Tripp Lite EVMA1530X NEW Eaton G4 3-Phase Managed Rack PDU, 208V, 42 Outlets, 24A, 8.6kW, L15-30 Input, 10 ft. Cord, 0U Vertical

Eaton G4 Gigabit Network Module GNM Firmware User Guide - Page 48

For EVMA1530X NEW.

PDF File Manual, 231 pages, Read Online | Download pdf file

EVMA1530X NEW photo
Loading ...
Loading ...
Loading ...
Protection
Contextual help of the web interface – 48
3.5.3.1 Shutdown on power outage criteria
Shutdown criteria are set per power source (outlet groups) if they are present in the UPS.
3.5.3.1.1 Shutdown criteria selection
The available criteria for shutdown are listed below:
a Maximize availability (default)
To end the shutdown sequence 30s before the end of backup time.
b Immediate OFF
To initiate the shutdown sequence when on battery for 10 seconds.
c Custom
Several conditions can be set to define shutdown criteria:
To initiate the shutdown sequence when on battery for 10 seconds.
To initiate the sequence when the battery reaches the set capacity in (%)
To initiate or end the shutdown sequence after the set time in (s) before the end of backup time.
When there are several conditions to start the shutdown sequence, the shutdown sequence will start as soon as one of the
condition is reached.
By default, shutdown criterias are set to Maximize availability.