26
2. Read the current measurements for phases A/L1, B/L2, C/L3, and N.
A yellow START button indicates errors found in the connection. Watch for undervoltage or
overvoltage indications, polarity of current probes, and the phase rotation for voltage and
current. Most installations use a clockwise rotation.
a. Make sure to check also phasor and scope in the Verify Phasor and Verif y Scope
menus.
b. Push Correct Digitally to make changes on the connection or push Auto Correct to
apply corrections automatically.
If no errors are found, the START button turns green.
3. Push START to activate all measurement parameters. The measurement parameters are
also stored to the internal flash drive.
4. Navigate through the available measurement screens with the left touch buttons. Swipe up
and down to see them all.
5. Push
C to take a screen shot.
6. Download the measurement during and after the logging session with Energy Analyze Plus.
a. In the software, click Download Data and copy the logging session from the Analyzer to
the PC.
b. Open the session and view the measurement data. For more information about how to
use the software, see Energy Analyze Plus Online Help.
Measurement Configuration
The Home screen has two configuration options for measurement: PQ Meter and PQ Logger.
PQ Meter Mode
The PQ Meter mode offers instant measurements to troubleshoot power quality. During the PQ
Meter session, the Analyzer captures and shows the measurements on the display. These
measurements are automatically stored in memory every second for up to 24 hours. A flashing
green power button on the Analyzer indicates an active session. See User Interface.
A red recording icon shows on the display above the measurements and indicates an
active logging session.