FLUKE 1587 FC-NIST Insulation Multimeter, includes Traceable Certificate

User Manual for the Fluke 1587 FC-NIST Insulation Multimeter, - Page 48

For 1587 FC-NIST.

PDF File Manual, 48 pages, Read Online | Download pdf file

1587 FC-NIST photo
Loading ...
Loading ...
Loading ...
1587 FC/1587/1577
Users Manual
42
Model 1587T
Output Voltage Display Range Resolution Test Current
Resistance Accuracy
±(% of Rdg + Counts)
50 V
(0 % to +20 %)
0.01 to 6.00 M 0.01 M
1 mA @ 50 k ±(3 % + 5 counts)
6.0 to 50.0 M 0.1 M
100 V
(0 % to +20 %)
0.01 to 6.00 M 0.01 M
1 mA @ 100 k ±(3 % + 5 counts)
6.0 to 60.0 M 0.1 M
60 to 100 M 1 M
Model 1587C FC
Output Voltage Display Range Resolution Test Current
Resistance Accuracy
±(% of Rdg + Counts)
50 V
(-10 % to +10 %)
0.01 to 6.00 M 0.01 M
1 mA @ 50 k ±(3 % + 5 counts)
6.0 to 50.0 M 0.1 M
100 V
(-10 % to +10 %)
0.01 to 6.00 M 0.01 M 1 mA @ 100 k ±(3 % + 5 counts)
250 V
(-10 % to +10 %)
0.1 to 60.0 M 0.1 M
1 mA @ 250 k ±(1.5 % + 5 counts)
60 to 250 M 1 M
500 V
(0 % to +20 %)
0.1 to 60.0 M 0.1 M
1 mA @ 500 k ±(1.5 % + 5 counts)
60 to 500 M 1 M
1000 V
(0 % to +20 %)
0.1 to 60.0 M 0.1 M
1 mA @ 1 M
±(1.5 % + 5 counts)
60 to 600 M 1 M
0.6 to 2.0 G 100 M ±(10 % + 3 counts)
1.888.610.7664 sales@GlobalTestSupply.com
Fluke-Direct
.com