FLUKE 1621 Earth Ground Tester

User Manual for the Fluke 1621 Earth Ground Tester - Page 19

For 1621.

PDF File Manual, 20 pages, Read Online | Download pdf file

1621 photo
Loading ...
Loading ...
Loading ...
Earth Ground Tester
Specifications
17
Measuring
Range
Resolution Display Range
Intrinsic
Uncertainty
Operating
Uncertainty
IEC 61557*
0.15 to 20 0.01 0 to 19.99
±(6 % of
measured
value + 5D)
±(18 % of
measured
value + 5D)
200 0.1 20 to 199.9
2 k 1 200 to 1999
*Covers all deviations caused by influence quantities E
1
-E
5
If the deviation E4 caused by high probe or auxiliary probe resistance is higher
than specified W flashes. Measured values are outside of the specified
operating uncertainty.
Measuring time: 8 seconds (average from when START is pressed)
Limit input: Tester retains set value even if instrument is turned off
(assuming battery power supply is sufficient)
If Tester detects stray interference voltage 20 V, W is displayed and the
measurement is not started.
1.888.610.7664 sales@GlobalTestSupply.com
Fluke-Direct.com
Loading ...