Tripp Lite SVX30KL SmartOnline SVX Series 30kVA Modular, Scalable 3-Phase, On-line Double-Conversion 400/230V 50/60Hz UPS System

Owner's Manual - Page 26

For SVX30KL. Series: SVX Series

PDF File Manual, 148 pages, Read Online | Download pdf file

SVX30KL photo
Loading ...
Loading ...
Loading ...
26
9. Control Panel
SmartOnline SVX-Series UPS Operating Mode
Standby Bypass Line Battery Battery Test Fault Converter ECO
Output Voltage Y Y
Bypass Voltage Range Y Y Y Y Y Y Y Y
Bypass Frequency Range Y Y
Converter Mode Y
ECO Mode Y Y Y
Bypass Mode Y Y
Auto Restart Y Y Y Y Y Y Y Y
Cold Start Y Y Y Y Y Y Y Y
Battery Mode Delay Time Y Y Y Y Y Y
System Shutdown Time Y Y Y Y Y Y Y Y
System Restore Time Y Y Y Y Y Y Y Y
Redundancy Y Y Y Y Y Y Y Y
Table 9.4
9.3.6.3 Battery
The SETUP – BATTERY screen may be accessed in any UPS operating mode. Some settings may only be amended in certain modes; refer to table
9.5 for details.
BATTERY
BATTERY LOW /
SHUTDOWN SETTING
MAXIMUM CHARGING
CURRENT
BATTERY CAPACITY IN Ah
BATTERY TEST
BATTERY AGE ALERT
TEMPERATURE
COMPENSATION
Battery Capacity in Ah
Maximum Charging Current
Battery Low Voltage
Battery Low Capacity
Battery Shutdown Voltage
Periodic Battery Test
Battery Test Interval
Stop by Time
Stop by Battery Voltage
Stop by Battery Capacity
Battery Age Alert
Temperature
Compensation
Set battery capacity (0-999) (Default: 009)
Set maximum battery charging current (1-64A)
(Default: 2)
Set battery low voltage: (10.5-11.5V) x
(number of batteries) (Default: 220V)
Set battery low capacity (20-50%) (Default: 20%)
Set voltage point for system shutdown (10-11V) x
(number of batteries) (Default: 200)
Set ‘Disable’ or ‘Enable’ (Default: Disabled)
Set battery test interval (7-99 days) (Default: 30)
Set testing time for battery test (10-1000 sec)
(Default: 10)
Set battery voltage cut-off to end battery test
(11-12V) x (number of batteries) (Default: 220V)
Set battery capacity cut-off for battery test (20-50%)
(Default: 20)
Set battery age for replacement alert
(Disable, 12-60 months) (Default: Disabled)
Set battery compensation (-5~0)
(Default is 0)