14 Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 04
Table 9. HotSwap MBP Connection Steps
1. Connect the input socket (48) on the HotSwap MBP module to the
AC power source.
2. Connect the UPS input power cord (13) to the receptacle "UPS
Input" (47) of the HotSwap MBP module.
3. Connect the "UPS Output" cable (46) of the HotSwap MBP module
to the outlet (3) of the UPS .
4. Connect the equipment to the outlets (42) on the HotSwap MBP
module.
These outlets differ, depending on the version of the HotSwap
MBP module.
Do not use UPS outlets (4) to supply equipment
because use of switch (45) on the HotSwap MBP
module would cut supply to the equipment.
Table 10. HotSwap MBP Module Operation
The HotSwap MBP module has a rotary switch (45) with two positions:
Normal : the load is supplied by the UPS, LED (43) is on.
Bypass : the load is supplied directly by the AC power source. LED (44)
is on. Load is not protected.
33..77..11 UUPPSS SSttaarrtt--UUpp wwiitthh tthhee HHoottSSwwaapp MMBBPP MMoodduullee
1. Check that the UPS is correctly connected to the HotSwap MBP module.
2. Start the UPS by pressing the
button on the UPS control panel. LED (43) "UPS ON - OK to switch" on
the HotSwap MBP module goes ON (otherwise, there is a connection error between the HotSwap MBP
module and the UPS).
3. Set switch (45) to Normal position. The red LED on the HotSwap MBP module goes OFF.
33..77..22 HHoottSSwwaapp MMBBPP mmoodduullee tteesstt
1. Set switch (45) to Bypass position and check that the load is still supplied.
2. Set switch (45) back to Normal position.
33..88 HHoottSSwwaapp MMBBPP mmoodduullee tteesstt
1. Set switch (45) to Bypass position and check that the load is still supplied.
2. Set switch (45) back to Normal position.