25
9. Control Panel
SmartOnline SV-Series UPS Operating Mode
Standby Bypass Line Battery Battery Test Fault Converter ECO
Time Y Y Y Y Y Y Y Y
Change Password Y Y Y Y Y Y Y Y
Audible Alarm Y Y Y Y Y Y Y Y
Factory Reset Y
EEPROM Reset Y
EPO Function Y
Save Setting Y Y
Table 9.3
9.3.6.2 System
The SETUP – SYSTEM screen may be accessed in any UPS operating mode. Some settings may only be amended in certain modes; refer to table
9.4 for details.
SYSTEM
Output Voltage
Bypass Setting
Converter Mode
ECO Mode
Bypass Mode
Auto Restart
Cold Start
Battery Mode Delay Time*
System Shutdown Time*
System Restore Time*
Redundancy*
Charger Test
Set output voltage: 120/127V (Default: 120V)
Voltage – Upper limit: +10/15%; Lower limit: -10/20% (Default: +15/-20%)
Frequency – Upper limit: +1/2/4Hz; Lower limit: -1/2/4Hz (Default: +/- 4 Hz)
Set “Disable” or “Enable” (Default: Disabled)
Set “Disable” or “Enable” (Default: Disabled)
Set “Disable” or “Enable” (Default: Enabled)
Set “Disable” or “Enable” (Default: Enabled)
Set “Disable” or “Enable” (Default: Disabled)
Refer to 7.3 Cold Start for more information
Set system shutdown delay time in battery mode (0-9990 sec.)
Set system shutdown time 0.2 – 99 min. (Default: 0.2 min.)
Set system restore time 0-9999 min. (Default: 001)
Total Power - Quantity of Power Modules installed
Redundancy - Quantity of Power Modules to be redundant
Set “Disable” or “Enable” (Default: Disabled)
When this feature is enabled and the battery breaker of the UPS system is on, LCD can
display the charger voltage