Transportation and Handling
3.1 Transportation
Transport the product as close to the installation location
a po before unpacking.
Do not put any material on the product.
Handling of Indoor Unit
Do not put any foreign material into the indoor unit and check
to ensure that none exists in the indoor unit before the
installation and test run. Otherwise, a fire or failure, etc. may
occur.
Be sure not to damage insulation materials of unit’s surface
during lifting operation.
6
Do not install the indoor unit in a flammable environment
to avoid fire or an explosion.
Do not install the indoor unit outdoors. If installed
outdoors, an electric hazard or electric leakage will occur.
Please contact the dealer if the accessories are not
delivered with machine.
It is recommended that indoor units be installed
higher than 98-27/64 in. from the floor level.
4.1 Factory-Supplied Accessories
Check to ensure that the following accessories are packed
with the indoor unit.
4.2 Initial Check
Install the indoor unit with a proper clearance
around it for operation and maintenance
working space, as shown in Fig. 4.1.
Models 05
~
24
Top View
Fig. 4.1 Space Around Indoor Unit
4.
Indoor Unit Installation
Install the indoor unit as per national standard.
Indoor unit must be so positioned that the indoor
temperature is distributed evenly.
There should be no obstruction that blocks air flow indoors
and at air vent.
Do not install the indoor unit in a machinery shop or
kitchen where vapor from oil or its mist flows to the indoor
unit.
The oil will deposit on the heat exchanger, thereby
reducing the indoor unit performance, and may deform and
in the worst case, break the plastic parts of the indoor unit.
(Unit:in.)
Rear
Electrical Cabinet
Manhole
Front
≥17-23/32
3-15/16
5-33/64
23-5/8
23-5/8
≥39-3/8
≥23-5/8
1.. Where the ceiling
not removable, please
arrange a necessary
service access under
the indoor unit.
2.2.The service access
shall be so arranged
that the electric box
cover/internal
components can be
removed/repaired in a
convenient manner.
Accessory Bag for
Magnetic Ring
Arranged around the Power Cord of indoor
Unit