Thermographic Cube Camera User Manual
13
alarm temperature as 50°C. The device sends pre-alarm when its temperature reaches 50°C
and it alarms when its temperature reaches 55°C and only when the device temperature is
lower than 52°C will the alarm be cancelled.
Pre-Alarm Output and Alarm Output
When the temperature of target exceeds the pre-alarm or alarm threshold, it triggers the pre-
alarm or alarm output of the connected device.
2. Save the settings.
Set Interval Temperature Measurement in Expert Mode
In interval temperature measurement alarm mode, the device outputs alarm if the detected
temperature is within the set temperature range.
Before You Start
Select Alarm Mode as Interval Temperature Measurement Alarm first in basic settings.
Steps
1. Select the alarm rule for interval temperature measurement.
2. Edit the interval name.
3. Set the temperature range. The device outputs an alarm if the detected temperature is within
the set temperature range.
4. Set the rule color in alarm status.
5. Select the alarm output channel.
Note
The function varies according to different models.
3.4 Manual Thermography
After enable the manual thermography function of the device, you can click any position on the
live view to show the real temperature.
Steps
1. Go to Configuration Local and select Display Temperature Info. as Yes.
2. Go to Configuration Temperature Measurement Basic Settings.
3. Check Enable Temperature Measurement.
4. Click Save.
5. Go to live view interface and select thermal channel, click . Click any position on the
interface to show the real temperature.