BT520
Users Manual
3-14
Measure DC Voltage
The Product can measure dc voltage. It also shows the polarity on the display.
To measure dc voltage, turn the rotary switch to . See Figure 3-3 for connections.
UPS
Vdc
Save
hsn019.eps
Figure 3-3. Measure DC Voltage
Set Measurement Range
In this measurement mode, auto range is used by default. When the input signal reaches
110 % of the upper limit of the current range, the Product automatically increases a
range. When the input signal reaches 90 % of the lower limit of the current range, the
Product automatically decreases a range.
To manually set the range, push to cycle through 6 V, 60 V, and 600 V.
Save DC Voltage Readings
In Meter mode, push the Save softkey to save the current dc voltage reading and the
timestamp. All saved data is stored in chorological order.
In Sequence mode, push the Save softkey to save the current dc voltage reading and
the timestamp. The current battery number automatically increases by 1. The cell that
corresponds to the tested point becomes full, and the cursors move forward.