13. Technical Specifications
MODEL 30K 60K 90K 120K 150K 180K 210K
CAPACITY
30kVA/30kW 60kVA/60kW 90kVA/90kW 120kVA/120kW 150kVA/150kW 180kVA/180kW 210kVA/210kW
TOPOLOGY
Voltage and Frequency Independent (VFI) True on-line Double Conversion
INPUT
Voltage 380/400/415V (Ph-Ph), 220/230/240V (Ph-N)
Voltage Range 305 to 477V (100% load) / 208 to 305V (70% load)
Phase 3-phase, neutral and ground
Operating Frequency 50/60 Hz (selectable)
Frequency Range 40 Hz ~ 70 Hz ± 0.1 Hz
Power Factor >0.99%
THDi <3%
Inverter Bridge IGBT technology
OUTPUT
Voltage 380/400/415V (3ph, 4 wire, neutral** reference to bypass neutral)
AC Voltage Regulation <1% (balanced load)
Frequency 50/60 Hz (selectable)
Frequency Range 40 Hz ~ 70 Hz ± 0.1 Hz
Overload AC mode 100-110%: 60 min
111-120%: 10 min
121-150%: 1 min
>150%: 200 ms
Battery mode 100-110%: 60 min
111-125%: 10 min
126-150%: 1 min
>150%: 200 ms
Crest Factor 3:1
Harmonic Distortion <2% (100% linear load); <4% (100% non-linear load)
Output Waveform Pure sine wave
BYPASS
Automatic Bypass Standard
Manual Maintenance Bypass Standard
Transfer Time 0 ms
Default Bypass Voltage Tolerance +15/-20%
Overload 105 to 110%: 60 min
111 to 125%: 10 min
126 to 150%: 1 min
>150%: 200 ms
BATTERY
Battery Type* Maintenance-free sealed valve-regulated lead acid (VRLA)
Battery Capacity* 12V 9Ah per battery module
Float Voltage 2.3V/cell
Boost Voltage 2.35V/cell
End of Discharge Voltage 1.67V/cell
Battery Storage Time* 6 months (without recharge, 25°C)
Battery Charger Capacity 8A per power module
ENVIRONMENT
Efficiency (Inverter Mode) >94%
Efficiency (ECO Mode) >98%
Operating Temperature 0 to 40°C
Storage Temperature (Excl Battery Module) -15 to 60°C
* Applies to Small- and Medium-Frame systems with internal battery modules. **The UPS output Neutral must be connected to the Load Neutral at all times.