility Setting (cooling at low outdoor temperature)
WARNING
• Make sure to turn the power OFF before performing work.
CAUTION
• If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
• Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
• Do not place humidiers or other items which might raise the humidity in rooms where facility settings are being used.
A humidier might cause dew condensation from the indoor unit outlet vent.
• Activating the facility setting sets the indoor fan tap to the highest position. Notify the user about this.
This function is designed for facilities such as equipment or computer rooms. It is never to be used in a
residence or ofce where people occupy the space.
Cutting jumper 7 (J7) on the PCB will extend the operation range to 14°F (–10°C). Installing an air direction adjustment grille
(sold separately) will further extend the operation range to –4°F (–20°C). In these cases, the unit will stop operating if the outdoor
temperature falls below –4°F (–20°C), restarting once the temperature rises above this level.
1) Remove the top plate of the outdoor unit. (6 screws)
2) Remove the front plate. (10 screws)
3) Remove the anti-drip cover.
4) Cut the jumper (J7) of the PCB inside.
Cut jumper J7.
J12
J8
J7
J5
J9
J4
Front plate
Anti-drip cover
Top plate
When attaching the drain pan heater
(Only for heat pump models)
WARNING
• Make sure to turn the power OFF before performing work.
In high humidity areas or heavy snow areas, it is recommended to attach a drain pan heater to prevent ice build-up from
the bottom frame.
1) Attach the drain pan heater in accordance with the installation manual included with the drain pan heater.
2) Cut the jumper (J9) of the PCB inside.
J12
J8
J7
J5
J9
J4
Cut jumper J9.
English
01_EN_3P740831-2E.indd 12 2024/07/17 13:18:35
background
13 ■English
Pump Down Operation
In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve caps from the liquid stop valve and gas stop valve.
2) Begin forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.
5) Attach the valve caps once procedures are complete.
Gas
stop valve
Valve cap
Hexagonal
wrench
Close
Liquid
stop valve
Service port
Forced cooling operation
Refer to the installation manual for the indoor unit.
Trial Operation and Testing
• When trial operation is conducted directly after the circuit breaker is turned on, in some cases no air will be output for about
15minutes in order to protect the air conditioner.
1. Trial operation and testing
Refer to the installation manual for the indoor unit.
2. Test items
Test items Symptom Check
Indoor and outdoor units are installed securely. Fall, vibration, noise
No refrigerant gas leaks. Incomplete cooling/heating function
Refrigerant gas and liquid pipes and indoor drain hose extension are
thermally insulated.
Water leakage
Draining line is properly installed. Water leakage
System is properly grounded. Electrical leakage
Only specied wires are used for all wiring, and all wires are connected
correctly.
No operation or burn damage
Indoor or outdoor unit’s air inlet or air outlet are unobstructed. Incomplete cooling/heating function
Stop valves are opened. Incomplete cooling/heating function
Indoor unit properly receives remote control commands. No operation
01_EN_3P740831-2E.indd 13 2024/07/17 13:18:35
background
14■English
MEMO
English
01_EN_3P740831-2E.indd 14 2024/07/17 13:18:35