Alarm/Fault Reason Action(s)
High Supply Air Temperature
Heat load exceeds cooling
capacity limit
Adjust airflow limit in factory menu to highest value
Add more cooling devices
Move heat-generating equipment closer to cooling In-Row
Cooler
Add aisle containment or attempt to redirect airflow
Cooling In-Row Cooler will not
come out of standby
Ensure group connection is set up properly
Low refrigerant
Check for refrigerant leaks, replace necessary components
Add more refrigerant
Issues with directional airflow
configuration
Ensure front and/or side discharge airflow vents do not
have obstructions and are configured properly
Compressor/fan speed is set to
fixed
Raise the upper limit of the temperature band or reset
compressor/fan speed to auto
Condenser signal wiring
disconnected
Ensure condenser signal wiring is still intact
If none of these solutions work, check for component
failure within the refrigeration circuit
Low Supply Air Temperature
Low load (minimum cooling
capacity exceeds the heat load
in the room)
If multiple cooling In-Row Coolers are on, turn off
additional cooling In-Row Coolers by either ensuring group
control is configured properly or manually putting In-Row
Cooler(s) into standby.
Add more thermal load by adding more equipment or
artificial heat (heat banks)
If none of these solutions work, check for component
failure within the refrigeration circuit
Compressor/fan speed is set to
fixed
Lower the lower limit of the temperature band or reset
compressor/fan speed to auto
Condenser signal wiring
disconnected
Ensure condenser signal wiring is still intact
If none of these solutions work, check for component
failure within the refrigeration circuit
High Humidity
High humidity environment
Install vapor barrier
Or wait for high humidity conditions to pass
Cooling In-Row Cooler not
dehumidifying
Ensure condensate management system is operational
Low Humidity
Dry environment
Add humidification in the IT space
Or adjust the lower humidity limit and wait for the dry
humidity conditions to pass
Cooling In-Row Cooler
dehumidifying
Check that In-Row Cooler is not cooling below the
setpoint.
Report any issues if yes.
Leakage/Water Overflow
Leak in drain pan Repair
Leak in condensate connection
or drainage tube
Repair
Fan blowing moisture off
evaporator coil
Record the evaporator fan speed at the time of
occurrence and report any issues
Leak from adjacent equipment/
room
Check origin of the leak
Drain pan overflow Ensure drain pan floats are operational
Displaced evaporator Repair
2. Operation and Maintenance