User Manual Mrcool NV503834 50 ft. Pre-Charged 3/8 in. x 3/4 in. No-Vac Quick Connect Line Set

Documents for Mrcool NV503834

The following documents are available:
Installation Instruction Other Documents Photos
NV503834 photo

Installation Instructions

For NV503834.

INSTALLATION NOTICE FOR NO-VAC™ QUICK CONNECT® LINE SET
KINK RESISTANT, PRECHARGED, SIMPLE SECURE QUICK CONNECT, 100% CONNECTION GUARANTEE
www.mrcool.com
v05-30-2019
Please read carefully and follow the instruc�ons as below
:
F1 to M1: Smaller connec�on (3/8”)
1.
Take out matching male connectors M1 and M2.
2.
Remove protec�ve cap with the copper gasket at each stop valve on the condenser
and ensure the threads are clean and complete.
3.
Tighten the M1 connector to the stop valve *1 with a �ghtening force of 50N.
Tighten the M2 connector to the stop valve *2 with a �ghtening force of 70N.
4.
Repeat step 3 for INDOOR UNIT at the other end of the LINE SET.
5.
Unroll and route the LINE SET between the INDOOR UNIT (Handler) and the
OUTDOOR UNIT (Condenser).
6.
Remove the protec�ve caps of the valves at both ends of the LINE SET. Verify
that all threads are clean and complete.
7.
Tighten the LINE SET F1 valve to the M1 Connector (a�ached in step 3) with a force
of 45N. Tighten the LINE SET F2 valve to the M2 Connector (a�ached in step 3) with a �ghtening force of 45N.
8. Repeat this process for the INDOOR UNIT at the other end of the LINE SET.
Connec�ons must be made exactly as specified to avoid system leaks and /or damage
F2 to M2: Larger connec�on (3/4”)
9.
At the OUTDOOR UNIT remove the protec�ve cap at the stop valve switch and open the stop valve with a hex wrench to
run the refrigera�on circuit. If there is any fizz, grease or other leakage, close the valve immediately and check that steps
3 and 7 were done properly. Otherwise, immediately apply soapy water for micro-leakage detec�on. Soak the joints using
a sponge or spray bo�le. If any bubbles form, close the valve immediately and check that steps 3 and 7 were done properly.
10. A�er the correct connec�on, re-�ghten the stop valve’s protec�on cap and cover the M1, M2 and F1, F2 connec�ons
with the grey insula�ng sleeve to help prevent condensa�on.
Failure to follow the instrucons provided could result in severe harm to you, this product, or other property.
The manufacturer, distributor, and seller are not responsible for any harm resulng from the failure to follow
instrucons and the failure to follow these instrucons will void any and all warranes express or implied.
NO-VAC
QUICK CONNEC
LINE SET
INDOOR UNITCONNECTOR M1 & M2OUTDOOR UNIT
STEP 6
NO-VAC™ QUICK CONNECT® LINE SETs allow you to connect indoor and outdoor units simpler, faster and safer.
NO-VAC™ QUICK CONNECT® LINE SETs are an�-kink and pre-charged with refrigerant; suitable for most MRCOOL® installa�ons.
NO-VAC™ QUICK CONNECT® LINE SETs are a double-sealing system with a unique automa�c safety valve that releases the
refrigerant only when the indoor and outdoor equipment is connected and sealed, thus avoiding any risk of leakage.
NO-VAC™ QUICK CONNECT® LINE SETs - no need to vacuum, no need to add refrigerant.
STEP3