General Installation Instructions
GENERAL INSTALLATION INSTRUCTIONS
This section contains general instructions for installing the ceiling mounted Capsule Pak ECO refrigeration system.
Note:
Proper temporary support of the ceiling panel with the cut out must be added prior to the installation of the
Capsule Pak ECO refrigeration system on the ceiling.
Due to the weight of these systems (up to 250 pounds), it is highly recommended that proper lifting equipment
such as a forklift or material lift be utilized during installation. Be sure to work in teams to prevent injury and
damage to the equipment.
The Capsule Pak ECO refrigeration system must be paired with a Master-Bilt or Norlake UL listed ignition
protected walk-in.
Be sure to allow sufficient airflow to the condenser. Allow a minimum clearance of 24" on each side of the system
for installation and operation. Consideration should be given to accessibility for service.
Capsule Pak ECO systems are designed for indoor applications only and should be operated in the controlled
environment of an air conditioned space. The ambient conditions should be at or below 75°F and 55% RH. Higher
humidity may result in condensate issues.
If multiple units are located in the same area, be sure they do not exhaust hot air into one another. The minimum
distance between units should be the width of the largest unit. If units are placed end to end, the minimum distance
should be 4 feet.
In addition to allowing for proper airflow, considerations should be given to the final mounting location of the
system relative to the customer location to avoid and possible risk of noise impacting the customer experience.
Once the Capsule Pak ECO has been lifted to the top of the walk-in, it will need to be positioned over the hole
in the ceiling panel. Before moving the Capsule Pak ECO into position, remove the diffuser panel that covers the
ceiling panel hole on the inside of the walk-in (see figures 1 and 2).