TOP MOUNT PACKAGED REFRIGERATION SYSTEM
14
RAPID PARAMETER SET SELECTION (EZY)
The easy controller features the EZY parameter which
is used to quickly choose a list of parameters, with
corresponding values, for the control of the refrigeration
system.
TABLE OF ALARMS AND SIGNALS
When an alarm is activated, the display shows the
corresponding message that flashes alternating with the
temperature; if fitter and enabled, the buzzer and the alarm
relay are also activated.
All the alarms have automatic reset (that is, they stop when
the causes are no longer present), except for alarm ‘CHt
which has manual reset (instrument on/o using the UP
button or by disconnecting the power supply).
NOTE:
To restore the selected rapid parameter set at any
time, turn the controller o and on again, while holding
SET. The display shows “CE” to indicate that the
selected rapid set (EZY= 1, 2, 3) has again over written
the operating parameters, thus restoring the original
set of parameters.
To restore all the parameters and return to the original
default values (factory settings), turn the controller o
and on again while holding DOWN and SET, until the
display shows “CF”. Use this procedure with extreme
car, as it may compromise the fundamental control
settings.
EZY= 0 brings no change
Pressing the SET button mutes the buzzer, while the code
displayed and the alarm relay only go o when the causes
of the alarm have been resolved. The alarm codes are
shown in the able below:
Alarm
Code
Buzzer and
Alarm Relay
LED Alarm Description Reset
Enable Alarm
parameters involved
E0 active ON probe 1 error= control automatic
E1 not active ON probe 2 error= defrost automatic d0= 0 / 1 / 4, F0= 1
E2 not active ON probe 3 error= condenser/ product automatic [A4=10]
IA active ON external alarm automatic [A4 = 1] [+A7]
dOr active ON open door alarm automatic [A4 = 7/8][+A7]
LO active ON low temperature alarm automatic [AL] [Ad]
HI active ON high temperature alarm automatic [AH] [Ad]
EE not active ON unit parameter error not possible
EF not active ON operating parameter error manual
Ed not active ON defrost ended by timeout on first defrost ended correctly [dP] [dt] [d4] [A8]
dF not active OFF defrost running automatic [d6=0]
cht not active ON dirty condenser pre-alarm automatic [A4=10]
CHt active ON dirty condenser alarm manual [A4=10]
EtC not active ON clock alarm by setting the time if bands active