Tripp Lite S3MT-30K480V SmartOnline S3MT-Series 3-Phase 30kVA Input Isolation Transformer

Owner’s Manual - Page 13

For S3MT-30K480V. Series: S3MT Series
Also, The document are for others Tripp Lite models: S3MT-20K480V

PDF File Manual, 48 pages, Read Online | Download pdf file

S3MT-30K480V photo
Loading ...
Loading ...
Loading ...
13
4. Operation
4.1 Over-Temperature Protection
4.1.1 Over-Temperature Red Warning LED
The transformer includes a warning LED light on the top portion of the front panel. The light turns ON when the transformer
reaches a temperature of 160°C ±5°C, i.e. a range of 155°C to 165°C (311°F to 329°F). The light turns OFF when the
transformer cools to a temperature of 125°C ±5°C, i.e. a range of 120°C to 130°C (248°F to 266°F).
4.1.2 Over-Temperature Protection Relay and Thermal Switch
The transformer includes an over-temperature protection relay and thermal switch to protect the transformer from overheating.
At temperatures of 160°C ±5°C, i.e. a range of 155°C to 165°C (311°F to 329°F), an over-temperature protection relay and
thermal switch will activate and will open the output beaker of the transformer. Once the transformer temperature has cooled
down and the warning LED light has turned OFF, you may manually re-activate (close) the output breaker to restart normal
operation.
WARNING: It is not advised to connect two UPS in parallel when using individual transformers for
each UPS.